ELECTRICAL WORKS- SUBSTATION WORKS

VACCUM CIRCUIT BREAKER PANEL

SL NO PARTICULARS QTY
550 LT DISTRIBUTION SYSTEM
551 MEDIUM VOLTAGE SWITCH BOARD
552 MAIN LT PANEL (S/S BUILDING)
553 SUPPLY, DELIVERY AT SITE, ERECTION, TESTING & COMMISSIONING OF
VERTICAL FLOOR MOUNTING FREE STANDING, EXTENSIBLE ON EITHER
SIDE, COMPARTMENTALISED CUBICAL TYPE PANEL BOARD MADE OF 14
SWG (2.04 MM) CRCA MS SHEET SUITABLE FOR 500/415V, 50HZ, AC, 3
PHASE AND NEUTRAL SYSTEM HAVING THE FOLLOWING FEATURES
PANEL SHALL BE DESIGNED TO ENSURE THAT THE WEIGHT OF THE
COMPONENTS IS ADEQUATLY SUPPORTED WITHOUT DEFORMATION OR
LOSS IN ALLIGNMENT. THE DOORS OF THE CUBICLE SHALL BE FITTED
WITH DUST EXCLUDING NEOPRENE GASKETS WITH FSTNERS FOR
PROPER COMPRESSION OF THE GASKETS.

554 PANEL SHALL BE MULTITIER COMPARTMENTALISED CUBICAL TYPE,


EXTENSIBLE ON EITHER SIDE AND SHALL BE TREATED WITH ALL
NTICORROSIVE PROCESS BEFORE PAINTING WITH TWO COATS OF ZINE
CHROMATE PRIMER AND FINAL APPROVED SHADE OF ENAMEL PAINT.

555 BUSBARS SHALL BE OF CONTINUOUS RATED ALUMINIUM ADEQUATE


FOR SPECIFIED RATED CONTINUOUS AND SHORT CIRCUIT CURRENT
COVERED BY, PROPER GRADED HEAT SHRINKABLE PVC SLEEVES
(COLOR CODED). BUSBARS SHALL BE SUPPORTED BY SUITABLE
HYLAM/DMC/SMC OR COMPATABLE INSULATOR SUPPORTS. HIGH
TENSILE BOLTS AND SPRINGS WASHERS ARE TO BE PROVIDED ON ALL
BUSBARS AND SUITABLE DRILLED HOLES FOR CONNECTION JOINTS. THE
BUSBARS SHALL HAVE A THROUTH FAULT WITH STAND CAPACITY OF
17MVA, RMS SYMMETRICAL FOR ONE SECOND. THE INTERCONNECTIONS
BETWEEN THE BUSBARS AND THE CIRCUIT BREAKERS SHALL BE MADE
BY CONTINUOUS RATED ALUMINIUM STRIPS SUITABLY COVERED BY
PROPER GRADED HEAT SHRINKABLE COLOUR CODED PVC SLEEVES. THE
EARTH BUSBAR SHALL RUN THROUGH THE LENGTH OF THE PANEL AND
TERMINATED AT TWO ENDS.

556 ALL THE MCCBS SHALL BE PROVIDED WITH EXTENDED ROTARY


OPERATED MECHANISM. SAFTY INTERLOCKS ARE TOO BE PROVIDED TO
PREVENT THE DOORS OF THE COMPARTMENTS HOUSING THE MCCBS TO
PREVENT THE DOORS TO OPEN WHEN THE MCCBS ARE 'ON' POSITION.
557 ACBS SHALL BE METAL CLAD, INDOOR TYPE (IN FULLY DRAWOUT
EXECUTION) MOUNTED ON FULLY DRAWOUT TRUCK WITH SERVICE,
TEST AND ISOLATED POSITION AND COMPLETE WITH THE FOLLOWING
SAFTY INTERLOCKS AND SAFTY SHUTTERS AND PADLOCK FACILITY.

558 IT SHALL NOT BE POSSIBLE TO MOVE THE TRUCK IN OR OUT OF CUBICLE


WHEN THE BREAKER IS CLOSED.
559 ACB COMPARTMENT DOOR SHALL BE MACHENICALLY INTERLOCKED SO
THAT IT WILL NOT POSSIBLE TO CLOSE THE ACB IN PLUG POSITION
WHEN THE DOOR IS OPEN.
560 IT SHALL NOT BE POSSIBLE TO PUSH THE TRUCK IN CLOSE POSITION IF
EITHER OF THE SAFETY SHUTTER IS NOT FREE AND NOT IN CLOSE
POSITION.
561 ACBS OF SIMILAR RATING SHALL BE INTERCHANGEABLE. ALL CONTROL
WIRING IN THE PANEL SHALL BE CARRIED OUT WITH 1.1KV GRADE
SINGLE CORE PVC INSULATED COPPER CONDUCTORS OF MINIMUM 2.5
SQ.MM. CROSS SECTION FOR POTENTIAL CIRCUITS AND CT CIRCUITS
WIRING SHOULD BE NEALTY BUNCHED , ADEQUATLY SUPPORTED,
PROPERLY ROULED AND FINALLY CRIMED. WIRES ARE TO BE
INDENTIFIED BY NUMBERED FERULES AT EITHER END. TERMINAL
BLOCKS USED ARE OF DAMP TYPE WITH BARRIERED TERMINALS AND
ARE TO BE NUMBERED.

562 ADEQUATE CABLING SPACE SHOULD BE AVAILABLE IN THE PANEL WITH


CABLE SUPPORTS, CABLE ALLEYS, ETC. PROVISION FOR TOP/BOTTOM
ENTRY AND TERMINATION OF REQUIRED NUMBER OF XLPE CABLE
SHALL BE PROVIDED. THE POSITION OF CONTROL SWITCHES, PUSH
BUTTONS, LEVERS, ETC REQUIRING MANUAL OPERATION SHALL BE AT A
HEIGHT NOT EXCEEDING 1850MM FROM THE FINISHED FLOOR LEVEL.
THE RATE SHALL ALSO INCLUDE PROVIDING AND FIXING SPACE HEATER
WITH THERMOSTAT CONTROL TEMPERATURE CONTROLLER INCLUDING
CONNECTING THE SAME WITH THE SYSTEM WITH ALL OTHER
ACCESSORIES VIZ SOCKETS, ETC. REQUIRED. THE PANEL SHALL ALSO BE
PROVIDED WITH CUBICLE ILLUMINATION LAMPS AS PER REQUIREMENT
INCLUDING CONNECTING THE SAME WITHIN THE PANEL WITH ALL
OTHER ACCESSORIES REQUIRED.

563 THE PANEL SHALL ALSO COMPROMISE OF NECESSARY METERS, CTS,


PROTECTION MCBS/HRC FUSES, INDICATION LAMPS RELAYS, LIFTING
BOLTS, LABEL INSCRIPTIONS (METALIC ENGRAVED INDENTIFICATION
TAGS) DESCRIBING THE RATING OF THE BREAKERS, BUS COUPLERS,
DESIGNATION OF THE FEDEERS ETC INCLUDING ALL OTHER
ACCESSORIES, COMPLETE AS PER IE RULES AND REGULATIONS
CONFORMING TO RELEAVANT IS AND DULY APPROVED BY CLIENT/
CONSULTANT. THE RATE SHALL INCLUDE NECESSARY CUTTING CHASES,
AND MENDING GOOD DAMAGES DURING INSTALLATION. THE PANEL
SHALL HAVE THE FOLLOWING MAJOR COMPONENTS.
564 INCOMER 1
565 3 NOS 1600A, 4P ELECTRICALLY OPERATED, MOTORISED-CUM-MANUAL
SPRING CHARGED WITHDRAWABLE TYPE acb OF RATED SERVICE
VOLTAGE UPTO 690V, 50HZ WITH MANUAL PUSH BUTTONS, INDICATIONS,
CURRENT SENSORS, CTS, ETC CONFIRMING TO THE SPECIFICATION AND
AS FOLLOWS:

566 ICU-50 KA( AT 415V, 50 HZ), ICS= 100% ICU AND ICW NOT LESS THAN 50 KA
FOR 1 SEC.
567 MICROPROCESSOR BASED S/C, E/F & O/C RELEASES.
568 RATED IMPULSE WITHSTAND VOLTAGE NOT LESS THAN 12 KV FOR M,AIN
CONDUCTING PATHS.
569 AUXILIARY CONTACTS, SHUNT TRIP COILS ETC.
570 3 SETS - CORE BALANCE CT WITH EARTH LEAKAGE RELAY.
571 3 SETS CT OPERATED DIGITAL MULTIFUCTION METER HAVING CI-1.0 FOR
APFCR WITH 15 VA BURDEN EACH.
572 3 SET (3 NOS/SET)1600/5-5A DUAL CORE CAST RESIN TYPE CURRENT
TRANSFORMER OF CL-5P10 FOR PROTECTION AND CL-1 FOR METERING
WITH 15VA BURDEN EACH.
573 3 SETS - CT OPERATED 3 O/C + 1 E/F RELAY HAVING PROTECTION CLASS
5P10.
574 2 SET (3 NOS/SET) 1600/5A CAST RESIN TYPE CURRENT TRANSFORMER OF
CL -.10 FOR APFCR WITH 15VA BURDEN EACH.
575 3SET (3 NOS./SET) - CAST RESIN CONSTRUCTION TYPE POTENTIAL
TRANSFORMER 415V/√3 : 110V/√3 WITH CL-0.1 ACCURACY WITH 100VA
BURDEN WITH HRC FUSES AT PRIMARY AND SECONDARY FOR
PROTECTION.

576 3 SETS( 3 NOS EACH) RYB CLUSTER TYPE LED PHASE INDICATION LAMPS.

577 3 SETS(7NOS EACH) - SPRING CHARGED/TEST/ON/OFF/TRIP/SELF


TRIP/TRIP CKT HEALTHY CLUSTER TYPE LED INDICATION LAMPS.
578 2 SETS- LINE VOLTAGE MONITORING MODULE.
579 BUS- COUPLER
580 1 NO. BUS-COUPLER 1600A, 4P ELECTRICALLY OPERATED, MOTORISED
-CUM-MANUAL SPRING CHARGED WITHDRAWABLE TYOE ACB OF RATED
SERVICE VOLTAGE UPTO 690V, 50 HZ WITH MANUAL PUSH BUTTONS,
INDICATIONS, CURRENT SENSORS. CTS ETC CONFIRMING TO THE
SPECIFICATION. ICU= 50KA (AT 415V, 50 HZ). ICS-100% ICU AND ICS NOT
LESS THAN 50KA FOR 1 SEC.MICROPROCESSOR BASED O/L, S/C & E/F
RELEASES WITH PROVISION FOR BACKNET, AUXILLIARY CONTACTS,
SHUNT TRIPS. 5 NOS ON/OFF/TRIP/SPRING CHARGED/TRIP CKT HEALTHY
CLUSTER TYPE LED INDICATION LAMPS ETC COMPLETE.

581 ELECTRICAL WIRED INTERLOCKING BETWEEN INCOMING BREAKERS


AND BUSCOUPLER BREAKER (3 NOS INCOMING & 1 NO BUSCOUPLER
UNIT) AS FOLLOW :
582 AUTO /MANUAL SELECTION FOR WHOLE OPERATION.
583 WHEN BOTH TRANSFORMER FED BREAKERS ARE HEALTHY (MONITORED
BY LVM) THE BUS-COUPLER AND ACB FEEDING DG SUPPLY SHALL BE
OFF.
584 IF ANY VOLTAGE VARIATION, NO VOLTAGE (MONITORED BY LVM) IN ANY
TRANSFORMERSUPPLY BREAKER THEN CLOSING COMMAND TO THE BUS
COUPLER IS TO BE GIVEN.
585 WHEN BOTH TRANSFORMER SUPPLY BREAKERS ARE CLOSED
( MONITORED BY LVM) THE AMF RELAY SHALL GIVE SIGNAL TO THE DG
CONTROL PANEL CLOSING THE DG SUPPLY ACB AND BUSCOUPLER. RATE
SHOULD INCLUDE AUXILIARY CONTACTS, SELECTOR SWITCHES, AMF
RELAY , PUSH BUTTONS, TIMERS ETC. INCLUDING ALL OTHER
MATERIALS TO SATISFY THE ABOVE OPERTION.

586 BUSBAR
587 2 SETS- 1600A, 415V, 50 HZ, 31 MVA AMPS SYMMETRICAL CONTINUOUS
RATED ALUMINIUM BUSBARS ( 2 NOS. 100MM X 10MM FOR PHASES AND 1
NO. 100MM X 10MM FOR NEUTRAL) MOUNTED ON SUITABLE
HYLAM/DMC/SMC/ INSULATORS/SUPPORTS WITH PROPER GRADED
COLOUR CODED HEAT SHRINKABLE PVC SLEEVES. SURGE PROTECTION
DEVICE WITH MPCB WITH RATED KA.

588 OUTGOING
589 a) 2 NOS 800A, 4P MANUALY OPERTAED TYPE ACB OF RATED SERVICE
VOLTAGE UPTO 690V, 50 HZ WITH AMNUAL PUSH BUTTONS, INDICATIONS,
CURRENT SENSORS, CTS, ETC CONFIRMING TO THE SPECIFICATION AND
AS FOLLOWS : ACB SHALL HAVE CURRENT AND VOLTAGE DISPLAY AND
LED INDICATION. ACB SHALL RECORD LAST 10 TRIP DATA HISTORY. ALL
VOLTAGE RELEASES SHALL BE FOR CONTINUOUSLY RATED.

590 ICU- 50 KA (AT 415V, 50HZ), ICS = 100% ICU &ICW NOT LESS THAN 50KA
FOR 1 SEC.
591 MICROPROCESSOR BASED S/C, E/F & O/C RELEASES.
592 2 SET - ON, OFF,TRIP SPRING CHARGED,READY TO CLOSE INDICATION
LED LAMPS WITH BACK-UP MCB.
593 2 SET OF R,Y,B INDICATING LAMPS, LED TYPE WITH 3 NOS. PROTECTION
FUSES.
594 2 SET VOLTMETER SELECTOR SWITCH WITH 3 NOS. PROTECTION FUSES.

595 2 SETS (3 NOS/SET)-800/5A, CL-1, 15VA CTS, 1 NO. ANALOG AMMETER (96
SQMM) 0-800A WITH SELECTOR SWITCH.
596 b) 2 NOS. 400A, 4P MCCBS' OF RATED SERVICE VOLTAGE UPTO 690V, ICU=
36KA ICS= 100% IEU AT 415V, 50 HZ WITH THERMO- MAGNETIC BASED O/L
& S/C RELEASES INCLUDING EXTENDED ROTARY OPERATED
MECHANISM, SHUNT TRIP COILS, AUXILIARY CONTACTS, SPREADERS
ETC AS NECESSARY.

597 2 SETS(3 NOS/SET) - 400/5A, CL-1, 15V CTS, 1 NO. ANALOG AMMETER (96
SQMM) 0-400A WITH SELECTOR SWITCH.
598 2 SETS- ( 3 NOS. EACH) - ON/ OFF/TRIP CLUSTER TYPE LED INDICATION
LAMPS FOR THE ABOVE MCCBS.
599 c) 2 NOS 250A, 4P MCCBS OF RATED SERVICE VOLTAGE UPTO 690V, ICU =
36 KA, ICS= 100% IEY AT 415V, 50HZ WITH THERMO-MAGNETIC BASED O/L
& S/C RELEASES INCLUDING EXTENDED ROTARY OPERATED
MECHANISM, SHUNT TRIP COILS. AUXILIARY CONTACTS, SPREADERS
ETC AS NECESSARY.

600 2 SETS ( 3 NOS/SET) - 250/5A, CL-1, 15VA CTS, 1 NO. ANALOG AMMETER ( 96
SQMM) 0-250A WITH SELECTOR SWITCH.
601 2SETS- ( 3 NOS EACH)- ON/OFF/TRIP CLUSTER TYPE LED INDICATION
LAMPS FOR THE ABOVE MCCBS.
602 d) 8 NOS 320A, 4P MCCBS OF RATED SERVICE VOLTAGE UPTO 690V. ICU=
100% IEU AT 415V, 50 HZ WITH THERMO MAGNETIC BASED O/L & S/C
RELEASES INCLUDING EXTENDED ROTARY OPERATED MECHANISM,
SHUNT TRIP COILS. AUXILIARY CONTACTS, SPREADERS ETC AS
NECESSARY.

603 8 SETS (3 NOS/SET) - 320/5A, CL-1, 15VA CTS, 1 NO. ANALOG AMMETER
( 96SQMM) 0-320A WITH SELECTOR SWITCH.
604 2 SETS- ( 3 NOS EACH) ON/OFF/TRIP CLUSTER TYPE LED INDICATION
LAMPS FOR THE ABOVE MCCBS.
605 e) 2 NOS 160A, 4P MCCBS OF RATED SERVICE VOLTAGE UP TO 690V, ICU=
25KA ICS= 100% IEU AT 415V, 50HZ WITH THERMO-MAGNETIC BASED O/L,
S/C RELEASES INCLUDING EXTENDED ROTARY OPERATED MECHANISM,
SHUNT TRIP COILS. AUXILIARY CONTACTS, SPREADERS ETC AS
NECESSARY.

606 2 SETS ( 3 NOS/SET) - 160/5A, CL-1, 15VA CTS, 1 NO. ANALOG AMMETER ( 96
SQMM) 0-160A WITH SELECTOR SWITCH.
607 2 SETS- ( 3 NOS EACH) ON/OFF/TRIP CLUSTER TYPE LED INDICATION
LAMPS FOR THE ABOVE MCCBS.
608 f) 2 NOS 100A, 4P MCCBS OF RATED SERVICE VOLTAGE UP TO 690V, ICU=
25KA ICS= 100% IEU AT 415V, 50HZ WITH THERMO-MAGNETIC BASED O/L,
S/C RELEASES INCLUDING EXTENDED ROTARY OPERATED MECHANISM,
SHUNT TRIP COILS. AUXILIARY CONTACTS, SPREADERS ETC AS
NECESSARY.

609 2 SETS ( 3 NOS/SET) - 100/5A, CL-1, 15VA CTS, 1 NO. ANALOG AMMETER ( 96
SQMM) 0-100A WITH SELECTOR SWITCH.
610 2 SETS- ( 3 NOS EACH) ON/OFF/TRIP CLUSTER TYPE LED INDICATION
LAMPS FOR THE ABOVE MCCBS.
611 g) 2 NOS - 63A 4P MCB( C-CURVE) OF RATED SERVICE VOLTAGE UPTO 415V,
ICU= 10KA , ICS= 100% ICU AT 240V 50HZ WITH THERMOMAGNETIC BASED
O/L & S/C RELEASES.
612 2 SETS- ( 3 NOS EACH) 63/5A, CL- 0.1 , 5VA , CTS WITH DIGITAL DUAL
ENERGY METER SHOWING MAXIMUM DEMAND.
613 2 SETS- (2 NOS EACH) ON/OFF CLUSTER TYPE LED INDICATION LAMPS
FOR THE ABOVE MCBS.
614 h) 8NOS -6- 32A 4P MCB( C-CURVE) OF RATED SERVICE VOLTAGE UPTO
415V, ICU= 10KA , ICS= 100% ICU AT 240V 50HZ WITH THERMOMAGNETIC
BASED O/L & S/C RELEASES.
615 2 SETS- ( 3 NOS EACH) 32/5A, CL- 0.1 , 5VA , CTS WITH DIGITAL DUAL
ENERGY METER SHOWING MAXIMUM DEMAND.
616 2 SETS- (2 NOS EACH) ON/OFF CLUSTER TYPE LED INDICATION LAMPS
FOR THE ABOVE MCBS.
617 i)3 NOS- 63A, TP, 10KA MCB(C-CURVE).
618 j)4NOS - 20A, SP , 10KA MCB (C-CURVE).
619 3 NOS. 415/240V, 200VA CONTROL TRANSFORMER.
620 EARTH BUSBAR
621 1SET - 50MM X 10 MM GI BUSBAR RUNNING ALONG THE BASE FRAME
COVERING ENTIRE LENGTH OF THE PANEL WITH HIGH TENSILE BOLTS,
NUTS, ETC AND NUMBER OF DRILLED HOLES AS REQUIRED FOR EARTH
CONNECTION AT BOTH ENDS.

622 1 NO. DANGER BOARD


623 440 KVAR AUTOMATIC POWER FACTOR CONTROL PANEL. 2
624 SUPPLY INSTALLATION TESTING AND COMISSIONING OF 500/415V, 50HZ
AC, 3 PHASE AUTOMATIC POWER FACTOR CORRECTION PANEL. THE
PANEL SHALL BE MADE OF 14 SWG THICK CRCA SHEET STEEL,
COMPARTMENTALIZED WITH METALIC PARTITIONS HAVING CONCEALED
HINGES, NEOPRENE RUBBER GASKETS, BRASS WIRE MESH FOR
VENTILATION OF CAPACITORS BY PROVIDING LAFGE SIZE OF AIR
LOUVERS. THE PANEL SHALL BE FREE STANDING WITH MS CHANNEL
BASE TO BE GROUTED ON FLOOR.

625 CABLE ALLEY SHOULD BE PROVIDED AT THE PANEL FOR TOP/BOTTOM


ENTRY OF CABLES, TERMINATION OF INCOMER MCCB AND ALSO
MULTICORE COPPER CONTROL OF SUITABLE CROSS SECTION FROM CTS
(EXISTING) IN THE MAIN LT PANEL, INCLUDING SUPPLYING AND LAYING
OF THE SAME CONTROL CABLE COMPLETE AS PER REQUIREMENT AND
WITH HORIZONTAL/VERTICAL COPPER LINK BARS OF REQUIRED
SECTION AND COVERED BY PROPER GRADED COLOUR CODED HEAT
SHRINKABLE PVC SLEEVES. EACH APFC PANEL SHALL CONSIST OF
FOLLOWING COMPONENTS :

626 INCOMER
627 1 NO 800AMP, 415V (UIMP= 12 KV) , ICW = 50KA OR HIGHER FOR 1 SEC (ICU
@415V =ICS=50KA MINIMUM) 3POLE MDO( MANUALLY OPERATED DRAW
OUT) TYPE MICROPROCESSOR CONTROLLED MODULAR ACB WITH LSG
RELEASE (ZONE : O/L,S/C, & GROUND FAULT); ACB SHALL HAVE
CURRENT AND VOLTAGE DISPLAY & LED INDICATION. ACB SHALL
RECORD LAST 10 TRIP DATA HISTORY. ALL VOLTAGE RELEASES SHALL BE
FOR CONTINUOUSLY RATED.

628 1 SET (3NOS EACH) - ON, OFF , TRIP, SPRING CHARGED, READY TO CLOSE
INDICATION LED LAMPS WITH BACK-UP MCB.
629 1 SET (3NOS EACH) - R-Y-B PHASE INDICATION LAMPS WITH 3NOS IA,SP,
MCB PROTECTION.
630 1 SET (3NOS/SET)- 800/5A, 10VA, CI-1 CURRENT TRANSFORMER.
631 1 SET CT OPERATED DIGITAL MULTIFUCTION METER HAVING CI-1
ACCURACY AND SHOWING (A,V,F MAXIMUM DEMAND).
632 1 SET -(0-500A) FLUSH MOUNTING ANALOGUE AMMETER WITH
AMMETER.
633 1 SET - (0-500V) FLUSH MOUNTING ANALOGUE VOLTMETER WITH VOLT
SELECTOR SWITCH AND HRC FUSE PROTECTION.
634 1 SET (3 NOS/SET) - CAST RESIN CONSTRUCTION TYPE POTENTIAL
TRANSFORMER 415 V/√3 WITH CL-0.1 ACCURACY WITH 100VA BURDEN
WUTH HRC FUSES AT PRIMARY AND SECONDARY FOR PROTECTION.

635 1 SET OF AUTO/MANUAL SELECTOR SWITCH.


636 BUSBAR
637 A) 1 SET - 1000A, 500V, 50 Hz, (125 MM x 6 MM) FOR NEUTRAL TPN
ALUMINIUM BUS BARS, CAPABLE FOR WITH STANDING STC OF 36 KS FOR
1 SECOND TO BE MOUNTED ON DMC/SMC INSULATOR COVERED WITH
COLOUR CODED HEAT SHRINKABLE PVC SLEEVES. SURGE PROTECTION
DEVICE WITH MPCB WITH RATED KA.

638 APRCR RELAY


639 MICROPROCESSOR BASED 12 STAGE POWER FACTOR CONTROLLER
OPERATED BY 3 NOS CT INPIUT AND MEASUREMENT OF 3 PHASE
VOLTAGE HAVING LCD DISPLAY. IT MUST DISPLAY POWER FACTOR. THE
CONTROLLER MUST ALSO HAVE ON/OFF/FAULT INDICATION FOR EACH
CONNECTED CAPACITOR.

640 OUTGOING
641 A) 2 NOS - 200A, 440V HRC FUSE FOR CAPACITOR DUTY CONTACTOR,

642 B) 2 NOS - 100A, 440V HRC FUSE FOR CAPACITOR DUTY CONTACTOR,

643 C) 6 NOS - 63A, 440V HRC FUSE FOR CAPACITOR DUTY CONTACTOR,

644 D) 2 NOS - 25A, 440V HRC FUSE FOR CAPACITOR DUTY CONTACTOR,

645 E) 2 NOS - TP CAPACITOR DUTY CONTACTOR FOR AUTOMATIC


SWITCHING 100 KVAR CAPACITOR.
646 F) 2 NOS - TP CAPACITOR DUTY CONTACTOR FOR AUTOMATIC
SWITCHING OF 50 KVAR CAPACITOR.
647 G) 6 NOS - TP CAPACITOR DUTY CONTACTOR FOR AUTOMATIC
SWITCHING OF 20 KVAR CAPACITOR.
648 H) 2 NOS - TP CAPACITOR DUTY CONTACTOR FOR AUTOMATIC
SWITCHING OF 10 KVAR CAPACITOR.
649 I) 12 SETS - ON/OFF PUSH BUTTON FOR MANUAL OPERATION WITH LED
INDICATION LAMP.
650 EARTH BUSBAR
651 1 SET - 40 MM x 6 MM GI BUSBAR RUNNING ALONG THE BASE FRAME
COVERING ENTIRE LENGTH OF THE PANEL WITH HIGH TENSILE BOLTS,
NUTS, ETC. AND NUMBER OF DRILLED HOLES AS REQUIRED FOR EARTH
CONNECTION AT BOTH ENDS.

652 1 NO. DANGER BOARD


653 GROUND FLOOR LT PANEL. 1
654 SUPPLY, DELIVERY AT SITE ERECTION, TESTING & COMMISSIONING OF
VERTICAL FLOOR MOUNTING FREE STANDING, EXTENSIBLE ON EITHER
SIDE, COMPARTMENTALISED CUBICAL TYPE PANEL BOARD MADE OF 14
SWG (2.04MM) CRCA MS SHEET SUITABLE FOR 500/415V, 50 HZ, AC, 3
PHASE AND NEUTRAL SYSTEM HAVING THE FOLLOWING FEATURES
PANEL SHALL BE DESIGNED TO ENSURE THAT THE WEIGHT OF THE
COMPONENTS IS ADEQUATELY SUPPORTED WITHOUT DEFORMATION OR
LOSS IN ALLIGNMENT. THE DOORS OF THE CUBICLE SHALL BE FITTED
WITH DUST ECLUDING NEOPRENE GASKETS WITH FASTNERS FOR
PROPER COMPRESSION OF THE GASKETS.

655 PANEL SHALL BE MULTITIER COMPARTMENTALISED CUBICAL TYPE,


EXTENSIBLE ON EITHER SIDE AND SHALL BE TREATED WITH ALL
NTICORROSIVE PROCESS BEFORE PAINTING WITH TWO COATS OF ZINE
CHROMATE PRIMER AND FINAL APPROVED SHADE OF ENAMEL PAINT.

656 BUSBARS SHALL BE OF CONTINUOUS RATED ALUMINIUM ADEQUATE


FOR SPECIFIED RATED CONTINUOUS AND SHORT CIRCUIT CURRENT
COVERED BY, PROPER GRADED HEAT SHRINKABLE PVC SLEEVES
(COLOR CODED). BUSBARS SHALL BE SUPPORTED BY SUITABLE
HYLAM/DMC/SMC OR COMPATABLE INSULATOR SUPPORTS. HIGH
TENSIBLE BOLTS AND SPRINGS WASHERS ARE TO BE PROVIDED ON ALL
BUSBARS AND SUITABLE DRILLED HOLES FOR CONNECTION JOINTS. THE
BUSBARS SHALL HAVE A THROUTH FAULT WITHSTAND CAPACITY OF 31
MVA, RMS SYMMENTRICAL FOR ONE SECOND. THE INTERCONNECTIONS
BETWEEN THE BUSBARS AND THE CIRCUIT BREAKERS SHALL BE MADE
BY CONTINUOUS RATED ALUMINIUM STRIPS SUITABLY COVERED BY
PROPER GRADED HEAT SHRINKABLE COLOUR CODED PVC SLEEVES. THE
EARTH BUSBAR SHALL RUN THROUGH THE LENGTH OF THE PANEL AND
TERMINATED AT TWO ENDS.

657 ALL THE MCCBS SHALL BE PROVIDED WITH EXTENDED ROTARY


OPERATED MECHANISM. SAFTY INTERLOCKS ARE TOO BE PROVIDED TO
PREVENT THE DOORS OF THE COMPARTMENTS HOUSING THE MCCBS TO
PREVENT THE DOORS TO OPEN WHEN THE MCCBS ARE 'ON' POSITION.
658 ADEQUATE CABLING SPACE SHOULD BE AVAILABLE IN THE PANEL WITH
CABLE SUPPORTS, CABLE ALLEYS, ETC. PROVISION FOR TOP/BOTTOM
ENTRY AND TERMINATION OF REQUIRED NUMBER OF XLPE CABLE
SHALL BE PROVIDED. THE POSITION OF CONTROL SWITCHES, PUSH
BUTTONS, LEVERS, ETC REQUIRING MANUAL OPERATION SHALL BE AT A
HEIGHT NOT EXCEEDING 1850MM FROM THE FINISHED FLOOR LEVEL.
THE RATE SHALL ALSO INCLUDE PROVIDING AND FIXING SPACE HEATER
WITH THERMOSTAT CONTROL TEMPERATURE CONTROLER INCLUDING
CONNECTING THE SAME WITH THE SYSTEM WITH ALL OTHER
ACCESSORIES VIZ SOCKETS. ETC. REQUIRED. THE PANEL SHALL ALSO BE
PROVIDED WITH CUBICLE ILLUMINATION LAMPS AS REQUIREMENT
INCLUDING CONNECTING THE SAME WITHIN THE PANEL WITH ALL
OTHER ACCESSORIES REQUIRED.

659 THE PANEL SHALL ALSO COMPROMISE OF NECESSARY METERS, CTS,


PROTECTION MCBS/HRC FUSES, INDICATION LAMPS RELAYS, LIFTING
BOLTS, LABEL INSCRIPTIONS (METALIC ENGRAVED INDENTIFICATION
TAGS) DESCRIBING THE RATING OF THE BREAKERS, BUS COUPLERS,
DESIGNATION OF THE RATING OF THE BREAKERS, BUS COUPLERS,
DESIGNATION OF THE FEEDERS ETC INCLUDING ALL OTHER
ACCESSORIES, COMPLETE AS PER IE RULES AND REGULATIONS
CONFORMING TO RELEVANT IS AND DULY APPROVED BY
CLIENT/CONSULTANT. THE RATE SHALL INCLUDE NECESSARY CUTTING
CHAES, AND MENDING GOOD DAMAGES DURING INSTALLATION. THE
PANEL SHALL HAVE THE FOLLOWING MAJOR COMPONENTS.

660 INCOMER
661 1 NO 320A, 4P ELECTRICALLY OPERATED, THERMO-MAGNETIC BASED
MCCB OF RELATED SERVICE VOLTAGE UPTO 690V, 50 HZ WITH MANUAL
PUSH BUTTONS, INDICATIONS, CURRENT SENSORS, CTS, ETC
CONFORMING TO THE SPECIFICATION AND AS FOLLOWS:

662 ICU-36KA ( AT 415V, 50 HZ), IC=100% ICU AND ICW NOT LESS THAN 36 KA
FOR 1 SEC.
663 THERMO-MAGNETIC S/C & O/C RELEASES.
664 RATED IMPULSE WITHSTAND VOLTAGE NOT LESS THAN 12 KV FOR M,AIN
CONDUCTING PATHS.
665 AUXILIARY CONTACTS, SHUNT TRIP COILS ETC.
666 1 SET. - CORE BALANCE CT WITH EARTH FAULT RELAY.
667 1 SET (3 NOS/SET) - 320/5A. 10VA, CL-1 CURRENT TRANSFORMER.
668 1 NO. - CT OPERATED DIGITAL MULTIFUCTION METER HAVING CL-1
ACCURACY AND SHOWING (A, V, F, MAXIMUM DEMAND)
669 1 SET (3 NOS/SET) - CAST RESIN CONSTRUCTION TYPE POTENTIAL
TRANSFORMER 415 V/√3 WITH CL-0.1 ACCURACY WITH 100VA BURDEN
WUTH HRC FUSES AT PRIMARY AND SECONDARY FOR PROTECTION.

670 1 SET (3 NOS EACH) RYB CLUSTER TYPE LED PHASE INDICATION LAMPS.
671 1 SET (3 NOS EACH) RYB CLUSTER TYPE LED PHASE INDICATION LAMPS.

672 1 SET - ON/OFF ILUMINATED PUSH BUTTON.


673 BUSBAR
674 1 SET - 400A, 415V, 50 HZ, 31 MVA AMPS SYMMETRICAL CONTINUOUS
RATED ALUMINIUM BUSBARS (40 MM x 10 MM) FOR PHASE AND 1 NO. 40
MMx 6 MM FOR NEUTRAL) MOUNTED ON SUITABLE HYLAM/DMC/SMC/
INSULATORS/SUPPORTS WITH PROPER GRADED COLOUR CODED HEAT
SHRINKABLE PVC SLEEVES.

675 OUTGOING
676 A) 11 NOS - 63A, FP, 10KA MCB (C-CURVE) OF RATED SERVICE VOLTAGE
UPTO 415V, ICU=10KA, ICS= 100% ICU AT 415V 50HZ, WITH THERMO-
MAGNETIC BASED O/L & S/C RELEASES.
677 11 SETS - (3 NOS EACH) 63/5A, CL-1.0, 5VA, CTS WITH DIGITAL DUAL
ENERGY METER SHOWING (A, V, F, MAXIMUM DEMAND).
678 EARTH BUSBAR
679 1 SET - 25 MMx 6 MM GI BUSBAR RUNNING ALONG THE BASE FRAME
COVERING ENTIRE LENGTH OF THE PANEL WITH HIGH TENSIBLE BOLTS,
NUTS, ETC. AND NUMBER OF DRILLED HOLES AS REQUIRED FOR EARTH
CONNECTION AT BOTH ENDS.

680 1 NO. DANGER BOARD


681 FIRST FLOOR TO SEVENTH FLOOR LT PANEL
682 SUPPLY, DELIVERY AT SITE ERECTION, TESTING & COMMISSIONING OF
VERTICAL FLOOR MOUNTING FREE STANDING, EXTENSIBLE ON EITHER
SIDE, COMPARTMENTALISED CUBICAL TYPE PANEL BOARD MADE OF 14
SWG (2.04MM) CRCA MS SHEET SUITABLE FOR 500/415V, 50 HZ, AC, 3
PHASE AND NEUTRAL SYSTEM HAVING THE FOLLOWING FEATURES
PANEL SHALL BE DESIGNED TO ENSURE THAT THE WEIGHT OF THE
COMPONENTS IS ADEQUATLY SUPPORTED WITHOUT DEFORMATION OR
LOSS IN ALLIGNMENT. THE DOORS OF THE CUBICLE SHALL BE FITTED
WITH DUST EXCLUDING NEOPRENE GASKETS FASTNERS FOR PROPER
COMPRESSION OF THE GASKETS.

683 PANEL SHALL BE MULTITIER COMPARTMENTALISED CUBICAL TYPE,


EXTENSIBLE ON EITHER SIDE AND SHALL BE TREATED WITH ALL
NTICORROSIVE PROCESS BEFORE PAINTING WITH TWO COATS OF ZINE
CHROMATE PRIMER AND FINAL APPROVED SHADE OF ENAMEL PAINT.
684 BUSBARS SHALL BE OF CONTINUOUS RATED ALUMINIUM ADEQUATE
FOR SPECIFIED RATED CONTINUOUS AND SHORT CIRCUIT CURRENT
COVERED BY, PROPER GRADED HEAT SHRINKABLE PVC SLEEVES
(COLOR CODED). BUSBARS SHALL BE SUPPORTED BY SUITABLE
HYLAM/DMC/SMC OR COMPATABLE INSULATOR SUPPORTS. HIGH
TENSIBLE BOLTS AND SPRINGS WASHERS ARE TO BE PROVIDED ON ALL
BUSBARS AND SUITABLE DRILLED HOLES FOR CONNECTION JOINTS. THE
BUSBARS SHALL HAVE A THROUTH FAULT WITHSTAND CAPACITY OF 31
MVA, RMS SYMMENTRICAL FOR ONE SECOND. THE INTERCONNECTIONS
BETWEEN THE BUSBARS AND THE CIRCUIT BREAKERS SHALL BE MADE
BY CONTINUOUS RATED ALUMINIUM STRIPS SUITABLY COVERED BY
PROPER GRADED HEAT SHRINKABLE COLOUR CODED PVC SLEEVES. THE
EARTH BUSBAR SHALL RUN THROUGH THE LENGTH OF THE PANEL AND
TERMINATED AT TWO ENDS.

685 ALL THE MCCBS SHALL BE PROVIDED WITH EXTENDED ROTARY


OPERATED MECHANISM. SAFTY INTERLOCKS ARE TOO BE PROVIDED TO
PREVENT THE DOORS OF THE COMPARTMENTS HOUSING THE MCCBS TO
PREVENT THE DOORS TO OPEN WHEN THE MCCBS ARE 'ON' POSITION.

686 ADEQUATE CABLING SPACE SHOULD BE AVAILABLE IN THE PANEL WITH


CABLE SUPPORTS, CABLE ALLEYS, ETC. PROVISION FOR TOP/BOTTOM
ENTRY AND TERMINATION OF REQUIRED NUMBER OF XLPE CABLE
SHALL BE PROVIDED. THE POSITION OF CONTROL SWITCHES, PUSH
BUTTONS, LEVERS, ETC REQUIRING MANUAL OPERATION SHALL BE AT A
HEIGHT NOT EXCEEDING 1850MM FROM THE FINISHED FLOOR LEVEL.
THE RATE SHALL ALSO INCLUDE CONNECTING THE SAME WITH THE
SYSTEM WITH ALL OTHER ACCESSORIESW VIZ SOCKETS. ETC.
REQUIRED. THE PANEL SHALL ALSO BE PROVIDED WITH CUBICLE
ILLUMINATION LAMPS AS PER REQUIEMENT INCLUDING CONNECTING
THE SAME WITHIN THE PANEL WITH ALL OTHER ACCESSORIES
REQUIRED.

687 THE PANEL SHALL ALSO COMPROMISE OF NECESSARY METERS, CTS,


PROTECTION MCBS/HRC FUSES, INDICATION LAMPS RELAYS, LIFTING
BOLTS, LABEL INSCRIPTIONS (METALIC ENGRAVED INDENTIFICATION
TAGS) DESCRIBING THE RATING OF THE BREAKERS, BUS COUPLERS,
DESIGNATION OF THE FEEDERS ETC. INCLUDING ALL OTHER
ACCESSORIES, COMPLETE AS PER IE RULES AND REGULATION
CONFORMING TO RELEVANT IS AND DULY APPROVED BY
CLIENT/CONSULTANT. THE RATE SHALL INCLUDE NECESSARY CUTTING
CHASES. AND MENDING GOOD DAMAGES DURING INSTALLATION. THE
PANEL SHALL HAVE THE FOLLOWING MAJOR COMPONENTS.

688 INCOMER
689 1 NO 320A, 4P ELECTRICALLY OPERATED, THERMO-MAGNETIC BASED
MCCB OF RELATED SERVICE VOLTAGE UPTO 690V, 50 HZ WITH MANUAL
PUSH BUTTONS, INDICATIONS, CURRENT SENSORS, CTS, ETC
CONFORMING TO THE SPECIFICATION AND AS FOLLOWS:

690 ICU-36 KA (AT 415V, 50HZ), ICS=100% ICU AND ICW NOT LESS THAN 36KA
FOR 1 SEC.
691 THERMO-MAGNETIC S/C & O/C RELEASES.
692 RATED IMPULSE WITHSTAND VOLTAGE NOT LESS THAN 12 KV FOR M,AIN
CONDUCTING PATHS.
693 AUXILIARY CONTACTS, SHUNT TRIP COILS ETC.
694 1 SET - CORE BALANCE CT WITH EARTH FAULT RELAY.
695 1 SET (3 NOS/SET) - 320/5A. 10VA, CL-1 CURRENT TRANSFORMER.
696 1 NO - CT OPERATED DIGITAL MULTIFUNCTION METER HAVING CL-1
ACCURACY AND SHOWING (A, V, F, MAXIMUM DEMAND).
697 1 SET (3 NOS/SET) - CAST RESIN CONSTRUCTION TYPE POTENTIAL
TRANSFORMER 415 V/√3 : 110V/√3 WITH CL-0.1 ACCURACY WITH 100VA
BURDEN WITH HRC FUSES AT PRIMARY AND SECONDARY FOR
PROTECTION.

698 1 SET (3 NOS EACH) RYB CLUSTER TYPE LED PHASE INDICATION LAMPS.

699 1 SET (3 NOS EACH) - ON/OFF/TRIP CLUSTER TYPE LED INDICATION


LAMPS.
700 1 SET - ON/OFF ILUMINATED PUSH BUTTON.
701 BUSBAR
702 1SET -400A , 415V, 50 HZ , 31MVA AMPS SYMMETRICAL CONTINUOUS
RATED ALUMINIUM BUSBARS (40MM X 10 MM FOR PHASES AND 1 NO
40MM X 6MM FOR NEUTRAL) MOUNTED ON SUITABLE HYLAM/DMC/SMC
INSULATORS/ SUPPORTS WITH PROPER GRADED COLOUR CODED HEAT
SHRINKABLE PVC SLEEVES.

703 OUTGOING
704 a) 10 NOS - 63A , FP, 10KA MCB (C-CURVE) OF RATED SERVICE VOLTAGE
UPTO 415V, ICU= 10KA, ICS = 100% ICU AT 415V 50 HZ , WITH THERMO-
MAGNETIC BASED O/L & S/C RELEASES.
705 10 SETS- (3NOS EACH)63/5A, CL-1.0, 5VA, CTS WITH DIGITAL DUAL
ENERGY METER SHOWING (A,V,F , MAXIMUM DEMAND).
706 EARTH BUSBAR
707 1 SET- 25MM X 6 MM GI BUSBAR RUNNING ALONG THE BASE FRAME
COVERING ENTIRE LENGTH OF THE PANEL WITH HIGH TENSILE BOLTS,
NUTS ETC AND NUMBER OF DRILLED HOLES AS REQUIRED FOR EARTH
CONNECTIONAT BOTH ENDS.

708 1 NO DANGER BOARD


709 ISOLATOR PANEL(S/S BUILDING)
710 SUPPLY INSTALLATION TESTING AND COMMISSIONING OF THE FLOOR 2
STANDING/WALL MOUNTING DEAD TYPE ISOLATOR PANEL MADE OF 14
SWG (2.03 MM) CRCA SHEET METAL FABRICATED INDOOR TYPE
SUITABLE FOR 500/415V , 50 HZ, AC , 3PHASE AND NEUTRAL SYSTEM,
WITH POWER COATED ANTICORROSIVE PAINT SUITABLE FOR FRONT
OPERATION OF LOAD BREAK SWITCH, BUSBAR CHAMBERS IN BOTH
INCOMING AND OUTGOING FEEDERS, CABLEAND BOXES, SUITABLE TO
TERMINATE UPTO 4 NOS. 3.5C 400SQMM XLPE CABLE ON BOTH SIDES,
NECESSARY METERS, SMALL WIRING WITH COPPER WIRE OF MINIMIUM
2.5SQMM CROSS SECTION, PROTECTION HRC FUSES, TERMINAL BLOCKS,
SELECTOR SWITCHES ETC INCLUING SUPPLY AND FIXING OF THE
EQUIPMENTS WITH SUITABLE INTERCONNECTIONS WITH ALUMINIUM
BARS, GLAND PLATES, EARTH BUS, REBEL INCRIPTION , DOOR
INTERLOCKING BOLTING SOCKETING, PAINTING, EARTHING ETC ALL
COMPLETE INCLUDING NECESSARY CHASES AND MENDING GOOD
DAMAGES AND DULY APPROVED BY THE CONSULTANT. THE ABOVE
PANEL COMPRISING THE FOLLOWING MAJOR COMPONENTS :

711 1 NO. 1600A , 4P 415 V, 50 HZ LOAD BREAK SWITCH (AC 23A)


712 1SET (3 NOS.) - 1600/5A, CL-1.0 , 15VA CTS WITH ANALOG AMMETER 0-
1600A WITH SELECTOR SWITCH.
713 1SET -0-500V, AC, VOLTMETER WITH 3 NOS MCBS AND SELECTOR SWITCH.

714 2 SETS (3NOS)-R-Y-B PHASE INDICATION CLUSTER TYPE LED LAMPS.

715 1 SET- 50MM X 6MM GI BUSBAR RUNNING ALONG THE BASE FRAME
COVERING ENTIRE LENGTH OF THE PANEL WITH HIGH TENSILE BOLTS,
NUTS ETC AND NUMBER OF DRILLED HOLES AS REQUIRED FOR EARTH
CONNECTIONAT BOTH ENDS.

716 1 NO. DANGER BOARD


717 MCCB WITH ENCLOSURE AT GROUND FLOOR
718 7 NOS-320A, 415V (UIMP=8KV), 36KA (ICU=ICS=100%),4P NON DRAWOUT 7
TYPE THERMO MAGNETIC MCCB HAVING FRONT II FACIA, DOUBLE
BREAK TECHNOLOGY. MCCB SHALL BE WITH ADJUSTABLE O/L SETTING
WITH ENCLOSER.

719 MCB WITH ENCLOSURE AT GROUND FLOOR


720 3 NOS-63A, TP, 10KA MCB (C-CURVE) WITH ENCLOSER. 3
UNIT RATE TOTAL
NO 0.00
NO. 0.00
NO 0.00
0.00
0.00
0.00

0.00

0.00
NOS 0.00

NOS 0.00

NOS 0.00
ELECTRICAL WORKS- SUBSTATION WORKS
VACCUM CIRCUIT BREAKER PANEL

SL NO PARTICULARS QTY
484 SUPPLY, DELIVERY AT SITE , ERECTION, TESTING & COMMISSIONING OF 1
THE FOLLOWING SWITCH BOARD PANEL(S) INCLUDING MAKING/ SUPPLY
NECESSARRY CC FOUNDATION, MOUNTING CHANNELS ETC AND FIXING
THE PANEL (S) ON THE FOUNDATION AND MOUNTING CHANNEL AFTER
PROPER ALIGNMENT WITH FOUNDATION BOLTS, NUTS , LEVELLING
CUTTING NECESSARRY CHASESON FLOOR AND MENDING GOOD
DAMAGES, EARTHING , PAINTING ETC. AS REQUIRED AS PER
SPECIFICATION. THE PANEL SHALL BE INSTALLED IN THE HT
SWITCHGEAR ROOM OF THE SUBSTATION BUILDING. THE PANEL SHALL
COMPRISE SELF POWER PACK ARRANGEMENT, ANTI PUMPING RELAY
AND TRANSFORMER NCT PROTECTION RELAY (STAND BY EARTH FAULT
RELAY).

485 ONE (1) SET OF THREE PANELS(1 NO. INCOMING & 2 NOS. OUTGOING)
CUBICLE TYPE INDOOR, FLOOR MOUNTED, METAL CLAD TOTALLY
ENCLOSED EXTENSIBLE ON EITHER SIDE HORIZONTAL DRAWOUT TYPE
11 KV VACUUM CIRCUIT BREAKER(VCB) HAVING FOLLOWING
COMPONENTS:

486 1 SET- 630A, TP, 12 KV, 50 HZ VACUUM CIRCUIT BREAKER (VCB) HAVING
STC OF 26.3KA FOR 3 SECONDS HAVING THE FOLLOWING COMPONENTS.

487 a) 1 SET ( 3 NOS/SET)-150/5-5A DUAL CORE CAST RESIN TYPE CURRENT


TRANSFORMER CL-5P10 FOR PROTECTION & CL-0.5 FOR METERING WITH
15VA BURDEN EACH.
488 b) 1 SET (3 NOS/SET)- CAST RESIN CONSTRUCTION TYPE POTENTIAL
TRANSFORMER 11 KV √3 : 110 V/ √3 WITH CL- 0.5 ACCURACY WITH 100 VA
BURDEN WITH HRC FUSES AT PRIMARY & SECONDARY FOR PROTECTION.

489 c) 1 SET - ANALOGUE AMMETER ( 0-150A) WITH AMMETER SELECTOR


SWITCH AND HRC FUSE PROTECTION TO BE OPERATED WITH CT.

490 d) 1 SET - ANALOGUE VOLTMETER (0-15 KV) WITH VOLTMETER


SELECTOR SWITCH AND HRC FUSE PROTECTION TO BE OPERATED WITH
PT.
491 e) 1 SET - NEUTRAL DISPLACEMENT AND TIME DELAY RELAY.
492 f) 1 SET - NUMERICAL TYPE IDMT RELAY( 50/51 , 50N51N) WITH TWO
ELEMENTS FOR OVERCURRENT AND EARTH FAULT HAVING SETTINGS
50% TO 200% FOR OVERCURRENT & 20% TO 80% FOR EARTH FAULT IN
EQUAL STEPS WITH TIME AND CURRENT SETTINGS AND HIGH SET
INSTANTANEOUS UNIT.

493 g) 1 SET- NUMERICAL TYPE OVERVOLTAGE AND UNDER VOLTAGE RELAY


HAVING SETTINGS RANGING FROM 80% TO 120% IN EQUAL STEPS.
494 h) 1 SET - HIGH SPEED MASTER TRIP RELAY WITH AUXILIARY CONTACTS.

495 I) 1 SET - TRIP CIRCUIT SUPERVISIPN RELAY.


496 J) 1 SET- STAND BY EARTH FAULT RELAY.
497 K) 1 SET ( 3 NOS/SET ) R-Y-B LED PHASE INDICATION LAMPS WITH 3 NOS.
1A, SP, MCB PROTECTION.
498 L) 1 SET - ON /OFF/TRIP/TEST/TRIP CIRCUIT HEALTHY/SERVICE POSITION/
SPRING CHARGE/PT FUSE FAILURE INDICATOR CLUSTER TYPE LED
INDICATION LAMPS AND PUSH BUTTONS.
499 M) 1 SET - ANNUCIATOR UNITS.
500 N) 1 SET - EARTH BUS BARS AND ALL OTHER ACCESSORIES.
501 O) 1 SET ( 3NOS) SURGE ARRESTOR( METAL OXIDE,GAPLESS) TO BE
PROVIDED.
502 P) 1 SET - CABLE TERMINATION BOX FOR TERMINATION OF 1 RUN OF
11/11 KV(UE) GRADE 3C, 185 SQMM XLPE INSULATED AL(A) CABLE.

503 Q) 1 SET- T-N-C SWITCH TO BE PROVIDED.


504 R) 1 SET - FLUSH MOUNTING DIGITAL TRIVECTOR METER HAVING CLASS
-0.5 ACCURACY AND MAXIMUM DEMAND INDICATION (MDI) INDICATOR
TO BE OPERATED BY CT & PT SUPPLY.
505 BUSBAR
506 1 SET - 630A ,12 KV , 50 HZ TP ELECTROLYTIC GRADE TINNED COPPER BUS
BARS HAVING A FAULT LEVEL WITHSTAND CAPACITY OF 26.3 KA FOR 3
SECONDS.
507 OUTGOING
508 2 SETS- 630A , TP,12KV, 50 HZ VACCUM CIRCUIT BREAKER ( VCB) HAVING
STC OF26.3 KA FOR 3 SECONDS HAVING THE FOLLOWING COMPONENTS.

509 a) 2 SETS ( 3 NOS/SET) - 60/5.5ADUAL CORE CAST RESIN TYPE CURRENT


TRANSFORMER CI-5P 10 FOR PROTECTION AND CLASS - 0.5 FOR
METERING WITH 15 VA BURDEN.
510 b) 2 SETS (3NOS/SET) - CAST RESIN CONSTRUCTION TYPE POTENTIAL
TRANSFORMER 11 KV : √3/110V/√3 WITH ACCURACY CI-0.5 WITH 100VA
BURDEN AND WITH HRC FUSE PROTECTION AT BOTH PRIMARY AND
SECONDARY.

511) C) 2 SETS - ANALOGUE AMMETER ( 0-60A) WITH AMMETER SELECTOR


SWITCH AND HRC FUSE PROTECTION TO BE OPERATED WITH CT.

512 D) 2 SETS- ANALOGUE VOLTMETER (0-15KV) WITH VOLTMETER


SELECTOR SWITCH AND WITH HRC FUSE FOR PROTECTION TO BE
OPERATED BY PT.
513 E) 2 SETS - NEUTRAL DISPLACEMENT AND TIME DELAY RELAY.
514 F) 2 SETS - NUMERICAL TYPE IDMT RELAY (50/51 , 50N/5IN) WITH TWO
ELEMENTS FOR OVERCURRENT AND EARTH FAULT , HAVING SETTINGS
50% TO 200% FOR OVERCURRENT AND 20% TO 80% FOR EARTH FAULT IN
EQUAL STEPS WITH TIME AND CURRENT SETTINGS AND HIGH SET
INSTANTANEOUS UNITS.
515 G) 2 SETS - NUMERICAL TYPE OVERVOLTAGE RELAY HAVING SETTINGS
RANGING FROM 80% TO 120% IN EQUAL STEPS.
516 H) 2 SETS - HIGH SPEED MASTER TRIP RELAY WITH AUXILIARY
CONTACTS
517 I) 2 SETS - TRIP CIRCUIT SUPERVISION RELAY.
518 J) 2 SETS - STAND BY EARTH FAULT RELAY.
519 K) 2 SETS - ( 3NOS/SET) R-Y-B LED PHASE INDICATION LAMP WITH 3 NOS
1A, SP, MCB PROTECTION.
520 L) 2 SET- ON/OFF/TRIP/TEST/TRIP CIRCUIT HEALTHY/ SERVICE POSITION/
SPRING CHARGE / PT FUSE FAILURE INDICATOR CLUSTER TYPE LED
INDICATION LAMPS AND PUSH BUTTONS.
521 M) 2 SETS - ANNUNCIATOR UNITS.
522 N) 2 SETS - EARTHING BUS BARS.
523 O) 2SETS - CABLE TERMINATION BOX FOR TERMINATION OF 1 RUN OF
11/11 KV (UE) GRADE 3C, 185 SQMM XLPE INSULATED AL (A) CABLE.

524 P) 2 SETS T-N-C SWITCH TO BE PROVIDED.


UNIT RATE TOTAL
SET 875000 875000.00
ELECTRICAL WORKS- SUBSTATION WORKS
VACCUM CIRCUIT BREAKER PANEL

SL NO PARTICULARS QTY
998 DG SET INSTALLATION WORK
999 SUPPLY, ERECTION, TESTING & COMMISSIONING OF OUTDOOR SOUND & 1
WESTHER PROOF TYPE "DIESEL GENERATOR-SET" WITH ANTI-VIBRATION
MOUNTS, FITTING, FIXING ETC. COMPLETE IN ALL RESPECT. THE DG-SET
SHALL ALSO COMPLY ISO 8528-2 & 3 AS WELL AS SHOULD BE OF "PRIME
POWER RATING" I.E. CAPABLE OF PROVIDING AN OUTPUT OF 10% IN
EXCESS OF THE RATED OUTPUT AT THE SAME SPEED FOR ONE HOUR IN
ANY PERIOD OF 12 HOURS CONSECUTIVE RUNNING. THE SOUND LEVEL
OF D.G. SET SHALL NOT BE MORE THE 75DBA AT 01 METER FROM SOUND
PROOF CANOPY. THE WORK SHALL BE COMPLETED WITH ALL
NECESSARY EQUIPMENT AS REQUIRED. TESTING AND TRIAL RUN
(MINIUM 8 HOURS WITH LOAD) INCLUDING ALL CONSUMABLES SUCH AS
FUEL, OIL ETC WHICH SHALL BE SUPPLIED BY THE CONTRACTOR AS PER
INSTRUCTION AND DIRECTION OF THE PROJECT IN CHARGE. THE DG-SET
SHOULD BE PROVIDED WITH FOLLOWING ACCESSORIES.

1000 DG-SET RATING : 1010KVA


1001 1500RPM, 4-STROKE TURBO CHARGES AFTER COOLED DISEL ENGINE OF
SUITABLE CAPACITY & RATED BHP TO DELIVER THE SPECIFIED LOAD AT
NTP COMPLETE WITH STANDARD ACCESSORIES AND SHALL
CONFORMING TO ISO:3046,BS:5514.

1002 THE ENGINE IS TO BE ELECTRICALLY STARTED BY AN ELECTRICALLY


DRIVEN SELF STARTER OPERATED THROUGH ENGINE BATTERY.

1003 ENGINE LOCAL CONTROL PANEL WITH EQUIPMENTS AND INSTRUMENTS


MOUNTED ON THE ENGINE FRAME COMPLETE.
1004 LEAD ACID MAINTENANCE FREE/SMF TYPE HEAVY DUTY STARTING
BATTERIES WITH SELF DRIVEN CHARGER UNIT.
1005 RADIATOR OF THE ENGINE WITH SELF DRIVEN FAN AND INNER CIRCUIT
WATER PUMPS COMPLETE.
1006 INLET MANIFOLD AND AIR CLEANERS.
1007 GEAR TYPE LUBE OIL PUMPS, LUBRICATING OIL FILTER, LUBE OIL
CENTRIFUGE AND LUBRICATING OIL COOLER.
1008 FURL INJECTION SYSTEM WITH INJECTION PUMP, FUEL FILTER, FUEL
PREFILTER, NOZZLES GOVERNOR AND FUEL LEVEL INDICATION, ANTI
VIBRATION MOUNT PADS ETC.
1009 THE ENGINE MOUNTED PANEL SHOULD CONSIST OF TACHO-HOUR
METER, LUBE OIL PRESSURE GAUGE, COOLANT TEMPERATURE GAGUGE,
BATERY CHARGER AMMETER AND OTHER ACCESSORIES ETC.
COMPLETE.

1010 AMF PANEL 1


1011 SUPPLY, DELIVERY AT SITE ERECTION, TESTING & COMMISSIONING OF
VERTICAL FLOOR MOUNTING FREE STANDING, EXTENSIBLE ON EITHER
SIDE, COMPARTMENTALISED CUBICAL TYPE PANEL BOARD MADE OF 14
SWG (2.04MM) CRCA MS SHEET SUITABLE FOR 500/415V, 50 HZ, AC, 3
PHASE AND NEUTRAL SYSTEM HAVING THE FOLLOWING FEATURES
PANEL SHALL BE DESIGNED TO ENSURE THAT THE WEIGHT OF THE
COMPONENTS IS ADEQUATELY SUPPORTED WITHOUT DEFORMATION OR
LOSS IN ALIGNMENT. THE DOORS OF THE CUBICLE SHALL BE FITTED
WITH DUST EXCLUDING NEOPRENE GASKETS WITH FASTNERS FOR
PROPER COMPRESSION OF THE GASKETS.

1012 PANEL SHALL BE MULTITIER COMPARTMENTALISED CUBICAL TYPE,


EXTENSIBLE ON EITHER SIDE AND SHALL BE TREATED WITH ALL
NTICORROSIVE PROCESS BEFORE PAINTING WITH TWO COATS OF ZINE
CHROMATE PRIMER AND FINAL APPROVED SHADE OF ENAMEL PAINT.

1013 BUSBARS SHALL BE OF CONTINUOUS RATED ALUMINIUM ADEQUATE


FOR SPECIFIED RATED CONTINUOUS AND SHORT CIRCUIT CURRENT
COVERED BY, PROPER GRADED HEAT SHRINKABLE PVC SLEEVES
(COLOR CODED). BUSBARS SHALL BE SUPPORTED BY SUITABLE
HYLAM/DMC/SMC OR COMPATABLE INSULATOR SUPPORTS. HIGH
TENSIBLE BOLTS AND SPRINGS WASHERS ARE TO BE PROVIDED ON ALL
BUSBARS AND SUITABLE DRILLED HOLES FOR CONNECTION JOINTS. THE
BUSBARS SHALL HAVE A THROUTH FAULT WITHSTAND CAPACITY OF 31
MVA, RMS SYMMETRICAL FOR ONE SECOND. THE INTERCONNECTIONS
BETWEEN THE BUSBARS AND THE CIRCUIT BREAKERS SHALL BE MADE
BY CONTINUOUS RATED ALUMINIUM STRIPS SUITABLY COVERED BY
PROPER GRADED HEAT SHRINKABLE COLOUR CODED PVC SLEEVES. THE
EARTH BUSBAR SHALL RUN THROUGH THE LENGTH OF THE PANEL AND
TERMINATED AT TWO ENDS.

1014 ALL THE MCCBS SHALL BE PROVIDED WITH EXTENDED ROTARY


OPERATED MECHANISM. SAFTY INTERLOCKS ARE TOO BE PROVIDED TO
PREVENT THE DOORS OF THE COMPARTMENTS HOUSING THE MCCBS TO
PREVENT THE DOORS TO OPEN WHEN THE MCCBS ARE 'ON' POSITION.

1015 ACBS SHALL BE METAL CLAD, INDOOR TYPE (IN FULLY DRAWOUT
EXECUTION) MOUNTED ON FULLY DRAWOUT TRUCK WITH SERVICE,
TEST AND ISOLATED POSITION AND COMPLETE WITH THE FOLLOWING
SAFTY INTERLOCKS AND SAFTY SHUTTERS AND PADLOCK FACILITY.

1016 IT SHALL NOT BE POSSIBLE TO MOVE THE TRUCK IN OR OUT OF CUBICLE


WHEN THE BREAKER IS CLOSED.
1017 ACB COMPARTMENT DOOR SHALL BE MACHENICALLY INTERLOCKED SO
THAT IT WILL NOT POSSIBLE TO CLOSE THE ACB IN PLUG POSITION
WHEN THE DOOR IS OPEN.
1018 IT SHALL NOT BE POSSIBLE TO PUSH THE TRUCK IN CLOSE POSITION IF
EITHER OF THE SAFETY SHUTTER IS NOT FREE AND NOT IN CLOSE
POSITION.
UNIT RATE TOTAL

SET 0.00

SET 0.00
ELECTRICAL WORKS- SUBSTATION WORKS
VACCUM CIRCUIT BREAKER PANEL

SL NO PARTICULARS QTY
525 CAST RESIN TYPE DRY TRANSFORMER
DESIGNING, MANUFACTURING, DELIVERY AND INSTALLATION 2
INCLUDING PLACING IN POSITION AT SITE , TESTING AND
COMMISSIONING OF 1000 KVA , 11/0.433 KV , 5 POSITION, 50 HZ COPPER
WOUND INDOOR CAST RESIN DRY TYPE TRANSFORMER WITH CLASS H
INSULATION & IP 23 ENCLOSURE. VECTOR GROUP DYn 11 HAVING HT
CABLE BOX AND LT CABLE BOX WITH CABLE GLAND PLATE SUITABLE
FOR TERMINATING 1.1 KV GRADE 4 NOS. 3.5C 400 SQMM XLPE LT CABLES
IN THE LT SIDE & 11/11 KV(E) GRADE 1 NO. 3C 185 SQMM ARMOURED AL
XLPE CABLE IN THE HT SIDE INCLUDING ALL OTHER COMPONENTS AS
SPECIFIED. SUPPLY OF ALL INSTALLATION MATERIALS LIKE MOUNTING
CHANNELS AS PER MANUFACTURERS DESIGN HIGH TENSILE BOLTS,
NUTS, WASHERS, SCREWS,CLAMPS, PAINTING, EARTHING, ETC
ASREQUIRED CONFIRMING TO THE TECHNICAL SPECIFICATION ALONG
WITH RATING & DIAGRAM PLATE , EARTHING TERMINALS,LIFTING
LUGS, OFFLOADTAP LINK, WINDING TEMPERATURE
INDICATOR,BIDIRECTIONAL ROLLERS, DIGITAL WINDING TEMPERATURE
INDICATOR WITH 2 SETS OF POTENTIAL FREE CONTCTS WITH SUITABLE
SENSORS IN EACH PHASE COMPLETE IN ALL RESPECT AS REQUIRED. THE
OFF LOAD TAP LINK WITH (+)% & (-) TAPPINGS IN STEP OF 2.5% . THE
INSTALLATION SHALL CONFIRM IS : 10028,1981(PART II)& AMENDED UP
TO DATE. THE RATE SHALL BE INCLUSIVE OF NECESSARY CIVIL WORKS,
MOUNTING CHANNELS,EARTHING ETC COMPLETE IN ALL RESPECT. THE
TRANSFORMER SHALL BE INSTALLED IN THE TRANSFORMER ROOM IN
SUBSTATION BUILDING.
UNIT RATE TOTAL

SET 1620000 3240000.00


ELECTRICAL WORKS- SUBSTATION WORKS
VACCUM CIRCUIT BREAKER PANEL

SL NO PARTICULARS QTY
721 MV CABLE
722 SUPPLY OF 1.1KV 3C X 6 SQMM XLPE ARMOURED AL.CABLE AS DIRECTED 650
BY EIC.
723 SUPPLY OF 1.1KV 3.5C X 25 SQMM XLPE ARMOURED AL.CABLE AS 1250
DIRECTED BY EIC.
724 SUPPLY OF 1.1KV 3.5C X 35 SQMM XLPE ARMOURED AL.CABLE AS 100
DIRECTED BY EIC.
725 SUPPLY OF 1.1KV 3.5C X 50 SQMM XLPE ARMOURED AL.CABLE AS 70
DIRECTED BY EIC.
726 SUPPLY OF 1.1KV 3.5C X 95 SQMM XLPE ARMOURED AL.CABLE AS 300
DIRECTED BY EIC.
727 SUPPLY OF 1.1KV 3.5C X 150 SQMM XLPE ARMOURED AL.CABLE AS 200
DIRECTED BY EIC.
728 SUPPLY OF 1.1KV 3.5C X 240 SQMM XLPE ARMOURED AL.CABLE AS 800
DIRECTED BY EIC.
729 SUPPLY OF 1.1KV 3.5C X 300 SQMM XLPE ARMOURED AL.CABLE AS 100
DIRECTED BY EIC.
730 SUPPLY OF 1.1KV 3.5C X 400 SQMM XLPE ARMOURED AL.CABLE AS 1000
DIRECTED BY EIC.
731 SUPPLY OF 1.1KV 4C X 6 SQMM XLPE ARMOURED AL.CABLE AS DIRECTED 1400
BY EIC.
732 SUPPLY OF 1.1KV 4C X 10 SQMM XLPE ARMOURED AL.CABLE AS 250
DIRECTED BY EIC.
733 SUPPLY OF 1.1KV 4C X 16 SQMM XLPE ARMOURED AL.CABLE AS 1000
DIRECTED BY EIC.
734 COMPRESSION GLAND
735 SUPPLYING & FIXING COMPRESSION TYPE GLAND COMPLETE WITH
BRASS GLAND, BRASS RING, RUBBER RING FOR DUST & MOISTURE
PROOF ENTRY OF XLPE / PVC ARMOURED CABLES AS BELOW :

736 FOR 2 CORE 60


737 UPTO 6 SQMM
738 FOR 3 CORE 16
739 UPTO 6 SQMM
740 FOR 4 CORE
741 UPTO 6 SQMM 25
742 UPTO 10 SQMM 40
743 UPTO 16 SQMM 50
744 FOR 3.5 CORE
745 UPTO 25 SQMM 40
746 UPTO 35 SQMM 10
747 UPTO 50 SQMM 10
748 UPTO 95 SQMM 16
749 UPTO 150 SQMM 10
750 UPTO 240 SQMM 30
751 UPTO 300 SQMM 10
752 UPTO 400 SQMM 50
753 FINISHING CABLE ENDS
754 FINISHING THE END OF FOLLOWING XLPE/PVC ARMOURED CABLES BY
CRIMPING METHOD INCL. SUPPLYING AND FIXING SOLDERLESS SOCKET
(DOWELS MAKE) , TAPES, ANTI CORROSIVE PASTE & JOINING MATERIALS
:

755 4C 6 SQMM CABLE 32


756 4C 10 SQMM CABLE 72
757 4C 16 SQMM CABLE 60
758 3.5C 25 SQMM CABLE 150
759 3.5C 35 SQMM CABLE 20
760 3.5C 50 SQMM CABLE 20
761 3.5C 95 SQMM CABLE 32
762 3.5C 150 SQMM CABLE 20
763 3.5C 240 SQMM CABLE 80
764 3.5C 300 SQMM CABLE 20
765 3.5C 400 SQMM CABLE 150
766 SCHEDULE OF RATES FOR LAYING OF XLPE / PVC INSULATED AND
ARMOURED CABLES
767 LAYING ON WALL/ SURFACE WITH SADDLES /CLAMPS
768 LAYING OF CABLE UPTO 2CORE 25 SQMM ON WALL/ SURFACE INCL. 70
S&MS SADDLES WITH EARTHING ATTACHMENT IN 10 SWG GI (HOT DIP )
WIRE, MAKING HOLES ETC AS NECY. MENDING GOOD DAMAGES AND
PAINTING.

769 LAYING OF CABLE UPTO 3/4 CORE 25 SQMM ON WALL/SURFACE INCL. S 100
& F MS SADDLES WITH EARTHING ATTACHMENT IN 10 SWG GI (HOT DIP),
WIRE, MAKING HOLES ETC AS NECY.MENDING GOOD DAMAGES AND
PAINTING.

770 LAYING THROUGH RCC/HUME/GI PIPE


771 LAYING ONLY CABLE UPTO 50 SQMM THROUGH EXISTING RCC/HUME/GI 90
PIPE/ OPEN MASONARY TRENCH FOR SINGLE,2,3,3.5 & 4C

772 LAYING ONLY CABLE ABOVE 50 SQMM BUT NOT EXCEEDING 400SQMM 55
THROUGH EXISTING RCC/HUME/GI PIPE/OPEN MASONARY TRENCH FOR
SINGLE ,2,3,3.5 & 4CORE.
773 LAYIING THROUGH UNDERGROUND TRENCH
774 LAYING OF ONE NO. CABLE UPTO 35 SQMM IN UNDERGROUND TRENCH 1250
460MM WIDE X 760 MM AVERAGE DEPTH, WITH BRICK PROTECTION ON
THE TOP OF THE CABLE WITH 8 NOS. BRICKS PER MTR, INCLUDING
FILLING THE SPACE BETEEN THE BRICK & CABLE AND ALSO THE
TRENCH WITH SHIFTED SOIL , LEVELLING UP AND RESTORING SURFACE
DULY RAMMED
775 LAYING OF ONE NO. CABLE UPTO 35 SQMM & UPTO 185SQMM IN 450
UNDERGROUND TRENCH 460MM WIDE X 760 MM AVERAGE DEPTH, WITH
BRICK PROTECTION ON THE TOP OF THE CABLE WITH 8 NOS. BRICKS PER
MTR, INCLUDING FILLING THE SPACE BETEEN THE BRICK & CABLE AND
ALSO THE TRENCH WITH SHIFTED SOIL , LEVELLIING UP AND
RESTORING SURFACE DULY RAMMED

776 LAYING OF ONE NO. CABLE ABOVE 185 SQMM IN UNDERGROUND 1250
TRENCH 460MM WIDE X 760 MM AVERAGE DEPTH, WITH BRICK
PROTECTION ON THE TOP OF THE CABLE WITH 8 NOS. BRICKS PER MTR,
INCLUDING FILLING THE SPACE BETEEN THE BRICK & CABLE AND ALSO
THE TRENCH WITH SHIFTED SOIL , LEVELLIING UP AND RESTORING
SURFACE DULY RAMMED

777 LAYING OF 2 NOS. CABLE UPTO 35 SQMM IN UNDERGROUND TRENCH IN 410


SINGLE TIER FORMATION (HORIZONTAL) THR TRENCH SIZE 680MM WIDE
X 760 MM AVERAGE DEPTH, WITH BRICK PROTECTION ON THE TOP OF
THE CABLE WITH 8 NOS. BRICKS PER MTR,AND 4 NOS.BRICKS PER MTR
AS SEPARATOR BETWEEN THE BRICK & CABLE AND ALSO THE TRENCH
WITH SHIFTED SOIL , LEVELLING UP AND RESTORING SURFACE DULY
RAMMED

778 LAYING OF 2 NOS. CABLE ABOVE 185 SQMM IN UNDERGROUND TRENCH 450
IN SINGLE TIER FORMATION (HORIZONTAL) THR TRENCH SIZE 680MM
WIDE X 760 MM AVERAGE DEPTH, WITH BRICK PROTECTION ON THE TOP
OF THE CABLE WITH 8 NOS. BRICKS PER MTR,AND 4 NOS.BRICKS PER
MTR AS SEPARATOR BETWEEN THE BRICK & CABLE AND ALSO THE
TRENCH WITH SHIFTED SOIL , LEVELLING UP AND RESTORING SURFACE
DULY RAMMED

779 LAYING THROUGH MASONRY TRENCH


780 LAYING OF ONE CABLE UPTO 150SQMM THROGH EXISTING COVERED 80
MASONARY TRENCH INCL. TAKING OUT RC COVERS, SETTING THEM IN
ORDER, MENDING GOOD,THE DAMAGES FILLING THE TRENCH WITH
FINE DRY SAND INCL.SUPPLYING SAND.

781 LAYING OF ONE CABLE ABOVE 150SQMM & UPTO 300 SQMM THROGH 200
EXISTING COVERED MASONARY TRENCH INCL. TAKING OUT RC COVERS,
SETTING THEM IN ORDER, MENDING GOOD,THE DAMAGES FILLING THE
TRENCH WITH FINE DRY SAND INCL.SUPPLYING SAND.

782 LAYING OF ONE CABLE ABOVE 300SQMM THROGH EXISTING COVERED 20


MASONARY TRENCH INCL. TAKING OUT RC COVERS, SETTING THEM IN
ORDER, MENDING GOOD,THE DAMAGES FILLING THE TRENCH WITH
FINE DRY SAND INCL.SUPPLYING SAND.

783 LAYING ON CABLE TRAY


784 LAYING OF CABLE AS BELOW, ON EXISTING CABLE TRAY AND BINDING
WITH SUITABLE SIZE GI WIRE.
785 UP TO 50 SQMM 1250
786 FROM 70 SQMM TO 150 SQMM 130
787 ABOVE 150 SQMM 600
UNIT RATE TOTAL

MTR 0.00

MTR 0.00

MTR 0.00

MTR 0.00

MTR 0.00

MTR 0.00

MTR 0.00

MTR 0.00

MTR 0.00

MTR 0.00

MTR 0.00

MTR 0.00

EACH 0.00
0.00
EACH 0.00

EACH 0.00
EACH 0.00
EACH 0.00
0.00
EACH 0.00
EACH 0.00
EACH 0.00
EACH 0.00
EACH 0.00
EACH 0.00
EACH 0.00
EACH 0.00

SET 0.00
SET 0.00
SET 0.00
SET 0.00
SET 0.00
SET 0.00
SET 0.00
SET 0.00
SET 0.00
SET 0.00
SET 0.00
0.00

MTR 58 4060.00

MTR 62 6200.00

MTR 48 4320.00

MTR 67 3685.00

MTR 170 212500.00


MTR 180 81000.00

MTR 195 243750.00

MTR 319 130790.00

MTR 333 149850.00

0.00
MTR 96 7680.00

MTR 136 27200.00

MTR 156 3120.00

0.00
MTR 11 13750.00
MTR 15 1950.00
MTR 19 11400.00
ELECTRICAL WORKS- SUBSTATION WORKS
VACCUM CIRCUIT BREAKER PANEL

SL NO PARTICULARS QTY
535 EARTHING INSTALLATIONS
536 EXCAVATION OF SOILFOR INSTALLATION OF EARTH ELECTRODE AND 54
FILLING & RAMMING
537 EARTHING WITH 65 MM DIA GI PIPE ( TATA MEDIUM) X 3.0 MTS LONG AND 14
1 NO. 50MM X 6 MM GALVANIZED BOLT, DOUBLE NUTS,DOUBLE
WASHERS INCLUDING FINISHING BOTH ENDS BY MAKING HOLES ETC
AND S & F 65 MM DIA GI PIPE (ISI-MEDIUM) PROTECTION (3MTR LONG)
TO BE FILLED WITH BITUMEN PARTLY UNDER THE GROUND LEVEL AND
PARTLY ABOVE GROUND LEVEL TO AN AVERAGE DEPTH OF 3.65 MTS.

538 EARTHING WITH COPPER PLATE (610 X 610 X 3MM SIZE ) HAVING WEIGHT 10
OF 9.84 KG AND 1 NO 25 X 5 MM COPPER STRIP (3.20 MT LONG) & 1 NO 6
SQMM PVC INSULATED STRANDED COPPER WIRE (4MT. LONG) TO BE
FILLED WITH BITUMEN, PARTLY UNDER GROUND LEVEL & PARTLY
ABOVE GROUND LEVEL TO AN AVERAGE DETHOF 3.65 MTS. BELOW THE
GROUND LEVEL AND RESTORING THE SURFACE DULY RAMMED INCL.
PROVIDING 3 MT. LONG , 25 MM DIA GI PIPE (ISI-MEDIUM) OF PERIODIC
TREATMENT , INCL. PROVIDING MASONERY ENCLOSURE ON THE TOP OF
THE EARTH ELECTRODE OF OVERALL SIZE 86.36 X 86.36 X 46 CM DEEP
(BELOW GROUND LEVEL) COMPLETE WITH CEMENTED BRICK WORK
(1:6) OF 25 CM WIDTH , DULY PLASTERED WITH CEMENT MORTER
(INSIDE) CL HINGED INSPECTION COVER OF SIZE 36.56 X 35.56 CM WITH
LOCKING ARRANGEMENT, GI REDUCER AND TREATMENT OF SOIL BY
USING SALT & CHARCOAL OR COKE FOR PLATE ELECTRODE.

539 EXTRA FOR PROVIDING MASONERY ENCLOSURE ON THE TOP OF THE 28


EARTH ELECTRODE OF OVERALL SIZE 86.36CM X 86.36 CM X 46 CM DEEP (
BELOW GROUND LEVEL) COMPLETE WITH CEMENTED BRICK WORK (1:6)
OF 25 CM WIDTH DULY PLASTERED WITH CEMENT MORTER(INSIDE) CL
HINGED INSPECTION COVER OF SIZE 36.36 CM X 35.56 CM WITH LOCKING
ARRANGEMENT, GI REDUCER INCLUDING DRILLING OF 46 NOS. 12 MM
DIA HOLES ON THE GI PIPE.

540 EXTRA FOR TREATMENT OF SOIL BY USING SALT & CHARCOAL OR COKE 18
FOR PLATE ELECTRODE.
541
542 SUPPLYING & FIXING EARTH BUSBAR OF 50MM X 6 MM G.I STRIP ON 40
WALL HAVING CLEARANCE OF 6 MM FROM WALL INCLUDING
PROVIDING DRILLED HOLES ON THE BUSBAR COMPLETE WITH G.I
BOLTS, NUTS, WASHERS, SPACING INSULATORS ETC ASREQUIRED.
543 EXTRA FOR CONNECTING THE NEUTRAL OF TRANSFORMERS /EARTH 400
BUSBAR TO EARTH ELECTRODE INCLUDING S & F 50MM X 6 MM GI STRIP
ON WALL / FLOOR WITH GI SADDLES & INSULATING THE SAME BY ONE
LAYER OF PVC STRIP OVER ONE LAYER OF AMPERE TAPE.

544 WITH 50 X 6 MM COPPER STRIP 150


793 EARTHING INSTALLATIONS
794 EXCAVATION OF SOIL FOR INSTALLATION OF EARTH ELECTRODE AND 50
FILLING & RAMMING
795 EARTHING WITH 50 MM DIA GI PIPE (TATA-MEDIUM) 3.64 MM THICK x 3.04 14
MTS. LONG 1 x 4 SWG GI (HOT DIP) WIRE (4 MTS. LONG), 13 MM DIA x 80
MM LONG GI BOLTS, DOUBLE NUTS, DOUBLE WASHERS INCL. S & F 15
MM DIA GI PIPE PROTECTION (1 MTS. LONG) TO BE FILLED WITH
BITUMEN PARTLY UNDER THE GROUND LEVEL AND PARTLY ABOVE
GROUND LEVEL DRIVEN TO AN AVERAGE DEPTH OF 3.65 MTS. BELOW
THE GROUND LEVEL.

796 EARTHING WITH COPPER PLATE (610x610x3MM SIZE) HAVING WEIGHT OF 6


9.84 KG AND 1 NO. 25x5MM COPPER STRIP (3.20MT LONG) & 1 NO. 6 SQMM
PVC INSULATED STRANDED COPPER WIRE (4 MT LONG) INCL. S & F 15
MM DIA GI PIPE (ISI-MEDIUM) PROTECTION (4 MT. LONG) TO BE FILLIED)
WITH BITUMEN, PARTLY UNDER THE GROUND LEVEL AND RESTORING
THE SURFACE DULY RAMMED INCL. PROVIDING 3.0 MT LONG, 25 MM DIA
GI PIPE (ISI-MEDIUM) FOR PERIODIC TREATMENT, INCL. PROVIDING
MASONERY ENCLOSURE ON THE TOP OF THE EARTH ELECTRODE OF
OVERALL SIZE 86.36x86.36x46CM DEEP (BELOW GROUND LEVEL)
COMPLETE WITH CEMENTED BRICK WORK (1:6) OF 25 M WIDTH, DULY
PLASTERED WITH CEMENT MORTER (INSIDE) CI HINGED INSPECTION
COVER OF SIZE 36.56x35.56CM WITH LOCKING ARRANGEMENT, GI
REDUCER AND TREATMENT OF SOIL BY USING SALT & CHARCOAL OR
COKE FOR PLATE ELECTRODE.

797 EXTRA FOR PROVIDING MASONERY ENCLOSURE ON THE TOP OF THE 20


EARTH ELECTRODE OF OVERALL SIZE 86.36CM X 86.36 CM X 46 CM DEEP (
BELOW GROUND LEVEL) COMPLETE WITH CEMENTED BRICK WORK (1:6)
OF 25 CM WIDTH DULY PLASTERED WITH CEMENT MORTER(INSIDE) CL
HINGED INSPEPECTION COVER OF SIZE 36.56 CM x 35.56 CM WITH
LOCKING ARRANGEMENT, GI REDUCER INCLUDING DRILLING OF 46 NOS.
12 MM DIA HOLES ON THE GI PIPE.

798 EXTRA FOR TREATMENT OF SOIL BY USING SALT & CHARCOAL OR COKE 16
FOR PLATE ELECTRODE.
799 EARTH BUSBAR
800 SUPPLYING & FIXING EARTH BUSBAR OF GALVANIZED ( HOT DIP) MS 100
FLAT 25 MM X 6 MM ON WALL HAVING CLEARANCE OF 6 MM FROM WALL
INCLUDING PROVIDING DRILLED HOLES ON THE BUSBAR COMPLETE
WITH GI BOLTS, NUTS, WASHERS, SPACING INSULATORS ETC AS
REQUIRED.

801 EQUIPMENT EARTHING


802 CONNECTING THE EQUIPMENTS BODY TO EARTH BUSBAR INCLUDING S 780
& F 25 MM X 6 MM GALVANISED (HOT DIP) MS FLAT ON WALL/FLOOR
WITH GI SADDLES AS REQUIRED AS REQUIRED AND CONNECTION TO
EQUIPMENTS INCL. DRILLING HOLES, WITH BOLTS, NUTS, WASHERS ETC

803 WITH 25 X 3 MM COPPER STRIP 120


985 LIGHTING PROTECTION SYSTEM
986 EMISSION LIGHTNING AIR TERMINAL
987 SUPPLY, ERECTION, TESTING & COMMISSIONING OF "EARLY STREAMER
EMISSION" TYPE LIGHTING PROTECTION SYSTEM COMPRISING OF AIR-
TERMINALS OR DYNASPHERE, DOWN CONDUCTORE, EVENT COUNTER,
LOW IMPEDANCE GROUNDING GRID INCLUDING ENHANCEMENT
METARIALS, GROUNDING ELECTRODE, MAST, SS CABLE TIE, IN LINE
COUPLING, GUY SET, HARDWARE ETC. COMPLETE. THE RATE SHALL
ALSO INCLUDE ALL CIVIL WORKS.

988 79 METER PROTECTION RADIOUS EARLY STREAMER EMISSION 1


TERMINAL CONFIRMING "NFC 17-102:2011 & LEVEL-I" WITH A MOUNTING
HEIGHT OF 5 METER.
989 ALLIED ITEMS
990 INSULATED FRP MAST, INLINE COUPLING & MAST BASE ETC. COMPLETE 1
IN ALL RESPECT.
991 LIGHTINING EVENT COUNTER & ACCESSORIES 1
992 EARTHING ROD
993 5/8" CU. BONDED EARTHING ROD, 14.2 MM DIA & 3000MM LENGTH 3
994 HORIZONTAL/DOWN CONDUCTOR
995 5/8" CU. BONDED EARTHING ROD, 14.2 MM DIA CLAMP & 3000MM LENGTH 70
WITH COPPER TAPE FOR INTERNAL EARTHING CONNECTIVITY

996 GROUND ENHANCING MATERIAL


997 HIGHLY CONDUCTIVE AND LOW RESISTANCE GROUND RESISTANCE 4
IMPROVEMENT POWDER TESTED TO THE RESISTIVITY OF 0.2 OHMS AS
PER IEC 62561-7 READ WITH ASTM G57-06, CL 3.4
UNIT RATE TOTAL
0.00
CUM 286 15444.00

SET 3146 44044.00

SET 11000 110000.00

ITEM 915 25620.00

ITEM 531 9558.00

MTR 216 8640.00


MTR 201 80400.00

MTR 201 30150.00


0.00
CUM 0.00

SET 0.00

SET 11479 68874.00

ITEM 1029 20580.00

ITEM 598 9568.00

0.00
MTR 170 17000.00

0.00
MTR 149 116220.00

MTR 135 16200.00


0.00
0.00
0.00

SET 0.00

0.00
SET 0.00

SET 0.00
0.00
NOS 0.00
0.00
MTR 0.00

0.00
NOS 0.00
ELECTRICAL WORKS- SUBSTATION WORKS
VACCUM CIRCUIT BREAKER PANEL

SL NO PARTICULARS QTY
806 INTERNAL ELECTRIFICATION
807 MCB DISTRIBUTION BOARD
808 SUPPLYING & FIXING DOUBLE DOOR SPN MCB DISTRIBUTION BOARD
WITH IP-42/43 PROTECTION , CONCEALED IN WALL AFTER CUTTING THE
WALL & MENING GOOD THE DAMAGES TO ORIGINAL FINISH INCL. INTER
CONNECTION WITH SUITABLE SIZES OF COPPER WIRE & NEUTRAL LINK
& PROVISON FOR EARTHING ATTACHMENT.

809 2+4 WAY ENCLOSURE ( 607710). 54


810 2+8 WAY ENCLOSURE (607711) 1
811 2+12 WAY ENCLOSURE 1
812 SUPPLYING & FIXING DOUBLE DOOR HORIZONTAL TPN MCB
DISTRIBUTION BOARD WITH IP-42/43 PROTECTION, CONCEALED IN WALL
AFTER CUTTING THE WALL & MENDING GOOD THE DAMAGES TO
ORIGINAL FINISH INCL. INTER CONNECTION WITH SUITABLE SIZE OF
COPPER WIRE & NEUTRAL LINK & PROVISION FOR EARTHING
ATTACHMENT.

813 4 WAY ENCLOSURE 104


814 SUPPLYING & FIXING DOUBLE DOOR HORIZONTAL TPN MCB
DISTRIBUTION BOARD WITH IP-42/43 PROTECTION, ON ANGLE IRON
FRAME ON WALL & MENDING GOOD THE DAMAGES TO ORIGINAL FINISH
INCL. INTER CONNECTION WITH SUITABLE SIZE OF COPPER WIRE &
NEUTRAL LINK & PROVISION FOR EARTHING ATTACHMENT.

815 UP TO 160A
816 4WAY ENCLOSURE ( LTVD04MGN) 1
817 6WAY ENCLOSURE ( LTVD06MGN) 54
818 8WAY ENCLOSURE ( LTVD08MGN) 1
819 MCB
820 SUPPLYING & FIXING 240/415V MCB OF BREAKING CAPACITY 10KA & C
CHARACTERISTICS ON DIN RAIL OF EXISTING DBS AND NECESSARY
CONNECTION
821 6-32 A SP 450
822 6-32 A DP 70
823 6-32 A TP 150
824 6-32 A FP 100
825 40,63 A FP 20
826 40, 63 A FP 75
827 100 A FP 1
828 MCB (D-CURVE)
829 6-32A SP MCB (D-CURVE) 10
830 6-32A FP MCB (D-CURVE) 10
831 MCB ENCLOSURE
832 SUPPLYING & FIXING MCB SS ENCLOSURE WITH IP-20/30 PROTECTION ,
POWDER COATED PROVISION FOR TWO/FOUR POLE MCB , CONCEALED
IN WALL AFTER CUTTING THE WALL & MENDING GOOD DAMAGES TO
ORIGINAL FINISH INCL. PAINTING , CONNECTION & PROVISION FOR
EARTHING ATTACHMENT.

833 4 WAY 54
834 AC STARTER
835 SUPPLY & FIXING OF 240V, 25A MODULAR TYPE STARTER WITH 25A 10
MODULAR SWITCH TYPE DP MCB (C-CURVE) & 4 MODULE GI MODULAR
TYPE SWITCHBOARD WITH 4 MODULE TOP COVER PLATE FLUSHED IN
WALL INCLUDING S & F SWITCHBOARD AND COVER PLATE AND MAKING
NECESSARY CONNECTIONS WITH PVC COPPER WIRE AND EARTH
CONTINUITY WIRE ETC

836 LAYING & FIXING POLYTHENE PIPE, MS BOXES, SWITCHES ETC.


837 CUTTING CHANNEL OF 40 MM X 40 MM SIZE ON MASONARY WALL INCL.
S & F HEAVY GAUGE POLYTHENE PIPE DIA ASSTATED BELOW.BY MEANS
OF IRON HOOKS & SUPPLYING AND DRAWING 18 SWG GI WIRE AS FISH
WIRE INCL. MENDING GOOD DAMAGES TO BUILDING WORKS.

838 19 MM DIA 3 MM THICK POLYTHENE PIPE WITHOUT EARTH CONTINUITY 350


WIRE
839 CUTTING CHANNEL OF 43 MM X 43 MM SIZE ON MASONARY WALL INCL.
S & F HEAVY GAUGE POLYTHENE PIPE DIA ASSTATED BELOW.BY MEANS
OF IRON HOOKS & SUPPLYING AND DRAWING 18 SWG GI WIRE AS FISH
WIRE INCL. MENDING GOOD DAMAGES TO BUILDING WORKS.

840 25 MM DIA 3 MM THICK POLYTHENE PIPE WITHOUT EARTH CONTINUITY 850


WIRE
841 SUPPLYING & FIXING SHEET METAL INSPECTION BOX (16 SWG) OF THE
FOLLOWING SIZES FLUSHED IN WALL BY HOUSING THE SAME AFTER
CUTTING BRICK WALL INCL.MAKING EARTH ATTACHMENT., PAINTING
AND MENDING GOOD DAMAGES TO BUILDING WORKS

842 100 MM X 100 MM X 65 MM 150


843 200 MM X 150 MM X 65 MM 100
844 SUPPLY & FIXING BAKELITE / PERSPEX TOP COVER ON EXISTING
INSPECTION BOARD BY BRASS SCREWS
845 100MM X 100 MM X 65 MM 150
846 200 MM X 150 MM X 65 MM 100
847 SCHEDULE OF RATES FOR PVC INSULATED AND SHEATHED WIRE IN
GI/PVC CONDUIT (SURFACE/ CONCEALED) INCLUDING REQUIRED
ACCESSORIES
848 SUPPLYING WIRING & DRAWING WITH 1.1 KV GRADE SINGLE CORE PVC
INSULATED STRANDED COPPER WIRE IN GI/PVC CONDUIT AND PAINTING

849 2 X 2.5 SQMM WIRE IN 19 MM CONDUIT INCL. S & F 1 X 14 SWG GI ECC 6000
850 2 X 4 SQMM WIRE IN 19 MM CONDUIT INCL. S & F 1 X 14 SWG GI ECC 600

851 3 X 1.5 SQMM WIRE IN 19 MM CONDUIT INCL. S & F 2 X 10 SWG GI ECC 600

852 3 X 2.5 SQMM WIRE IN 19 MM CONDUIT INCL. S & F 2 X 10 SWG GI ECC 800

853 4 X 6 SQMM WIRE IN 25 MM CONDUIT INCL. S & F 2 X 10 SWG GI ECC 300

854 DUMMY CONDUIT


855 SUPPLYING & FIXING PVC RIGID CONDUIT "FR ( PRECISION MAKE ) ON
WALL , CEILING WITH SADDLES AND OTHER ACCESSORIES AND
MENDING GOOD DAMAGES TO BUILDING WORKS
856 20 MM SIZE 2000
857 25 MM SIZE 3000
858 32 MM SIZE 3000
859 SUPPLYING & CARRYING WIRING FOR LIGHT FAN & DEPENDENT SOCKET
PAINTS BY USING 16 SWG MS/PVC CONDUITS WITH THREADED JOINTS OF
REQUIRED DIA AS PER IS 732, MS CONDUIT ACCESSORIES, MS FLEXIBLE

860 1 LIGHT POINT CONTROLLED BY A SWITCH WITH INDICATOR 425


861 2 LIGHT POINTS CONTROLLED BY A 6A SWITCH WITH INDICATOR 5
862 3 LIGHT POINTS CONTROLLED BY A 6A SWITCH WITH INDICATOR 7
863 EXHAUST FAN / FAN POINT CONTROLLED BY 6AAMP SWITCH & CEILLING 5
ROSE NEAR FAN
864 UNITS IN MS ENCLOSER
865 SITC OF FOLLOWING COMPONENTS LIKE APPROVED PLATE TYPE
MODULAR SWITCHS, SOCKET ETC DULY WIRED. ALL THE SWITCH
SOCKETS ARE WITH FRONT PLATE & WITHOUT BOXES INCE THE SAME IS
COVERED UNDER DIFFERENT ITEM.

866 1 NO- 6/16A, 6 PIN IN UNIVERSAL SOCKET CONTROLLED BY 16A, SP 250


SWITCH WITH INDICATOR, RP FOR UPS INCOMING SUPPLY ETC WITHOUT
MS BOX.
867 SAME AS ABOVE BUT WITH MS BOX 50
868 3 NOS-6A, 5PIN SOCKET CONTROLLED BY COMMON 16A, SP SWITCH WITH 250
INDICATOR, WORKSTATIONS WITHOUT MS BOX
869 SAME AS ABOVE BUT WITH MS BOX 50
870 SUPPLY & FIXING GI MODULAR BOXES, SWITCHES ETC.
871 SUPPLYING & FIXING GI MODULAR SWITCH BOARD OF THE FOLLOWING
SIZES COMPLETE WITH THREE NO. SUITABLE SIZE COPPER BAR WITH
HOLES (FOR PH, N & E) FIXED ON BAKELITE/HARD RUBBER INSULATOR
OVER THE MS WELDED CHAIRS INCL. TOP COVER FLUSHED IN WALL FOR
HOUSING THE BOARD AFTER CUTTING THEBRICK WALL INCL. MAKING
EARTHING ATTACHMENT, PAINTING AND MENDING GOOD DAMAGES TO
BUILDING WORKS.

872 4 MODULE 450


873 6 MODULE 40
874 SUPPLYING & FIXING GI MODULAR SWITCH BOARD OF THE FOLLOWING
SIZES COMPLETE WITH TOP COVER PLATE FLUSHED IN WALL FOR
HOUSING THE BOARD AFTER CUTTING THE BRICK WALL INCL. MAKING
EARTHING ATTACHMENT, PAINTING AND MENDING GOOD DAMAGES TO
BUILDING WORKS

875 2 MODULE. 200


876 SUPPLYING & FIXING 240 V 6 A MODULAR TYPE SWITCH (BRAND 200
APPROVED BY EIC) ON EXISTING GI MODULAR TYPE SWITCH BOARD
HAVING TOP COVER PLATE AND NECESSARY CONNECTIONS AS
REQUIRED.

877 SUPPLY & FIXING 240 V 16 A MODULAR KEY TYPE SWITCH ( BRAND 55
APPROVED BY EIC) ON EXISTING GI MODULAR TYPE SWITCH BOARD
HAVING TOP COVER PLATE AND MAKING NECESSARY CONNECTIONS AS
REQUIRED.

878 SUPPLY & FIXING 240 V, 6A, 5 PIN MODULAR TYPE PLUG SOCKET (BRAND 500
APPROVED BY EIC), WITHOUT SWITCH & PLUG TOP, ON EXISTING GI
MODULAR TYPE SWITCH BOARD WITH TOP COVER PLATE AND MAKING
NECY. CONNECTIONS WITH PVC CU WIRE AND EARTH CONTINUITY WIRE
ETC.

879 SUPPLY & FIXING 240 V, 16 A, 3 PIN MODULAR TYPE PLUG SOCKET 65
(BRAND APPROVED BY EIC), WITHOUT PLUG TOP AND SWITCH,
ONEXISTING GI MODULAR TYPE SWITCH BOARD WITH TOP COVER
PLATE AND MAKING NECY. CONNECTIONS WITH PVC CU WIRE AND
EARTH CONTINUITY WIRE ETC.

880 SUPPLY & FIXING 240V, MODULAR SOCKET (2 MODULE) TYPE FAN 100
REGULATOR (STEP TYPE) (BRAND APPROVED BY EIC) ON EXISTING
MODULAR GI SWITCH BOARD WITH TOP COVER PLATE INCL. MAKING
NECY. CONNECTIONS ETC.

881 1NO BLANK PLATE.(1M) 300


882 SUPPLY & FIXING 240 V, 25A MODULAR STARTER ( BRAND APPROVED BY 20
EIC) ON EXISTING GI MODULAR TYPE SWITCH BOARD WITH TOP COVER
PLATE AND MAKING NECY. CONNECTIONS WITH PVC CU WIRE AND
EARTH CONTINUITY WIRE ETC.

883 FINISHING COPPER WIRE ENDS


884 FINISHING OF THE PVC INSULATED WIRE ENDS BY SOCKETING WITH
PIN/RING TYPE COPPER SOCKETS AND INSULATED TAPES ETC.,
INCLUDING SUPPLYING SOCKETS, TAPES.
885 2.5SQMM. 1150
886 4SQ.MM. 500
887 6SQ.MM. 1150
888 POP-UP TYPE FLUSH-MOUNTING BOXES
889 SUPPLY & INSTALLATION OF SUPPLY AND ERECTION OF "MATT-
ALUMINIUM FINISH POP-UP TYPE FLUSH-MOUNTING BOXES" FOR
WORKSTATIO & MEETING ROOM TABLE APPLICATIONS WITH "PUSH AND
SLIDE" LOCKING SYSTEM FOR INSTALLATION USE THE FLUSH-
MOUNTING BOXES FOR CONCETE FLOORS OR THE KITS FOR RAISED
ACCESS FLOORS OR TABLE TOP.
890 AL.-MATT FINISH 6MODULES (2NOS 6A SOCKET+2NO+RJ45) 10
891 JUNCTION BOX
892 SUPPLY AND INSTALLATION OF FOLLOWING "16G GI POWDER COATED
COMPARTMENT TYPE RACEWAY" CONFORMING EN 50085-2-2 WITH
FIXING BRACKETS ETC. COMPLETE. THE RATE SHALL BE INCLUSIVE OF
FIXING ACCESSORIES & NECESSARY CIVIL WORKS.

893 150x150x37-90 MM GI JUNCTION BOX 250


894 225x225x37-90 MM GI JUNCTION BOX WITH FLY OVER. 150
UNIT RATE TOTAL

NOS 0.00
NOS 0.00
NOS. 0.00
0.00

NOS 0.00
0.00

0.00
NOS. 0.00
NOS 0.00
NOS. 0.00
0.00
0.00

NOS 0.00
NOS 0.00
NOS 0.00
NOS 0.00
NOS 0.00
NOS 0.00
NOS 0.00
0.00
NOS 0.00
NOS 0.00
0.00
0.00

NOS 0.00
0.00
MTR 0.00

0.00
0.00

MTR 0.00

0.00

MTR 0.00

0.00

EACH 0.00
EACH 0.00
0.00

EACH 0.00
EACH 0.00
0.00

0.00

RM 0.00
RM 0.00

RM 0.00

RM 0.00

RM 0.00

0.00
0.00

RM 0.00
RM 35 105000.00
RM 46 138000.00
0.00

POINT 0.00
POINT 0.00
POINT 0.00
POINT 0.00

0.00
0.00

NOS 0.00

NOS 0.00
NOS 0.00

NOS 0.00
0.00
0.00

NOS 0.00
NOS 0.00
0.00

NOS 0.00
NOS 0.00

NOS 0.00

NOS 0.00

NOS 0.00

NOS 0.00

NOS 0.00
NOS 0.00

0.00
0.00

SET 0.00
SET 0.00
SET 0.00
0.00
0.00
SET 0.00
0.00
0.00

NOS 0.00
NOS 0.00
ELECTRICAL WORKS- SUBSTATION WORKS
VACCUM CIRCUIT BREAKER PANEL

SL NO PARTICULARS QTY
895 LIGHT & FANS FIXTURES
896 SUPPLY OF RECESS MOUNTED LED LIGHT FIXTURE LUMINARE WITH 220
LUMINOUS EFFICACY OF MIN. 110 LUMEN/WATT AND MINIUM FLUX OF
3500 LUMEN OR MORE. (PHILIPS RC380B LED36S-6500 G4 PSD OD (FULL
GLOW) OR SIMILAR APPROVED EQUIVALENT).

897 DOWN-LIGHT LUMINARE


898 SUPPLY OF RECESS MOUNTED LED LIGHT FIXTURE LUMINARE WITH 100
LUMINOUS EFFICACY OF MIN. 110 LUMEN/WATT AND MINIUM FLUX OF
1900 LUMEN OR MORE. (PHILIPS DN195B LED20S-6500 PSU WH S1
(GREENLEDI) OR SIMILAR APPROVED EQUIVALENT).

899 SUPPLY OF RECESS MOUNTED LED LIGHT FIXTURE LUMINARE WITH 120
LUMINOUS EFFICACY OF MIN. 110 LUMEN/WATT AND MINIUM FLUX OF
1100 LUMEN OR MORE. (PHILIPS DN392B LED10S-6500 PSU WH
(GREENPERFORM) OR SIMILAR APPROVED EQUIVALENT).

900 FIXING ONLY PENDENT LIGHT FITTING COMPLETE WITH LAMP, SHADE 50
AND 24/0.2 MM (1.5SQ.MM) FLEXIBLE COPPER WIRE INCL. S&F PENDENT
HOLDER.
901 SURFACE LUMINARE
902 SUPPLY OF SURFACE MOUNTED LED LIGHT FIXTURE WITH 16W 10
LUMINAIRE. (PHILIPS SM2006 LED16S 6500 PSU OD WH (CIRRUS MINI
PRO ) OR SIMILAR APPROVED EQUIVALENT.)
903 SUPPLY OF SURFACE MOUNTED LED LIGHT FIXTURE WITH 10W LAMP. 25
(PHILIPS BN021C LED 10S PSU CDL GRS1 (SMARTBRIGHT OR SIMILAR
APPROVED EQUIVALENT.)
904 SUPPLY OF SURFACE MOUNTED LED LIGHT FIXTURE WITH 20W LAMP. 30
(PHILIPS BN021C LED 20S PSU CDL GR (SMARTBRIGHT OR SIMILAR
APPROVED EQUIVALENT.)
905 FIXING ONLY SINGLE/ TWIN FLUROSCENT LIGHT FITTING COMPLETE 40
WITH ALL ACCESSORIES DIRECTLY ON WALL/CEILING/HWROUND BLOCK
AND SUITABLE SIZE OF MS FASTENER

906 SUPPLY OF BULKHEAD LED LIGHT FIXTURE WITH 6W LUMINAIRE. 40


(PHILIPS WT202W LED6S NW PSU S2 PC (ENDURA LED BULKHEAD) OR
SIMILAR APPROVED EQUIPVALENT)
907 FIXING ONLY BULK HEAD CEILING FITTING ON WALL / CEILING BY 40
SCREWS ETC.
908 LED AVATION LIGHT LUMINAIRE
909 SUPPLY OF LED TYPE SINGLE DOME AVIATION OBSTRUCTION LIGHT . 1
( BGAV 302 LED OR SIMILAR APPROVED EQUIPVALENT.)
910 FIXING ONLY FLOODLIGHT FITTINGS ON TOP OF MASONARY STRUCTURE 1
BY 3 NOS. 10MM DIA X 87MM LONG RAG BOLTS, NUTS & DOUBLE
WASHERS COMPLETE EITHER 37 MM X 10 MM MS FLAT SUPPORT / OR BY
OTHER MEANS ASREQUIRED

911 CEILING FAN


912 SUPPLY & INSTALLATION OF CEILING FAN". THE RATE SHALL BE
INCLUSIVE OF FIXING & MOUNTING ACCESSORIES.
913 1200MM SWEEP , 3- BLADE 5 STAR RATING AC CEILING FAN .( HAVELLS 10
ES-50 OR SIMILAR APPROVED EQUIVALENT.)
914 SUPPLYING & FIXING OF BOX TYPE FAN CLAMP OF 150MM DIA & 80MM 10
DEPTH MADE OF 16 SWG CRCA SHEET WITH ONE END DULY SEALED BY
COVER, PROPERLY WELDED, , INCL. S&F 12 MM DIA 600MM LONG MS
ROD DULY BENT BY HEAT TREATMENT AT THE CENTRE POSITION OF ROD
TO GRIP FAN BOBBIN PROPERLY, INCL. BINDING THE ROD AND FAN BOX
WITH REINFORCEMENT BY 22 SWG STEEL BINDING WIRE, INCL. SUPPLY
& COVERING THE BOX WITH ALKATHENE SHEET, PLACED IN ORDER TO
PREVENT CONCRETE FROM ENTERING THE BOX.

915 FIXING ONLY CEILING FAN COMPLETE WITH BLADES, CANOPY, FORK, 10
RUBBER BUSH ETC. INCL. S&F CONNECTING WIRE FOR DOWN ROD UPTO
30CM INCL. PAINTING THE ROD WITH APPROVED PAINT AND MAKING
NECESSARY CONNECTION AS REQUIRED BY 2x1.5 SQMM FLEXIBLE
COPPER WIRE.

916 WALL MOUINTING FAN


917 SUPPLY & INSTALLATION OF " DECORATIVE WALL-MOUNTED"
OSCILLATING TYPE FAN WITH INBUILT SPEED CONTROLLER. THE RATE
SHALL BE INCLUSIVE OF FIXING & MOUNTING ACCESSORIES.

918 450MM SWEEP WALL FAN. (HAVELLS AIRBOLL HI-SPEED OR SIMILAR 10


APPROVED EQUIVALENT)
919 FIXING ONLY CABIN FAN ON WALL/CEILING BY S&F RAG BOLTS, NUTS & 10
WASHERS (6 MM DIA x 62 MM LONG) OR AS REQD. INCL. S&F 24/0.20 PVC
INSULATED FLEXIBLE COPPER WIRE 0.5 MT. LENGTH

920 EXHAUST FAN


921 SUPPLY & INSTALLATION OF " EXHAUST FAN" WITH LOUVERS. THE RATE
SHALL BE INCLUSIVE OF FIXING & MOUNTING ACCESSORIES.

922 150MM VENTILATING FAN NON-METALLIC TYPE. (HAVELLS VENTIL AIR- 25


DXR OR SIMILAR APPROVED EQUIVALENT)
923 380MM, 1PH,900RPM HEAVY DUTY EXHAUST FAN. (HAVELLS TURBO 15
FORCE SP OR SIMILAR APPROVED EQUIVALENT)
924 FIXING ONLY EXHAUST FAN AFTER MAKING HOLE IN WALL AND
MAKING GOOD DAMAGES AND SMOOTH CEMENT FINISH ETC. AS
PRACTICABLE AS POSSIBLE AND PROVIDING NECY. LENGTH OF PVC
INSULATED WIRE AND MAKING CONNECTION FOR EXHAUST OF
FOLLOWING DIAMETER:

925 23 CM (9") 25
926 38 CM (15") 15
927 FIXING ONLY LOUVER SHUTTER/COWL ON WALL ON WALL WITH NECY.
BOLTS & NUTS (6 MM DIA x 62 MM LONG)
928 FOR 23 CM (9") EXHAUST FAN 25
929 FOR 38 CM (15") EXHAUST FAN 15
930 STREET LIGHT POLE
931 SUPPLY & ERECTION OF FOLLOWING "SWWAGED TYPE STEEL TUBULAR
POLES". THE POLE SHALL BE PROVIDED WITH ELMEX CONNECTOR/SP
MCB CONTROL FOR "LLOP IN LOOP OUT" OF THE CABLE ALONG WITH
CABLE ENTRY HOLE AND INTERNAL WIRING FROM THE ELMEX
CONNECTOR/SP MCB TO THE LAMP CONTROL GEAR & LAMP WITH
2Rx2.5SQMM+1Rx1.5SQMM CU. WIRES AND ALL OTHER ACCESSORIES
COMPLETE AS REQUIRED. THE POLE SHALL CONFIRM IS-2713/1980 FOR
POLES HT STEEL GRADE BASE PLATE SHALL CONFIRM IS : 226/IS: 2062,
EN.8 GRADE FOR FOUNDATION BOLTS & AMENDED UPTO DATE. THE
RATE SHALL BE INCLUSIVE OF BASE PLATE, ARM, FOUNDATION BOLTS,
SPIRAL EARTHING WITH 10SWG GI WIRES, PAINTING, ELMEX
CONNECTOR & NECESSARY FOUNDATION CIVIL WORKS ETC. COMPLETE
IN ALL RESPECT.

932 7 METERS HIGH - BOLT-4.00 M, MID-1.50 M, TOP-1.50 M 15


933 STREET LIGHT FIXTURE
934 SUPPLY & FIXING OF THE "OUTDOOR STREET LIGHT LUMINARIE" WITH
LAMP, IGNITOR, CONTROLGEAR, HINGED FRONT FRAME WITH GLASS
COVER ETC. COMPLETE. THE INSTALLATION SHALL CONFIRM IS : 7323.
1989 & AMENDED UPTO DATE. THE RATE SHALL INCLUSIVE OF FIXING &
MOUNTING ACCESSORIES.

935 SUPPLY OF 1x40W LED STREET LIGHT LUMINARIES. (PHILIPS BRP 409 LED 15
040 CW HO MR FG S1 PSU GR (GREENLINE) OR APPROVED EQUIVALENT)

936 FIXING ONLY OUTDOOR / STREET LIGHT TYPE FLUORESCENT LIGHT 15


FITTING COMPLETE WITH ALL ACCESSORIES TO BE FIXED/PROJECTED
FROM THE WALL OF THE BUILDING INCL. MAKING HOLES TO BUILDING,
S&F 40 MM DIA GI PIPE (ISI-MEDIUM) 1.50 MTS. AVERAGE LENGTH, WITH
GI SOCKET AT ONE END AND THREAD AT THE OTHER END & SUITABLE
BEND TO HOUSE THE FITTING & MAKING NECY. CONNECTIONS WITH
S&F NECY. LENGTH OF 1.5 SQMM PVC INSULATED SINGLE CORE
STRANDED ANNEALED COPPER WIRE AND MAKING CONNECTIONS AS
REQUIRED AND MENDING GOOD DAMAGES TO WALL AND PAINTING.

937 GATE LIGHT FIXTURE


938 SUPPLY & FIXING OF THE "GATE LIGHTS" WITH LAMP, IGNITOR,
CONTROLGEAR ETC. COMPLETE. THE RATE SHALL BE INCLUSIVE OF
FIXING & MOUNTING ACCESSORIES
939 SUPPLY OF SURFACE MOUNTED LED LIGHT FIXTURE WITH 10W 10
LUMINAIRE. (PHILIPS DN170C LED 10S 6500 PSU WH (GREEN LED
SURFACE MOUNTED) OR SIMILAR APPROVED EQUIVALENT)
940 FIXING ONLY SINGLE/ TWIN FLUROSCENT LIGHT FITTING COMPLETE 10
WITH ALL ACCESSORIES DIRECTLY ON WALL/CEILING/HWROUND BLOCK
AND SUITABLE SIZE OF MS FASTENER

941 SUPPLY OF 1x25W INTEGRAL DECORATIVE LED GATE LIGHT WITH IP-65 4
PROTECTION. (PHILIPS BGP 161 LED2500/NW PSU 220-240V 7043 IN (LED
POST TOP) OR APPROVED EQUIVALENT)
942 SUPPLY OF 1x25W INTEGRAL DECORATIVE LED GATE LIGHT WITH IP-65 4
PROTECTION. (PHILIPS BGP 161 LED2500/NW PSU 220-240V 7043 IN (LED
POST TOP) OR APPROVED EQUIVALENT)
943 BOLLARD LIGHT FIXTURE
944 SUPPLY & FIXING OF THE "OUTDOOR BOLLARD LIGHTS" WITH LAMP,
IGNITOR, CONTROLGEAR ETC. COMPLETE. THE RATE SHALL BE
INCLUSIVE OF FIXING & MOUNTING ACCESSORIES.
945 SUPPLY OF 1x9W INTEGRAL DECORATIVE LED BOLLARD LIGHT. (PHILIPS 10
BCP400 LED09 D CW PSU OR APPROVED EQUIVALENT)
946 FIXING ONLY FLOODLIGHT FITTINGS ON TOP OF MASONARY STRUCTURE 10
BY 3 NOS. 10MM DIA X 87MM LONG RAG BOLTS, NUTS & DOUBLE
WASHERS COMPLETE EITHER 37 MM X 10 MM MS FLAT SUPPORT / OR BY
OTHER MEANS ASREQUIRED
UNIT RATE TOTAL

NOS 0.00

NOS 0.00

NOS 0.00

EACH 0.00

0.00
NOS 0.00

NOS 0.00

NOS 0.00

EACH 0.00

NOS 0.00

EACH 0.00

0.00
NOS. 0.00
EACH 0.00

0.00
0.00

NOS. 0.00

EACF 0.00

EACH 0.00

0.00
0.00

NOS 0.00

EACH 0.00

0.00
0.00

NOS 0.00

NOS 0.00

0.00

EACH 247 6175.00


EACH 411 6165.00
0.00

EACH 82 2050.00
EACH 110 1650.00
0.00
0.00

NOS 0.00
0.00
0.00

NOS 0.00

EACH 0.00

0.00
0.00

NOS 0.00
EACH 0.00

NOS 0.00

NOS 0.00

0.00
0.00

NOS 0.00

EACH 0.00
ELECTRICAL WORKS- SUBSTATION WORKS
VACCUM CIRCUIT BREAKER PANEL

SL NO PARTICULARS QTY
947 EXTRA LOW VOLTAGE
948 TELEPHONE CABLE
949 SUPPLYING & DRAWING 2-PAIR TELEPHONE CABLES WITH HIGH DENSITY 1500
POLYETHYLENE INSULATED SOILD ANNEALED HIGH CONDUCTIVITY
BARE COPPER OF DIA 0.5MM IN PRELAID PVC RIGID CONDUIT/IN
POLYTHENE PIPE EMBEDED IN WALL

950 SUPPLY OF 20PAIR TELEPHONE CABLE 500


951 SUPPLY OF 30PAIR TELEPHONE CABLE 1000
952 LAYING OF TELEPHONE CABLE AS BELOW, ON EXISTING CABLE TRAY 1500
AND BINDING WITH SUITABLE SIZE GI WIRE
953 TELEPHONE DISTRIBUTION BOX
954 SUPPLY & INSTALLATION OF "INDOOR TELEPHONE DISTRIBUTION BOX"
MADE OF 16GAUGE M.S. BOX WITH TERMINAL MODULES ETC
COMPLETE.
955 200 PAIR MDF KRONE MODULE WITH BOX 1
956 50 PAIR MDF KRONE MODULE WITH BOX 10
957 20 PAIR MDF KRONE MODULE WITH BOX 1
958 VOICE PORT
959 SUPPLY & FIXING TELEPHONE SOCKET(RJ11) MODULAR TYPE (BRAND 250
APPROVED BY EIC) ON EXISTING GI MODULAR BOARD HAVING TOP

960 LAN CABLE


961 SUPPLYING & DRAWING LAN CABLE (CAT6) (BRAND APPROVED BY EIC) 500
IN PRELAID PVC RIGID CONDUIT/INPOLYTHENE PIPE EMBEDED IN WALL

962 DATA PORT


963 SUPPLY & FIXING MODULAR TYPE RJ45 SUITABLE FOR CAT6 CABLE 250
(BRAND APPROVED BY EIC) ON EXIATING PVC BOARD AND TOP COVER
PLATE ON
964 SUPPLY & FIXING GI MODULAR BOXES, SWITCHES ETC.
965 SUPPLYING & FIXING GI MODULAR SWITCH BOARD OF THE FOLLOWING
SIZES COMPLETE WITH TOP COVER PLATE FLUSHED IN WALL FOR
HOUSING THE BOARD AFTER CUTTING THE BRICK WALL INCL. MAKING
EARTHING ATTACHMENT, PAINTING AND MENDING GOOD DAMAGES TO
BUILDING WORKS

966 2 MODULE. 700


967 LAYING & FIXING POLYTHENE PIPE, MS BOXES, SWITCHES ETC.
968 CUTTING CHANNEL OF 40 MM X 40 MM SIZE ON MASONARY WALL INCL.
S & F HEAVY GAUGE POLYTHENE PIPE DIA ASSTATED BELOW.BY MEANS
OF IRON HOOKS & SUPPLYING AND DRAWING 18 SWG GI WIRE AS FISH
WIRE INCL. MENDING GOOD DAMAGES TO BUILDING WORKS.
969 19 MM DIA 3 MM THICK POLYTHENE PIPE WITHOUT EARTH CONTINUITY 470
WIRE
970 CUTTING CHANNEL OF 43 MM X 43 MM SIZE ON MASONARY WALL INCL.
S & F HEAVY GAUGE POLYTHENE PIPE DIA ASSTATED BELOW.BY MEANS
OF IRON HOOKS & SUPPLYING AND DRAWING 18 SWG GI WIRE AS FISH
WIRE INCL. MENDING GOOD DAMAGES TO BUILDING WORKS.

971 25 MM DIA 3 MM THICK POLYTHENE PIPE WITHOUT EARTH CONTINUITY 450


WIRE
972 SUPPLYING & FIXING SHEET METAL INSPECTION BOX (16 SWG) OF THE
FOLLOWING SIZES FLUSHED IN WALL BY HOUSING THE SAME AFTER
CUTTING BRICK WALL INCL.MAKING EARTH ATTACHMENT., PAINTING
AND MENDING GOOD DAMAGES TO BUILDING WORKS

973 100 MM X 100 MM X 65 MM 45


974 200 MM X 150 MM X 65 MM 15
975 SUPPLY & FIXING BAKELITE / PERSPEX TOP COVER ON EXISTING
INSPECTION BOARD BY BRASS SCREWS
976 100 MM X 100 MM X 65 MM 45
977 200 MM X 150 MM X 65 MM 15
978 DUMMY CONDUIT
979 SUPPLYING AND FIXING PVC RIGID CINDUIT 'FR' (PRECISION MAKE) ON
WALL, CEILING WITH SADDLES AND OTHER ACCESSORIES AS REQUIRED
AND MENDING GOOD DAMAGES TO BUILDING WORKS

980 20MM SIZE 165


981 25MM SIZE 175
982 SUPPLYING AND FIXING GI CONDUIT 1.6MM THICK ON WALL, CEILING
WITH SADDLES AND OTHER ACCESSORIES AS REQUIRED AND MENDING
GOOD DAMAGES TO BUILDING WORKS
983 19MM SIZE 750
984 25MM SIZE 1000
UNIT RATE TOTAL

MTR 0.00

NOS 0.00
NOS 0.00
MTR 0.00

0.00

NOS 0.00
NOS 0.00
NOS 0.00

EACH 0.00

0.00
MTR 0.00

0.00
EACH 0.00

0.00

NOS 0.00
MTR 0.00

MTR 0.00

EACH 0.00
EACH 0.00

EACH 0.00
EACH 0.00

SET 0.00
SET 0.00

SET 0.00
SET 0.00
ELECTRICAL WORKS- SUBSTATION WORKS
VACCUM CIRCUIT BREAKER PANEL

SL NO PARTICULARS QTY
484 SUPPLY, DELIVERY AT SITE , ERECTION, TESTING & COMMISSIONING OF 1
THE FOLLOWING SWITCH BOARD PANEL(S) INCLUDING MAKING/ SUPPLY
NECESSARRY CC FOUNDATION, MOUNTING CHANNELS ETC AND FIXING
THE PANEL (S) ON THE FOUNDATION AND MOUNTING CHANNEL AFTER
PROPER ALIGNMENT WITH FOUNDATION BOLTS, NUTS , LEVELLING
CUTTING NECESSARRY CHASESON FLOOR AND MENDING GOOD
DAMAGES, EARTHING , PAINTING ETC. AS REQUIRED AS PER
SPECIFICATION. THE PANEL SHALL BE INSTALLED IN THE HT
SWITCHGEAR ROOM OF THE SUBSTATION BUILDING. THE PANEL SHALL
COMPRISE SELF POWER PACK ARRANGEMENT, ANTI PUMPING RELAY
AND TRANSFORMER NCT PROTECTION RELAY (STAND BY EARTH FAULT
RELAY).

485 ONE (1) SET OF THREE PANELS(1 NO. INCOMING & 2 NOS. OUTGOING)
CUBICLE TYPE INDOOR, FLOOR MOUNTED, METAL CLAD TOTALLY
ENCLOSED EXTENSIBLE ON EITHER SIDE HORIZONTAL DRAWOUT TYPE
11 KV VACUUM CIRCUIT BREAKER(VCB) HAVING FOLLOWING
COMPONENTS:

486 1 SET- 630A, TP, 12 KV, 50 HZ VACUUM CIRCUIT BREAKER (VCB) HAVING
STC OF 26.3KA FOR 3 SECONDS HAVING THE FOLLOWING COMPONENTS.

487 a) 1 SET ( 3 NOS/SET)-150/5-5A DUAL CORE CAST RESIN TYPE CURRENT


TRANSFORMER CL-5P10 FOR PROTECTION & CL-0.5 FOR METERING WITH
15VA BURDEN EACH.
488 b) 1 SET (3 NOS/SET)- CAST RESIN CONSTRUCTION TYPE POTENTIAL
TRANSFORMER 11 KV √3 : 110 V/ √3 WITH CL- 0.5 ACCURACY WITH 100 VA
BURDEN WITH HRC FUSES AT PRIMARY & SECONDARY FOR PROTECTION.

489 c) 1 SET - ANALOGUE AMMETER ( 0-150A) WITH AMMETER SELECTOR


SWITCH AND HRC FUSE PROTECTION TO BE OPERATED WITH CT.

490 d) 1 SET - ANALOGUE VOLTMETER (0-15 KV) WITH VOLTMETER


SELECTOR SWITCH AND HRC FUSE PROTECTION TO BE OPERATED WITH
PT.
491 e) 1 SET - NEUTRAL DISPLACEMENT AND TIME DELAY RELAY.
492 f) 1 SET - NUMERICAL TYPE IDMT RELAY( 50/51 , 50N51N) WITH TWO
ELEMENTS FOR OVERCURRENT AND EARTH FAULT HAVING SETTINGS
50% TO 200% FOR OVERCURRENT & 20% TO 80% FOR EARTH FAULT IN
EQUAL STEPS WITH TIME AND CURRENT SETTINGS AND HIGH SET
INSTANTANEOUS UNIT.

493 g) 1 SET- NUMERICAL TYPE OVERVOLTAGE AND UNDER VOLTAGE RELAY


HAVING SETTINGS RANGING FROM 80% TO 120% IN EQUAL STEPS.
494 h) 1 SET - HIGH SPEED MASTER TRIP RELAY WITH AUXILIARY CONTACTS.

495 I) 1 SET - TRIP CIRCUIT SUPERVISIPN RELAY.


496 J) 1 SET- STAND BY EARTH FAULT RELAY.
497 K) 1 SET ( 3 NOS/SET ) R-Y-B LED PHASE INDICATION LAMPS WITH 3 NOS.
1A, SP, MCB PROTECTION.
498 L) 1 SET - ON /OFF/TRIP/TEST/TRIP CIRCUIT HEALTHY/SERVICE POSITION/
SPRING CHARGE/PT FUSE FAILURE INDICATOR CLUSTER TYPE LED
INDICATION LAMPS AND PUSH BUTTONS.
499 M) 1 SET - ANNUCIATOR UNITS.
500 N) 1 SET - EARTH BUS BARS AND ALL OTHER ACCESSORIES.
501 O) 1 SET ( 3NOS) SURGE ARRESTOR( METAL OXIDE,GAPLESS) TO BE
PROVIDED.
502 P) 1 SET - CABLE TERMINATION BOX FOR TERMINATION OF 1 RUN OF
11/11 KV(UE) GRADE 3C, 185 SQMM XLPE INSULATED AL(A) CABLE.

503 Q) 1 SET- T-N-C SWITCH TO BE PROVIDED.


504 R) 1 SET - FLUSH MOUNTING DIGITAL TRIVECTOR METER HAVING CLASS
-0.5 ACCURACY AND MAXIMUM DEMAND INDICATION (MDI) INDICATOR
TO BE OPERATED BY CT & PT SUPPLY.
505 BUSBAR
506 1 SET - 630A ,12 KV , 50 HZ TP ELECTROLYTIC GRADE TINNED COPPER BUS
BARS HAVING A FAULT LEVEL WITHSTAND CAPACITY OF 26.3 KA FOR 3
SECONDS.
507 OUTGOING
508 2 SETS- 630A , TP,12KV, 50 HZ VACCUM CIRCUIT BREAKER ( VCB) HAVING
STC OF26.3 KA FOR 3 SECONDS HAVING THE FOLLOWING COMPONENTS.

509 a) 2 SETS ( 3 NOS/SET) - 60/5.5ADUAL CORE CAST RESIN TYPE CURRENT


TRANSFORMER CI-5P 10 FOR PROTECTION AND CLASS - 0.5 FOR
METERING WITH 15 VA BURDEN.
510 b) 2 SETS (3NOS/SET) - CAST RESIN CONSTRUCTION TYPE POTENTIAL
TRANSFORMER 11 KV : √3/110V/√3 WITH ACCURACY CI-0.5 WITH 100VA
BURDEN AND WITH HRC FUSE PROTECTION AT BOTH PRIMARY AND
SECONDARY.

511) C) 2 SETS - ANALOGUE AMMETER ( 0-60A) WITH AMMETER SELECTOR


SWITCH AND HRC FUSE PROTECTION TO BE OPERATED WITH CT.

512 D) 2 SETS- ANALOGUE VOLTMETER (0-15KV) WITH VOLTMETER


SELECTOR SWITCH AND WITH HRC FUSE FOR PROTECTION TO BE
OPERATED BY PT.
513 E) 2 SETS - NEUTRAL DISPLACEMENT AND TIME DELAY RELAY.
514 F) 2 SETS - NUMERICAL TYPE IDMT RELAY (50/51 , 50N/5IN) WITH TWO
ELEMENTS FOR OVERCURRENT AND EARTH FAULT , HAVING SETTINGS
50% TO 200% FOR OVERCURRENT AND 20% TO 80% FOR EARTH FAULT IN
EQUAL STEPS WITH TIME AND CURRENT SETTINGS AND HIGH SET
INSTANTANEOUS UNITS.
515 G) 2 SETS - NUMERICAL TYPE OVERVOLTAGE RELAY HAVING SETTINGS
RANGING FROM 80% TO 120% IN EQUAL STEPS.
516 H) 2 SETS - HIGH SPEED MASTER TRIP RELAY WITH AUXILIARY
CONTACTS
517 I) 2 SETS - TRIP CIRCUIT SUPERVISION RELAY.
518 J) 2 SETS - STAND BY EARTH FAULT RELAY.
519 K) 2 SETS - ( 3NOS/SET) R-Y-B LED PHASE INDICATION LAMP WITH 3 NOS
1A, SP, MCB PROTECTION.
520 L) 2 SET- ON/OFF/TRIP/TEST/TRIP CIRCUIT HEALTHY/ SERVICE POSITION/
SPRING CHARGE / PT FUSE FAILURE INDICATOR CLUSTER TYPE LED
INDICATION LAMPS AND PUSH BUTTONS.
521 M) 2 SETS - ANNUNCIATOR UNITS.
522 N) 2 SETS - EARTHING BUS BARS.
523 O) 2SETS - CABLE TERMINATION BOX FOR TERMINATION OF 1 RUN OF
11/11 KV (UE) GRADE 3C, 185 SQMM XLPE INSULATED AL (A) CABLE.

524 P) 2 SETS T-N-C SWITCH TO BE PROVIDED.


525 CAST RESIN TYPE DRY TRANSFORMER
DESIGNING, MANUFACTURING, DELIVERY AND INSTALLATION 2
INCLUDING PLACING IN POSITION AT SITE , TESTING AND
COMMISSIONING OF 1000 KVA , 11/0.433 KV , 5 POSITION, 50 HZ COPPER
WOUND INDOOR CAST RESIN DRY TYPE TRANSFORMER WITH CLASS H
INSULATION & IP 23 ENCLOSURE. VECTOR GROUP DYn 11 HAVING HT
CABLE BOX AND LT CABLE BOX WITH CABLE GLAND PLATE SUITABLE
FOR TERMINATING 1.1 KV GRADE 4 NOS. 3.5C 400 SQMM XLPE LT CABLES
IN THE LT SIDE & 11/11 KV(E) GRADE 1 NO. 3C 185 SQMM ARMOURED AL
XLPE CABLE IN THE HT SIDE INCLUDING ALL OTHER COMPONENTS AS
SPECIFIED. SUPPLY OF ALL INSTALLATION MATERIALS LIKE MOUNTING
CHANNELS AS PER MANUFACTURERS DESIGN HIGH TENSILE BOLTS,
NUTS, WASHERS, SCREWS,CLAMPS, PAINTING, EARTHING, ETC
ASREQUIRED CONFIRMING TO THE TECHNICAL SPECIFICATION ALONG
WITH RATING & DIAGRAM PLATE , EARTHING TERMINALS,LIFTING
LUGS, OFFLOADTAP LINK, WINDING TEMPERATURE
INDICATOR,BIDIRECTIONAL ROLLERS, DIGITAL WINDING TEMPERATURE
INDICATOR WITH 2 SETS OF POTENTIAL FREE CONTCTS WITH SUITABLE
SENSORS IN EACH PHASE COMPLETE IN ALL RESPECT AS REQUIRED. THE
OFF LOAD TAP LINK WITH (+)% & (-) TAPPINGS IN STEP OF 2.5% . THE
INSTALLATION SHALL CONFIRM IS : 10028,1981(PART II)& AMENDED UP
TO DATE. THE RATE SHALL BE INCLUSIVE OF NECESSARY CIVIL WORKS,
MOUNTING CHANNELS,EARTHING ETC COMPLETE IN ALL RESPECT. THE
TRANSFORMER SHALL BE INSTALLED IN THE TRANSFORMER ROOM IN
SUBSTATION BUILDING.

527 HT CABLE
528 SUPPLY OF 11/11KV {E}, 3C HT XLPE{E} AL ARMOURED CABLE . THE RATE
SHALL BE INCLUSIVE OF NECESSARY SUPPORTING & CLAMPING
ARRANGEMENT FOR LAYING OF CABLES WITHIN TRAY/ PIPE/TRENCH.
THE INSTALLATION SHALL CONFIRM IS : 1255.1983 & AMENDED UP TO
DATE.

529 11KV,3C X 185 SQMM XLPE AL CABLE 40


530 HT CABLE END TERMINATION
531 SUPPLY & FIXING OF "HEAT SHRINKABLE INDOOR TYPE CABLE END
TERMINATION KIT " SUITABLE FOR THE 11KV XLPE {E} CABLE WITH
EPOXY/POLYURETHANE RESIN BASED KITS, TAPES, PUSH ON
KITS,MULTICONDUCTOR CONSTRUCTION ETC.COMPLETE. THE
INSTALLATION SHALL CONFIRM IS: 1225.1983 & AMENDED UPTO DATE.

532 11/11KV{E}, 3C X 185 SQMM XLPE CABLE END TERMINATION KIT 4


533 LAYING THROUGH MASONRY TRENCH
534 LAYING OF ONE CABLE ABOVE 150 SQMM ND UP TO 300 SQMM THROUGH 55
EXISTING COVERED MASONRY TRENCH INCL. TAKING OUT RC COVERS,
SETTING THEM IN ORDER, MENDING GOOD THE DAMAGES FILLING THE
TRENCH WITH FINE DRY SAND INCL.SUPPLYING SAND.

535 EARTHING INSTALLATIONS


536 EXCAVATION OF SOILFOR INSTALLATION OF EARTH ELECTRODE AND 54
FILLING & RAMMING
537 EARTHING WITH 65 MM DIA GI PIPE ( TATA MEDIUM) X 3.0 MTS LONG AND 14
1 NO. 50MM X 6 MM GALVANIZED BOLT, DOUBLE NUTS,DOUBLE
WASHERS INCLUDING FINISHING BOTH ENDS BY MAKING HOLES ETC
AND S & F 65 MM DIA GI PIPE (ISI-MEDIUM) PROTECTION (3MTR LONG)
TO BE FILLED WITH BITUMEN PARTLY UNDER THE GROUND LEVEL AND
PARTLY ABOVE GROUND LEVEL TO AN AVERAGE DEPTH OF 3.65 MTS.

538 EARTHING WITH COPPER PLATE (610 X 610 X 3MM SIZE ) HAVING WEIGHT 10
OF 9.84 KG AND 1 NO 25 X 5 MM COPPER STRIP (3.20 MT LONG) & 1 NO 6
SQMM PVC INSULATED STRANDED COPPER WIRE (4MT. LONG) TO BE
FILLED WITH BITUMEN, PARTLY UNDER GROUND LEVEL & PARTLY
ABOVE GROUND LEVEL TO AN AVERAGE DETHOF 3.65 MTS. BELOW THE
GROUND LEVEL AND RESTORING THE SURFACE DULY RAMMED INCL.
PROVIDING 3 MT. LONG , 25 MM DIA GI PIPE (ISI-MEDIUM) OF PERIODIC
TREATMENT , INCL. PROVIDING MASONERY ENCLOSURE ON THE TOP OF
THE EARTH ELECTRODE OF OVERALL SIZE 86.36 X 86.36 X 46 CM DEEP
(BELOW GROUND LEVEL) COMPLETE WITH CEMENTED BRICK WORK
(1:6) OF 25 CM WIDTH , DULY PLASTERED WITH CEMENT MORTER
(INSIDE) CL HINGED INSPECTION COVER OF SIZE 36.56 X 35.56 CM WITH
LOCKING ARRANGEMENT, GI REDUCER AND TREATMENT OF SOIL BY
USING SALT & CHARCOAL OR COKE FOR PLATE ELECTRODE.
539 EXTRA FOR PROVIDING MASONERY ENCLOSURE ON THE TOP OF THE 28
EARTH ELECTRODE OF OVERALL SIZE 86.36CM X 86.36 CM X 46 CM DEEP (
BELOW GROUND LEVEL) COMPLETE WITH CEMENTED BRICK WORK (1:6)
OF 25 CM WIDTH DULY PLASTERED WITH CEMENT MORTER(INSIDE) CL
HINGED INSPECTION COVER OF SIZE 36.36 CM X 35.56 CM WITH LOCKING
ARRANGEMENT, GI REDUCER INCLUDING DRILLING OF 46 NOS. 12 MM
DIA HOLES ON THE GI PIPE.

540 EXTRA FOR TREATMENT OF SOIL BY USING SALT & CHARCOAL OR COKE 18
FOR PLATE ELECTRODE.
541
542 SUPPLYING & FIXING EARTH BUSBAR OF 50MM X 6 MM G.I STRIP ON 40
WALL HAVING CLEARANCE OF 6 MM FROM WALL INCLUDING
PROVIDING DRILLED HOLES ON THE BUSBAR COMPLETE WITH G.I
BOLTS, NUTS, WASHERS, SPACING INSULATORS ETC ASREQUIRED.

543 EXTRA FOR CONNECTING THE NEUTRAL OF TRANSFORMERS /EARTH 400


BUSBAR TO EARTH ELECTRODE INCLUDING S & F 50MM X 6 MM GI STRIP
ON WALL / FLOOR WITH GI SADDLES & INSULATING THE SAME BY ONE
LAYER OF PVC STRIP OVER ONE LAYER OF AMPERE TAPE.

544 WITH 50 X 6 MM COPPER STRIP 150


545 SAFETY ITEM
546 RUBBER MATS UPTO 11 KV GRAD ( CLASS- C), 1.0 METER X 2.0 METER 30
AND OF 2.5MM THICKNESS AND CONFIRM IS : 15652 : 2006.
547 SUPPLY & FIXING OF WOODEN BOUND, GLASS COVERED , SHOCK 2
TREATMENT CHART(BOTH IN BENGALI & ENGLISH) ONWALL WITH
NECESSARY SCREW& OTHER AS REQUIRED.
548 SUPPLY & FIXING OF FIRST AID BOX COMPLETE WITH ALL ITEMS AS 1
REQUIRED.
549 SUPPLY & FIXING OF DANGER BOARD FOR HIGH VOLTAGE, 11KV, 415V 10
(250 X 200MM ) AS PER IS BOTH IN ENGLISH & BENGALI.
550 LT DISTRIBUTION SYSTEM
551 MEDIUM VOLTAGE SWITCH BOARD
552 MAIN LT PANEL (S/S BUILDING)
553 SUPPLY, DELIVERY AT SITE, ERECTION, TESTING & COMMISSIONING OF
VERTICAL FLOOR MOUNTING FREE STANDING, EXTENSIBLE ON EITHER
SIDE, COMPARTMENTALISED CUBICAL TYPE PANEL BOARD MADE OF 14
SWG (2.04 MM) CRCA MS SHEET SUITABLE FOR 500/415V, 50HZ, AC, 3
PHASE AND NEUTRAL SYSTEM HAVING THE FOLLOWING FEATURES
PANEL SHALL BE DESIGNED TO ENSURE THAT THE WEIGHT OF THE
COMPONENTS IS ADEQUATLY SUPPORTED WITHOUT DEFORMATION OR
LOSS IN ALLIGNMENT. THE DOORS OF THE CUBICLE SHALL BE FITTED
WITH DUST EXCLUDING NEOPRENE GASKETS WITH FSTNERS FOR
PROPER COMPRESSION OF THE GASKETS.
554 PANEL SHALL BE MULTITIER COMPARTMENTALISED CUBICAL TYPE,
EXTENSIBLE ON EITHER SIDE AND SHALL BE TREATED WITH ALL
NTICORROSIVE PROCESS BEFORE PAINTING WITH TWO COATS OF ZINE
CHROMATE PRIMER AND FINAL APPROVED SHADE OF ENAMEL PAINT.

555 BUSBARS SHALL BE OF CONTINUOUS RATED ALUMINIUM ADEQUATE


FOR SPECIFIED RATED CONTINUOUS AND SHORT CIRCUIT CURRENT
COVERED BY, PROPER GRADED HEAT SHRINKABLE PVC SLEEVES
(COLOR CODED). BUSBARS SHALL BE SUPPORTED BY SUITABLE
HYLAM/DMC/SMC OR COMPATABLE INSULATOR SUPPORTS. HIGH
TENSILE BOLTS AND SPRINGS WASHERS ARE TO BE PROVIDED ON ALL
BUSBARS AND SUITABLE DRILLED HOLES FOR CONNECTION JOINTS. THE
BUSBARS SHALL HAVE A THROUTH FAULT WITH STAND CAPACITY OF
17MVA, RMS SYMMETRICAL FOR ONE SECOND. THE INTERCONNECTIONS
BETWEEN THE BUSBARS AND THE CIRCUIT BREAKERS SHALL BE MADE
BY CONTINUOUS RATED ALUMINIUM STRIPS SUITABLY COVERED BY
PROPER GRADED HEAT SHRINKABLE COLOUR CODED PVC SLEEVES. THE
EARTH BUSBAR SHALL RUN THROUGH THE LENGTH OF THE PANEL AND
TERMINATED AT TWO ENDS.

556 ALL THE MCCBS SHALL BE PROVIDED WITH EXTENDED ROTARY


OPERATED MECHANISM. SAFTY INTERLOCKS ARE TOO BE PROVIDED TO
PREVENT THE DOORS OF THE COMPARTMENTS HOUSING THE MCCBS TO
PREVENT THE DOORS TO OPEN WHEN THE MCCBS ARE 'ON' POSITION.

557 ACBS SHALL BE METAL CLAD, INDOOR TYPE (IN FULLY DRAWOUT
EXECUTION) MOUNTED ON FULLY DRAWOUT TRUCK WITH SERVICE,
TEST AND ISOLATED POSITION AND COMPLETE WITH THE FOLLOWING
SAFTY INTERLOCKS AND SAFTY SHUTTERS AND PADLOCK FACILITY.

558 IT SHALL NOT BE POSSIBLE TO MOVE THE TRUCK IN OR OUT OF CUBICLE


WHEN THE BREAKER IS CLOSED.
559 ACB COMPARTMENT DOOR SHALL BE MACHENICALLY INTERLOCKED SO
THAT IT WILL NOT POSSIBLE TO CLOSE THE ACB IN PLUG POSITION
WHEN THE DOOR IS OPEN.
560 IT SHALL NOT BE POSSIBLE TO PUSH THE TRUCK IN CLOSE POSITION IF
EITHER OF THE SAFETY SHUTTER IS NOT FREE AND NOT IN CLOSE
POSITION.
561 ACBS OF SIMILAR RATING SHALL BE INTERCHANGEABLE. ALL CONTROL
WIRING IN THE PANEL SHALL BE CARRIED OUT WITH 1.1KV GRADE
SINGLE CORE PVC INSULATED COPPER CONDUCTORS OF MINIMUM 2.5
SQ.MM. CROSS SECTION FOR POTENTIAL CIRCUITS AND CT CIRCUITS
WIRING SHOULD BE NEALTY BUNCHED , ADEQUATLY SUPPORTED,
PROPERLY ROULED AND FINALLY CRIMED. WIRES ARE TO BE
INDENTIFIED BY NUMBERED FERULES AT EITHER END. TERMINAL
BLOCKS USED ARE OF DAMP TYPE WITH BARRIERED TERMINALS AND
ARE TO BE NUMBERED.

562 ADEQUATE CABLING SPACE SHOULD BE AVAILABLE IN THE PANEL WITH


CABLE SUPPORTS, CABLE ALLEYS, ETC. PROVISION FOR TOP/BOTTOM
ENTRY AND TERMINATION OF REQUIRED NUMBER OF XLPE CABLE
SHALL BE PROVIDED. THE POSITION OF CONTROL SWITCHES, PUSH
BUTTONS, LEVERS, ETC REQUIRING MANUAL OPERATION SHALL BE AT A
HEIGHT NOT EXCEEDING 1850MM FROM THE FINISHED FLOOR LEVEL.
THE RATE SHALL ALSO INCLUDE PROVIDING AND FIXING SPACE HEATER
WITH THERMOSTAT CONTROL TEMPERATURE CONTROLLER INCLUDING
CONNECTING THE SAME WITH THE SYSTEM WITH ALL OTHER
ACCESSORIES VIZ SOCKETS, ETC. REQUIRED. THE PANEL SHALL ALSO BE
PROVIDED WITH CUBICLE ILLUMINATION LAMPS AS PER REQUIREMENT
INCLUDING CONNECTING THE SAME WITHIN THE PANEL WITH ALL
OTHER ACCESSORIES REQUIRED.

563 THE PANEL SHALL ALSO COMPROMISE OF NECESSARY METERS, CTS,


PROTECTION MCBS/HRC FUSES, INDICATION LAMPS RELAYS, LIFTING
BOLTS, LABEL INSCRIPTIONS (METALIC ENGRAVED INDENTIFICATION
TAGS) DESCRIBING THE RATING OF THE BREAKERS, BUS COUPLERS,
DESIGNATION OF THE FEDEERS ETC INCLUDING ALL OTHER
ACCESSORIES, COMPLETE AS PER IE RULES AND REGULATIONS
CONFORMING TO RELEAVANT IS AND DULY APPROVED BY CLIENT/
CONSULTANT. THE RATE SHALL INCLUDE NECESSARY CUTTING CHASES,
AND MENDING GOOD DAMAGES DURING INSTALLATION. THE PANEL
SHALL HAVE THE FOLLOWING MAJOR COMPONENTS.

564 INCOMER 1
565 3 NOS 1600A, 4P ELECTRICALLY OPERATED, MOTORISED-CUM-MANUAL
SPRING CHARGED WITHDRAWABLE TYPE acb OF RATED SERVICE
VOLTAGE UPTO 690V, 50HZ WITH MANUAL PUSH BUTTONS, INDICATIONS,
CURRENT SENSORS, CTS, ETC CONFIRMING TO THE SPECIFICATION AND
AS FOLLOWS:

566 ICU-50 KA( AT 415V, 50 HZ), ICS= 100% ICU AND ICW NOT LESS THAN 50 KA
FOR 1 SEC.
567 MICROPROCESSOR BASED S/C, E/F & O/C RELEASES.
568 RATED IMPULSE WITHSTAND VOLTAGE NOT LESS THAN 12 KV FOR M,AIN
CONDUCTING PATHS.
569 AUXILIARY CONTACTS, SHUNT TRIP COILS ETC.
570 3 SETS - CORE BALANCE CT WITH EARTH LEAKAGE RELAY.
571 3 SETS CT OPERATED DIGITAL MULTIFUCTION METER HAVING CI-1.0 FOR
APFCR WITH 15 VA BURDEN EACH.
572 3 SET (3 NOS/SET)1600/5-5A DUAL CORE CAST RESIN TYPE CURRENT
TRANSFORMER OF CL-5P10 FOR PROTECTION AND CL-1 FOR METERING
WITH 15VA BURDEN EACH.
573 3 SETS - CT OPERATED 3 O/C + 1 E/F RELAY HAVING PROTECTION CLASS
5P10.
574 2 SET (3 NOS/SET) 1600/5A CAST RESIN TYPE CURRENT TRANSFORMER OF
CL -.10 FOR APFCR WITH 15VA BURDEN EACH.
575 3SET (3 NOS./SET) - CAST RESIN CONSTRUCTION TYPE POTENTIAL
TRANSFORMER 415V/√3 : 110V/√3 WITH CL-0.1 ACCURACY WITH 100VA
BURDEN WITH HRC FUSES AT PRIMARY AND SECONDARY FOR
PROTECTION.

576 3 SETS( 3 NOS EACH) RYB CLUSTER TYPE LED PHASE INDICATION LAMPS.

577 3 SETS(7NOS EACH) - SPRING CHARGED/TEST/ON/OFF/TRIP/SELF


TRIP/TRIP CKT HEALTHY CLUSTER TYPE LED INDICATION LAMPS.

578 2 SETS- LINE VOLTAGE MONITORING MODULE.


579 BUS- COUPLER
580 1 NO. BUS-COUPLER 1600A, 4P ELECTRICALLY OPERATED, MOTORISED
-CUM-MANUAL SPRING CHARGED WITHDRAWABLE TYOE ACB OF RATED
SERVICE VOLTAGE UPTO 690V, 50 HZ WITH MANUAL PUSH BUTTONS,
INDICATIONS, CURRENT SENSORS. CTS ETC CONFIRMING TO THE
SPECIFICATION. ICU= 50KA (AT 415V, 50 HZ). ICS-100% ICU AND ICS NOT
LESS THAN 50KA FOR 1 SEC.MICROPROCESSOR BASED O/L, S/C & E/F
RELEASES WITH PROVISION FOR BACKNET, AUXILLIARY CONTACTS,
SHUNT TRIPS. 5 NOS ON/OFF/TRIP/SPRING CHARGED/TRIP CKT HEALTHY
CLUSTER TYPE LED INDICATION LAMPS ETC COMPLETE.

581 ELECTRICAL WIRED INTERLOCKING BETWEEN INCOMING BREAKERS


AND BUSCOUPLER BREAKER (3 NOS INCOMING & 1 NO BUSCOUPLER
UNIT) AS FOLLOW :
582 AUTO /MANUAL SELECTION FOR WHOLE OPERATION.
583 WHEN BOTH TRANSFORMER FED BREAKERS ARE HEALTHY (MONITORED
BY LVM) THE BUS-COUPLER AND ACB FEEDING DG SUPPLY SHALL BE
OFF.
584 IF ANY VOLTAGE VARIATION, NO VOLTAGE (MONITORED BY LVM) IN ANY
TRANSFORMERSUPPLY BREAKER THEN CLOSING COMMAND TO THE BUS
COUPLER IS TO BE GIVEN.
585 WHEN BOTH TRANSFORMER SUPPLY BREAKERS ARE CLOSED
( MONITORED BY LVM) THE AMF RELAY SHALL GIVE SIGNAL TO THE DG
CONTROL PANEL CLOSING THE DG SUPPLY ACB AND BUSCOUPLER. RATE
SHOULD INCLUDE AUXILIARY CONTACTS, SELECTOR SWITCHES, AMF
RELAY , PUSH BUTTONS, TIMERS ETC. INCLUDING ALL OTHER
MATERIALS TO SATISFY THE ABOVE OPERTION.
586 BUSBAR
587 2 SETS- 1600A, 415V, 50 HZ, 31 MVA AMPS SYMMETRICAL CONTINUOUS
RATED ALUMINIUM BUSBARS ( 2 NOS. 100MM X 10MM FOR PHASES AND 1
NO. 100MM X 10MM FOR NEUTRAL) MOUNTED ON SUITABLE
HYLAM/DMC/SMC/ INSULATORS/SUPPORTS WITH PROPER GRADED
COLOUR CODED HEAT SHRINKABLE PVC SLEEVES. SURGE PROTECTION
DEVICE WITH MPCB WITH RATED KA.

588 OUTGOING
589 a) 2 NOS 800A, 4P MANUALY OPERTAED TYPE ACB OF RATED SERVICE
VOLTAGE UPTO 690V, 50 HZ WITH AMNUAL PUSH BUTTONS, INDICATIONS,
CURRENT SENSORS, CTS, ETC CONFIRMING TO THE SPECIFICATION AND
AS FOLLOWS : ACB SHALL HAVE CURRENT AND VOLTAGE DISPLAY AND
LED INDICATION. ACB SHALL RECORD LAST 10 TRIP DATA HISTORY. ALL
VOLTAGE RELEASES SHALL BE FOR CONTINUOUSLY RATED.

590 ICU- 50 KA (AT 415V, 50HZ), ICS = 100% ICU &ICW NOT LESS THAN 50KA
FOR 1 SEC.
591 MICROPROCESSOR BASED S/C, E/F & O/C RELEASES.
592 2 SET - ON, OFF,TRIP SPRING CHARGED,READY TO CLOSE INDICATION
LED LAMPS WITH BACK-UP MCB.
593 2 SET OF R,Y,B INDICATING LAMPS, LED TYPE WITH 3 NOS. PROTECTION
FUSES.
594 2 SET VOLTMETER SELECTOR SWITCH WITH 3 NOS. PROTECTION FUSES.

595 2 SETS (3 NOS/SET)-800/5A, CL-1, 15VA CTS, 1 NO. ANALOG AMMETER (96
SQMM) 0-800A WITH SELECTOR SWITCH.
596 b) 2 NOS. 400A, 4P MCCBS' OF RATED SERVICE VOLTAGE UPTO 690V, ICU=
36KA ICS= 100% IEU AT 415V, 50 HZ WITH THERMO- MAGNETIC BASED O/L
& S/C RELEASES INCLUDING EXTENDED ROTARY OPERATED
MECHANISM, SHUNT TRIP COILS, AUXILIARY CONTACTS, SPREADERS
ETC AS NECESSARY.

597 2 SETS(3 NOS/SET) - 400/5A, CL-1, 15V CTS, 1 NO. ANALOG AMMETER (96
SQMM) 0-400A WITH SELECTOR SWITCH.
598 2 SETS- ( 3 NOS. EACH) - ON/ OFF/TRIP CLUSTER TYPE LED INDICATION
LAMPS FOR THE ABOVE MCCBS.
599 c) 2 NOS 250A, 4P MCCBS OF RATED SERVICE VOLTAGE UPTO 690V, ICU =
36 KA, ICS= 100% IEY AT 415V, 50HZ WITH THERMO-MAGNETIC BASED O/L
& S/C RELEASES INCLUDING EXTENDED ROTARY OPERATED
MECHANISM, SHUNT TRIP COILS. AUXILIARY CONTACTS, SPREADERS
ETC AS NECESSARY.

600 2 SETS ( 3 NOS/SET) - 250/5A, CL-1, 15VA CTS, 1 NO. ANALOG AMMETER ( 96
SQMM) 0-250A WITH SELECTOR SWITCH.
601 2SETS- ( 3 NOS EACH)- ON/OFF/TRIP CLUSTER TYPE LED INDICATION
LAMPS FOR THE ABOVE MCCBS.
602 d) 8 NOS 320A, 4P MCCBS OF RATED SERVICE VOLTAGE UPTO 690V. ICU=
100% IEU AT 415V, 50 HZ WITH THERMO MAGNETIC BASED O/L & S/C
RELEASES INCLUDING EXTENDED ROTARY OPERATED MECHANISM,
SHUNT TRIP COILS. AUXILIARY CONTACTS, SPREADERS ETC AS
NECESSARY.

603 8 SETS (3 NOS/SET) - 320/5A, CL-1, 15VA CTS, 1 NO. ANALOG AMMETER
( 96SQMM) 0-320A WITH SELECTOR SWITCH.
604 2 SETS- ( 3 NOS EACH) ON/OFF/TRIP CLUSTER TYPE LED INDICATION
LAMPS FOR THE ABOVE MCCBS.
605 e) 2 NOS 160A, 4P MCCBS OF RATED SERVICE VOLTAGE UP TO 690V, ICU=
25KA ICS= 100% IEU AT 415V, 50HZ WITH THERMO-MAGNETIC BASED O/L,
S/C RELEASES INCLUDING EXTENDED ROTARY OPERATED MECHANISM,
SHUNT TRIP COILS. AUXILIARY CONTACTS, SPREADERS ETC AS
NECESSARY.

606 2 SETS ( 3 NOS/SET) - 160/5A, CL-1, 15VA CTS, 1 NO. ANALOG AMMETER ( 96
SQMM) 0-160A WITH SELECTOR SWITCH.
607 2 SETS- ( 3 NOS EACH) ON/OFF/TRIP CLUSTER TYPE LED INDICATION
LAMPS FOR THE ABOVE MCCBS.
608 f) 2 NOS 100A, 4P MCCBS OF RATED SERVICE VOLTAGE UP TO 690V, ICU=
25KA ICS= 100% IEU AT 415V, 50HZ WITH THERMO-MAGNETIC BASED O/L,
S/C RELEASES INCLUDING EXTENDED ROTARY OPERATED MECHANISM,
SHUNT TRIP COILS. AUXILIARY CONTACTS, SPREADERS ETC AS
NECESSARY.

609 2 SETS ( 3 NOS/SET) - 100/5A, CL-1, 15VA CTS, 1 NO. ANALOG AMMETER ( 96
SQMM) 0-100A WITH SELECTOR SWITCH.
610 2 SETS- ( 3 NOS EACH) ON/OFF/TRIP CLUSTER TYPE LED INDICATION
LAMPS FOR THE ABOVE MCCBS.
611 g) 2 NOS - 63A 4P MCB( C-CURVE) OF RATED SERVICE VOLTAGE UPTO 415V,
ICU= 10KA , ICS= 100% ICU AT 240V 50HZ WITH THERMOMAGNETIC BASED
O/L & S/C RELEASES.
612 2 SETS- ( 3 NOS EACH) 63/5A, CL- 0.1 , 5VA , CTS WITH DIGITAL DUAL
ENERGY METER SHOWING MAXIMUM DEMAND.
613 2 SETS- (2 NOS EACH) ON/OFF CLUSTER TYPE LED INDICATION LAMPS
FOR THE ABOVE MCBS.
614 h) 8NOS -6- 32A 4P MCB( C-CURVE) OF RATED SERVICE VOLTAGE UPTO
415V, ICU= 10KA , ICS= 100% ICU AT 240V 50HZ WITH THERMOMAGNETIC
BASED O/L & S/C RELEASES.
615 2 SETS- ( 3 NOS EACH) 32/5A, CL- 0.1 , 5VA , CTS WITH DIGITAL DUAL
ENERGY METER SHOWING MAXIMUM DEMAND.
616 2 SETS- (2 NOS EACH) ON/OFF CLUSTER TYPE LED INDICATION LAMPS
FOR THE ABOVE MCBS.
617 i)3 NOS- 63A, TP, 10KA MCB(C-CURVE).
618 j)4NOS - 20A, SP , 10KA MCB (C-CURVE).
619 3 NOS. 415/240V, 200VA CONTROL TRANSFORMER.
620 EARTH BUSBAR
621 1SET - 50MM X 10 MM GI BUSBAR RUNNING ALONG THE BASE FRAME
COVERING ENTIRE LENGTH OF THE PANEL WITH HIGH TENSILE BOLTS,
NUTS, ETC AND NUMBER OF DRILLED HOLES AS REQUIRED FOR EARTH
CONNECTION AT BOTH ENDS.

622 1 NO. DANGER BOARD


623 440 KVAR AUTOMATIC POWER FACTOR CONTROL PANEL. 2
624 SUPPLY INSTALLATION TESTING AND COMISSIONING OF 500/415V, 50HZ
AC, 3 PHASE AUTOMATIC POWER FACTOR CORRECTION PANEL. THE
PANEL SHALL BE MADE OF 14 SWG THICK CRCA SHEET STEEL,
COMPARTMENTALIZED WITH METALIC PARTITIONS HAVING CONCEALED
HINGES, NEOPRENE RUBBER GASKETS, BRASS WIRE MESH FOR
VENTILATION OF CAPACITORS BY PROVIDING LAFGE SIZE OF AIR
LOUVERS. THE PANEL SHALL BE FREE STANDING WITH MS CHANNEL
BASE TO BE GROUTED ON FLOOR.

625 CABLE ALLEY SHOULD BE PROVIDED AT THE PANEL FOR TOP/BOTTOM


ENTRY OF CABLES, TERMINATION OF INCOMER MCCB AND ALSO
MULTICORE COPPER CONTROL OF SUITABLE CROSS SECTION FROM CTS
(EXISTING) IN THE MAIN LT PANEL, INCLUDING SUPPLYING AND LAYING
OF THE SAME CONTROL CABLE COMPLETE AS PER REQUIREMENT AND
WITH HORIZONTAL/VERTICAL COPPER LINK BARS OF REQUIRED
SECTION AND COVERED BY PROPER GRADED COLOUR CODED HEAT
SHRINKABLE PVC SLEEVES. EACH APFC PANEL SHALL CONSIST OF
FOLLOWING COMPONENTS :

626 INCOMER
627 1 NO 800AMP, 415V (UIMP= 12 KV) , ICW = 50KA OR HIGHER FOR 1 SEC (ICU
@415V =ICS=50KA MINIMUM) 3POLE MDO( MANUALLY OPERATED DRAW
OUT) TYPE MICROPROCESSOR CONTROLLED MODULAR ACB WITH LSG
RELEASE (ZONE : O/L,S/C, & GROUND FAULT); ACB SHALL HAVE
CURRENT AND VOLTAGE DISPLAY & LED INDICATION. ACB SHALL
RECORD LAST 10 TRIP DATA HISTORY. ALL VOLTAGE RELEASES SHALL BE
FOR CONTINUOUSLY RATED.

628 1 SET (3NOS EACH) - ON, OFF , TRIP, SPRING CHARGED, READY TO CLOSE
INDICATION LED LAMPS WITH BACK-UP MCB.
629 1 SET (3NOS EACH) - R-Y-B PHASE INDICATION LAMPS WITH 3NOS IA,SP,
MCB PROTECTION.
630 1 SET (3NOS/SET)- 800/5A, 10VA, CI-1 CURRENT TRANSFORMER.
631 1 SET CT OPERATED DIGITAL MULTIFUCTION METER HAVING CI-1
ACCURACY AND SHOWING (A,V,F MAXIMUM DEMAND).
632 1 SET -(0-500A) FLUSH MOUNTING ANALOGUE AMMETER WITH
AMMETER.
633 1 SET - (0-500V) FLUSH MOUNTING ANALOGUE VOLTMETER WITH VOLT
SELECTOR SWITCH AND HRC FUSE PROTECTION.
634 1 SET (3 NOS/SET) - CAST RESIN CONSTRUCTION TYPE POTENTIAL
TRANSFORMER 415 V/√3 WITH CL-0.1 ACCURACY WITH 100VA BURDEN
WUTH HRC FUSES AT PRIMARY AND SECONDARY FOR PROTECTION.

635 1 SET OF AUTO/MANUAL SELECTOR SWITCH.


636 BUSBAR
637 A) 1 SET - 1000A, 500V, 50 Hz, (125 MM x 6 MM) FOR NEUTRAL TPN
ALUMINIUM BUS BARS, CAPABLE FOR WITH STANDING STC OF 36 KS FOR
1 SECOND TO BE MOUNTED ON DMC/SMC INSULATOR COVERED WITH
COLOUR CODED HEAT SHRINKABLE PVC SLEEVES. SURGE PROTECTION
DEVICE WITH MPCB WITH RATED KA.

638 APRCR RELAY


639 MICROPROCESSOR BASED 12 STAGE POWER FACTOR CONTROLLER
OPERATED BY 3 NOS CT INPIUT AND MEASUREMENT OF 3 PHASE
VOLTAGE HAVING LCD DISPLAY. IT MUST DISPLAY POWER FACTOR. THE
CONTROLLER MUST ALSO HAVE ON/OFF/FAULT INDICATION FOR EACH
CONNECTED CAPACITOR.

640 OUTGOING
641 A) 2 NOS - 200A, 440V HRC FUSE FOR CAPACITOR DUTY CONTACTOR,

642 B) 2 NOS - 100A, 440V HRC FUSE FOR CAPACITOR DUTY CONTACTOR,

643 C) 6 NOS - 63A, 440V HRC FUSE FOR CAPACITOR DUTY CONTACTOR,

644 D) 2 NOS - 25A, 440V HRC FUSE FOR CAPACITOR DUTY CONTACTOR,

645 E) 2 NOS - TP CAPACITOR DUTY CONTACTOR FOR AUTOMATIC


SWITCHING 100 KVAR CAPACITOR.
646 F) 2 NOS - TP CAPACITOR DUTY CONTACTOR FOR AUTOMATIC
SWITCHING OF 50 KVAR CAPACITOR.
647 G) 6 NOS - TP CAPACITOR DUTY CONTACTOR FOR AUTOMATIC
SWITCHING OF 20 KVAR CAPACITOR.
648 H) 2 NOS - TP CAPACITOR DUTY CONTACTOR FOR AUTOMATIC
SWITCHING OF 10 KVAR CAPACITOR.
649 I) 12 SETS - ON/OFF PUSH BUTTON FOR MANUAL OPERATION WITH LED
INDICATION LAMP.
650 EARTH BUSBAR
651 1 SET - 40 MM x 6 MM GI BUSBAR RUNNING ALONG THE BASE FRAME
COVERING ENTIRE LENGTH OF THE PANEL WITH HIGH TENSILE BOLTS,
NUTS, ETC. AND NUMBER OF DRILLED HOLES AS REQUIRED FOR EARTH
CONNECTION AT BOTH ENDS.

652 1 NO. DANGER BOARD


653 GROUND FLOOR LT PANEL. 1
654 SUPPLY, DELIVERY AT SITE ERECTION, TESTING & COMMISSIONING OF
VERTICAL FLOOR MOUNTING FREE STANDING, EXTENSIBLE ON EITHER
SIDE, COMPARTMENTALISED CUBICAL TYPE PANEL BOARD MADE OF 14
SWG (2.04MM) CRCA MS SHEET SUITABLE FOR 500/415V, 50 HZ, AC, 3
PHASE AND NEUTRAL SYSTEM HAVING THE FOLLOWING FEATURES
PANEL SHALL BE DESIGNED TO ENSURE THAT THE WEIGHT OF THE
COMPONENTS IS ADEQUATELY SUPPORTED WITHOUT DEFORMATION OR
LOSS IN ALLIGNMENT. THE DOORS OF THE CUBICLE SHALL BE FITTED
WITH DUST ECLUDING NEOPRENE GASKETS WITH FASTNERS FOR
PROPER COMPRESSION OF THE GASKETS.

655 PANEL SHALL BE MULTITIER COMPARTMENTALISED CUBICAL TYPE,


EXTENSIBLE ON EITHER SIDE AND SHALL BE TREATED WITH ALL
NTICORROSIVE PROCESS BEFORE PAINTING WITH TWO COATS OF ZINE
CHROMATE PRIMER AND FINAL APPROVED SHADE OF ENAMEL PAINT.

656 BUSBARS SHALL BE OF CONTINUOUS RATED ALUMINIUM ADEQUATE


FOR SPECIFIED RATED CONTINUOUS AND SHORT CIRCUIT CURRENT
COVERED BY, PROPER GRADED HEAT SHRINKABLE PVC SLEEVES
(COLOR CODED). BUSBARS SHALL BE SUPPORTED BY SUITABLE
HYLAM/DMC/SMC OR COMPATABLE INSULATOR SUPPORTS. HIGH
TENSIBLE BOLTS AND SPRINGS WASHERS ARE TO BE PROVIDED ON ALL
BUSBARS AND SUITABLE DRILLED HOLES FOR CONNECTION JOINTS. THE
BUSBARS SHALL HAVE A THROUTH FAULT WITHSTAND CAPACITY OF 31
MVA, RMS SYMMENTRICAL FOR ONE SECOND. THE INTERCONNECTIONS
BETWEEN THE BUSBARS AND THE CIRCUIT BREAKERS SHALL BE MADE
BY CONTINUOUS RATED ALUMINIUM STRIPS SUITABLY COVERED BY
PROPER GRADED HEAT SHRINKABLE COLOUR CODED PVC SLEEVES. THE
EARTH BUSBAR SHALL RUN THROUGH THE LENGTH OF THE PANEL AND
TERMINATED AT TWO ENDS.

657 ALL THE MCCBS SHALL BE PROVIDED WITH EXTENDED ROTARY


OPERATED MECHANISM. SAFTY INTERLOCKS ARE TOO BE PROVIDED TO
PREVENT THE DOORS OF THE COMPARTMENTS HOUSING THE MCCBS TO
PREVENT THE DOORS TO OPEN WHEN THE MCCBS ARE 'ON' POSITION.
658 ADEQUATE CABLING SPACE SHOULD BE AVAILABLE IN THE PANEL WITH
CABLE SUPPORTS, CABLE ALLEYS, ETC. PROVISION FOR TOP/BOTTOM
ENTRY AND TERMINATION OF REQUIRED NUMBER OF XLPE CABLE
SHALL BE PROVIDED. THE POSITION OF CONTROL SWITCHES, PUSH
BUTTONS, LEVERS, ETC REQUIRING MANUAL OPERATION SHALL BE AT A
HEIGHT NOT EXCEEDING 1850MM FROM THE FINISHED FLOOR LEVEL.
THE RATE SHALL ALSO INCLUDE PROVIDING AND FIXING SPACE HEATER
WITH THERMOSTAT CONTROL TEMPERATURE CONTROLER INCLUDING
CONNECTING THE SAME WITH THE SYSTEM WITH ALL OTHER
ACCESSORIES VIZ SOCKETS. ETC. REQUIRED. THE PANEL SHALL ALSO BE
PROVIDED WITH CUBICLE ILLUMINATION LAMPS AS REQUIREMENT
INCLUDING CONNECTING THE SAME WITHIN THE PANEL WITH ALL
OTHER ACCESSORIES REQUIRED.

659 THE PANEL SHALL ALSO COMPROMISE OF NECESSARY METERS, CTS,


PROTECTION MCBS/HRC FUSES, INDICATION LAMPS RELAYS, LIFTING
BOLTS, LABEL INSCRIPTIONS (METALIC ENGRAVED INDENTIFICATION
TAGS) DESCRIBING THE RATING OF THE BREAKERS, BUS COUPLERS,
DESIGNATION OF THE RATING OF THE BREAKERS, BUS COUPLERS,
DESIGNATION OF THE FEEDERS ETC INCLUDING ALL OTHER
ACCESSORIES, COMPLETE AS PER IE RULES AND REGULATIONS
CONFORMING TO RELEVANT IS AND DULY APPROVED BY
CLIENT/CONSULTANT. THE RATE SHALL INCLUDE NECESSARY CUTTING
CHAES, AND MENDING GOOD DAMAGES DURING INSTALLATION. THE
PANEL SHALL HAVE THE FOLLOWING MAJOR COMPONENTS.

660 INCOMER
661 1 NO 320A, 4P ELECTRICALLY OPERATED, THERMO-MAGNETIC BASED
MCCB OF RELATED SERVICE VOLTAGE UPTO 690V, 50 HZ WITH MANUAL
PUSH BUTTONS, INDICATIONS, CURRENT SENSORS, CTS, ETC
CONFORMING TO THE SPECIFICATION AND AS FOLLOWS:

662 ICU-36KA ( AT 415V, 50 HZ), IC=100% ICU AND ICW NOT LESS THAN 36 KA
FOR 1 SEC.
663 THERMO-MAGNETIC S/C & O/C RELEASES.
664 RATED IMPULSE WITHSTAND VOLTAGE NOT LESS THAN 12 KV FOR M,AIN
CONDUCTING PATHS.
665 AUXILIARY CONTACTS, SHUNT TRIP COILS ETC.
666 1 SET. - CORE BALANCE CT WITH EARTH FAULT RELAY.
667 1 SET (3 NOS/SET) - 320/5A. 10VA, CL-1 CURRENT TRANSFORMER.
668 1 NO. - CT OPERATED DIGITAL MULTIFUCTION METER HAVING CL-1
ACCURACY AND SHOWING (A, V, F, MAXIMUM DEMAND)
669 1 SET (3 NOS/SET) - CAST RESIN CONSTRUCTION TYPE POTENTIAL
TRANSFORMER 415 V/√3 WITH CL-0.1 ACCURACY WITH 100VA BURDEN
WUTH HRC FUSES AT PRIMARY AND SECONDARY FOR PROTECTION.
670 1 SET (3 NOS EACH) RYB CLUSTER TYPE LED PHASE INDICATION LAMPS.

671 1 SET (3 NOS EACH) RYB CLUSTER TYPE LED PHASE INDICATION LAMPS.

672 1 SET - ON/OFF ILUMINATED PUSH BUTTON.


673 BUSBAR
674 1 SET - 400A, 415V, 50 HZ, 31 MVA AMPS SYMMETRICAL CONTINUOUS
RATED ALUMINIUM BUSBARS (40 MM x 10 MM) FOR PHASE AND 1 NO. 40
MMx 6 MM FOR NEUTRAL) MOUNTED ON SUITABLE HYLAM/DMC/SMC/
INSULATORS/SUPPORTS WITH PROPER GRADED COLOUR CODED HEAT
SHRINKABLE PVC SLEEVES.

675 OUTGOING
676 A) 11 NOS - 63A, FP, 10KA MCB (C-CURVE) OF RATED SERVICE VOLTAGE
UPTO 415V, ICU=10KA, ICS= 100% ICU AT 415V 50HZ, WITH THERMO-
MAGNETIC BASED O/L & S/C RELEASES.
677 11 SETS - (3 NOS EACH) 63/5A, CL-1.0, 5VA, CTS WITH DIGITAL DUAL
ENERGY METER SHOWING (A, V, F, MAXIMUM DEMAND).
678 EARTH BUSBAR
679 1 SET - 25 MMx 6 MM GI BUSBAR RUNNING ALONG THE BASE FRAME
COVERING ENTIRE LENGTH OF THE PANEL WITH HIGH TENSIBLE BOLTS,
NUTS, ETC. AND NUMBER OF DRILLED HOLES AS REQUIRED FOR EARTH
CONNECTION AT BOTH ENDS.

680 1 NO. DANGER BOARD


681 FIRST FLOOR TO SEVENTH FLOOR LT PANEL
682 SUPPLY, DELIVERY AT SITE ERECTION, TESTING & COMMISSIONING OF
VERTICAL FLOOR MOUNTING FREE STANDING, EXTENSIBLE ON EITHER
SIDE, COMPARTMENTALISED CUBICAL TYPE PANEL BOARD MADE OF 14
SWG (2.04MM) CRCA MS SHEET SUITABLE FOR 500/415V, 50 HZ, AC, 3
PHASE AND NEUTRAL SYSTEM HAVING THE FOLLOWING FEATURES
PANEL SHALL BE DESIGNED TO ENSURE THAT THE WEIGHT OF THE
COMPONENTS IS ADEQUATLY SUPPORTED WITHOUT DEFORMATION OR
LOSS IN ALLIGNMENT. THE DOORS OF THE CUBICLE SHALL BE FITTED
WITH DUST EXCLUDING NEOPRENE GASKETS FASTNERS FOR PROPER
COMPRESSION OF THE GASKETS.

683 PANEL SHALL BE MULTITIER COMPARTMENTALISED CUBICAL TYPE,


EXTENSIBLE ON EITHER SIDE AND SHALL BE TREATED WITH ALL
NTICORROSIVE PROCESS BEFORE PAINTING WITH TWO COATS OF ZINE
CHROMATE PRIMER AND FINAL APPROVED SHADE OF ENAMEL PAINT.
684 BUSBARS SHALL BE OF CONTINUOUS RATED ALUMINIUM ADEQUATE
FOR SPECIFIED RATED CONTINUOUS AND SHORT CIRCUIT CURRENT
COVERED BY, PROPER GRADED HEAT SHRINKABLE PVC SLEEVES
(COLOR CODED). BUSBARS SHALL BE SUPPORTED BY SUITABLE
HYLAM/DMC/SMC OR COMPATABLE INSULATOR SUPPORTS. HIGH
TENSIBLE BOLTS AND SPRINGS WASHERS ARE TO BE PROVIDED ON ALL
BUSBARS AND SUITABLE DRILLED HOLES FOR CONNECTION JOINTS. THE
BUSBARS SHALL HAVE A THROUTH FAULT WITHSTAND CAPACITY OF 31
MVA, RMS SYMMENTRICAL FOR ONE SECOND. THE INTERCONNECTIONS
BETWEEN THE BUSBARS AND THE CIRCUIT BREAKERS SHALL BE MADE
BY CONTINUOUS RATED ALUMINIUM STRIPS SUITABLY COVERED BY
PROPER GRADED HEAT SHRINKABLE COLOUR CODED PVC SLEEVES. THE
EARTH BUSBAR SHALL RUN THROUGH THE LENGTH OF THE PANEL AND
TERMINATED AT TWO ENDS.

685 ALL THE MCCBS SHALL BE PROVIDED WITH EXTENDED ROTARY


OPERATED MECHANISM. SAFTY INTERLOCKS ARE TOO BE PROVIDED TO
PREVENT THE DOORS OF THE COMPARTMENTS HOUSING THE MCCBS TO
PREVENT THE DOORS TO OPEN WHEN THE MCCBS ARE 'ON' POSITION.

686 ADEQUATE CABLING SPACE SHOULD BE AVAILABLE IN THE PANEL WITH


CABLE SUPPORTS, CABLE ALLEYS, ETC. PROVISION FOR TOP/BOTTOM
ENTRY AND TERMINATION OF REQUIRED NUMBER OF XLPE CABLE
SHALL BE PROVIDED. THE POSITION OF CONTROL SWITCHES, PUSH
BUTTONS, LEVERS, ETC REQUIRING MANUAL OPERATION SHALL BE AT A
HEIGHT NOT EXCEEDING 1850MM FROM THE FINISHED FLOOR LEVEL.
THE RATE SHALL ALSO INCLUDE CONNECTING THE SAME WITH THE
SYSTEM WITH ALL OTHER ACCESSORIESW VIZ SOCKETS. ETC.
REQUIRED. THE PANEL SHALL ALSO BE PROVIDED WITH CUBICLE
ILLUMINATION LAMPS AS PER REQUIEMENT INCLUDING CONNECTING
THE SAME WITHIN THE PANEL WITH ALL OTHER ACCESSORIES
REQUIRED.

687 THE PANEL SHALL ALSO COMPROMISE OF NECESSARY METERS, CTS,


PROTECTION MCBS/HRC FUSES, INDICATION LAMPS RELAYS, LIFTING
BOLTS, LABEL INSCRIPTIONS (METALIC ENGRAVED INDENTIFICATION
TAGS) DESCRIBING THE RATING OF THE BREAKERS, BUS COUPLERS,
DESIGNATION OF THE FEEDERS ETC. INCLUDING ALL OTHER
ACCESSORIES, COMPLETE AS PER IE RULES AND REGULATION
CONFORMING TO RELEVANT IS AND DULY APPROVED BY
CLIENT/CONSULTANT. THE RATE SHALL INCLUDE NECESSARY CUTTING
CHASES. AND MENDING GOOD DAMAGES DURING INSTALLATION. THE
PANEL SHALL HAVE THE FOLLOWING MAJOR COMPONENTS.

688 INCOMER
689 1 NO 320A, 4P ELECTRICALLY OPERATED, THERMO-MAGNETIC BASED
MCCB OF RELATED SERVICE VOLTAGE UPTO 690V, 50 HZ WITH MANUAL
PUSH BUTTONS, INDICATIONS, CURRENT SENSORS, CTS, ETC
CONFORMING TO THE SPECIFICATION AND AS FOLLOWS:

690 ICU-36 KA (AT 415V, 50HZ), ICS=100% ICU AND ICW NOT LESS THAN 36KA
FOR 1 SEC.
691 THERMO-MAGNETIC S/C & O/C RELEASES.
692 RATED IMPULSE WITHSTAND VOLTAGE NOT LESS THAN 12 KV FOR M,AIN
CONDUCTING PATHS.
693 AUXILIARY CONTACTS, SHUNT TRIP COILS ETC.
694 1 SET - CORE BALANCE CT WITH EARTH FAULT RELAY.
695 1 SET (3 NOS/SET) - 320/5A. 10VA, CL-1 CURRENT TRANSFORMER.
696 1 NO - CT OPERATED DIGITAL MULTIFUNCTION METER HAVING CL-1
ACCURACY AND SHOWING (A, V, F, MAXIMUM DEMAND).
697 1 SET (3 NOS/SET) - CAST RESIN CONSTRUCTION TYPE POTENTIAL
TRANSFORMER 415 V/√3 : 110V/√3 WITH CL-0.1 ACCURACY WITH 100VA
BURDEN WITH HRC FUSES AT PRIMARY AND SECONDARY FOR
PROTECTION.

698 1 SET (3 NOS EACH) RYB CLUSTER TYPE LED PHASE INDICATION LAMPS.

699 1 SET (3 NOS EACH) - ON/OFF/TRIP CLUSTER TYPE LED INDICATION


LAMPS.
700 1 SET - ON/OFF ILUMINATED PUSH BUTTON.
701 BUSBAR
702 1SET -400A , 415V, 50 HZ , 31MVA AMPS SYMMETRICAL CONTINUOUS
RATED ALUMINIUM BUSBARS (40MM X 10 MM FOR PHASES AND 1 NO
40MM X 6MM FOR NEUTRAL) MOUNTED ON SUITABLE HYLAM/DMC/SMC
INSULATORS/ SUPPORTS WITH PROPER GRADED COLOUR CODED HEAT
SHRINKABLE PVC SLEEVES.

703 OUTGOING
704 a) 10 NOS - 63A , FP, 10KA MCB (C-CURVE) OF RATED SERVICE VOLTAGE
UPTO 415V, ICU= 10KA, ICS = 100% ICU AT 415V 50 HZ , WITH THERMO-
MAGNETIC BASED O/L & S/C RELEASES.
705 10 SETS- (3NOS EACH)63/5A, CL-1.0, 5VA, CTS WITH DIGITAL DUAL
ENERGY METER SHOWING (A,V,F , MAXIMUM DEMAND).
706 EARTH BUSBAR
707 1 SET- 25MM X 6 MM GI BUSBAR RUNNING ALONG THE BASE FRAME
COVERING ENTIRE LENGTH OF THE PANEL WITH HIGH TENSILE BOLTS,
NUTS ETC AND NUMBER OF DRILLED HOLES AS REQUIRED FOR EARTH
CONNECTIONAT BOTH ENDS.

708 1 NO DANGER BOARD


709 ISOLATOR PANEL(S/S BUILDING)
710 SUPPLY INSTALLATION TESTING AND COMMISSIONING OF THE FLOOR 2
STANDING/WALL MOUNTING DEAD TYPE ISOLATOR PANEL MADE OF 14
SWG (2.03 MM) CRCA SHEET METAL FABRICATED INDOOR TYPE
SUITABLE FOR 500/415V , 50 HZ, AC , 3PHASE AND NEUTRAL SYSTEM,
WITH POWER COATED ANTICORROSIVE PAINT SUITABLE FOR FRONT
OPERATION OF LOAD BREAK SWITCH, BUSBAR CHAMBERS IN BOTH
INCOMING AND OUTGOING FEEDERS, CABLEAND BOXES, SUITABLE TO
TERMINATE UPTO 4 NOS. 3.5C 400SQMM XLPE CABLE ON BOTH SIDES,
NECESSARY METERS, SMALL WIRING WITH COPPER WIRE OF MINIMIUM
2.5SQMM CROSS SECTION, PROTECTION HRC FUSES, TERMINAL BLOCKS,
SELECTOR SWITCHES ETC INCLUING SUPPLY AND FIXING OF THE
EQUIPMENTS WITH SUITABLE INTERCONNECTIONS WITH ALUMINIUM
BARS, GLAND PLATES, EARTH BUS, REBEL INCRIPTION , DOOR
INTERLOCKING BOLTING SOCKETING, PAINTING, EARTHING ETC ALL
COMPLETE INCLUDING NECESSARY CHASES AND MENDING GOOD
DAMAGES AND DULY APPROVED BY THE CONSULTANT. THE ABOVE
PANEL COMPRISING THE FOLLOWING MAJOR COMPONENTS :

711 1 NO. 1600A , 4P 415 V, 50 HZ LOAD BREAK SWITCH (AC 23A)


712 1SET (3 NOS.) - 1600/5A, CL-1.0 , 15VA CTS WITH ANALOG AMMETER 0-
1600A WITH SELECTOR SWITCH.
713 1SET -0-500V, AC, VOLTMETER WITH 3 NOS MCBS AND SELECTOR SWITCH.

714 2 SETS (3NOS)-R-Y-B PHASE INDICATION CLUSTER TYPE LED LAMPS.

715 1 SET- 50MM X 6MM GI BUSBAR RUNNING ALONG THE BASE FRAME
COVERING ENTIRE LENGTH OF THE PANEL WITH HIGH TENSILE BOLTS,
NUTS ETC AND NUMBER OF DRILLED HOLES AS REQUIRED FOR EARTH
CONNECTIONAT BOTH ENDS.

716 1 NO. DANGER BOARD


717 MCCB WITH ENCLOSURE AT GROUND FLOOR
718 7 NOS-320A, 415V (UIMP=8KV), 36KA (ICU=ICS=100%),4P NON DRAWOUT 7
TYPE THERMO MAGNETIC MCCB HAVING FRONT II FACIA, DOUBLE
BREAK TECHNOLOGY. MCCB SHALL BE WITH ADJUSTABLE O/L SETTING
WITH ENCLOSER.

719 MCB WITH ENCLOSURE AT GROUND FLOOR


720 3 NOS-63A, TP, 10KA MCB (C-CURVE) WITH ENCLOSER. 3
721 MV CABLE
722 SUPPLY OF 1.1KV 3C X 6 SQMM XLPE ARMOURED AL.CABLE AS DIRECTED 650
BY EIC.
723 SUPPLY OF 1.1KV 3.5C X 25 SQMM XLPE ARMOURED AL.CABLE AS 1250
DIRECTED BY EIC.
724 SUPPLY OF 1.1KV 3.5C X 35 SQMM XLPE ARMOURED AL.CABLE AS 100
DIRECTED BY EIC.
725 SUPPLY OF 1.1KV 3.5C X 50 SQMM XLPE ARMOURED AL.CABLE AS 70
DIRECTED BY EIC.
726 SUPPLY OF 1.1KV 3.5C X 95 SQMM XLPE ARMOURED AL.CABLE AS 300
DIRECTED BY EIC.
727 SUPPLY OF 1.1KV 3.5C X 150 SQMM XLPE ARMOURED AL.CABLE AS 200
DIRECTED BY EIC.
728 SUPPLY OF 1.1KV 3.5C X 240 SQMM XLPE ARMOURED AL.CABLE AS 800
DIRECTED BY EIC.
729 SUPPLY OF 1.1KV 3.5C X 300 SQMM XLPE ARMOURED AL.CABLE AS 100
DIRECTED BY EIC.
730 SUPPLY OF 1.1KV 3.5C X 400 SQMM XLPE ARMOURED AL.CABLE AS 1000
DIRECTED BY EIC.
731 SUPPLY OF 1.1KV 4C X 6 SQMM XLPE ARMOURED AL.CABLE AS DIRECTED 1400
BY EIC.
732 SUPPLY OF 1.1KV 4C X 10 SQMM XLPE ARMOURED AL.CABLE AS 250
DIRECTED BY EIC.
733 SUPPLY OF 1.1KV 4C X 16 SQMM XLPE ARMOURED AL.CABLE AS 1000
DIRECTED BY EIC.
734 COMPRESSION GLAND
735 SUPPLYING & FIXING COMPRESSION TYPE GLAND COMPLETE WITH
BRASS GLAND, BRASS RING, RUBBER RING FOR DUST & MOISTURE
PROOF ENTRY OF XLPE / PVC ARMOURED CABLES AS BELOW :

736 FOR 2 CORE 60


737 UPTO 6 SQMM
738 FOR 3 CORE 16
739 UPTO 6 SQMM
740 FOR 4 CORE
741 UPTO 6 SQMM 25
742 UPTO 10 SQMM 40
743 UPTO 16 SQMM 50
744 FOR 3.5 CORE
745 UPTO 25 SQMM 40
746 UPTO 35 SQMM 10
747 UPTO 50 SQMM 10
748 UPTO 95 SQMM 16
749 UPTO 150 SQMM 10
750 UPTO 240 SQMM 30
751 UPTO 300 SQMM 10
752 UPTO 400 SQMM 50
753 FINISHING CABLE ENDS
754 FINISHING THE END OF FOLLOWING XLPE/PVC ARMOURED CABLES BY
CRIMPING METHOD INCL. SUPPLYING AND FIXING SOLDERLESS SOCKET
(DOWELS MAKE) , TAPES, ANTI CORROSIVE PASTE & JOINING MATERIALS
:

755 4C 6 SQMM CABLE 32


756 4C 10 SQMM CABLE 72
757 4C 16 SQMM CABLE 60
758 3.5C 25 SQMM CABLE 150
759 3.5C 35 SQMM CABLE 20
760 3.5C 50 SQMM CABLE 20
761 3.5C 95 SQMM CABLE 32
762 3.5C 150 SQMM CABLE 20
763 3.5C 240 SQMM CABLE 80
764 3.5C 300 SQMM CABLE 20
765 3.5C 400 SQMM CABLE 150
766 SCHEDULE OF RATES FOR LAYING OF XLPE / PVC INSULATED AND
ARMOURED CABLES
767 LAYING ON WALL/ SURFACE WITH SADDLES /CLAMPS
768 LAYING OF CABLE UPTO 2CORE 25 SQMM ON WALL/ SURFACE INCL. 70
S&MS SADDLES WITH EARTHING ATTACHMENT IN 10 SWG GI (HOT DIP )
WIRE, MAKING HOLES ETC AS NECY. MENDING GOOD DAMAGES AND
PAINTING.

769 LAYING OF CABLE UPTO 3/4 CORE 25 SQMM ON WALL/SURFACE INCL. S 100
& F MS SADDLES WITH EARTHING ATTACHMENT IN 10 SWG GI (HOT DIP),
WIRE, MAKING HOLES ETC AS NECY.MENDING GOOD DAMAGES AND
PAINTING.

770 LAYING THROUGH RCC/HUME/GI PIPE


771 LAYING ONLY CABLE UPTO 50 SQMM THROUGH EXISTING RCC/HUME/GI 90
PIPE/ OPEN MASONARY TRENCH FOR SINGLE,2,3,3.5 & 4C

772 LAYING ONLY CABLE ABOVE 50 SQMM BUT NOT EXCEEDING 400SQMM 55
THROUGH EXISTING RCC/HUME/GI PIPE/OPEN MASONARY TRENCH FOR
SINGLE ,2,3,3.5 & 4CORE.
773 LAYIING THROUGH UNDERGROUND TRENCH
774 LAYING OF ONE NO. CABLE UPTO 35 SQMM IN UNDERGROUND TRENCH 1250
460MM WIDE X 760 MM AVERAGE DEPTH, WITH BRICK PROTECTION ON
THE TOP OF THE CABLE WITH 8 NOS. BRICKS PER MTR, INCLUDING
FILLING THE SPACE BETEEN THE BRICK & CABLE AND ALSO THE
TRENCH WITH SHIFTED SOIL , LEVELLING UP AND RESTORING SURFACE
DULY RAMMED

775 LAYING OF ONE NO. CABLE UPTO 35 SQMM & UPTO 185SQMM IN 450
UNDERGROUND TRENCH 460MM WIDE X 760 MM AVERAGE DEPTH, WITH
BRICK PROTECTION ON THE TOP OF THE CABLE WITH 8 NOS. BRICKS PER
MTR, INCLUDING FILLING THE SPACE BETEEN THE BRICK & CABLE AND
ALSO THE TRENCH WITH SHIFTED SOIL , LEVELLIING UP AND
RESTORING SURFACE DULY RAMMED

776 LAYING OF ONE NO. CABLE ABOVE 185 SQMM IN UNDERGROUND 1250
TRENCH 460MM WIDE X 760 MM AVERAGE DEPTH, WITH BRICK
PROTECTION ON THE TOP OF THE CABLE WITH 8 NOS. BRICKS PER MTR,
INCLUDING FILLING THE SPACE BETEEN THE BRICK & CABLE AND ALSO
THE TRENCH WITH SHIFTED SOIL , LEVELLIING UP AND RESTORING
SURFACE DULY RAMMED
777 LAYING OF 2 NOS. CABLE UPTO 35 SQMM IN UNDERGROUND TRENCH IN 410
SINGLE TIER FORMATION (HORIZONTAL) THR TRENCH SIZE 680MM WIDE
X 760 MM AVERAGE DEPTH, WITH BRICK PROTECTION ON THE TOP OF
THE CABLE WITH 8 NOS. BRICKS PER MTR,AND 4 NOS.BRICKS PER MTR
AS SEPARATOR BETWEEN THE BRICK & CABLE AND ALSO THE TRENCH
WITH SHIFTED SOIL , LEVELLING UP AND RESTORING SURFACE DULY
RAMMED

778 LAYING OF 2 NOS. CABLE ABOVE 185 SQMM IN UNDERGROUND TRENCH 450
IN SINGLE TIER FORMATION (HORIZONTAL) THR TRENCH SIZE 680MM
WIDE X 760 MM AVERAGE DEPTH, WITH BRICK PROTECTION ON THE TOP
OF THE CABLE WITH 8 NOS. BRICKS PER MTR,AND 4 NOS.BRICKS PER
MTR AS SEPARATOR BETWEEN THE BRICK & CABLE AND ALSO THE
TRENCH WITH SHIFTED SOIL , LEVELLING UP AND RESTORING SURFACE
DULY RAMMED

779 LAYING THROUGH MASONRY TRENCH


780 LAYING OF ONE CABLE UPTO 150SQMM THROGH EXISTING COVERED 80
MASONARY TRENCH INCL. TAKING OUT RC COVERS, SETTING THEM IN
ORDER, MENDING GOOD,THE DAMAGES FILLING THE TRENCH WITH
FINE DRY SAND INCL.SUPPLYING SAND.

781 LAYING OF ONE CABLE ABOVE 150SQMM & UPTO 300 SQMM THROGH 200
EXISTING COVERED MASONARY TRENCH INCL. TAKING OUT RC COVERS,
SETTING THEM IN ORDER, MENDING GOOD,THE DAMAGES FILLING THE
TRENCH WITH FINE DRY SAND INCL.SUPPLYING SAND.

782 LAYING OF ONE CABLE ABOVE 300SQMM THROGH EXISTING COVERED 20


MASONARY TRENCH INCL. TAKING OUT RC COVERS, SETTING THEM IN
ORDER, MENDING GOOD,THE DAMAGES FILLING THE TRENCH WITH
FINE DRY SAND INCL.SUPPLYING SAND.

783 LAYING ON CABLE TRAY


784 LAYING OF CABLE AS BELOW, ON EXISTING CABLE TRAY AND BINDING
WITH SUITABLE SIZE GI WIRE.
785 UP TO 50 SQMM 1250
786 FROM 70 SQMM TO 150 SQMM 130
787 ABOVE 150 SQMM 600
788 WIRE MESH TYPE CABLE TRAY
789 SUPPLY & ERECTION OF FOLLOWING " WIRE MESH CABLE TRAY ". THE
TRAY SHALL BE FABRICATED OF PRE GALVANISED ELECTRO ZINC
PLATED (INDOOR USE) SHALL CONFIRM IEC 61 537 & AMENDED UPTO
DATE. THE RATE SHALL BE INCLUSIVE OF TOP COVER AND STEEL ITEMS
AS REQUIRED.

790 100MM WIDEX50-55MM DEPTH. 300


791 150MM WIDEX50-55MM DEPTH. 250
792 300MM WIDEX50-55MM DEPTH. 400
793 EARTHING INSTALLATIONS
794 EXCAVATION OF SOIL FOR INSTALLATION OF EARTH ELECTRODE AND 50
FILLING & RAMMING
795 EARTHING WITH 50 MM DIA GI PIPE (TATA-MEDIUM) 3.64 MM THICK x 3.04 14
MTS. LONG 1 x 4 SWG GI (HOT DIP) WIRE (4 MTS. LONG), 13 MM DIA x 80
MM LONG GI BOLTS, DOUBLE NUTS, DOUBLE WASHERS INCL. S & F 15
MM DIA GI PIPE PROTECTION (1 MTS. LONG) TO BE FILLED WITH
BITUMEN PARTLY UNDER THE GROUND LEVEL AND PARTLY ABOVE
GROUND LEVEL DRIVEN TO AN AVERAGE DEPTH OF 3.65 MTS. BELOW
THE GROUND LEVEL.

796 EARTHING WITH COPPER PLATE (610x610x3MM SIZE) HAVING WEIGHT OF 6


9.84 KG AND 1 NO. 25x5MM COPPER STRIP (3.20MT LONG) & 1 NO. 6 SQMM
PVC INSULATED STRANDED COPPER WIRE (4 MT LONG) INCL. S & F 15
MM DIA GI PIPE (ISI-MEDIUM) PROTECTION (4 MT. LONG) TO BE FILLIED)
WITH BITUMEN, PARTLY UNDER THE GROUND LEVEL AND RESTORING
THE SURFACE DULY RAMMED INCL. PROVIDING 3.0 MT LONG, 25 MM DIA
GI PIPE (ISI-MEDIUM) FOR PERIODIC TREATMENT, INCL. PROVIDING
MASONERY ENCLOSURE ON THE TOP OF THE EARTH ELECTRODE OF
OVERALL SIZE 86.36x86.36x46CM DEEP (BELOW GROUND LEVEL)
COMPLETE WITH CEMENTED BRICK WORK (1:6) OF 25 M WIDTH, DULY
PLASTERED WITH CEMENT MORTER (INSIDE) CI HINGED INSPECTION
COVER OF SIZE 36.56x35.56CM WITH LOCKING ARRANGEMENT, GI
REDUCER AND TREATMENT OF SOIL BY USING SALT & CHARCOAL OR
COKE FOR PLATE ELECTRODE.

797 EXTRA FOR PROVIDING MASONERY ENCLOSURE ON THE TOP OF THE 20


EARTH ELECTRODE OF OVERALL SIZE 86.36CM X 86.36 CM X 46 CM DEEP (
BELOW GROUND LEVEL) COMPLETE WITH CEMENTED BRICK WORK (1:6)
OF 25 CM WIDTH DULY PLASTERED WITH CEMENT MORTER(INSIDE) CL
HINGED INSPEPECTION COVER OF SIZE 36.56 CM x 35.56 CM WITH
LOCKING ARRANGEMENT, GI REDUCER INCLUDING DRILLING OF 46 NOS.
12 MM DIA HOLES ON THE GI PIPE.

798 EXTRA FOR TREATMENT OF SOIL BY USING SALT & CHARCOAL OR COKE 16
FOR PLATE ELECTRODE.
799 EARTH BUSBAR
800 SUPPLYING & FIXING EARTH BUSBAR OF GALVANIZED ( HOT DIP) MS 100
FLAT 25 MM X 6 MM ON WALL HAVING CLEARANCE OF 6 MM FROM WALL
INCLUDING PROVIDING DRILLED HOLES ON THE BUSBAR COMPLETE
WITH GI BOLTS, NUTS, WASHERS, SPACING INSULATORS ETC AS
REQUIRED.

801 EQUIPMENT EARTHING


802 CONNECTING THE EQUIPMENTS BODY TO EARTH BUSBAR INCLUDING S 780
& F 25 MM X 6 MM GALVANISED (HOT DIP) MS FLAT ON WALL/FLOOR
WITH GI SADDLES AS REQUIRED AS REQUIRED AND CONNECTION TO
EQUIPMENTS INCL. DRILLING HOLES, WITH BOLTS, NUTS, WASHERS ETC
803 WITH 25 X 3 MM COPPER STRIP 120
804 SAFETY ITEM
805 SUPPLY & PROVIDING OF 1.0 MTR WIDTH & 2 MM THICKNESS RUBBER 24
INSULATING MAT TESTED UPTO 1.1 KV OF APPROVED MAKE AS PER IS

806 INTERNAL ELECTRIFICATION


807 MCB DISTRIBUTION BOARD
808 SUPPLYING & FIXING DOUBLE DOOR SPN MCB DISTRIBUTION BOARD
WITH IP-42/43 PROTECTION , CONCEALED IN WALL AFTER CUTTING THE
WALL & MENING GOOD THE DAMAGES TO ORIGINAL FINISH INCL. INTER
CONNECTION WITH SUITABLE SIZES OF COPPER WIRE & NEUTRAL LINK
& PROVISON FOR EARTHING ATTACHMENT.

809 2+4 WAY ENCLOSURE ( 607710). 54


810 2+8 WAY ENCLOSURE (607711) 1
811 2+12 WAY ENCLOSURE 1
812 SUPPLYING & FIXING DOUBLE DOOR HORIZONTAL TPN MCB
DISTRIBUTION BOARD WITH IP-42/43 PROTECTION, CONCEALED IN WALL
AFTER CUTTING THE WALL & MENDING GOOD THE DAMAGES TO
ORIGINAL FINISH INCL. INTER CONNECTION WITH SUITABLE SIZE OF
COPPER WIRE & NEUTRAL LINK & PROVISION FOR EARTHING
ATTACHMENT.

813 4 WAY ENCLOSURE 104


814 SUPPLYING & FIXING DOUBLE DOOR HORIZONTAL TPN MCB
DISTRIBUTION BOARD WITH IP-42/43 PROTECTION, ON ANGLE IRON
FRAME ON WALL & MENDING GOOD THE DAMAGES TO ORIGINAL FINISH
INCL. INTER CONNECTION WITH SUITABLE SIZE OF COPPER WIRE &
NEUTRAL LINK & PROVISION FOR EARTHING ATTACHMENT.

815 UP TO 160A
816 4WAY ENCLOSURE ( LTVD04MGN) 1
817 6WAY ENCLOSURE ( LTVD06MGN) 54
818 8WAY ENCLOSURE ( LTVD08MGN) 1
819 MCB
820 SUPPLYING & FIXING 240/415V MCB OF BREAKING CAPACITY 10KA & C
CHARACTERISTICS ON DIN RAIL OF EXISTING DBS AND NECESSARY
CONNECTION
821 6-32 A SP 450
822 6-32 A DP 70
823 6-32 A TP 150
824 6-32 A FP 100
825 40,63 A FP 20
826 40, 63 A FP 75
827 100 A FP 1
828 MCB (D-CURVE)
829 6-32A SP MCB (D-CURVE) 10
830 6-32A FP MCB (D-CURVE) 10
831 MCB ENCLOSURE
832 SUPPLYING & FIXING MCB SS ENCLOSURE WITH IP-20/30 PROTECTION ,
POWDER COATED PROVISION FOR TWO/FOUR POLE MCB , CONCEALED
IN WALL AFTER CUTTING THE WALL & MENDING GOOD DAMAGES TO
ORIGINAL FINISH INCL. PAINTING , CONNECTION & PROVISION FOR
EARTHING ATTACHMENT.

833 4 WAY 54
834 AC STARTER
835 SUPPLY & FIXING OF 240V, 25A MODULAR TYPE STARTER WITH 25A 10
MODULAR SWITCH TYPE DP MCB (C-CURVE) & 4 MODULE GI MODULAR
TYPE SWITCHBOARD WITH 4 MODULE TOP COVER PLATE FLUSHED IN
WALL INCLUDING S & F SWITCHBOARD AND COVER PLATE AND MAKING
NECESSARY CONNECTIONS WITH PVC COPPER WIRE AND EARTH
CONTINUITY WIRE ETC

836 LAYING & FIXING POLYTHENE PIPE, MS BOXES, SWITCHES ETC.


837 CUTTING CHANNEL OF 40 MM X 40 MM SIZE ON MASONARY WALL INCL.
S & F HEAVY GAUGE POLYTHENE PIPE DIA ASSTATED BELOW.BY MEANS
OF IRON HOOKS & SUPPLYING AND DRAWING 18 SWG GI WIRE AS FISH
WIRE INCL. MENDING GOOD DAMAGES TO BUILDING WORKS.

838 19 MM DIA 3 MM THICK POLYTHENE PIPE WITHOUT EARTH CONTINUITY 350


WIRE
839 CUTTING CHANNEL OF 43 MM X 43 MM SIZE ON MASONARY WALL INCL.
S & F HEAVY GAUGE POLYTHENE PIPE DIA ASSTATED BELOW.BY MEANS
OF IRON HOOKS & SUPPLYING AND DRAWING 18 SWG GI WIRE AS FISH
WIRE INCL. MENDING GOOD DAMAGES TO BUILDING WORKS.

840 25 MM DIA 3 MM THICK POLYTHENE PIPE WITHOUT EARTH CONTINUITY 850


WIRE
841 SUPPLYING & FIXING SHEET METAL INSPECTION BOX (16 SWG) OF THE
FOLLOWING SIZES FLUSHED IN WALL BY HOUSING THE SAME AFTER
CUTTING BRICK WALL INCL.MAKING EARTH ATTACHMENT., PAINTING
AND MENDING GOOD DAMAGES TO BUILDING WORKS

842 100 MM X 100 MM X 65 MM 150


843 200 MM X 150 MM X 65 MM 100
844 SUPPLY & FIXING BAKELITE / PERSPEX TOP COVER ON EXISTING
INSPECTION BOARD BY BRASS SCREWS
845 100MM X 100 MM X 65 MM 150
846 200 MM X 150 MM X 65 MM 100
847 SCHEDULE OF RATES FOR PVC INSULATED AND SHEATHED WIRE IN
GI/PVC CONDUIT (SURFACE/ CONCEALED) INCLUDING REQUIRED
ACCESSORIES
848 SUPPLYING WIRING & DRAWING WITH 1.1 KV GRADE SINGLE CORE PVC
INSULATED STRANDED COPPER WIRE IN GI/PVC CONDUIT AND PAINTING

849 2 X 2.5 SQMM WIRE IN 19 MM CONDUIT INCL. S & F 1 X 14 SWG GI ECC 6000
850 2 X 4 SQMM WIRE IN 19 MM CONDUIT INCL. S & F 1 X 14 SWG GI ECC 600

851 3 X 1.5 SQMM WIRE IN 19 MM CONDUIT INCL. S & F 2 X 10 SWG GI ECC 600

852 3 X 2.5 SQMM WIRE IN 19 MM CONDUIT INCL. S & F 2 X 10 SWG GI ECC 800

853 4 X 6 SQMM WIRE IN 25 MM CONDUIT INCL. S & F 2 X 10 SWG GI ECC 300

854 DUMMY CONDUIT


855 SUPPLYING & FIXING PVC RIGID CONDUIT "FR ( PRECISION MAKE ) ON
WALL , CEILING WITH SADDLES AND OTHER ACCESSORIES AND
MENDING GOOD DAMAGES TO BUILDING WORKS
856 20 MM SIZE 2000
857 25 MM SIZE 3000
858 32 MM SIZE 3000
859 SUPPLYING & CARRYING WIRING FOR LIGHT FAN & DEPENDENT SOCKET
PAINTS BY USING 16 SWG MS/PVC CONDUITS WITH THREADED JOINTS OF
REQUIRED DIA AS PER IS 732, MS CONDUIT ACCESSORIES, MS FLEXIBLE

860 1 LIGHT POINT CONTROLLED BY A SWITCH WITH INDICATOR 425


861 2 LIGHT POINTS CONTROLLED BY A 6A SWITCH WITH INDICATOR 5
862 3 LIGHT POINTS CONTROLLED BY A 6A SWITCH WITH INDICATOR 7
863 EXHAUST FAN / FAN POINT CONTROLLED BY 6AAMP SWITCH & CEILLING 5
ROSE NEAR FAN
864 UNITS IN MS ENCLOSER
865 SITC OF FOLLOWING COMPONENTS LIKE APPROVED PLATE TYPE
MODULAR SWITCHS, SOCKET ETC DULY WIRED. ALL THE SWITCH
SOCKETS ARE WITH FRONT PLATE & WITHOUT BOXES INCE THE SAME IS
COVERED UNDER DIFFERENT ITEM.

866 1 NO- 6/16A, 6 PIN IN UNIVERSAL SOCKET CONTROLLED BY 16A, SP 250


SWITCH WITH INDICATOR, RP FOR UPS INCOMING SUPPLY ETC WITHOUT
MS BOX.
867 SAME AS ABOVE BUT WITH MS BOX 50
868 3 NOS-6A, 5PIN SOCKET CONTROLLED BY COMMON 16A, SP SWITCH WITH 250
INDICATOR, WORKSTATIONS WITHOUT MS BOX
869 SAME AS ABOVE BUT WITH MS BOX 50
870 SUPPLY & FIXING GI MODULAR BOXES, SWITCHES ETC.
871 SUPPLYING & FIXING GI MODULAR SWITCH BOARD OF THE FOLLOWING
SIZES COMPLETE WITH THREE NO. SUITABLE SIZE COPPER BAR WITH
HOLES (FOR PH, N & E) FIXED ON BAKELITE/HARD RUBBER INSULATOR
OVER THE MS WELDED CHAIRS INCL. TOP COVER FLUSHED IN WALL FOR
HOUSING THE BOARD AFTER CUTTING THEBRICK WALL INCL. MAKING
EARTHING ATTACHMENT, PAINTING AND MENDING GOOD DAMAGES TO
BUILDING WORKS.

872 4 MODULE 450


873 6 MODULE 40
874 SUPPLYING & FIXING GI MODULAR SWITCH BOARD OF THE FOLLOWING
SIZES COMPLETE WITH TOP COVER PLATE FLUSHED IN WALL FOR
HOUSING THE BOARD AFTER CUTTING THE BRICK WALL INCL. MAKING
EARTHING ATTACHMENT, PAINTING AND MENDING GOOD DAMAGES TO
BUILDING WORKS

875 2 MODULE. 200


876 SUPPLYING & FIXING 240 V 6 A MODULAR TYPE SWITCH (BRAND 200
APPROVED BY EIC) ON EXISTING GI MODULAR TYPE SWITCH BOARD
HAVING TOP COVER PLATE AND NECESSARY CONNECTIONS AS
REQUIRED.

877 SUPPLY & FIXING 240 V 16 A MODULAR KEY TYPE SWITCH ( BRAND 55
APPROVED BY EIC) ON EXISTING GI MODULAR TYPE SWITCH BOARD
HAVING TOP COVER PLATE AND MAKING NECESSARY CONNECTIONS AS
REQUIRED.

878 SUPPLY & FIXING 240 V, 6A, 5 PIN MODULAR TYPE PLUG SOCKET (BRAND 500
APPROVED BY EIC), WITHOUT SWITCH & PLUG TOP, ON EXISTING GI
MODULAR TYPE SWITCH BOARD WITH TOP COVER PLATE AND MAKING
NECY. CONNECTIONS WITH PVC CU WIRE AND EARTH CONTINUITY WIRE
ETC.

879 SUPPLY & FIXING 240 V, 16 A, 3 PIN MODULAR TYPE PLUG SOCKET 65
(BRAND APPROVED BY EIC), WITHOUT PLUG TOP AND SWITCH,
ONEXISTING GI MODULAR TYPE SWITCH BOARD WITH TOP COVER
PLATE AND MAKING NECY. CONNECTIONS WITH PVC CU WIRE AND
EARTH CONTINUITY WIRE ETC.

880 SUPPLY & FIXING 240V, MODULAR SOCKET (2 MODULE) TYPE FAN 100
REGULATOR (STEP TYPE) (BRAND APPROVED BY EIC) ON EXISTING
MODULAR GI SWITCH BOARD WITH TOP COVER PLATE INCL. MAKING
NECY. CONNECTIONS ETC.

881 1NO BLANK PLATE.(1M) 300


882 SUPPLY & FIXING 240 V, 25A MODULAR STARTER ( BRAND APPROVED BY 20
EIC) ON EXISTING GI MODULAR TYPE SWITCH BOARD WITH TOP COVER
PLATE AND MAKING NECY. CONNECTIONS WITH PVC CU WIRE AND
EARTH CONTINUITY WIRE ETC.

883 FINISHING COPPER WIRE ENDS


884 FINISHING OF THE PVC INSULATED WIRE ENDS BY SOCKETING WITH
PIN/RING TYPE COPPER SOCKETS AND INSULATED TAPES ETC.,
INCLUDING SUPPLYING SOCKETS, TAPES.
885 2.5SQMM. 1150
886 4SQ.MM. 500
887 6SQ.MM. 1150
888 POP-UP TYPE FLUSH-MOUNTING BOXES
889 SUPPLY & INSTALLATION OF SUPPLY AND ERECTION OF "MATT-
ALUMINIUM FINISH POP-UP TYPE FLUSH-MOUNTING BOXES" FOR
WORKSTATIO & MEETING ROOM TABLE APPLICATIONS WITH "PUSH AND
SLIDE" LOCKING SYSTEM FOR INSTALLATION USE THE FLUSH-
MOUNTING BOXES FOR CONCETE FLOORS OR THE KITS FOR RAISED
ACCESS FLOORS OR TABLE TOP.
890 AL.-MATT FINISH 6MODULES (2NOS 6A SOCKET+2NO+RJ45) 10
891 JUNCTION BOX
892 SUPPLY AND INSTALLATION OF FOLLOWING "16G GI POWDER COATED
COMPARTMENT TYPE RACEWAY" CONFORMING EN 50085-2-2 WITH
FIXING BRACKETS ETC. COMPLETE. THE RATE SHALL BE INCLUSIVE OF
FIXING ACCESSORIES & NECESSARY CIVIL WORKS.

893 150x150x37-90 MM GI JUNCTION BOX 250


894 225x225x37-90 MM GI JUNCTION BOX WITH FLY OVER. 150
895 LIGHT & FANS FIXTURES
896 SUPPLY OF RECESS MOUNTED LED LIGHT FIXTURE LUMINARE WITH 220
LUMINOUS EFFICACY OF MIN. 110 LUMEN/WATT AND MINIUM FLUX OF
3500 LUMEN OR MORE. (PHILIPS RC380B LED36S-6500 G4 PSD OD (FULL
GLOW) OR SIMILAR APPROVED EQUIVALENT).

897 DOWN-LIGHT LUMINARE


898 SUPPLY OF RECESS MOUNTED LED LIGHT FIXTURE LUMINARE WITH 100
LUMINOUS EFFICACY OF MIN. 110 LUMEN/WATT AND MINIUM FLUX OF
1900 LUMEN OR MORE. (PHILIPS DN195B LED20S-6500 PSU WH S1
(GREENLEDI) OR SIMILAR APPROVED EQUIVALENT).

899 SUPPLY OF RECESS MOUNTED LED LIGHT FIXTURE LUMINARE WITH 120
LUMINOUS EFFICACY OF MIN. 110 LUMEN/WATT AND MINIUM FLUX OF
1100 LUMEN OR MORE. (PHILIPS DN392B LED10S-6500 PSU WH
(GREENPERFORM) OR SIMILAR APPROVED EQUIVALENT).

900 FIXING ONLY PENDENT LIGHT FITTING COMPLETE WITH LAMP, SHADE 50
AND 24/0.2 MM (1.5SQ.MM) FLEXIBLE COPPER WIRE INCL. S&F PENDENT
HOLDER.
901 SURFACE LUMINARE
902 SUPPLY OF SURFACE MOUNTED LED LIGHT FIXTURE WITH 16W 10
LUMINAIRE. (PHILIPS SM2006 LED16S 6500 PSU OD WH (CIRRUS MINI
PRO ) OR SIMILAR APPROVED EQUIVALENT.)
903 SUPPLY OF SURFACE MOUNTED LED LIGHT FIXTURE WITH 10W LAMP. 25
(PHILIPS BN021C LED 10S PSU CDL GRS1 (SMARTBRIGHT OR SIMILAR
APPROVED EQUIVALENT.)
904 SUPPLY OF SURFACE MOUNTED LED LIGHT FIXTURE WITH 20W LAMP. 30
(PHILIPS BN021C LED 20S PSU CDL GR (SMARTBRIGHT OR SIMILAR
APPROVED EQUIVALENT.)
905 FIXING ONLY SINGLE/ TWIN FLUROSCENT LIGHT FITTING COMPLETE 40
WITH ALL ACCESSORIES DIRECTLY ON WALL/CEILING/HWROUND BLOCK
AND SUITABLE SIZE OF MS FASTENER

906 SUPPLY OF BULKHEAD LED LIGHT FIXTURE WITH 6W LUMINAIRE. 40


(PHILIPS WT202W LED6S NW PSU S2 PC (ENDURA LED BULKHEAD) OR
SIMILAR APPROVED EQUIPVALENT)
907 FIXING ONLY BULK HEAD CEILING FITTING ON WALL / CEILING BY 40
SCREWS ETC.
908 LED AVATION LIGHT LUMINAIRE
909 SUPPLY OF LED TYPE SINGLE DOME AVIATION OBSTRUCTION LIGHT . 1
( BGAV 302 LED OR SIMILAR APPROVED EQUIPVALENT.)
910 FIXING ONLY FLOODLIGHT FITTINGS ON TOP OF MASONARY STRUCTURE 1
BY 3 NOS. 10MM DIA X 87MM LONG RAG BOLTS, NUTS & DOUBLE
WASHERS COMPLETE EITHER 37 MM X 10 MM MS FLAT SUPPORT / OR BY
OTHER MEANS ASREQUIRED

911 CEILING FAN


912 SUPPLY & INSTALLATION OF CEILING FAN". THE RATE SHALL BE
INCLUSIVE OF FIXING & MOUNTING ACCESSORIES.
913 1200MM SWEEP , 3- BLADE 5 STAR RATING AC CEILING FAN .( HAVELLS 10
ES-50 OR SIMILAR APPROVED EQUIVALENT.)
914 SUPPLYING & FIXING OF BOX TYPE FAN CLAMP OF 150MM DIA & 80MM 10
DEPTH MADE OF 16 SWG CRCA SHEET WITH ONE END DULY SEALED BY
COVER, PROPERLY WELDED, , INCL. S&F 12 MM DIA 600MM LONG MS
ROD DULY BENT BY HEAT TREATMENT AT THE CENTRE POSITION OF ROD
TO GRIP FAN BOBBIN PROPERLY, INCL. BINDING THE ROD AND FAN BOX
WITH REINFORCEMENT BY 22 SWG STEEL BINDING WIRE, INCL. SUPPLY
& COVERING THE BOX WITH ALKATHENE SHEET, PLACED IN ORDER TO
PREVENT CONCRETE FROM ENTERING THE BOX.

915 FIXING ONLY CEILING FAN COMPLETE WITH BLADES, CANOPY, FORK, 10
RUBBER BUSH ETC. INCL. S&F CONNECTING WIRE FOR DOWN ROD UPTO
30CM INCL. PAINTING THE ROD WITH APPROVED PAINT AND MAKING
NECESSARY CONNECTION AS REQUIRED BY 2x1.5 SQMM FLEXIBLE
COPPER WIRE.

916 WALL MOUINTING FAN


917 SUPPLY & INSTALLATION OF " DECORATIVE WALL-MOUNTED"
OSCILLATING TYPE FAN WITH INBUILT SPEED CONTROLLER. THE RATE
SHALL BE INCLUSIVE OF FIXING & MOUNTING ACCESSORIES.

918 450MM SWEEP WALL FAN. (HAVELLS AIRBOLL HI-SPEED OR SIMILAR 10


APPROVED EQUIVALENT)
919 FIXING ONLY CABIN FAN ON WALL/CEILING BY S&F RAG BOLTS, NUTS & 10
WASHERS (6 MM DIA x 62 MM LONG) OR AS REQD. INCL. S&F 24/0.20 PVC
INSULATED FLEXIBLE COPPER WIRE 0.5 MT. LENGTH

920 EXHAUST FAN


921 SUPPLY & INSTALLATION OF " EXHAUST FAN" WITH LOUVERS. THE RATE
SHALL BE INCLUSIVE OF FIXING & MOUNTING ACCESSORIES.

922 150MM VENTILATING FAN NON-METALLIC TYPE. (HAVELLS VENTIL AIR- 25


DXR OR SIMILAR APPROVED EQUIVALENT)
923 380MM, 1PH,900RPM HEAVY DUTY EXHAUST FAN. (HAVELLS TURBO 15
FORCE SP OR SIMILAR APPROVED EQUIVALENT)
924 FIXING ONLY EXHAUST FAN AFTER MAKING HOLE IN WALL AND
MAKING GOOD DAMAGES AND SMOOTH CEMENT FINISH ETC. AS
PRACTICABLE AS POSSIBLE AND PROVIDING NECY. LENGTH OF PVC
INSULATED WIRE AND MAKING CONNECTION FOR EXHAUST OF
FOLLOWING DIAMETER:

925 23 CM (9") 25
926 38 CM (15") 15
927 FIXING ONLY LOUVER SHUTTER/COWL ON WALL ON WALL WITH NECY.
BOLTS & NUTS (6 MM DIA x 62 MM LONG)
928 FOR 23 CM (9") EXHAUST FAN 25
929 FOR 38 CM (15") EXHAUST FAN 15
930 STREET LIGHT POLE
931 SUPPLY & ERECTION OF FOLLOWING "SWWAGED TYPE STEEL TUBULAR
POLES". THE POLE SHALL BE PROVIDED WITH ELMEX CONNECTOR/SP
MCB CONTROL FOR "LLOP IN LOOP OUT" OF THE CABLE ALONG WITH
CABLE ENTRY HOLE AND INTERNAL WIRING FROM THE ELMEX
CONNECTOR/SP MCB TO THE LAMP CONTROL GEAR & LAMP WITH
2Rx2.5SQMM+1Rx1.5SQMM CU. WIRES AND ALL OTHER ACCESSORIES
COMPLETE AS REQUIRED. THE POLE SHALL CONFIRM IS-2713/1980 FOR
POLES HT STEEL GRADE BASE PLATE SHALL CONFIRM IS : 226/IS: 2062,
EN.8 GRADE FOR FOUNDATION BOLTS & AMENDED UPTO DATE. THE
RATE SHALL BE INCLUSIVE OF BASE PLATE, ARM, FOUNDATION BOLTS,
SPIRAL EARTHING WITH 10SWG GI WIRES, PAINTING, ELMEX
CONNECTOR & NECESSARY FOUNDATION CIVIL WORKS ETC. COMPLETE
IN ALL RESPECT.

932 7 METERS HIGH - BOLT-4.00 M, MID-1.50 M, TOP-1.50 M 15


933 STREET LIGHT FIXTURE
934 SUPPLY & FIXING OF THE "OUTDOOR STREET LIGHT LUMINARIE" WITH
LAMP, IGNITOR, CONTROLGEAR, HINGED FRONT FRAME WITH GLASS
COVER ETC. COMPLETE. THE INSTALLATION SHALL CONFIRM IS : 7323.
1989 & AMENDED UPTO DATE. THE RATE SHALL INCLUSIVE OF FIXING &
MOUNTING ACCESSORIES.

935 SUPPLY OF 1x40W LED STREET LIGHT LUMINARIES. (PHILIPS BRP 409 LED 15
040 CW HO MR FG S1 PSU GR (GREENLINE) OR APPROVED EQUIVALENT)

936 FIXING ONLY OUTDOOR / STREET LIGHT TYPE FLUORESCENT LIGHT 15


FITTING COMPLETE WITH ALL ACCESSORIES TO BE FIXED/PROJECTED
FROM THE WALL OF THE BUILDING INCL. MAKING HOLES TO BUILDING,
S&F 40 MM DIA GI PIPE (ISI-MEDIUM) 1.50 MTS. AVERAGE LENGTH, WITH
GI SOCKET AT ONE END AND THREAD AT THE OTHER END & SUITABLE
BEND TO HOUSE THE FITTING & MAKING NECY. CONNECTIONS WITH
S&F NECY. LENGTH OF 1.5 SQMM PVC INSULATED SINGLE CORE
STRANDED ANNEALED COPPER WIRE AND MAKING CONNECTIONS AS
REQUIRED AND MENDING GOOD DAMAGES TO WALL AND PAINTING.

937 GATE LIGHT FIXTURE


938 SUPPLY & FIXING OF THE "GATE LIGHTS" WITH LAMP, IGNITOR,
CONTROLGEAR ETC. COMPLETE. THE RATE SHALL BE INCLUSIVE OF
FIXING & MOUNTING ACCESSORIES
939 SUPPLY OF SURFACE MOUNTED LED LIGHT FIXTURE WITH 10W 10
LUMINAIRE. (PHILIPS DN170C LED 10S 6500 PSU WH (GREEN LED
SURFACE MOUNTED) OR SIMILAR APPROVED EQUIVALENT)
940 FIXING ONLY SINGLE/ TWIN FLUROSCENT LIGHT FITTING COMPLETE 10
WITH ALL ACCESSORIES DIRECTLY ON WALL/CEILING/HWROUND BLOCK
AND SUITABLE SIZE OF MS FASTENER

941 SUPPLY OF 1x25W INTEGRAL DECORATIVE LED GATE LIGHT WITH IP-65 4
PROTECTION. (PHILIPS BGP 161 LED2500/NW PSU 220-240V 7043 IN (LED
POST TOP) OR APPROVED EQUIVALENT)
942 SUPPLY OF 1x25W INTEGRAL DECORATIVE LED GATE LIGHT WITH IP-65 4
PROTECTION. (PHILIPS BGP 161 LED2500/NW PSU 220-240V 7043 IN (LED
POST TOP) OR APPROVED EQUIVALENT)
943 BOLLARD LIGHT FIXTURE
944 SUPPLY & FIXING OF THE "OUTDOOR BOLLARD LIGHTS" WITH LAMP,
IGNITOR, CONTROLGEAR ETC. COMPLETE. THE RATE SHALL BE
INCLUSIVE OF FIXING & MOUNTING ACCESSORIES.
945 SUPPLY OF 1x9W INTEGRAL DECORATIVE LED BOLLARD LIGHT. (PHILIPS 10
BCP400 LED09 D CW PSU OR APPROVED EQUIVALENT)
946 FIXING ONLY FLOODLIGHT FITTINGS ON TOP OF MASONARY STRUCTURE 10
BY 3 NOS. 10MM DIA X 87MM LONG RAG BOLTS, NUTS & DOUBLE
WASHERS COMPLETE EITHER 37 MM X 10 MM MS FLAT SUPPORT / OR BY
OTHER MEANS ASREQUIRED

947 EXTRA LOW VOLTAGE


948 TELEPHONE CABLE
949 SUPPLYING & DRAWING 2-PAIR TELEPHONE CABLES WITH HIGH DENSITY 1500
POLYETHYLENE INSULATED SOILD ANNEALED HIGH CONDUCTIVITY
BARE COPPER OF DIA 0.5MM IN PRELAID PVC RIGID CONDUIT/IN
POLYTHENE PIPE EMBEDED IN WALL

950 SUPPLY OF 20PAIR TELEPHONE CABLE 500


951 SUPPLY OF 30PAIR TELEPHONE CABLE 1000
952 LAYING OF TELEPHONE CABLE AS BELOW, ON EXISTING CABLE TRAY 1500
AND BINDING WITH SUITABLE SIZE GI WIRE
953 TELEPHONE DISTRIBUTION BOX
954 SUPPLY & INSTALLATION OF "INDOOR TELEPHONE DISTRIBUTION BOX"
MADE OF 16GAUGE M.S. BOX WITH TERMINAL MODULES ETC
COMPLETE.
955 200 PAIR MDF KRONE MODULE WITH BOX 1
956 50 PAIR MDF KRONE MODULE WITH BOX 10
957 20 PAIR MDF KRONE MODULE WITH BOX 1
958 VOICE PORT
959 SUPPLY & FIXING TELEPHONE SOCKET(RJ11) MODULAR TYPE (BRAND 250
APPROVED BY EIC) ON EXISTING GI MODULAR BOARD HAVING TOP

960 LAN CABLE


961 SUPPLYING & DRAWING LAN CABLE (CAT6) (BRAND APPROVED BY EIC) 500
IN PRELAID PVC RIGID CONDUIT/INPOLYTHENE PIPE EMBEDED IN WALL

962 DATA PORT


963 SUPPLY & FIXING MODULAR TYPE RJ45 SUITABLE FOR CAT6 CABLE 250
(BRAND APPROVED BY EIC) ON EXIATING PVC BOARD AND TOP COVER
PLATE ON
964 SUPPLY & FIXING GI MODULAR BOXES, SWITCHES ETC.
965 SUPPLYING & FIXING GI MODULAR SWITCH BOARD OF THE FOLLOWING
SIZES COMPLETE WITH TOP COVER PLATE FLUSHED IN WALL FOR
HOUSING THE BOARD AFTER CUTTING THE BRICK WALL INCL. MAKING
EARTHING ATTACHMENT, PAINTING AND MENDING GOOD DAMAGES TO
BUILDING WORKS

966 2 MODULE. 700


967 LAYING & FIXING POLYTHENE PIPE, MS BOXES, SWITCHES ETC.
968 CUTTING CHANNEL OF 40 MM X 40 MM SIZE ON MASONARY WALL INCL.
S & F HEAVY GAUGE POLYTHENE PIPE DIA ASSTATED BELOW.BY MEANS
OF IRON HOOKS & SUPPLYING AND DRAWING 18 SWG GI WIRE AS FISH
WIRE INCL. MENDING GOOD DAMAGES TO BUILDING WORKS.

969 19 MM DIA 3 MM THICK POLYTHENE PIPE WITHOUT EARTH CONTINUITY 470


WIRE
970 CUTTING CHANNEL OF 43 MM X 43 MM SIZE ON MASONARY WALL INCL.
S & F HEAVY GAUGE POLYTHENE PIPE DIA ASSTATED BELOW.BY MEANS
OF IRON HOOKS & SUPPLYING AND DRAWING 18 SWG GI WIRE AS FISH
WIRE INCL. MENDING GOOD DAMAGES TO BUILDING WORKS.

971 25 MM DIA 3 MM THICK POLYTHENE PIPE WITHOUT EARTH CONTINUITY 450


WIRE
972 SUPPLYING & FIXING SHEET METAL INSPECTION BOX (16 SWG) OF THE
FOLLOWING SIZES FLUSHED IN WALL BY HOUSING THE SAME AFTER
CUTTING BRICK WALL INCL.MAKING EARTH ATTACHMENT., PAINTING
AND MENDING GOOD DAMAGES TO BUILDING WORKS

973 100 MM X 100 MM X 65 MM 45


974 200 MM X 150 MM X 65 MM 15
975 SUPPLY & FIXING BAKELITE / PERSPEX TOP COVER ON EXISTING
INSPECTION BOARD BY BRASS SCREWS
976 100 MM X 100 MM X 65 MM 45
977 200 MM X 150 MM X 65 MM 15
978 DUMMY CONDUIT
979 SUPPLYING AND FIXING PVC RIGID CINDUIT 'FR' (PRECISION MAKE) ON
WALL, CEILING WITH SADDLES AND OTHER ACCESSORIES AS REQUIRED
AND MENDING GOOD DAMAGES TO BUILDING WORKS

980 20MM SIZE 165


981 25MM SIZE 175
982 SUPPLYING AND FIXING GI CONDUIT 1.6MM THICK ON WALL, CEILING
WITH SADDLES AND OTHER ACCESSORIES AS REQUIRED AND MENDING
GOOD DAMAGES TO BUILDING WORKS
983 19MM SIZE 750
984 25MM SIZE 1000
985 LIGHTING PROTECTION SYSTEM
986 EMISSION LIGHTNING AIR TERMINAL
987 SUPPLY, ERECTION, TESTING & COMMISSIONING OF "EARLY STREAMER
EMISSION" TYPE LIGHTING PROTECTION SYSTEM COMPRISING OF AIR-
TERMINALS OR DYNASPHERE, DOWN CONDUCTORE, EVENT COUNTER,
LOW IMPEDANCE GROUNDING GRID INCLUDING ENHANCEMENT
METARIALS, GROUNDING ELECTRODE, MAST, SS CABLE TIE, IN LINE
COUPLING, GUY SET, HARDWARE ETC. COMPLETE. THE RATE SHALL
ALSO INCLUDE ALL CIVIL WORKS.

988 79 METER PROTECTION RADIOUS EARLY STREAMER EMISSION 1


TERMINAL CONFIRMING "NFC 17-102:2011 & LEVEL-I" WITH A MOUNTING
HEIGHT OF 5 METER.
989 ALLIED ITEMS
990 INSULATED FRP MAST, INLINE COUPLING & MAST BASE ETC. COMPLETE 1
IN ALL RESPECT.
991 LIGHTINING EVENT COUNTER & ACCESSORIES 1
992 EARTHING ROD
993 5/8" CU. BONDED EARTHING ROD, 14.2 MM DIA & 3000MM LENGTH 3
994 HORIZONTAL/DOWN CONDUCTOR
995 5/8" CU. BONDED EARTHING ROD, 14.2 MM DIA CLAMP & 3000MM LENGTH 70
WITH COPPER TAPE FOR INTERNAL EARTHING CONNECTIVITY

996 GROUND ENHANCING MATERIAL


997 HIGHLY CONDUCTIVE AND LOW RESISTANCE GROUND RESISTANCE 4
IMPROVEMENT POWDER TESTED TO THE RESISTIVITY OF 0.2 OHMS AS
PER IEC 62561-7 READ WITH ASTM G57-06, CL 3.4

998 DG SET INSTALLATION WORK


999 SUPPLY, ERECTION, TESTING & COMMISSIONING OF OUTDOOR SOUND & 1
WESTHER PROOF TYPE "DIESEL GENERATOR-SET" WITH ANTI-VIBRATION
MOUNTS, FITTING, FIXING ETC. COMPLETE IN ALL RESPECT. THE DG-SET
SHALL ALSO COMPLY ISO 8528-2 & 3 AS WELL AS SHOULD BE OF "PRIME
POWER RATING" I.E. CAPABLE OF PROVIDING AN OUTPUT OF 10% IN
EXCESS OF THE RATED OUTPUT AT THE SAME SPEED FOR ONE HOUR IN
ANY PERIOD OF 12 HOURS CONSECUTIVE RUNNING. THE SOUND LEVEL
OF D.G. SET SHALL NOT BE MORE THE 75DBA AT 01 METER FROM SOUND
PROOF CANOPY. THE WORK SHALL BE COMPLETED WITH ALL
NECESSARY EQUIPMENT AS REQUIRED. TESTING AND TRIAL RUN
(MINIUM 8 HOURS WITH LOAD) INCLUDING ALL CONSUMABLES SUCH AS
FUEL, OIL ETC WHICH SHALL BE SUPPLIED BY THE CONTRACTOR AS PER
INSTRUCTION AND DIRECTION OF THE PROJECT IN CHARGE. THE DG-SET
SHOULD BE PROVIDED WITH FOLLOWING ACCESSORIES.

1000 DG-SET RATING : 1010KVA


1001 1500RPM, 4-STROKE TURBO CHARGES AFTER COOLED DISEL ENGINE OF
SUITABLE CAPACITY & RATED BHP TO DELIVER THE SPECIFIED LOAD AT
NTP COMPLETE WITH STANDARD ACCESSORIES AND SHALL
CONFORMING TO ISO:3046,BS:5514.

1002 THE ENGINE IS TO BE ELECTRICALLY STARTED BY AN ELECTRICALLY


DRIVEN SELF STARTER OPERATED THROUGH ENGINE BATTERY.

1003 ENGINE LOCAL CONTROL PANEL WITH EQUIPMENTS AND INSTRUMENTS


MOUNTED ON THE ENGINE FRAME COMPLETE.
1004 LEAD ACID MAINTENANCE FREE/SMF TYPE HEAVY DUTY STARTING
BATTERIES WITH SELF DRIVEN CHARGER UNIT.
1005 RADIATOR OF THE ENGINE WITH SELF DRIVEN FAN AND INNER CIRCUIT
WATER PUMPS COMPLETE.
1006 INLET MANIFOLD AND AIR CLEANERS.
1007 GEAR TYPE LUBE OIL PUMPS, LUBRICATING OIL FILTER, LUBE OIL
CENTRIFUGE AND LUBRICATING OIL COOLER.
1008 FURL INJECTION SYSTEM WITH INJECTION PUMP, FUEL FILTER, FUEL
PREFILTER, NOZZLES GOVERNOR AND FUEL LEVEL INDICATION, ANTI
VIBRATION MOUNT PADS ETC.
1009 THE ENGINE MOUNTED PANEL SHOULD CONSIST OF TACHO-HOUR
METER, LUBE OIL PRESSURE GAUGE, COOLANT TEMPERATURE GAGUGE,
BATERY CHARGER AMMETER AND OTHER ACCESSORIES ETC.
COMPLETE.

1010 AMF PANEL 1


1011 SUPPLY, DELIVERY AT SITE ERECTION, TESTING & COMMISSIONING OF
VERTICAL FLOOR MOUNTING FREE STANDING, EXTENSIBLE ON EITHER
SIDE, COMPARTMENTALISED CUBICAL TYPE PANEL BOARD MADE OF 14
SWG (2.04MM) CRCA MS SHEET SUITABLE FOR 500/415V, 50 HZ, AC, 3
PHASE AND NEUTRAL SYSTEM HAVING THE FOLLOWING FEATURES
PANEL SHALL BE DESIGNED TO ENSURE THAT THE WEIGHT OF THE
COMPONENTS IS ADEQUATELY SUPPORTED WITHOUT DEFORMATION OR
LOSS IN ALIGNMENT. THE DOORS OF THE CUBICLE SHALL BE FITTED
WITH DUST EXCLUDING NEOPRENE GASKETS WITH FASTNERS FOR
PROPER COMPRESSION OF THE GASKETS.

1012 PANEL SHALL BE MULTITIER COMPARTMENTALISED CUBICAL TYPE,


EXTENSIBLE ON EITHER SIDE AND SHALL BE TREATED WITH ALL
NTICORROSIVE PROCESS BEFORE PAINTING WITH TWO COATS OF ZINE
CHROMATE PRIMER AND FINAL APPROVED SHADE OF ENAMEL PAINT.

1013 BUSBARS SHALL BE OF CONTINUOUS RATED ALUMINIUM ADEQUATE


FOR SPECIFIED RATED CONTINUOUS AND SHORT CIRCUIT CURRENT
COVERED BY, PROPER GRADED HEAT SHRINKABLE PVC SLEEVES
(COLOR CODED). BUSBARS SHALL BE SUPPORTED BY SUITABLE
HYLAM/DMC/SMC OR COMPATABLE INSULATOR SUPPORTS. HIGH
TENSIBLE BOLTS AND SPRINGS WASHERS ARE TO BE PROVIDED ON ALL
BUSBARS AND SUITABLE DRILLED HOLES FOR CONNECTION JOINTS. THE
BUSBARS SHALL HAVE A THROUTH FAULT WITHSTAND CAPACITY OF 31
MVA, RMS SYMMETRICAL FOR ONE SECOND. THE INTERCONNECTIONS
BETWEEN THE BUSBARS AND THE CIRCUIT BREAKERS SHALL BE MADE
BY CONTINUOUS RATED ALUMINIUM STRIPS SUITABLY COVERED BY
PROPER GRADED HEAT SHRINKABLE COLOUR CODED PVC SLEEVES. THE
EARTH BUSBAR SHALL RUN THROUGH THE LENGTH OF THE PANEL AND
TERMINATED AT TWO ENDS.

1014 ALL THE MCCBS SHALL BE PROVIDED WITH EXTENDED ROTARY


OPERATED MECHANISM. SAFTY INTERLOCKS ARE TOO BE PROVIDED TO
PREVENT THE DOORS OF THE COMPARTMENTS HOUSING THE MCCBS TO
PREVENT THE DOORS TO OPEN WHEN THE MCCBS ARE 'ON' POSITION.

1015 ACBS SHALL BE METAL CLAD, INDOOR TYPE (IN FULLY DRAWOUT
EXECUTION) MOUNTED ON FULLY DRAWOUT TRUCK WITH SERVICE,
TEST AND ISOLATED POSITION AND COMPLETE WITH THE FOLLOWING
SAFTY INTERLOCKS AND SAFTY SHUTTERS AND PADLOCK FACILITY.

1016 IT SHALL NOT BE POSSIBLE TO MOVE THE TRUCK IN OR OUT OF CUBICLE


WHEN THE BREAKER IS CLOSED.
1017 ACB COMPARTMENT DOOR SHALL BE MACHENICALLY INTERLOCKED SO
THAT IT WILL NOT POSSIBLE TO CLOSE THE ACB IN PLUG POSITION
WHEN THE DOOR IS OPEN.
1018 IT SHALL NOT BE POSSIBLE TO PUSH THE TRUCK IN CLOSE POSITION IF
EITHER OF THE SAFETY SHUTTER IS NOT FREE AND NOT IN CLOSE
POSITION.
UNIT RATE TOTAL
SET 875000 875000.00
SET 1620000 3240000.00

0.00
0.00

MTR 0.00
0.00

NOS. 15000 60000.00


0.00
MTR 0.00

0.00
CUM 286 15444.00

SET 3146 44044.00

SET 11000 110000.00


ITEM 915 25620.00

ITEM 531 9558.00

MTR 216 8640.00

MTR 201 80400.00

MTR 201 30150.00


0.00
SQ.MTR 13000 390000.00

NOS. 1000 2000.00

NOS. 2000 2000.00

NOS. 500 5000.00

0.00
0.00
0.00
0.00
0.00

0.00

0.00

0.00

0.00

0.00

0.00
0.00

0.00

0.00

NO 0.00
0.00

0.00

0.00
0.00

0.00
0.00
0.00

0.00

0.00

0.00

0.00

0.00

0.00

0.00
0.00
0.00

0.00

0.00
0.00

0.00

0.00
0.00
0.00

0.00
0.00

0.00

0.00
0.00

0.00

0.00

0.00

0.00

0.00

0.00

0.00

0.00

0.00
0.00

0.00

0.00

0.00

0.00

0.00

0.00

0.00

0.00

0.00

0.00

0.00

0.00

0.00

0.00

0.00
0.00
0.00
0.00
0.00

0.00
NO. 0.00
0.00

0.00

0.00
0.00

0.00

0.00

0.00
0.00

0.00

0.00
0.00

0.00
0.00
0.00

0.00
0.00

0.00
0.00

0.00

0.00

0.00

0.00

0.00

0.00

0.00

0.00

0.00
0.00

0.00
NO 0.00
0.00

0.00

0.00

0.00
0.00

0.00

0.00
0.00

0.00

0.00
0.00

0.00
0.00
0.00
0.00

0.00
0.00

0.00

0.00
0.00
0.00

0.00
0.00

0.00

0.00
0.00

0.00
0.00
0.00

0.00
0.00

0.00

0.00

0.00

0.00
0.00

0.00

0.00
0.00

0.00
0.00
0.00
0.00

0.00

0.00

0.00

0.00
0.00
0.00

0.00
0.00

0.00

0.00
0.00

0.00
0.00
NOS 0.00

0.00
0.00

0.00

0.00

0.00

0.00
0.00
NOS 0.00

0.00
NOS 0.00
0.00
MTR 0.00

MTR 0.00

MTR 0.00

MTR 0.00
MTR 0.00

MTR 0.00

MTR 0.00

MTR 0.00

MTR 0.00

MTR 0.00

MTR 0.00

MTR 0.00

0.00
0.00

EACH 0.00
0.00
EACH 0.00
0.00
0.00
EACH 0.00
EACH 0.00
EACH 0.00
0.00
EACH 0.00
EACH 0.00
EACH 0.00
EACH 0.00
EACH 0.00
EACH 0.00
EACH 0.00
EACH 0.00
0.00
0.00

SET 0.00
SET 0.00
SET 0.00
SET 0.00
SET 0.00
SET 0.00
SET 0.00
SET 0.00
SET 0.00
SET 0.00
SET 0.00
0.00

0.00
MTR 58 4060.00

MTR 62 6200.00

0.00
MTR 48 4320.00

MTR 67 3685.00

0.00
MTR 170 212500.00

MTR 180 81000.00

MTR 195 243750.00


MTR 319 130790.00

MTR 333 149850.00

0.00
MTR 96 7680.00

MTR 136 27200.00

MTR 156 3120.00

0.00
0.00

MTR 11 13750.00
MTR 15 1950.00
MTR 19 11400.00
0.00
0.00

MTR 0.00
MTR 0.00
MTR 0.00
0.00
CUM 0.00

SET 0.00

SET 11479 68874.00

ITEM 1029 20580.00

ITEM 598 9568.00

0.00
MTR 170 17000.00

0.00
MTR 149 116220.00
MTR 135 16200.00
0.00
MTR 0.00

0.00
0.00
0.00

NOS 0.00
NOS 0.00
NOS. 0.00
0.00

NOS 0.00
0.00

0.00
NOS. 0.00
NOS 0.00
NOS. 0.00
0.00
0.00

NOS 0.00
NOS 0.00
NOS 0.00
NOS 0.00
NOS 0.00
NOS 0.00
NOS 0.00
0.00
NOS 0.00
NOS 0.00
0.00
0.00

NOS 0.00
0.00
MTR 0.00

0.00
0.00

MTR 0.00

0.00

MTR 0.00

0.00

EACH 0.00
EACH 0.00
0.00

EACH 0.00
EACH 0.00
0.00

0.00

RM 0.00
RM 0.00

RM 0.00

RM 0.00

RM 0.00

0.00
0.00

RM 0.00
RM 35 105000.00
RM 46 138000.00
0.00

POINT 0.00
POINT 0.00
POINT 0.00
POINT 0.00

0.00
0.00

NOS 0.00

NOS 0.00
NOS 0.00

NOS 0.00
0.00
0.00

NOS 0.00
NOS 0.00
0.00

NOS 0.00
NOS 0.00

NOS 0.00

NOS 0.00

NOS 0.00

NOS 0.00

NOS 0.00
NOS 0.00

0.00
0.00

SET 0.00
SET 0.00
SET 0.00
0.00
0.00
SET 0.00
0.00
0.00

NOS 0.00
NOS 0.00
0.00
NOS 0.00

0.00
NOS 0.00

NOS 0.00

EACH 0.00

0.00
NOS 0.00

NOS 0.00

NOS 0.00

EACH 0.00

NOS 0.00

EACH 0.00
0.00
NOS. 0.00

EACH 0.00

0.00
0.00

NOS. 0.00

EACF 0.00

EACH 0.00

0.00
0.00

NOS 0.00

EACH 0.00

0.00
0.00

NOS 0.00

NOS 0.00
0.00

EACH 247 6175.00


EACH 411 6165.00
0.00

EACH 82 2050.00
EACH 110 1650.00
0.00
0.00

NOS 0.00
0.00
0.00

NOS 0.00

EACH 0.00

0.00
0.00

NOS 0.00

EACH 0.00

NOS 0.00

NOS 0.00

0.00
0.00

NOS 0.00

EACH 0.00

0.00
0.00
MTR 0.00

NOS 0.00
NOS 0.00
MTR 0.00

0.00
0.00

NOS 0.00
NOS 0.00
NOS 0.00
0.00
EACH 0.00

0.00
MTR 0.00

0.00
EACH 0.00

0.00
0.00

NOS 0.00
0.00
0.00

MTR 0.00

0.00

MTR 0.00

0.00

EACH 0.00
EACH 0.00
0.00

EACH 0.00
EACH 0.00
0.00
0.00

SET 0.00
SET 0.00
0.00

SET 0.00
SET 0.00
0.00
0.00
0.00

SET 0.00

0.00
SET 0.00

SET 0.00
0.00
NOS 0.00
0.00
MTR 0.00

0.00
NOS 0.00

0.00
SET 0.00

0.00
0.00

0.00

0.00

0.00

0.00

0.00
0.00

0.00

0.00

SET 0.00
0.00

0.00

0.00

0.00

0.00

0.00

0.00
0.00

You might also like