TEM Evolution System
Notes
1 Notes
Identification Name of the limit value Exceeding a limit value with message
e.g. power reduction due to excess temperature inlet air
Sensor monitoring
Limit value Limit value for monitoring with unit
Limit value for monitoring with delay time On parametrizable limit values the standard value is
entered.
RA RA: Remote acknowledgement
10 h: Remote acknowledgement every 10 h possible
© GW2032_161106EN Page 2
TEM Evolution System
Notes
CH4K Extension of option CH4. VAWT Measuring of the heating water temperature before
exhaust gas heat exchanger
DK Leakage check
VSWT Measuring cooling/heating wateer before lubricaton oil
GK Intercooler circuit heat exchanger
HK Heat utilization with heating circuit ZG Dual gas operation with change of the gas type only at a
standstill
© GW2032_161106EN Page 3
TEM Evolution System
List of limit values
© GW2032_161106EN Page 4
TEM Evolution System
List of limit values
© GW2032_161106EN Page 5
TEM Evolution System
List of limit values
© GW2032_161106EN Page 6
TEM Evolution System
List of limit values
© GW2032_161106EN Page 7
TEM Evolution System
List of limit values
© GW2032_161106EN Page 8
TEM Evolution System
List of limit values
© GW2032_161106EN Page 9
TEM Evolution System
List of limit values
Fault 0 ms
AKR Knock sensor fault bank A [AKR]
Alarm 0 (code) 10 s Enable from 50% of load
AKR Knock sensor fault bank B [AKR]
Alarm 0 (code) 10 s Enable from 50% of load
ZA Maximum adjustment ignition point [AKR] Sturdy ZZP-adjustment
Alarm -3 ° 0 ms Sturdy ZZP-adjustment;
limit value: Par. 11503 - 3.0°
Critical fault! Engine test required! [AKR] Maximum ZZP-adjustment
Fault -9 ° 6s Limit value: Par. 11502-1.0°;
at least 3.0 °
AKR Speed signal [AKR] Error speed signal
Alarm 0 ms enable during load run
Anti-knock governor available [AKR]
Alarm 0 ms AKR-card missing
ZA ignites Feedback from ZA
Fault 3s Ignition does not ignite
ZA Fault code Fault message from ZA
Fault 0 (code) 3s 5min after appearance of alarm:
Delay = 0
Alarm 0 (code) 0 ms
ZA Capacitor discharge bank A Error capacitor discharge
Alarm 0 (code) 1 min
Message 0 (code) 0 ms
ZA Capacitor discharge bank B Error capacitor discharge
Alarm 0 (code) 1 min
© GW2032_161106EN Page 10
TEM Evolution System
List of limit values
Message 0 (code) 0 ms
ZA Condition serial connection S Timeout ZA-communication
Fault 10 s
ZA Condition serial connection W Error ZA-communication
Message 0 ms
xxxx Number of start attempts
Fault 3 0 ms X
T209 Generator-winding U Fault 500 ms [GK]
Fault 140 °C 10 s Limit value: Par. 13500
Alarm 135 °C 10 s Limit value: Par. 13500 - 5,0K
T210 Generator-winding V Fault 500 ms [GK]
Fault 140 °C 10 s Limit value: Par. 13500
Alarm 135 °C 10 s Limit value: Par. 13500 - 5,0K
T211 Generator-winding W Fault 500 ms [GK]
Fault 140 °C 10 s Limit value: Par. 13500
Alarm 135 °C 10 s Limit value: Par. 13500 - 5,0K
T459 Generator bearing A Fault 500 ms [GL]
Fault 60 °C 2s Limit value: Par. 13501
Alarm 55 °C 2s Limit value: Par. 13501 - 5.0K
T460 Generator bearing B Fault 500 ms [GL]
Fault 60 °C 2s Limit value: Par. 13501
Alarm 55 °C 2s Limit value: Par. 13501 - 5.0K
T487 Generator-air inlet Fault 500 ms [GLU]
Fault 80 °C 2s Limit value: Par. 13030
Alarm 75 °C 2s Limit value: Par. 13030 - 5.0K
© GW2032_161106EN Page 11
TEM Evolution System
List of limit values
© GW2032_161106EN Page 12
TEM Evolution System
List of limit values
© GW2032_161106EN Page 13
TEM Evolution System
List of limit values
Fault 0 ms
Q311 CH4-value Fault 2s [CH4]
Fault 38 % 5 min Limit value: Par. 12806
Message 38 % 0 ms Limit value: Par. 12806
Message 0% 30 s Deselection; enable/limit value: Par.
12810, Par. 12811
Message 50 % 5 min Power reduction.; limit value: Par. 12803;
Island: delay 30s
Stop due to CH4 calibration [CH4K]
Fault 75 min Timeout calibration
Alarm 75 min Timeout calibration
T289 Heating water-return Alarm 500 ms [HK] Enable with Par. 14009
Message 80 °C 0 ms [NK]; Limit value: Par. 24510
T290 Heating water before KWT Alarm 500 ms [VKWT]
T291 Heating water flow Fault 500 ms [HK] Enable with par. 14008
T384 Heat. water at emergency cooler Alarm 500 ms [NK+VNK]
T385 Heating water before AWT Alarm 500 ms [VAWT]
T386 Heating water before SWT Alarm 500 ms [VSWT]
T286 Exh. after engine Alarm 500 ms [NMOT]
Alarm 550 °C 2s Limit value: Par. 15111 / 15113
T287 Exhaust after KAT Fault 500 ms [NKAT]
Fault 550 °C 2s Limit value: Par. 15111 / 15113
T496 Exhaust gas after KAT B Fault 500 ms [NKAT]
Fault 550 °C 0 ms Limit value: Par. 15111 / 15113
T288 Exhaust after AWT Alarm 500 ms [NAWT]
Alarm 180 °C 2s Limit value: Par. 15112
© GW2032_161106EN Page 14
TEM Evolution System
List of limit values
© GW2032_161106EN Page 15
TEM Evolution System
List of limit values
© GW2032_161106EN Page 16
TEM Evolution System
List of limit values
T419 Emergency cooler-dry cooler- Alarm 500 ms [NKS] Enable with Par. 14055
outlet
Air inlet VW limit stop warm [AVW]
Message 500 ms
Air inlet VW limit stop cold [AVW]
Message 500 ms
T404 Cabin air Alarm 500 ms [RL1x] Enable with Par. 13092
Fault 40 °C 2s Limit value: Par. 13900
Alarm 35 °C 2s Limit value: Par. 13900 - 5,0K
Message 32 °C 2s Limit value: Par. 13900 - 8,0K
Cabin ventilation [RL]
Fault 3s Delay during start 60s
Cabin ventil. flap limit stop warm [RL1x]
Message 500 ms
Cabin ventil. flap limit stop cold [RL1x]
Message 500 ms
P127 Gas pressure gas control system [ZG]
B
Fault 0 ms X [CH4] Auto acknowledgement (Par.
12900)
P128 Leakage check gas B [ZG+DK]
Fault 1 min Timeout leakage check
T131 Temperature monitor gas control [ZG]
system B Fault 0 ms
E149 Supply voltage Fault 500 ms
Alarm 20 V 0 ms
© GW2032_161106EN Page 17
TEM Evolution System
List of limit values
Alarm 30 V 0 ms
Exxx Earth leakage monitor switching Fault 0 ms
cabinet
Alarm 10 kOhm 5s
G143 Circuit breaker TEM swtiching
cabinet
Fault 0 ms
H141 Internal quick stop
Fault 0 ms
H117 Ext. quick stop without heat Input security chain
removal
Fault 0 ms
H116 Ext. quick stop with heat removal Input security chain
Fault 0 ms X
Security chain Security chain open
Fault 0 ms X
Parametrizable message 01 [xM] Par. message; free text
Message 0 ms X Limit value, delay, enable parametrizable
Parametrizable measured value 01 Alarm 500 ms [xMW] Par. measured value; free text
Message 0 0 ms X Limit value, delay, enable parametrizable
Message 0 0 ms X Limit value, delay, enable parametrizable
Control deviation parametrizable [xPR] control deviation par. governor;
controllers 1 XX=1..3
Message 10 0 ms X Limit value, delay, enable parametrizable
© GW2032_161106EN Page 18