E-05 Cable Size Calculation - HT

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

R0 01-02-18 Submitted for Approval

Rev. No. Date Description/Purpose of Revision


PROJECT NAME : RAJASTHAN URBAN SECTOR DEVELOPMENT PROGRAM (RUSDP)
SCHEME : BULK WATER SUPPLY SYSTEM FOR PALI PHASE-II
RAJASTHAN URBAN INFRASTRUCTURE DEVELOPMENT
PROJECT(RUIDP)
CLIENT :
AVS BUILDING , JLN MARG, JAWAHAR CIRCLE,
JAIPUR-302017
SHAH TECHNICAL CONSULTANT (P) LTD
CONSULTANT
IN ASSOCIATION WITH
(PMDSC) :
GRONTMIJ A/S AND DRA CONSULTANTS PVT. LTD
VISHNU PRAKASH R PUNGALIYA LTD.
H-01,FIRST FLOOR SHIVALIC COMPLEX NEAR GOL BUILDING,
CONTRACTOR :
SARDARPURA , JODHPUR - 324001 TELEFAX-0291-2434396 ,
E-mail : pungliyasanjay@gmail.com
REVISION Signature of
Cable Size Calcultion_HT for RWPS - NO. OF
TITLE : VPRPL’s
MANDLI NO. DATE SHEETS:
Representative:

DOCUMENT NO. : RUSDP-RWPSMND/E-05 R0 01-02-18 3

Page 1 of 3
Document Tittle: Cable Size Calculations_HT for RWPS - MANDLI
Document No.: RUSDP-RWPSMND/E-05, Rev.:R00

HT CABLE CALCULATION FOR RWPS MANDLI PALI-02 PHASE-III Remarks


Drive/Load Transformer
Fed From Isolator
Rating of Transformer
500.00
KW/KVA
Proposed Cable Size
3 C*240SQMM
(SQMM) AL
No. of Run-N 1
Voltage Rating of HT
11000
System
Cable Derating factor 0.750
Allowable Running
Voltage Drop (%) 2.50%
Running Power Factor
0.80
(Cos Φ)
Input Data Reactive Running Power
0.600
Factor (Sin Φ)
Resistance of Cable
Selected at 90 Deg. C in 0.161 (From Polycab Catalogue)
Ω/Km (R)
Reactance (X) at 50 Hz.
0.0964 (From Polycab Catalogue)
(Ohm/Km)
Short Circuit Rating for
22.680 (From Polycab Catalogue)
01 Sec. (KA)
Capacitance 0.290 (From Polycab Catalogue)
Length - L (km) 0.1 (Approx.)
Current Carrying
Capacity (Cable
315 (From Polycab Catalogue)
Ampacity) in Ground at
30 Deg. C.

BULK WATER SUPPLY SYSTEM FOR PALI-02 PHASE-III Page 2 of 3


RWPS - MANDLI
Document Tittle: Cable Size Calculations_HT for RWPS - MANDLI
Document No.: RUSDP-RWPSMND/E-05, Rev.:R00

Calculated Data :
(01) Current Carrying Capacity of Cable :

Selected Transformer Rating (KVA)/√3 * Voltage Rating (KV)


(A) Full Load Current - I ( A)
= 500 / √3 * 11
26.24396389 Amp.

(B) Cable Derated Current No. of Run of Cable * Cable Derating Factor *Current Rating of Cable
=
236.25 Amp.
CONDITION -01 = B > A (FULL LOAD CURRENT > CABLE DERATED CURRENT)

(02) Calculation of Allowable Voltage Drop During Running Condition:

Impedance of the Cable = ( R Cos Φ + X Sin Φ ) / No. of Runs of Cable


when Laid in Parallel
= ( 0.89 * 0.8 + 0.102 * 0.600)/1
(Running) =
0.1288

Voltage Drop During √3 * Maximum Length of Cable * Full Load Current * Impedance of Cable(Running)
Running (Volt.) =
0.585454545 Volt.
(Voltage Drop During Running / Voltage Rating) * 100
Voltage Drop in %
0.5322%
HENCE SATISFIED THAT % OF VOLTAGE DROP DURING CONDITION IS LESS THAN 2.5%
Short Circuit Current in
18.500 KA
KA
T (Duration of short
1 SEC.
Maximum Area of Cross circuit current in sec.)
Section Required (A) = K - Factor Value for
0.094
Aluminium XLPE Cables
=( Short Circuit Current * (T)^1/2) / K SQMM
196.8085106 SQMM
HENCE SELECTED CABLE SIZE = 3C X 240 SQMM

BULK WATER SUPPLY SYSTEM FOR PALI-02 PHASE-III Page 3 of 3


RWPS - MANDLI