8-1. Examples of using only Refnet joint (during eight rooms installation)
Outdoor unit
Outdoor unit
Distributor kit
Λ
41
DVM TM(chapter5-2)_E<03759 6/14/02 2:22 PM Page 42
Λ
. Installation
Outdoor unit
b c d e f
a
H1
g h i j k
H2
Outdoor unit
5.0HP 6.0HP 7.0/7.5HP 8.0/10.0HP
Item
Actual length 70 100
Max. Distance of the (m) ex) In case of 10 horse power a+b+c+d+e+f ≤ 100m
allowable remotest indoor unit
length from the outdoor unit Equivalent 87 125
length (m) ✻ 1) ex) In case of 10 horse power ≤ 125m
Height difference between outdoor unit
Max. and indoor unit (m) = H1(the figures in the
allowable parenthesis is applied when the outdoor 30 (30) 50 (40)
height unit is installed below the indoor unit)
difference Height difference between indoor unit = H2 15m
The distance from the first refnet joint to the indoor unit :
shorter than 30m ex) b+c+d+e+f ≤ 30m, b+c+i ≤ 30m
Allowable length after branching
The distance between the max piping and min piping length
from 1 refnet joint ≤ 20m
✻ 1) Equivalent length means a calculated value of the actual length plus pressure loss caused by piping curve.
For instance, the equivalent in the case of 10 horse power should be 125 meters (The detailed calculation
of equivalent length should be referenced in page V-43).
Λ
42
DVM TM(chapter5-2)_E<03759 6/14/02 2:22 PM Page 43
Outdoor unit
b c d Distributor kit
a
H1
e f g h i j
H2
Outdoor unit
5.0HP 6.0HP 7.0/7.5HP 8.0/10.0HP
Item
Actual length 70 100
Max. Distance of the (m) ex) In case of 10 horse power a+b+c+d+j ≤ 100m
allowable remotest indoor unit
length from the outdoor unit Equivalent 87 125
length (m) ✻ 1) ex) In case of 10 horse power ≤ 125m
Height difference between outdoor unit
Max.
and indoor unit (m) = H1(the figures in the
allowable 30 (30) 50 (40)
parenthesis is applied when the outdoor
height
unit is installed below the indoor unit)
difference
Height difference between indoor unit = H2 15m
The distance from the first refnet joint to the indoor unit :
ex) b+c+d+j ≤ 30m, b+c+d+h ≤ 30m
Allowable length after branching
Between distributor kit and indoor unit ≤ 30m
Note ◆ The distributor kit is applicable to indoor units that are not embedded with electronic expansion
valve, that is, 1-way cassette or Wall-mounted type, and it has less coolant noise compared to
the electronic expansion valve kit of embedded type. Therefore we recommend the product to
be used in study rooms or private offices where noise control is required.
✻ 1) Equivalent length means a calculated value of the actual length plus pressure loss caused by piping curve.
For instance, the equivalent in the case of 10 horse power should be 125 meters (The detailed calculation
of equivalent length should be referenced in pages V-43).
Λ
43
DVM TM(chapter5-2)_E<03759 6/14/02 2:22 PM Page 44
Λ
. Installation
Λ
44
DVM TM(chapter5-2)_E<03759 6/14/02 2:22 PM Page 45
equivalent length = actual pipe length + number of elbows + number of elbows X equivalent length of each elbows
+ number of oil traps X equivalent length of each oil trap
Type
Elbow Oil Trap
Piping diameter (mm)
9.52 0.18 1.3
12.70 0.20 1.5
15.88 0.25 2.0
19.05 0.35 2.4
22.02 0.40 3.0
25.40 0.45 3.4
28.58 0.50 3.7
31.80 0.55 4.0
◆ Examples of equivalent length calculation : When 10 horse power outdoor unit’s actual length is 80 meters,
the piping diameter is 25.40mm, twelve elbows and two traps are used,
the equivalent length is 80+0.45X12+3.4X2 = 92.2(m)
1. When the equivalent length is more than 90% of the actually allowed piping length (more than
63 meters in five/six horse powers, 90 meters in seven/eight/ten horse powers, the gas pipe
diameter of the main piping (piping from the outdoor unit to the first bypass) is expanded a level.
For instance, when the equivalent length of 10 horse power outdoor unit is more than 100 meters,
the gas pipe diameter is changed to 31.80 from 28.58.
2. When the diameter of gas pipes is uplifted one level, the effective equivalent length is
recalculated, and the piping length is calculated based on the effective equivalent length
when looking into the graph to calculate the performance reduction by the long piping.
Effective equivalent length = equivalent length of main piping X 0.5 + equivalent length after the by path
(when the diameter of gas pipe of the main piping is uplifted a level)
◆ Examples of effective equivalent length calculation : When the actual length of 10 horse power outdoor unit is 80
meters, piping after bypass 20 meters), the diameter of gas pipe
of the main piping is 25.40 mm, twelve elbows and two oil traps
are used (elbows and oil traps are used only in main piping).
① Equivalent length = 80+0.45X12+3.4X2=92.2(m)
➁ As the equivalent length is more than 90 meters, the
diameter of gas pipe in the main piping is uplifted one level.
➂ Effective equivalent length = (60+0.45X12+3.4X2)X0.5+20=56.1(m)
➃ The performance loss due to the long piping is the same with
equivalent length of 56.1 meters when the diameter of gas pipes
of the main piping is not uplifted one level.
Λ
45
DVM TM(chapter5-2)_E<03759 6/14/02 2:22 PM Page 46
Λ
. Installation
Λ
46