Professional Documents
Culture Documents
Electric Power Technical Standards - en Cambodia PDF
Electric Power Technical Standards - en Cambodia PDF
Electric Power Technical Standards - en Cambodia PDF
KINGDOM OF CAMBODIA
NATION RELIGION KING
JULY 2004
ISSUED BY MINISTRY OF INDUSTRY, MINES AND ENERGY IN ACCORDANCE
WITH THE ELECTRICITY LAW OF THE KINGDOM OF CAMBODI
1
KINGDOM OF CAMBODIA
NATION KING RELIGION
PROKAS
ON ESTABLISHMENT OF GENERAL REQUIREMENT OF ELECTRIC
POWER TECHNICAL STANDARDS OF THE KINGDOM OF
CAMBODIA
DECIDES
Article 1
To establish the General Requirement of Electric Power Technical Standards of the Kingdom of
Cambodia, for implementation, in 5 main parts as below:
1- Fuel Oil Generation Plant and Steam Power Plant
2- Hydro Power Plant
3- Transmission and Distribution System
4- Renewable Energy System
5- House and General Building Wiring System
Article 2
To issue the General Requirement of Electric Power Technical Standards of the Kingdom of
Cambodia, full contents of which are attached here with.
2
Article 3
The Specific Requirement of each part shall be prepared and issued from time to time accordance
with the priority.
Article 4
All electric suppliers and consumers shall fully follow this Standard.
Article 5
The electric suppliers are allowed to use their existing electric system for 2 years or any extension as
decided by Electricity Authority of Cambodia from the date of signing of this Prokas, during which
they are to improve their facilities to be in accordance with the electric power technical Standard.
When the system is improved or changed, this standard shall be followed. The existing House and
General Building Wiring System is allowed to remain in use except the unsafe system.
Article 6
Prokas or any decision in contradition to this Prokas shall be null and void.
Article 7
This Prokas shall come into force from the date of signing.
SUY SEM
3
KINGDOM OF CAMBODIA
NATION KING RELIGION
PROKAS
ON THE FIRST AMENDMENT ON THE PROKAS NO. 470, DATED
JULY 16, 2004 ON THE ESTABLISHMENT OF ELECTRIC POWER
TECHNICAL STANDARDS OF THE KINGDOM OF CAMBODIA
DECIDES
Article 1
To amend the General Requirement of Electric Power Technical Standards of the Kingdom of
Cambodia issued by Prokas No. 470, dated July 16, 2004 as follow:
- To add the definition of the word “Remote Areas” at paragraph 19 of clause 1 (“Remote
Areas” means the areas whose electric demand is too small and whose grids are not
connected to other grids).
4
The Electricity (Overhead Lines) Regulations:
2.0 - 2.5 or more
U.K.
VDE0210: Germany 2.3 - 2.5 or more
*U.T.S.: Ultimate tensile strength
1.2 The Weather Conditions in Cambodia (temperature, wind velocity)
(1) Temperature
Temperature Average
Station Temperature Max (qC) Temperature Min (qC)
(qC)
Banteaymean Chey 37.0 21.5 29.3
Battambang 37.4 17.6 27.5
Kampong Cham 37.1 17.7 27.4
Kampot 34.4 19.7 27.1
Kratie 37.6 14.0 25.8
Pochentong 36.8 19.7 28.3
Prey Veng 37.6 21.0 29.3
Pursat 39.5 19.9 29.7
Siem Reap 40.1 17.9 29.0
Sihanoukville 34.0 21.3 27.7
Stung Treng 36.4 17.5 27.0
Svay Rieng 36.4 18.8 27.6
Average 37.0 18.9 28.0
*Source: Department of Meteorology, Ministry of Water Resources and Meteorology
*Observation duration: 1985 to 2001
(2) Wind Velocity (annual maximum value of 10-minute average wind velocity)
Observation place: Pochentong, Phnom Penh
Year 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 1991
wind(m/s) 12 16 16 16 14 14 10 6 16 16 14
1992 1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003
17 18 18 17 11 14 13 11 11 10 12 12
1992 1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003
230
24 24 40 20 28 24 26 24 16 24 14 16
231
1.3 Design Wind Velocity Applied for Transmission Lines in Cambodia
1.5 Reference Wind Velocity (the yearly maximum of 10-mimute average wind velocity by 50year return
period)
Here the yearly maximum of 10-minute average wind velocity (50year return period) in Cambodia is
calculated from observation data at two places in Cambodia provided by Department of Meteorology,
Ministry of Water Resources and Meteorology.
Before that, all of data are confirmed whether they are significant or not according to Annex
“Observation data of wind velocity and Gumbel distribution”.
*Gumbel distribution: A special case of the generalized extreme value distribution. It is used in the
environmental sciences to model extreme values associated with flooding, rainfall, wind, etc.
ª ° ˭ §
·½°º
PV 1 exp « exp® ¨V V 0.45˰ V ¸¾» .......... (formula 1)
«¬ °̄ 6˰ V © ¹°¿»¼
232
1
Where P(v): probability that wind velocity will exceed V ( = , T: Recurrence interval)
T
V : Average value of the yearly maximum wind velocity
˰ V : Standard deviation of the yearly maximum wind velocity
6˰ v ª § 1 · ½º
V « ln ® ln¨1 ¸¾» V 0.45˰ v ........... (formula 2)
˭ ¬ ¯ © T ¹ ¿¼
Moreover, V ,˰ V are calculated from the wind velocity data of Cambodia shown in Annex (1).
V ᧹13.65 (m/s)
˰ V ᧹2.97
These values are substituted to formula 2 and the yearly maximum of 10-minute average wind velocity
(50year return Period) in Pochentong is finally given as follows:
˰ V ᧹3.91
These values are substituted to formula 2 and the yearly maximum of 10-minute average wind velocity
(50year return Period) in Siem Reap is finally given as follows;
233
1.6 Maximum Instantaneous Wind Speed
Maximum instantaneous wind speed is given by multiplying the above value and Gust Factor. On
condition that Gust Factor is 1.3-1.5, the maximum instantaneous wind velocity is given as formula 3.
(1) Pochentong
Maximum instantaneous wind velocity (50year return Period) 21.36 u G ᧤1.3 to 1.5᧥
= 27.8 to 32.0
(2) Siem Reap
Maximum instantaneous wind velocity (50year return Period) 31.86 u G ᧤1.3 to 1.5᧥
= 41.4 to 47.8
It might be premature to fix the reference wind velocity from insufficient observed data at this moment.
Because transmission lines need to be secured adequate reliability to send bulk power, it is efficient to
show a standard value in SREPTS. Minimum reliability has to be secured.
This paragraph requests the designer of a transmission line to consider the wind pressure load very
carefully on a case-by-case basis according to the required reliability of the transmission line, the conditions
and circumstances of the route, wind observation data of the area.
In case of designing a transmission line connected to neighboring countries, it is necessary to consider and
coordinate the design conditions of the country.
234
Annex
“Observation data of wind velocity and Gumbel distribution”
(1) Pochentong
The data is assumed to be adjusted to Gumbel distribution as the graph27A.
235
14 4 50.00 21.36
13 1 40.00 20.83
˰ V : Standard deviation of
12 3 the yearly maximum wind velocity 30.00 20.16
11 3 = 2.97 20.00 19.20
10 2 10.00 17.53
9 0 8.00 16.98
8 0 6.00 16.26
7 0 4.00 15.20
6 2.00 13.16
1.80 12.80
1.60 12.36
1.40 11.79
1.20 10.96
1.10 10.29
(2) Siem Reap
- Case 1
As the following frequency distribution, 40m/s (1994) is far from other data.
According to Graph 27B, 40m/s (1994) shows a marked different tendency from other data. Therefore an
analysis excluding 40m/s (1994) is tried as (3).
236
Frequency distribution Gumbel distribution
Return
Wind(m/s) Number Wind(m/s)
6˰ ª § 1 ·½º period(year)
« ln ® ln ¨ 1 ¸ ¾ » V 0 . 45˰
v
V
˭
v
40 1 ¬ ¯ © T ¹¿¼ 90.00 40.65
39 0 80.00 40.11
38 0 70.00 39.50
V : Average value of
37 0 the yearly maximum wind velocity 60.00 38.79
= 22.88 m/s
36 0 50.00 37.96
35 0 40.00 36.94
˰ : Standard deviation of
34 0 V 30.00 35.61
the yearly maximum wind velocity
33 0 = 5.82 20.00 33.73
32 0 10.00 30.47
31 0 8.00 29.39
30 0 6.00 27.98
29 0 4.00 25.91
28 1 2.00 21.92
27 0 1.80 21.21
26 1 1.60 20.34
25 1 1.40 19.23
24 5 1.20 17.61
23 0 1.10 16.29
22 0
21 1
20 3 As a result, this data is not adopted.
19 0
18 0
17 0
16 2
15 0
14 1
- Case 2
The data is assumed to be adjusted to Gumbel distribution as the graph27C. The value 40m/s (1994) in
case1 is quite larger than neighboring countries in which it is supposed that the wind is stronger than that in
Cambodia. In this case, the yearly maximum of 10-minute average wind velocity (50year return Period) is
calculated from the data excluding 40m/s (1994) because it is doubtful whether this data was observed in a
proper manner.
237
Observation data Thomas Plot
Number Excess probability Return period
Year Wind (m/s) Year Wind (m/s)
(i) W=i/(n+1) 1/w (year)
1988 20 1 1996 28 0.06 15.87
1989 20 2 1998 26 0.13 8.00
1990 25 3 1990 25 0.19 5.32
1991 21 4 1992 24 0.25 4.00
1992 24 5 1993 24 0.31 3.19
1993 24 6 1997 24 0.38 2.67
1995 20 7 1999 24 0.44 2.28
1996 28 8 2001 24 0.50 2.00
1997 24 9 1991 21 0.56 1.78
1998 26 arrange 10 1988 20 0.63 1.60
1999 24 11 1989 20 0.69 1.45
2000 16 12 1995 20 0.75 1.33
2001 24 13 2000 16 0.81 1.23
2002 14 14 2003 16 0.88 1.14
2003 16 15=n 2002 14 0.94 1.07
238
1.10 17.31
7KRPDV3ORW
*XPEHOGLVWULEXWLRQ
ZLQGYHORFLW\P V
\HDU
Graph 27A: Modeling of Observation Data (Pochentong)
ZLQGYHORFLW\P V
7KRPDV3ORW
*XPEHOGLVWULEXWLRQ
\HDU
Graph 27B: Modeling of Observation Data (Siem Reap)
239
ZLQGYHORFLW\P V
7KRPDV3ORW
*XPEHOGLVWULEXWLRQ
\HDU
Graph 27C: Modeling of Observation Data (Siem Reap, where 40m/s (1994) is excluded
2 The Maximum Working Tension of Overhead Conductors᧤for High-voltage lines᧥
2.1 Concept
The limiting conditions for conductor tensions may be governed by either the worst condition (Strong
wind) or Normal condition (Every Day Stress).
Lower one between these two tensions calculated by following two conditions should be adopted.
The real maximum tension loaded on the conductor is the maximum tension Ts max on high-side
supporting point and is larger than the maximum working tension Tmax.
Ts max
Tmax
Supporting Tmax: The maximum working tension
structure
240