Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

PROJECT : HILTON CLARK

SUBJECT: FIRE DETECTION AND ALARM SYSTEM - CAUSE AND EFFECT MATRIX
FACP/ANNUNCIATOR / PC MONITORING NOTIFICATION INTERFACING

SUPERVISOR OR TROUBLE INDICATION AT MIMIC FIRE

ALARM SIGNAL AT MAIN FIRE PANEL AND MIMIC FIRE

THRU PA SPEAKERS AND HORN STROBES ON THE FIRE


INITIATE EVACUATION WITH ALARM TONE/MESSAGE

INITIATE EVACUATION WITH ALARM TONE/MESSAGE


SUPERVISOR OR TROUBLE INDICATION AT MAIN FIRE

ACTIVATION OF SOUNDER BASE IN AFFECTED GUEST

OVERRIDE BGM MUSIC ON FIRE FLOOR, ONE FLOOR


ACTIVATE ALL SOUDNER BASES IN THE SAME SUITE

DE-ENERGIZE ELECTRONICALLY LOCKED DOORS IN


Lifts in that Lift Bank go to the next available floor
PRINTER TO PRINT EACH ACTIVITY ON FIRE PANEL

THRU PA SPEAKERS AND HORN STROBES IN THE

KITCHEN GAS SHUT OFF WITH MANUAL RESET


STARICASE PRESSURIZATION FAN ACTIVATION
and stop working while lifts in other lift bank

KITCHEN HOOD EXHAUST AND MAKE-UP AIR


ALARM OR TROUBLE ON FIRE SOFTWARE PC

OVERRIDE BGM MUSIC ON ENIRE BUILDING

LIFT INTERFACE - ALL LIFTS GROUNDED TO


FLOOR, ONE FLOOR ABOVE AND BELOW

STOP AHU ON EVACUATIO FLOORS


SMOKE EXTRACT FAN ACTIVATION
CAUSE AND EFFECT

EGRESS PATH IN PUBLIC AREAS


FIRE SIGNAL STATUS TO BMS
PANEL (HOTEL RECEPTION)

PREDETERMINED FLOORS

(WHERE APPLICABLE)
continue to operate
ABOVE AND BELOW
ENTIRE BUILDING
PANEL (FCC RM)

SHUTDOWN
PANEL.

RM
A B C D E F G H I J K L M N O P Q R S T

Single Room Guest Room Smoke Detector


1 0 0 0 0 4 8 4 8 0 4 4 4 4 4
Activation

Suite Main Guest Room Smoke Detector


2 0 0 0 0 4 8 4 8 0 4 4 4 4 4
Activation

Suite Secondary Guest Room Smoke Detector


3 0 0 0 0 0 4 8 4 8 0 4 4 4 4 4
Activation

4 Hallway/Corridor Smoke Detector Activation 0 0 0 0 4 8 4 8 0 4 4 4 4 4

5 Elevator Lobby Smoke Detector Activation 0 0 0 4 8 4 8 0 0 4 4 4 4 4

6 Common Area Smoke Detector Activation 0 0 0 4 8 4 8 0 4 4 4 4 4

7 Manual Pull Station Activation 0 0 0 0 4 0 4 0 0 0 0 0 0

8 In-Duct Detector Activation 0 0 0

9 Heat Detector Activation 0 0 0 0 4 0 4 0 0 0 0 0 0

10 Carbon Monoxide Detector Alarm 0 0 0

11 Fire Pump Power Fail Signal 0 0 0

12 Low Level Float Alarm 0 0 0

13 Sprinkler/Hydrant Waterflow Switch Activation 0 0 0 0 4 0 4 0 0 0 0 0 0

Server Room or Electrial Room Gas


14 0 0 0 0 4 0 4 0 0 0 0 0 0
Suppression System Activation

15 Kitchen Gas Leak Detector Activation 0 0 0 0

16 Kitchen Hood Suppression System Activation 0 0 0 0 4 0 4 0 0 0 0 0 0 0 0

17 Tamper Switch Alarm 0 0 0

Notes:
1. See below

0 Action Immediately; no time delay


4 Action at the 4th minute if condition still exist
8 Action at the 8th minute if condition still exist

HILTON HOTEL CLARK