Amca 600-16

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 28

AMCA Publication 600-16

Application Manual for


Airflow Measurement Stations

Air Movement and Control Association International


30 W. University Drive
Arlington Heights, Illinois
60004
AMCA Publications

Authority AMCA Publication 600 was approved by the membership of the Air Movement and Control Association
International Inc. on March 4, 2016.

Copyright © 2006 by Air Movement and Control Association International Inc.

All rights reserved. Reproduction or translation of any part of this work beyond that permitted by Sections
107 and 108 of the United States Copyright Act without the permission of the copyright owner is unlawful.
Requests for permission or further information should be addressed to the executive director, Air Move-
ment and Control Association International Inc. at 30 West University Drive, Arlington Heights, IL 60004-
1893 U.S.A.

Objections Air Movement and Control Association International Inc. will consider and take action upon all written
complaints regarding its standards, certification programs or interpretations thereof. For information on
procedures for submitting and handling complaints, write to

Air Movement and Control Association International


30 West University Drive
Arlington Heights, IL 60004-1893 U.S.A.

AMCA International, Incorporated


c/o Federation of Environmental Trade Associations
2 Waltham Court, Milley Lane, Hare Hatch
Reading, Berkshire, United Kingdom
RG10 9TH

Disclaimer AMCA uses its best efforts to produce standards for the benefit of the industry and the public in light of
available information and accepted industry practices. However, AMCA does not guarantee, certify or
assure the safety or performance of any products, components or systems tested, designed, installed
or operated in accordance with AMCA standards or that any tests conducted under its standards will be
non-hazardous or free from risk.
Review Committee

Paresh Davé Air Monitor Corporation

Glenn Esser Ruskin Company

Michael Khoury Paragon Controls Inc.

Keith Foszcz Paragon Controls Inc.

Armin Hauer ebm-papst Inc.

Josiah Wiley Ruskin Company

Tim Orris AMCA International Staff


Related AMCA Documents

Related AMCA Publication 11 Damper Application Manual for Heating/ Ventilating and Air Conditioning
Publications
AMCA Publication 611 Certified Ratings Program – Product Rating Manual for Airflow
Measurement Stations

Related ANSI/AMCA Standard 610 Laboratory Methods of Testing Airflow Measurement Stations for
Standards Performance Rating
Contents

1. Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

2. Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

3. Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

3.1 Airflow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

3.2 Airflow measurement station (AMS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

3.3 Static pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

3.4 Total pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

3.5 Airflow measurement station performance variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

4. Principles of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

4.1 Types of AMS devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

5. Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

6. Selection Criteria . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

6.1 Obstructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

6.2 Operational range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

6.3 Environmental suitability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

6.4 Maintenance access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

7. Locating the AMS in the Air System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

8. Airflow Turndown Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

9. Conditions of Air Being Measured: Temperature, Altitude, Static Pressure and Humidity . . . . . . . . . . . . . . . . . . . . . . 4

10. Materials of Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

11. Installed Performance Validation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5


Application Manual for
Airflow Measurement Stations

1. Purpose 3.3 Static pressure

This application guide is intended to assist designers and That portion of the air pressure that exists by virtue of the
users with the proper application, performance consider- degree of compression or expansion.
ations, selection and limitations of airflow measurement
stations. 3.4 Total pressure

This publication provides information and important points to The air pressure that exists by virtue of the degree of
be considered when designing or specifying heating, venti- compression and rate of motion. It is the algebraic sum of
lating and air conditioning (HVAC) and other applications in the velocity pressure and the static pressure at a point. Thus
installations requiring an airflow measurement station (AMS) if the air is at rest, the total pressure will equal the static
for use in temperatures from -30 °C to +120 °C (-20 °F to pressure.
+250 °F), pressures to 250 Pa (10 in. wg) and velocities to
28 m/s (5500 fpm). 3.5 Airflow measurement station performance
variables
2. Scope
3.5.1 Tested AMS airflow rate (QAMS)
The purpose of this document is to help avoid problems The AMS reported airflow rate or measurement as calcu-
associated with misapplied or incorrectly installed AMSs. lated according to the manufacturer’s instructions. This
Problems may include incorrect location, inappropriate calculation is based upon the output (pressure, current or
measurement range, mismatched accompanying instrumen- voltage) of the AMS.
tation and an AMS incompatible with intended application.
3.5.2 AMS differential pressure
This guide provides an overview of permanently installed The observed differential pressure between the high pres-
AMSs and their application. This publication does not sure output and the low pressure output of a differential
address portable devices used to measure airflow in test- pressure type AMS.
and-balance applications.
3.5.3 AMS electronic output
It is not the intent of this manual to be used for detailed spec- The observed voltage or current output of an electronic
ifications; rather it serves as a guide toward understanding output type AMS that correlates directly and proportionately
the various types of AMSs available and items to be consid- to the velocity of airflow in a duct.
ered for their proper use.
3.5.4 Test AMS face area (AFACE)
The total cross sectional area of a louver, duct, wall or AMS
3. Definitions
opening.

3.1 Airflow 3.5.5 AMS free area (AFREE)


The minimum area through which air can pass.
A flow of air or an air current, specifically one that passes
through a dimensionally defined plane.
4. Principles of Operation
3.2 Airflow measurement station (AMS)
Proper application requires knowledge of the various types
of AMSs and their principles of operation.
A sensing device that is used to measure the airflow rate
in a system or fan appurtenance. It may consist of a single
The airflow sensing devices used in an AMS include but are
sensor or an array of sensors in permanent position in the
not limited to pitot types, differential pressure types, thermal
air system. It may be supplied as a probe to be inserted into
dispersions, vortex shedding airflow sensors, orifice plates,
a ductwork or supplied in a casing approximating the size
fan inlets or air measurement louvers. These devices are
of the air system in which it is installed or as an air intake
explained as follows:
louver.

AMCA 600-16 | 1
4.1 Types of AMS devices follows the same form as with pitot type devices except that
a flow coefficient (K) value other than one is used in the
4.1.1 Pitot type airflow computation. (See Figure 4.)
A pitot type AMS operates on the principle of measuring the
separate components of total pressure and static pressure Q = 2993 ADUCT K (Pv /ρ)0.5 (SI)
that exist within ducted airflow. The measurement process
consists of subtracting static pressure from total pressure
to obtain velocity pressure, then mathematically converting Q = 1097 ADUCT K (Pv /ρ)0.5 (I-P)
the velocity pressure into units of airflow velocity or volume.
Where:
Q = Airflow rate at actual conditions, m3/s (cfm)
The functions of subtracting static pressure from total pres-
ADUCT = Area inside of duct, m2 (ft2)
sure and conversion of velocity pressure into an analog or
K = A dimensionless constant that pertains to
digital signal is typically performed by a differential pressure
that specific S pitot tube
transducer.
Pv = Velocity pressure in the duct, Pa (in. wg)
ρ = Actual airstream density, kg/m3 (lbm/ft)
Transmitters can be equipped with mathematical computa-
tion capabilities that can convert velocity pressure into an
4.1.3 Orifice plate
analog or digital output corresponding to units of airflow
An orifice plate is a plate having a circular concentric hole
velocity or volume. Figure 1 shows the components of total
that is slightly smaller in diameter than the inside diameter
pressure and static pressure and how they are converted to
of the duct in which it is installed. When air flows through
air velocity measurements.
the orifice plate, the plate creates a differential pressure that
is mathematically related to the airflow velocity. A measure-
Airflow is related to velocity pressure by the formula:
ment of the differential pressure is achieved by measuring
the upstream and downstream static pressure across the
Q = 2993 ADUCT(Pv /ρ)0.5 (SI)
orifice plate using wall static pressure taps. (See Figure 5.)

Q = 1097 ADUCT(Pv /ρ)0.5 (I-P) For an orifice plate, airflow is related to differential pressure
by the formulae:

Where: Q = C (2 ΔP/ρ)0.5 A (SI)


Q = Airflow rate at actual conditions, m3/s (cfm)
ADUCT = Area inside of duct, m2 (ft2)
Pv = Velocity pressure in the duct, Pa (in. wg) Q = C 1097 (2 ΔP/ρ)0.5 A (I-P)
ρ = Actual airstream density, kg/m3 (lbm/ft3)

To obtain airflow measurements, nearly all pitot type AMS


C = Cd (1 / (1 − β ))
4

units use multiple points of pressure measurement to


Where:
traverse the duct cross section, with the multiple points
being pneumatically averaged to produce an average total
Q = Airflow through orifice, m3/s (cfm)
pressure and an average static pressure as output signals.
ΔP = Measured differential pressure across orifice, Pa
(in. wg)
Airflow straighteners are sometimes used on pitot type AMS
ρ = Air density, kg/m3 (lbm/ft3)
devices to reduce both the presence of turbulence and the
A = Area of orifice hole, m2 (ft2)
angularity of the airflow as it passes through the AMS.
C = Orifice flow coefficient
β = d/D
Figure 2 shows a typical AMS with a flow straightener,
Cd = Coefficient of discharge, dimensionless
Figure 3 shows a typical AMS without a flow straightener
and Figure 4 shows a typical S type pitot tube measurement.
Note: Cd is dependent upon the Reynolds number of the
airflow system. Where sharp edge orifice plates are used in
4.1.2 Pitot suction type
the duct system, Cd is also dependent upon the ratio of the
Pitot suction type AMS devices, also known as amplified
orifice diameter to the duct diameter. For values of Cd, refer
pitot type, operate in a manner similar to pitot-type devices
to values for K in ASME PTC 19.5.
except that they use elements that create a suction pres-
sure rather than static pressure. The resulting differential
The function of converting the differential pressure into an
pressure between suction pressure and velocity pressure

2 | AMCA 600-16
electronic output is typically performed by a differential pres- 4.1.6 Vortex shedding type
sure transducer. Differential pressure transmitters can be A vortex shedding type AMS operates on the principle that
equipped with mathematical computation capabilities that as airflow passes around a fixed obstruction (bluff body or
can generate an electronic output corresponding to units of shedder), vortices (eddies) are created in the wake of the
velocity or airflow volume. obstruction. These vortices, which develop and shed in an
alternating manner from one side of the obstruction to the
4.1.4 Instrumented fan inlet cone other, create pressure pulses that are digitally sensed. (See
A fan inlet cone has a flared inlet and a narrow throat for Figure 9.)
efficiently receiving and guiding airflow into a rotating fan
impeller. An instrumented fan inlet cone uses pressure taps Multiple sensors are typically used in most ducts to obtain
to measure the static pressures at both the inlet and near point velocity measurements across the cross section of the
the throat diameter. The difference between these static duct. For each point of measurement, the AMS electronics
pressures, adjusted for the empirically determined charac- convert the shedding frequency into a point velocity and
teristics of the inlet cone, is used as an indication of the fan then average the multiple point velocities to generate an
airflow. (See Figure 6.) electronic output corresponding to units of airflow velocity or
volume. (See Figure 10.)
The technique is based on the Bernoulli and continuity equa-
tions, which allow calculation of flow through a converging Airflow is related to the frequency of vortex shedding by the
nozzle based upon measurement of the static pressure drop formula:
across the nozzle.
F = St(V/d)
Airflow is related to the static pressure differential by the
formula Where:
F = Frequency of vortex shedding
Q=k• (ΔP / ρ )
St = Strouhal number, a constant for the shape
where: of the shedder over the airflow range
V = Velocity of the airflow
Q = airflow (acfm) d = Width of the bluff body
k = inlet cone calibration factor
ΔP = differential pressure across the inlet cone 4.1.7 Thermal type
ρ = actual air density A thermal type AMS operates on the principle that there is a
relationship between airflow velocity and the heat dissipating
effect of that airflow upon a heated element. Multiple sensor
If the fan inlet is entirely unobstructed, then single pressure pairs are used to obtain point velocity measurements. For
taps at the cone’s inlet and throat will suffice. Otherwise, two each point of measurement, the AMS converts the power
piezometer rings, each consisting of typically four conduit dissipation and ambient airflow temperature to determine
connected pressure taps, should be used for pneumatically the velocity. It then averages the multiple point velocities
averaging, and the inlet cone calibration factor should be to generate a temperature compensated electronic output
established experimentally by test. corresponding to units of duct airflow velocity or volume.
(See Figure 11.)
4.1.5 Fixed and variable area AMS
A fixed area device employing a screen is designed to 4.1.8 Air measurement louver
be mounted in a system so that the pressure differential An air measuring louver combines the functions of an
across the obstruction or orifice can be compared to a chart outside air intake louver and an air measuring station in one
or converted to an electric output to determine the airflow assembly. A wind driven rain resistant louver provides air
rate. The obstruction may be a perforated plate or cali- straightening function for an outside air intake AMS’s veloc-
brated orifice with pressure sensing probes on either side ity pressure pickup ports. (See Figure 12.)
of the obstruction to measure the differential pressure and
compared to an airflow chart. 5. Applications
A variable area device may be a movable damper integrated Accurate airflow measurement devices are necessary to
into the AMS, in which the differential pressure is measured ensure proper fan control and building ventilation for indoor
at multiple blade angles and integrated into a microproces- air quality. They also ensure ventilation system efficiency.
sor to determine airflow rate. Additional applications include volumetric synchronization
for space pressurization control, filter loading optimization,

AMCA 600-16 | 3
minimum air change requirements maintenance for health
and safety and required minimum outdoor air measurement 4. When it is necessary to locate an AMS downstream of a
and control. (See Figures 13 through 19 for examples of damper, maximize the distance between the damper and
AMS applications.) the AMS and use an opposed blade damper rather than a
parallel blade damper.
6. Selection Criteria
5. When an AMS is located in close proximity to and down-
When selecting an airflow measurement station, consider- stream of an elbow, specify a vaned or sweep elbow.
ation should be given to the following factors.
6. Avoid locating an AMS where airflow is decompressing,
6.1 Obstructions such as immediately downstream of a sound attenuator,
expanding transition, fan discharge, etc.
Upstream/downstream flow obstructions (turbulence induc-
ing appurtenances) are discussed in detail in Section 7. 7. Avoid locations downstream of fan cooling coils, humidi-
fiers, etc., that can introduce condensing moisture into the
6.2 Operational range airstream.

The AMS should be capable of operating over the velocity 8. If sufficient straight duct is not available downstream of at
range of the application. This aspect is discussed in detail a sharp edged inlet or abrupt transition, the addition of an
in Section 8. inlet cone or bell mouth is recommended.

6.3 Environmental suitability 9. If sufficient straight duct is not available after a turbu-
lence producing device, consider using straightening vanes,
The AMS design and construction must be suitable for the honeycomb or other airflow conditioning device upstream of
airflow environment. Environmental considerations include the AMS.
temperature, humidity, condensation, water droplets, corro-
sives, process constituents and entrained particulates. This 8. Airflow Turndown Considerations
aspect is discussed in detail in Sections 9 and 10.
Turndown capability of the AMS is defined as the ratio of
6.4 Maintenance access maximum to minimum measurable airflow over its designed
operating range. The designer needs to be aware that
The installation location of the AMS should be accessible for different types of AMS device technologies have varying
maintenance. recommended airflow measurement ranges and turndown
capabilities.
7. Locating the AMS in the Air System
On variable air volume systems, the required turndown for
To minimize measurement error induced by turbulence, a particular application is the ratio of the maximum design
the manufacturer’s installation requirements should be airflow to the minimum design airflow.
observed, along with the following guidelines for selecting
an appropriate location for an AMS device. (Refer to AMCA 9. Conditions of Air Being Measured:
Standard 610 for location criteria used to rate the AMS.) Temperature, Altitude, Static Pressure and
Humidity
1. On straight runs of duct that do not meet the manufac-
turer’s minimum installation recommendations, the AMS Technologies differ in their reactions to conditions. The
should be located two-thirds of the distance downstream in following factors should be considered with respect to airflow
the longest straight run of duct. measurement accuracy at conditions other than standard air
(see definitions in Section 3), as may be referenced by the
2. It is generally recommended that, whenever possible, an AMS manufacturer. The following are examples.
AMS should be located upstream of a turbulence producing
device in the ductwork (elbows, transitions, sound attenua- 1. Temperature
tors, fans, branch take-offs, mixing boxes, air blenders, etc.).
A cubic meter (cubic foot) of air measured at standard condi-
3. When locating an AMS near any flow modulating device tions will experience a measurement error of approximately
(damper, air valve, etc.), the AMS must not be placed imme- 1% for each 5°C (10°F) deviation from standard conditions.
diately downstream of the flow modulating device. Therefore, it is recommended that if measurement is made

4 | AMCA 600-16
over a broad range of temperature conditions, then tempera- •  The inaccuracies of the portable test instruments
ture compensation should be considered. This is particularly as compared to the AMS. For example, if the AMS
important when measuring outdoor airflow. accuracy is ± 2% of reading and the test instrument
is ± 5%, the discrepancy in readings could be as
2. Altitude great as ± 7%, even though all instruments are
within their respective tolerances. Instruments and
procedures commonly used in manual duct travers-
A cubic meter (cubic foot) of air measured at standard condi-
ing are generally accurate to within 5–10% of actual
tions will experience a measurement error of 3.4% for each airflow.
300 meters (1000 feet) above sea level. Therefore, it is
recommended that consideration be given to compensate •  Variability and inconsistency in the technique.
Different techniques used by the individual perform-
for the change in air density due to altitude.
ing the field measurement can lead to greater than
expected difference between test and balance field
3. Humidity measurements and AMS reported airflow measure-
ment. Additional errors may be introduced when
Since humidity does not have an appreciable effect (less using multiple AMSs to validate another AMS.
than 0.5% measurement variance error for a 50% deviation
•  Field measurements made at locations that are
in relative humidity from standard conditions), compensa- inconsistent with specified and recognized stan-
tion is not normally necessary. However, care should be dards. These cannot be considered a reliable
given to avoid any location where the AMS will be exposed source for validating AMS field measurements.
to condensing moisture.
•  Portable instrument(s) out of calibration or in disre-
pair. Equipment that has not been regularly main-
4. Static pressure tained should not be used.
•  Air leakage occurring between the point of field
A cubic meter (cubic foot) of air measured at standard condi-
measurement and the installed location of the AMS.
tions will experience a measurement error of 0.96% for
Leakage can result in air measurements that are
each 1000 Pa (4 in. wg) deviation from standard conditions. greater or less than expected. Often, air handlers
Therefore, it is recommended that pressure compensation are serving the same space and cannot be shut
be considered at variation greater than 1000 Pa (4 in. wg) down or isolated when performing calibration
from standard conditions. checks. Dampers that are assumed closed may
have significant leakage.
10. Materials of Construction •  Fluctuations and pulsations in the actual airflow
versus the responsiveness and sampling period
Standard AMS materials of construction are normally suit- of the portable instrumentation. This can produce
able for environmental HVAC systems. When the AMS will readings that are highly variable and unstable.
be exposed to corrosive or other harmful airstream constit- When an applicable situation arises, time averaging
uents, its materials of construction must be selected for or applied noise filters should be applied to both
compatibility. AMS under test and reference instrumentation.

11. Installed Performance Validation

Caution must be exercised when comparing the readings of


a properly applied and installed AMS to readings produced
by handheld/portable devices such as those typically used
in the process of testing and balancing an air system.
Variances of 10% or greater between the AMS readings and
those obtained via test-and-balance measurement proce-
dures should be expected, representing the cumulative
effect of AMS accuracies, portable instrumentation accura-
cies, traverse methods, installation conditions, temperature,
altitude, pressure and humidity.

These following may be causes of significant differences


between the readings of an AMS and those of portable
devices:

AMCA 600-16 | 5
PSTATIC

PTOTAL

Pitot Tube
Measurement PSTATIC

PV
PTOTAL

Formula: Velocity Pressure (PV) = PTOTAL - PSTATIC

Figure 1
Pitot Type Airflow Measurement Components

Figure 2
Pitot Type AMS with Flow Straightener

6 | AMCA 600-16
Figure 3
Pitot Type AMS without Flow Straightener

PTOTAL PREFERENCE

‘S’ Type Pitot Tube


Measurement PREFERENCE

PTOTAL PV

Formula: Velocity Pressure (PV) = PTOTAL - PREFERENCE

Figure 4
Pitot Suction Airflow Measurement Components

AMCA 600-16 | 7
Duct Static Pressure Taps

D D/2

AIRFLOW D d

2
d 
Orifice area = π  
2
Figure 5
Orifice Type AMS

8 | AMCA 600-16
Inlet
(examplenum b
ple) ox

Low-side static
pressure taps (4x)

Piezometer ring

Stationary fan
inlet cone

AIRF
LOW
Differential
Fan impeller pressure
measurement

Recommended
clearance
D

Impeller
Diameter
D AIRFLOW

Narrow throat

Flared
inlet

Static pressure High-static


difference side pressure tap
∆P

Figure 6
Instrumented Fan Inlet Cone

AMCA 600-16 | 9
Temperature sensor
mounted in junction box
Inlet reference
Outside reference
signal connection
signal connection

Inlet reference sensor

Height Airflow

Expanded metal Outside reference


sensor

Flange Width Depth

Figure 7
Fixed Area AMS

Airflow

SP

Figure 8
Variable Area AMS TP

10 | AMCA 600-16
AIRFLOW Vortices

Figure 9
Vortices Generated by a Fixed Obstruction

Figure 10
Vortex Shedding AMS

AMCA 600-16 | 11
Figure 11
Thermal AMS

12 | AMCA 600-16
Airflow Sensing Blade

Airflow Sensing Blade

AIRFLOW

Total Pressure Static Pressure


Measuring Chamber Measuring Chamber

Figure 12
Air Measurement Louver

AMCA 600-16 | 13
P H C

F C C SF Supply
VSD Airflow

AMS

Airflow
Processing
Center Airflow Signal
Control Signal

Supply air volume readout and control


Constant air volume control to compensate for filter loading

Figure 13
AMS Application 1

14 | AMCA 600-16
E.A. O.A.
RF P H C

R.A.

F C C SF
VSD Supply
Airflow

Return
Airflow

AMS AMS

Airflow
Airflow Signal
Processing
Control Signal
Center

Volumetric tracking of return fan with supply for building pressurization

Not recommended for minimum ventilation control

Figure 14
AMS Application 2

AMCA 600-16 | 15
E.A. O.A.
RF P H C
AMS
M

R.A.

F C C SF
VSD Supply
Airflow
Return
Airflow

Airflow Airflow Signal


Processing Control Signal
Center

Outdoor air volume readout and control

Figure 15
AMS Application 3

16 | AMCA 600-16
Exhaust
Airflow

AMS

Airflow
Airflow Signal
Processing
Control Signal
Center

Exhaust air volume readout and control

Figure 16
AMS Application 4

AMCA 600-16 | 17
Space

AMS
Exhaust
Air
AMS

Supply
Air NC M

DP
H L

Airflow
Processing Airflow Signal
Center Control Signal

Space pressurization control by volumetric tracking of exhaust airflow with supply airflow

Note: Tight spaces where air leakage and volume offset are extremely low, the space pressurization is best accomplished using
the direct pressure measurement and control. Monitor space pressure to adjust volume offset.

Figure 17
AMS Application 5

18 | AMCA 600-16
AMS

Airflow Airflow Signal


Processing Control Signal
Center

Fan inlet air volume measurement

Figure 18
AMS Application 6

AMCA 600-16 | 19
Wall

Airflow Airflow Signal


Processing Control Signal
Center

Outside air louver

Figure 19
AMS Application 7

20 | AMCA 600-16
amca international
30 West University Drive
Arlington Heights, IL 60004-1893 U.S.
www.amca.org ■ +1 (847) 394-0150 ■ publications@amca.org
The Air Movement and Control Association International Inc. is a not-for-profit association of the world’s
manufacturers of air system equipment, such as fans, louvers, dampers, air curtains, airflow measurement
stations, acoustic attenuators and other air system components for the industrial and commercial markets.

You might also like