DECS-250N Digital Excitation Control System

DECS-250N
Digital Excitation
Control System

Basler Electric's DECS-250N digital excitation control system offers high performance, high flexibility, and
extreme reliability for brushless excited AC synchronous generators. The DECS-250N utilizes a 20 amp
six-thyristor negative forcing output, providing exceptional system transient response. Multiple communication
options and an optional integrated power system stabilizer make the DECS-250N a complete system solution
in a reliable and cost-effective package.

FEATURES
• True RMS sensing, single- or three-phase voltage • Extensive Communication Options
and current • USB Communication
• Full generator metering capabilities
• Modbus™ RS-485 RTU
• AVR / FCR / FVR, power factor and var modes of
• J1939 CAN bus
operation
• Ethernet 100Base-T (Modbus TCP)
• Integrated generator protection 24, 25, 27, 32R,
• Ethernet 100Base-F (optional)
40Q, 51F, 59, 59F, 81O/U, EDM, Loss of PMG, and
• PROFIBUS™ (optional)
field short circuit
• IRIG-B for time synchronization
• Configurable protection
• Reactive Load Sharing via Ethernet
• Overexcitation Limiting
Communication
(with temperature compensation)
• Auto-tuning feature for automatic PID Gain setup
• Underexcitation Limiting
• Internal Autotracking between modes of operation
• Stator Current Limiting
• External Autotracking between DECS units
(with temperature compensation)
• Voltage Matching
• Var Limiting
• Optional Automatic Synchronizer
• Underfrequency Limiting or V/Hz Limiting
• Optional integrated Power System Stabilizer
• Exciter Diode Monitoring
• Trending, Oscillography, and Sequence of
Events Recording
• 16 programmable contact inputs
• 12 programmable contact outputs FEATURES
• I/O Expansion Module compatibility Page 1
(CEM-2020 and AEM-2020)

SPECIFICATIONS
Page 2
ADDITIONAL INFORMATION
INSTRUCTION MANUAL
Request Publication 9440500990 ORDERING
Page 4

SZQ-1
7-14
12570 STATE ROUTE 143, HIGHLAND, ILLINOIS 62249 USA PHONE 618-654-2341 FAX 618-654-2351
DECS-250N Digital Excitation Control System

DECS-250N SPECIFICATIONS
Control Power Generator Current Sensing
Nominal: Style LXXXXXX: 16-60 Vdc Configuration: 1- or 3-Phase with separate input for
Style CXXXXXX: 90-150 Vdc, cross current compensation
82-132 Vac Current Ranges: 1 Aac or 5 Aac nominal
Burden: 50 VA or 30 Watts Frequency Range: 50/60 Hz Nominal
Burden: 1 Aac sensing: < 5 VA
AC Operating Power and DC Output Power 5 Aac sensing: <10 VA
32Vdc:
Power Input Configuration: 1- and 3-Phase Inputs and Outputs
Nominal Input Voltage: 60Vac Contact Inputs: 16 programmable inputs
Full Load Continuous Voltage: 32Vdc (dry contacts)
Full Load Continuous Current: 20Adc Auxiliary Input: Connection available in
Power Input Frequency: 50/60Hz or 61-420Hz 4-20mA or ±10 Vdc input
Operating Temperature: -40°C to +60°C Output Contacts: 11 programmable form A
Minimum Field Resistance: 1.6 Ω contacts and one form C for
watchdog function
63Vdc: Rating: Make, break and carry 7A
Power Input Configuration: 1- and 3-phase resistive @ 24/48/125 Vdc
Nominal Input Voltage: 120Vac (120/240 Vac).
Full Load Continuous Voltage: 63Vdc
Full Load Continuous Current: 20Adc Communication
Power Input Frequency: 50/60Hz or 61-420Hz USB: USB type B for use with BESTCOMSPlus®
Operating Temperature: -40°C to +60°C RS-232: 9 pin, sub D for external autotracking
Minimum Field Resistance: 3.15 Ω RS-485: Modbus RTU protocol
CAN bus: 1 port for ECU communications. 1 port for
125Vdc: expansion modules.
Power Input Configuration: 1- and 3-phase Ethernet: Standard unit uses 100Base-T, optional
Nominal Input Voltage: 240Vac selection of 100Base-F is available. Modbus TCP
Full Load Continuous Voltage: 125Vdc protocol or unit-to-unit communication.
Full Load Continuous Current: 20Adc Expansion Port: Optional PROFIBUS communication
Power Input Frequency: 50/60Hz or 61-420Hz protocol.
Operating Temperature: -40°C to +60°C
Minimum Field Resistance: 6.25 Ω Agency/Certifications
CSA certified, UL recognized, CE EMC and LVD compliant,
250Vdc: DNV (Det Norske Veritas) and GL (Germanischer Lloyd)
Power Input Configuration: 1- and 3-phase recognized
Nominal Input Voltage: 480Vac
Full Load Continuous Voltage: 250Vdc Environmental
Full Load Continuous Current: 20Adc Operating Temp: -40°C to +60°C (-40°F - 140°F)
Power Input Frequency: 50/60Hz Storage Temp: -40°C to +85°C (-40°F - 185°F)
Operating Temperature: -40°C to +60°C Salt Fog: Per MIL-STD 810E method 509.3
Minimum Field Resistance: 12.5 Ω Shock: 15G’s in each of three
perpendicular planes
Generator and Bus Voltage Sensing Vibration: 5G’s from 18-2000Hz in each
Configuration: 1- or 3-Phase of three perpendicular planes
Voltage Ranges: 100/120 Vac ±10%
200/240 Vac ±10% Physical
400/480 Vac ±10% Weight: 6.62 kg (14.6 lbs)
600 Vac ±10% Dimensions (WxHxD):
Frequency Range: 50/60 Hz Nominal 6.26” x 12.00” x 8.62”
Burden: < 1 VA per phase (159.0mm x 304.8mm x 219.0mm)

2
DECS-250N Digital Excitation Control System

NOTES:
DECS-250N Digital Excitation Control System

HOW TO ORDER

P.A.E. Les Pins, 67319 Wasselonne Cedex, FRANCE


Tel +33 3.88.87.1010 Fax +33 3.88.87.0808
e-mail: franceinfo@basler.com
No. 59 Heshun Road Loufeng District (N),
Suzhou Industrial Park, 215122, Suzhou, P.R.China
12570 State Route 143, Highland, Illinois 62249-1074 USA Tel +86(0)512 8227 2888 Fax +86(0)512 8227 2887
e-mail: chinainfo@basler.com
Tel +1 618.654.2341 Fax +1 618.654.2351
e-mail: info@basler.com 111 North Bridge Road #15-06 Peninsula Plaza
Singapore 179098
www.basler.com Tel +65 68.44.6445 Fax +65 68.44.8902
e-mail: singaporeinfo@basler.com

You might also like