Professional Documents
Culture Documents
Analysis, Design, and Detailing of Various Foundation Layouts
Analysis, Design, and Detailing of Various Foundation Layouts
Analysis, Design, and Detailing of Various Foundation Layouts
FACULTY OF ENGINEERING
Semester: Fall
____________________________
Student Signature
i
Table of Content
Conclusion
b. Conclusion ................................................................................................................................ 23
ii
List of Figures
iii
List of Tables
iv
This Page Intentionally Left Blank
v
Introduction, Structural Plan, and Project Information
This report covers the design of two different foundation layouts for a 6-story building structural
system. The analysis and design of the seismic system for the building was completed prior to this project,
and the reactions obtained from ETABS will be used to complete the requirements of this project. The
first layout will consist of isolated, strip, and partial mat foundations and the second layout will be a
Seismic provisions will be done in accordance to UBC ‘97 and ACI 318M - 14. Additional
information regarding foundations and structural detailing will be obtained from ACI 336.2R - 88 and
ACI 315 - 99, respectfully. All foundation analysis and design will be done using SAFE.
NOTE:
40 x 40 cm or 70 x 30
cm.
thickness of 25 cm.
-1-
c. Material Details and Load Combinations
The following service load combinations are used (for soil and punching shear verification):
The following ultimate (strength) load combinations are used (for reinforced concrete design):
The above load combinations are obtained by multiplying selective service combinations by 1.5. All other
details can be found in the completed SAFE models corresponding to this project.
-2-
d. Project Requirements
The following requirements will all be covered throughout the rest of this report in the sequence listed
below.
Design the foundations using SAFE assuming the building is supported on isolated footings under
the columns, strip footings under the basement walls, and partial mat under the staircase connected
all by tie-beams.
Design the foundations using SAFE assuming the building is supported on a full mat foundation.
In each case provide: verification of soil bearing capacity and punching shear, check for uplift, and
-3-
Foundation Layout #1 – Isolated, Strip, and Partial Mat Foundations
The first layout will consist of isolated, strip, and partial mat foundations distributed under the various
columns and walls. All the foundations will be connected by tie-beams in an attempt to minimalize
differential settlement. The figures below illustrate the final layout on SAFE used in this project.
Moment Release
The strip footing under the perimeter basement walls are 1 m wide and are offset 375 mm from
each face of the 250 mm thick wall. The partial mat, under the staircase and two columns, is 6 x 5 m and
the second strip footing, under the shear wall and column, is 2 x 6 m. The final thickness that was used to
satisfy both soil bearing capacity and punching shear was 400 mm. These verifications will be seen in the
next section of this report. All tie-beams are 400 mm wide and 350 mm thick in order to account for 50
mm of extruded polystyrene foam. Also, all tie-beams are released on their edges to ensure they don’t
transfer moments.
-4-
-5-
Figure 3 – Perspective View of Layout #1
b. Soil Bearing Capacity and Punching Shear Verification
After adjusting the foundation surface area (offset values) and thickness, the final dimensions as stated
in the previous section resulted in a maximum pressure of 300 KPa and this is less than the allowable soil
bearing capacity which is given as 350 KPa. The pressure diagram below shows the region of high
pressure occurs under the strip footing supporting a shear wall and column.
-6-
Only three columns are present in the basement of this building structure, while all the other
vertical elements are walls and so punching shear is not criterial in these regions. The figure below shows
the demand over capacity ratios of each column. Since all values are less than 1 then there is no issue with
the slab thickness. It is also worth noting that punching shear was the controlling factor in selecting a
A quick analysis was run to check if there was any region of uplift under the foundations. This was
done by converting all the service load combinations to nonlinear static cases and ensuring that the
supporting soil only accepted compression. This analysis showed that the partial mat under the staircase
has major regions of uplift on both sides (due to the service envelope) as seen in the following figure.
These regions need to be carefully designed and detailed to avoid failure in the concrete.
-7-
Uplift Regions
-8-
Figure 6 –Uplift Verification of Layout #1
d. Reinforcing Steel Design
As stated before, all reinforcing steel design will be done in accordance to ACI 318M - 14 using
SAFE’s inbuilt design algorithms. The concrete covers of the foundations will be taken as 75 mm at the
bottom and 50 mm in all other directions as seen in ACI table 20.6.1.3.1. Also, minimum reinforcing
steel will be provided in regions that analysis deems no steel is needed in accordance to ACI table
7.6.1.1. The tie-beams will also be designed using SAFE and a concrete cover of 40 mm will be used in
all directions.
Uniform steel sizes and spacing will be used in each foundation and beam element to facilitate on-site
execution. All these results will be summarized in tables and element ID’s will be based on the figure
shown below. The steel direction will be based on the axis also shown in the figure below.
-9-
The two tables below show the required bar sizes and spacing for the footings and tie-beams.
* - Additional localized steel is needed to deal with regions of high concentrated stresses.
** - No top steel is needed since beams are simply supported, 2T10 are provided to aid in tying stirrups.
- 10 -
Foundation Layout #2 – Mat Foundation
The second layout to be analyzed and designed will consist of a full mat foundation distributed under
all the columns and walls. The mat foundation thickness will be determined by satisfying the soil bearing
capacity and punching shear. An offset of 200 mm was taken from all edges of the foundation to allow
the well spreading of loads from the retaining walls spread across the entire perimeter. The figure below
The dimensions of the mat foundation are 21.4 x 13.4 m and the thickness was finally set as 500
mm after several iterations that involved satisfying the soil bearing capacity and punching shear. These
- 11 -
Figure 9 – Deformed Shape of Layout #2
The deformed shape seen above shows excessive downward deflections at the perimeter and under the
staircase and shear wall. This is important because these regions require large amounts of steel at the
The final dimensions and thickness, as stated in the previous section, resulted in a maximum pressure
of 215 KPa and this is less than the allowable soil bearing capacity which is given as 350 KPa. Also, as
expected the mat foundation resulted in a much smaller maximum pressure due to its large surface area
Only three columns are present in the basement of this building structure, while all the other vertical
elements are walls and so punching shear is not criterial in these regions. The following figure shows the
demand over capacity ratios of each column. Since all values are less than 1 then there is no issue with the
slab thickness. It is also worth noting that punching shear was the controlling factor in selecting a
- 12 -
Figure 10 – Soil Pressure of Layout #2
- 13 -
c. Uplift Analysis and Verification
The same analysis steps used for the first foundation layout are used for the full mat foundation. The
results showed that no uplift regions are generated by any of the service load combinations. Therefore, no
All reinforcing steel design will be done in accordance to ACI 318M - 14 using SAFE’s inbuilt design
algorithms. The concrete covers of the foundations will be taken as 75 mm at the bottom and 50 mm in
all other directions as seen in ACI table 20.6.1.3.1. Also, minimum reinforcing steel will be provided in
regions that analysis deems no steel is needed in accordance to ACI table 7.6.1.1.
Uniform steel sizes and spacing will be used in each direction and location of the mat foundation to
facilitate on-site execution. All these results will be summarized in the table seen below. Additional steel
will be provided in regions of high stress where the typical steel was not sufficient.
* - Additional localized steel is needed to deal with regions of high concentrated stresses. See the
- 14 -
e. Steel Layout
- 15 -
Figure 13 – Additional Top Steel X - Direction of Layout #2
- 16 -
Figure 14 – Typical Bottom Steel X - Direction of Layout #2
- 17 -
Figure 15 – Additional Bottom Steel X - Direction of Layout
- 18
#2-
Figure 16 – Typical Top Steel Y - Direction of Layout #2
- 19 -
Figure 17 – Additional Top Steel Y - Direction of Layout #2
- 20 -
Figure 18 – Typical Bottom Steel Y - Direction of Layout #2
- 21 -
Figure 19 – Additional Bottom Steel Y - Direction of Layout
#2 -
- 22
Conclusion
a. Final Results
The final results of this project proved to be similar to that of the previous project. Seismic designed
elements always require large amounts of steel when compared to classical gravity load designed
elements. This is due to the high levels of stresses that are induced by the lateral earthquake forces.
Overall, seismic resisting elements need to be properly and carefully designed to ensure that in the case of
an earthquake all element can continuously provide structural support and avoid total collapse.
b. Conclusion
In conclusion, this project was an excellent opportunity to apply all the techniques learned throughout
the semester and apply them in a very practical manner. It also required modest amounts of engineering
judgment when selecting steel bars for examples. Being able to apply all the analysis and design methods
into one practical seismic project was truly beneficial in understanding all topics.
Building Code Requirements for Structural Concrete (ACI 318M-14). (2015). Farmington, MI: American
Concrete Institute.
Details and Detailing of Concrete Reinforcement (ACI 315-04). (2005). Farmington, MI: American
Concrete Institute.
Suggested Analysis and Design Procedures for Combined Footings and Mats (ACI 336.2R-88). (2002).
Uniform Building Code 1997 (UBC ‘97). (1997). Whittier, CA: International Conference of Building
Officials.
- 23 -