I. Raw Design Calculation Capacity Results from SLFE III. Calculation of Water Flow Rate (WFR)
II. SKM Compact Screw Chillers APCY-H Series Selection Procedure b) Refer to Water Flow Rate Capacity (see Fig 4)
a) Refer to Capacity Correction and Limits and apply the following factors to convert the required capacity to
tabulated capacity ratings. (see Fig. 1) For APCY 6355 TH:
Selected Model is APCY 6375 TH and 1230 kW (by interpolation) - FIRST OPTION All capacities are meeting the requirement as stated in the approved NMR's.
Capacity = 1218 kW
Note:
In compliance with AHRI 550 / 590 and SAES-K-001, SKM meticulously applied care and
good engineering that lead to an efficient and cost effective selection for APCY-H Chillers.