TECHNICAL SPECIFICATIONS(V1.20)
PAC-E100ST(IE)
(Over Current & Earth Fault Relay)
1. General Data
1.1 Power Supply
Input Voltage 110~220 VAC±20 %, 50/60 Hz, 80~300 VDC
19~130 VDC
Power Consumption less than 15 VA
1.6 HMI
LEDs Run, System Error, Trip, Pickup
Local, Remote, CB open, CB Close, 79 active,
6 Programmable LEDs
Keys Local, Remote, Open, Close, Reset, Menu,
Enter, 79 enable
LCD 3P+I0 current RMS can be displayed on single page.
2
PAC-E100ST (Over Current & Earth Fault Relay)
1.8 Environmental
Carrying and Storage -30 °C~+75 °C
Operating Temperatures -25 °C~+70 °C
Altitude up to 2000 m
3
PAC-E100ST (Over Current & Earth Fault Relay)
2.Protection
2.1 Definite Time Overcurrent(50_1,50_2,50N_1,50N_2)
Setting
Pickup Current(50_1,50_2) 0.50~100.00 A, 0.05 step*)
Pickup Current(50N_1,50N_2) 0.05~100.00 A, 0.05 step *)
Operating Delay 0.00~300.00 sec, 0.01 step
Dropout Delay 0.00~1.00sec, 0.01 step(valid only for 50N_1 and 50N_2)
Accuracy
Pickup Current 2 % of setting value or 70 mA
Operating Time 3 % or ±35 msec of setting value, @ 2xpickup current
Dropout Level 96~98 % of pickup current
Dropout Time less than 40 msec
Information
Pickup 50_1_PKP_A, 50_1_PKP_B, 50_1_PKP_C, 50_1_PKP_OR
50_2_PKP_A, 50_2_PKP_B, 50_2_PKP_C, 50_2_PKP_OR
50N_1_PKP, 50N_2_PKP
Operation 50_1_OP_A, 50_1_OP_B, 50_1_OP_C, 50_1_OP_OR
50_2_OP_A, 50_2_OP_B, 50_2_OP_C, 50_2_OP_OR
50N_1_OP, 50N_2_OP
*)
for 1A rated, all value divided by 5
TM sec
K
T L
C
G
1
GS
T : Trip time in second
K,C,L,M : Constants
G : Current input
GS : Pickup current setting
TM : Time multiplier
Curve K L C
IEC Normal Inverse 0.14 0.02 0.00
IEC Very Inverse 13.50 1.00 0.00
IEC Extremely Inverse 80.00 2.00 0.00
IEC Long Inverse 120.00 1.00 0.00
ANSI Inverse 8.9341 2.0938 0.17966
4
PAC-E100ST (Over Current & Earth Fault Relay)
Accuracy
Pickup Current 2 % of setting value or 70 mA
Operating Time 3 % or ±35 msec of setting value
Dropout Level 96~98 % of pickup current
Dropout Time less than 40 msec for instantaneously reset setting
Information
Pickup 51_PKP_A, 51_PKP_B, 51_PKP_C, 51_PKP_OR, 51N_PKP
Operation 51_OP_A, 51_OP_B, 51_OP_C, 51_OP_OR, 51N_OP
*)
for 1A rated, all value divided by 5
2.3 Negative Phase Sequence Overcurrent (46)
Setting
Pickup Current 0.50~100.00 A, 0.05 step*)
Operating Delay 0.00~180.00 sec, 0.01 step
Accuracy
Pickup Current Accuracy 2 % of setting value or 70 mA
Operating Time Accuracy 3 % or ±35 msec of setting value, @ 2xpickup current
Dropout Level 96~98 % of pickup current
Dropout Time less than 40 msec
Information
Pickup 46_PKP
Operation 46_OP
*)
for 1A rated, all value divided by 5
Accuracy
Pickup Current Accuracy 2 % of setting value or 70 mA
Operating Time Accuracy 3 % or ±35 msec of setting value, @ 0xpickup current
Dropout Level 102~104 % of pickup current
Dropout Time less than 40 msec
Information
Pickup 37_PKP_A, 37_PKP_B, 37_PKP_C, 37_PKP_OR
Operation 37_OP_A, 37_OP_B, 37_OP_C, 37_OP_OR
*)
for 1A rated, all value divided by 5
5
PAC-E100ST (Over Current & Earth Fault Relay)
t : Trip time
τ : Temperature rise time constant
I : Load current
IP : Pre-load current
k : Setting factor
IN : Nominal current
Thermal State Calculation
2
I
m1 1 exp( t / ) m exp( t / )
k IN
θ being calculated every 100ms
I means True RMS
Accuracy
Pickup Current Accuracy 2 % of setting value or 70 mA
Operating Time Accuracy 10 % or ±2 sec of setting value
Dropout Level 98~100 % of thermal trip setting
Information
Alarm 49_ARM
Trip 49_TRIP
2.6 Auto-Reclosing(79)
Setting
Shot Number 1~5, 1 step
Prepare Condition EasyLogic Operand
Cycle Start Condition EasyLogic Operand
Prepare Time 0.05~200.00 sec, 0.01 step
Discriminating Time 0.01~5.00 sec, 0.01 step
Reclaim Time 0.01~350.00 sec, 0.01 step
1st ~ 5th Shot Delay 0.01~300.00sec, 0.01 step
Command
CB Close Command 79_CLS_CMD
CB Final Trip Command 79_OPN_CMD
6
PAC-E100ST (Over Current & Earth Fault Relay)
Information
Auto-Reclosing Ready 79_READY
Auto-Reclosing In Progressing 79_IN_PROG
Auto-Reclosing Fail(Final Trip) 79_FAIL
Accuracy
Pickup Current 3 % of setting value
Operating Time ±20 msec of setting value
Dropout Time less than 40 msec, after trip relay reset
Information
Operation 50BF_OP
*)
for 1A rated, all value divided by 5
During Cold Load Pickup is operating, all overcurrent protection(50_1, 50_2, 51, 50N_1,50N_2,51N,46)
pickup values are multiplied by Pickup Multiplier setting value.
Accuracy
Pickup Current 3 % of setting value
Information
Pickup COLD_LD_PKP
Operation COLD_LD_OP
*)
for 1A rated, all value divided by 5
7
PAC-E100ST (Over Current & Earth Fault Relay)
Accuracy
Pickup Current 3 % of setting value
Operating Time ±20 msec of setting value
Dropout Time less than 40 msec
Information
Operation I2/I_OP
*)
for 1A rated, all value divided by 5
3.Control
3.1 Circuit Breaker Control
Setting
Trip Pulse Time 0.1~5.0 sec, 0.1 step
Close Pulse Time 0.1~5.0 sec, 0.1 step
3.2 Setting Group
Number of Setting Group 4
Manual Setting Group Change Command(KeyPad), Communication
Auto Setting Group Change DI function Setting
Auto)
1) If one of DI is set to ”SG SEL0”, then Setting Group change range are 0~1.
2) If 2 DIs set to ”SG SEL0” and ”SG SEL1”respectively, then Setting Group change range are 0~3.
3) If only 1 DI is set to ”SG SEL1”, then Setting Group changing function is blocked(Error)
Manual)
If auto changing is blocked(no settting), manual changing is valid.
3.3 EasyLogic
Contact Output, Programmable LED, 4 User Logic
Logic OR8(8 input OR)
, HALF-OR8(Non inverting 4 input & inverting 4 input OR)
, AND8(8 input AND)
, HALF-AND8(Non inverting 4 input & inverting 4 input AND)
Logic Input Input1~8, refer to < PAC-E100S Logic Input >
Reset Type Self(latched until delay timer is expired)
, Manual(latched until reset is issued)
Reset Input refer to < PAC-E100S Logic Input >
Self Reset Delay 0.00~60.00sec(0.01sec step)
Contact Input
Function General Input
, CB Open
, CB Close
, Annunciator Reset
, SG SEL0(Setting Group Select 0)
, SG SEL1(Setting Group Select 1)
8
PAC-E100ST (Over Current & Earth Fault Relay)
9
PAC-E100ST (Over Current & Earth Fault Relay)
10
PAC-E100ST (Over Current & Earth Fault Relay)
4. Monitoring
4.1 Self-Diagnosis
Memory After power-on reset, RAM pattern test error
Setting When power-on reset or setting is changed,
Non-volatile memory setting is checked.
Setting value is out of boundary
Total check-sum Error
A/D Converter A/D running counter stop
, A/D reference input is out of boundary
Auto-Calibration Each analog input calibration factor is out of boundary
, Ttotal check-sum error
4.2 Trip Circuit Supervision(TCS)
Only One DI is used for TSC.
TCS DI Input is checked every 10 msec.
If consecutive check is failed after expiring timer, TCS fail annunciation is reported.
After TSC fail is cleared, the failure annunciation is reset automatically
Setting
Time setting 0.02 ~ 600.00sec, 0.01 step
11
PAC-E100ST (Over Current & Earth Fault Relay)
Setting
1. FUNCTION ENABLED, Whether function use or not
DISABLED
2. LOW kA 0.00~650.00 kA Current at low current point CB
3. LOW CNT 0~65000 - Allowed operation at low current point maintenance
4. MID kA 0.00~650.00 kA Current at middle current point curve setting
5. MID CNT 0~65000 - Allowed operation at middle current point
6. HIG kA 0.00~650.00 kA Current at high current point
7. HIG CNT 0~65000 - Allowed operation at high current point
8. ALARM 0.0~100.0 % Alarm level
Metering
CB_MON_%A CB wear monitor A phase accumulation % value( ~250.0%)
CB_MON_%B CB wear monitor B phase accumulation % value( ~250.0%)
CB_MON_%C CB wear monitor C phase accumulation % value ( ~250.0%)
CB_MON_ALM 3 phase alarm logic OR of CB wear monitor
CB_MON_ALM_A A phase alarm of CB wear monitor
CB_MON_ALM_B B phase alarm of CB wear monitor
CB_MON_ALM_C C phase alarm of CB wear monitor
12
PAC-E100ST (Over Current & Earth Fault Relay)
5. Measurement
Current
Phase, Ground Current RMS
Input Range 0.5~250 A*)
Accuracy ±2 %(0.5~1 A), ±0.5 %(1~6 A) *)
Sequence Current
Positive/Negative/Zero Sequence Current RMS
Harmonic Current
2nd Harmonic Current A/B/C
Frequency
Range 40 Hz~70 Hz, Phase A Current
Accuracy ±0.03 Hz at Nominal current input
*)
for 1A rated, all value divided by 5
6. Record
6.1 Events(Including Fault Report)
Storage Capacity Max 700 events with 1 msec time resolution
Data System reset
, Annuciator reset
, Setting changed
, Clear event record
, Clear waveform recording
, Protection pickup/operate/release etc.
Analog input information(current rms) are recorded when a protection element triggered.
6.3 Waveform
Storage Capacity Max 16sec@50Hz
Record Type(block*cycle) 16*50, 8*100 or 4*200(16*1s, 8*2s or 4*4s@50Hz)
Trigger Position 0 ~ 99%
Trigger Source Protection trip
, Change of contact input status
Data Current sample(IA, IB, IC, IN)
, Contact input/Output status
, Enabled protection status
13
PAC-E100ST (Over Current & Earth Fault Relay)
7.Communication
7.1 USB
Front Panel USB232, 38400 (fixed), ModbusRTU
7.2 RS-485
2 Galvanic isolated RS-485
BPS 300~57600
Protocol COM1 : ModbusRTU , DNP3.0 or IEC60870-5-103
COM2 : ModbusRTU(fixed)
Connection
Num COM1 Num COM2
1 -- 1 --
2 RS485_DATA- 2 RS485_DATA-
3 RS485_DATA+ 3 RS485_DATA+
4 -- 4 --
5 RS485_COM 5 RS485_COM
6 -- 6 --
7 -- 7 --
8 -- 8 --
9 -- 9 --
8.PC Software
Relay setting upload and download.
Event upload from relay and save to file.
Waveform upload from relay and analysis in PC supported.
14
PAC-E100ST (Over Current & Earth Fault Relay)
<Dimensions of PAC-E100ST>
15
PAC-E100ST (Over Current & Earth Fault Relay)
<Dimensions of PAC-E100ST(IE)>
16
PAC-E100ST (Over Current & Earth Fault Relay)
PAC-E100ST(IE) C B A
15
TS1_COM
5 PAC_E100ST(IE )
TS1_NO
16
TS2_COM
6 IA
TS2_NO
17
TS3_COM IB
7 Rogowski coil CT
TS3_NO
8 IC or LPCT
TS4_NO
18
TS4_COM 8Pin Modular Jack
9
TS4_NC
TS5_NO 20
19
TS5_COM PAC_E100ST
10
TS5_NC 11
IA 1
21 12
TCS_P
30 IB 2
TCS_COM 22
DI1_P 13
31
DI1_COM IC 3
23 14
DI2_P
32
DI2_COM IN 4
24
DI3_P
34
DI4_P
25
DI5_P
35 27,36
DI6_P AC/DC 110~220V POWER+
28,37
DC 19~130V
29,38
POWER-
26 SURGE
DI7_P
DI3~7_COM 33
GROUND
BUS
COM1 COM2
RS485 RS485
USB RS-232
DB-9 DB-9
Front
Rear Rear
11.Ordering Information
Power Supply 125 VDC/110 VAC or 250 VDC/220 VAC
24/48 VDC
CT Rated Secondary 1 A or 5 A
Language English, Turkish
17
PAC-E100ST (Over Current & Earth Fault Relay)
18