DATA SHEET
3UA
OVERLOAD
RELAYS
The relays comply with IEC947-4, VDE0660 and GB14048. Several functions provided by these relays are: phase-failure protection, temperature
compensation, ON/OFF indication and manual/automatic reset. The relays can be mounted onto contactors or installed as single units.
Operating Conditions
● The altitude of the site of installation does not exceed 2000 meters
above sea levels.
● The ambient air temperature: -25 ~ +55ºC
● Relative humidity does not exceed 90% at +25ºC
Features
● 3UA series are bimetal thermal relays with release class 10A.
● With differential phase- failure protection
● With continuous current adjusting scale
● With temperature compensation
● With ON/OFF indicator
● With TEST(OFF)button
3
● With Manual/Auto reset button
3UA50 40 - 1F 3.2 - 5 35 16
3UA50 40 - 1G 4 - 6.3 35 16 0.14
3UA50 40 - 1H 5-8 35 20
3UA50 40 - 1J 6.3 - 10 35 25
3UA50 40 - 1K 8 - 12.5 35 25 0.14
3UA50 40 - 2S 10 - 14.5 35 25
3UA52 40 - 1D 2 - 3.2 63 10
3UA52 40 - 1E 2.5 - 4 63 10 0.14
3UA52 40 - 1F 3.2 - 5 63 16
3UA52 40 - 1G 4 - 6.3 63 16
3UA52 40 - 1H 5-8 63 20 0.14
3UA52 40 - 1J 6.3 - 10 63 25
3UA52 40 - 1K 8 - 12.5 63 25
3UA52 40 - 2A 10 - 16 63 35 0.14
3UA52 40 - 2B 12.5 - 20 63 35
3UA52 40 - 2C 16 - 25 63 50
1
) Installing as a single unit with individual wiring only
3UA55 40 - 2C
3UA55 40 - 2D
16 - 25
20 - 32
100
100
50
80 0.20 3
3UA55 40 - 2Q 25 - 36 100 80
3UA55 40 - 2R 32 - 40 100 80
0.20
3UA55 40 - 8M 36 - 45 100 80
Fuse links (A)
Setting range Weight
3UA58 Order No. IEC947 - 4 For contactor
(A) kg
“1” ”2”
1
) Installing as a single unit with individual wiring only
“1” ”2”
“1” ”2”
3UA59 40 - 1A 1 - 1.6 25 6
3UA59 40 - 1B 1.25 - 2 25 6 0.28
3UA59 40 - 1C 1.6 - 2.5 25 6
3UA59 40 - 1D 2 - 3.2 25 10
3UA59 40 - 1E 2.5 - 4 25 10 0.28
3UA59 40 - 1F 3.2 - 5 25 16
3UA59 40 - 1G 4 - 6.3 25 16
3UA59 40 - 1H 5-8 25 16 0.28
3UA59 40 - 1J 6.3 - 10 25 16
3UA59 40 - 1K 8 - 12.5 35 25
3UA59 40 - 2A 10 - 16 63 35 0.28
3UA59 40 - 2B 12.5 - 20 63 50
3UA59 40 - 2C 16 - 25 63 50
3UA59 40 - 2D 20 - 32 80 63 0.28
3UA59 40 - 2E 25 - 40 125 80
3UX1015 400mm
3UX1015 0.07
Cable release 3UX1016 600mm
3UX1016
For resetting relays at a long distance
Sealable cap 3UX1110 For covering setting knob and OFF button 0.01
3UX1111
Links For connection of 3UA62, 3UA66 (to 200A) with 3TF53, 0.1
(1set=3items) 3UX1210 3TF54, 3TB54, 3TD54, 3TE54 contactors
Relay base 3UX1420 For installing 3UA52, 3UA54 as a single unit 0.05
Box terminal block 3UX1424 For installing 3UA60 as a single unit 0.2
1
) Installing as a single unit with individual wiring only
2
) Use 3UX1210 links for connection to 3TF53 contactors
Rated insulation voltage (V) 690 690 690 1000 1000 1000 1000 1000
Rated operational voltage (V) 690 690 690 1000 1000 1000 1000 1000
Type of current, frequency DC; AC up to 400Hz AC 50 to 400Hz
Ambient temperature (ºC) -25~+55 -25~+55 -25~+55 -25~+55 -25~+55 -25~+55 -25~+55 -25~+55
Phase - failure protection Yes Yes Yes Yes Yes Yes Yes Yes
Manual/Auto reset Yes Yes Yes Yes Yes Yes Yes Yes
Temperature compensation Yes Yes Yes Yes Yes Yes Yes Yes
(-25~+55ºC)
Switch position indicator Yes Yes Yes Yes Yes Yes Yes Yes
Test button Yes Yes Yes Yes Yes Yes Yes Yes
Auxiliary contacts 1NO+1NC 1NO+1NC 1NO+1NC 1NO+1NC 1NO+1NC 1NO+1NC 1NO+1NC 1NO+1NC
Switching capacity (380V) AC - 15 1.1A 1.1A 1.1A 1.1A 1.1A 1.1A 1.1A 1.1A
Mounting Plug - in Plug - in as a single unit Plug - in as a single unit as a single unit as a single unit as a single unit
Terminal screw M3.5 M3.5 M3.5 M3.5 M3.5 M3.5 M3.5 M3.5
Protection characteristics
Item No. Times the setting current Release time Test condition
Hot state means heat the overload relay into steady state with the current as shown in “Item 1”
.
6 1.15 0 <2h )2
Hot state
Hot state means heat the overload relay into steady state with the current as shown in “Item 1”
.
1
) Release time with 3-pole symmetrical load at ambient termperature +20ºC
2
) Release time with 3-pole unsymmetrical load (phase-failure) at ambient termperature +20 ºC
Connection leads
Cu 4 mm2, 4 m long
OFF button
3UA66, 3UA68 3UA66, 3UA68 separate mounting of current transformer and release
relay
3. Switching capacity
AC-15 DC-13
Ue Ie Ue Ie
(V) (A) (V) (A)
24 2
60 1.5 24 2
125 1.25 60 0.5
230 1.15 110 0.3
400 1.1 220 0.2
500 1
690 0.8
Panel of 3UA50 3UA52 3UA54 3UA55 Panel of 3UA58 3UA59 3AU60 3UA61 3UA62 3UA66
Overload relays with 3TF or 3TB contactors Overload relay with 3UX14 tripping relay installed as a single unit
terminal brackets as a single unit
b1 b2 c1 c2
I 125 55 80 108
II 130 60 95 100
3UA55+3TF44/45 contactor
3UA58+3UX1421 terminal bracket as a single unit. 3UA59 for installing as a single unit.
3UA58+ a1 a2 a3 b1 b2 b3 c1 d1 d2 d3 e e1 f1 f2 f3 g øg1 g2
3TF46, 3TF47 90 113 70 117 175 100 132 10.5 26.5 25 102 31.5 80 63 122 28 4.8 6.1
3TF48, 3TF49 100 123 80 133 194 110 140 10.5 26.5 25 116 31.5 89 71 132 39 5.5 6.1
3TB46 90 117 70 118 176 100 123 - 29 - - 34 79 61 122 - 4.8 M5
3TB47, 3TB48 100 127 80 130 192 110 140 - 30 - - 36 86 68 128 - 5.8 M5/M6
3UA60 for mounting on to contactors or mounting as a single unit 3UA61 3UA62 for mounting on to contactors and for intalling as a
with 3UX1424. single unit
* ) The distance to earthed part. 1) For 35mm standard mounting rail (DIN EN 50 022).
* * ) The distance to square OFF-button (stroke 3mm) 2) Height and spacing of the connection rails can accmodated to
The distance to round RESET-button (stroke 2.5mm) less 2.5mm 3TF50/3TF52 contactors (not for 3UA61).
a1 a2 a3 b1 b2 b3 c1 d1 d2 d3 e e1 e2 f1 f2 f3 øg1 øg2 g
3TB50 120 147 100 150 230 130 150 37 15 - 133 213 43 90 89 149 7 M6 -
3TF51 120 143 100 150 232 130 150 20 42 37 139 215.5 40.5 93 80 146 6.3 M8 45 3
3TB52 135 162 110 180 257 160 185 42 20 - 154 234 38 115 93 153 7 M8 -
3TF50 120 143 100 150 232 130 150 15 37 37 130 213 40 93 80 146 6.3 6.6 45
3TF52 135 158 110 180 257 160 185 20 42 42 154 234 40 115 93 153 7 M8 48
Type a b c d e f