Produced on 01-Aug-18 with Xpress Selection V8.2.0 - database DIL 12.5.

Project name Showroom


Project address Jl Perak Timur no 198, Surabaya
Indonesia
Reference 001
Client name PT Anjaya
Client address Jl Perak Timur no 198, Surabaya

Selection parameters of the indoor units can be found under the chapter Indoor unit details
Selection parameters of the outdoor units can be found under the chapter Outdoor unit details
Only the data published in the data book are correct. This program uses close approximations of these data.

1. Material List
Model Qty Description
RPZQ6AV1 1 Home Central - VRV Home Series (RPZQ)
FPEKQ28AV1 1 HCAC FPEKQ-A - High Durability Moisture Control
Kitchen Ceiling Mounted Cassette
FPRSQ25APV1 1 HCAC FPRSQ-AP - Moisture Control Intelligent 3D Air
Flow Ceiling Mounted Duct
FXFQ50LV14 1 VRV FL(LV14) - Ceiling Mounted Cassette(Round
Flow)
KHRP24B22T 1 Refnet branch piping kit
KHRP26A22T 1 Refnet branch piping kit
BRC1E62 1 Wired Remote Controller (Navigation Remote
Controller)
BRC1E642 1 Wired remote controller
BRC63A622 1 Wired remote controller
BYCP125K-W1 1 Decoration panel
BYEKP28AY1E 1 Decoration panel
R410A 1.6kg Extra refrigerant charge
Piping ¼" 12.0m
Piping ⅜" 18.5m
Piping ½" 21.5m
Piping ⅝" 2.0m
Piping ¾" 7.5m

2. Indoor Unit Details


2.1. Table of Abbreviations
Name Logical name of the device
FCU Device model name
Tmp C Indoor conditions in cooling (dry bulb temp. / RH)
Rq TC Required total cooling capacity
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 1
Max TC Available total cooling capacity
Rq SC Required sensible cooling capacity
Max SC Available sensible cooling capacity
Tevap Evaporating temperature of indoor unit coil
Tdis C Indoor unit discharge air temperature in cooling
Tmp H Indoor temperature in heating
Rq HC Required heating capacity
Max HC Available heating capacity
Tdis H Indoor unit discharge air temperature in heating
Airflow Supplied airflow
Sound Sound pressure low and high
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
WxHxD WidthxHeightxDepth
Wght Weight of the device

2.2. Out 1 - RPZQ6AV1


Capacity data at conditions and connection ratio (69%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tdis C Tmp H Rq HC Max H
°C kW kW kW kW °C °C °C kW kW
Ind 1 FXFQ50LV14 25.0 / 55% n/a 5.5 n/a 3.9 6.0 13.2 n/a n/a n
Ind 2 FPRSQ25APV1 25.0 / 55% n/a 2.7 n/a n/a 6.0 11.7 n/a n/a n
Ind 3 FPEKQ28AV1 25.0 / 55% n/a 3.1 n/a n/a 6.0 11.3 n/a n/a n

Required cooling capacity towards the outdoor unit: 11.2kW.

The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest
temperature in case of heating mode), assuming the indoor unit is running at full load at the given indoor
temperature design conditions. In practice the discharge temperature will modulate based on actual capacity
requirements and during defrost mode (heating mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a
thermal comfort level.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
Ind 1 27-32 230V 1ph 0.3 840×246×840 20
Ind 2 29 230V 1ph 0.44 700×200×620 24
Ind 3 43 230V 1ph 0.6 555×280×540 19

Outdoor unit placed 4.0m below the indoor units.


The minimum connection ratio for this height difference is 50%.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 2
3. Outdoor Unit Details
3.1. Table of Abbreviations
Name Logical name of the device
Model Device model name
Tmp C Outdoor temperature in cooling
CC Available cooling capacity
Rq CC Required cooling capacity
Tmp H Outdoor conditions in heating (dry bulb temp. / RH)
HC Available heating capacity (integrated heating capacity)
Rq HC Required heating capacity
Piping Largest distance from indoor unit to outdoor unit
Bse Refr Standard factory refrigerant charge (5m actual piping length)
excluding extra refrigerant charge
For calculation of extra refrigerant charge refer to the databook
Ex Refr Extra refrigerant charge
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
WxHxD WidthxHeightxDepth
Wght Weight of the device

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 3
3.2. Outdoor Details
Name Model Comb Tmp C CC Rq CC Tmp H HC Rq HC
% °C kW kW °C kW kW
Out 1 RPZQ6AV1 69 32.0 14.6 11.2

Name Model Piping Refrigerant


m Type
Bse Refr Ex Refr
kg kg
Out 1 RPZQ6AV1 16.6 R410A 3.6 1.6

Name Model PS MCA WxHxD Wght


A mm kg
Out 1 RPZQ6AV1 230V 1ph 29.1 900×1345×320 104

4. Piping Diagrams
Pipes marked with * in the diagrams must be connected to the device with a reducing joint.

⅜"× ¾"
O u t1
R Z
P Q

7 ×

⅜"× ⅝
6 AV

m ½"
.5 [ *2

.0 m
" ×
2
½"
]
1

K H
R P

K H
3 .0
2 6 A
m
¼"[× 2
2 2

4 .0
T

m[ 2
¼"× "½ ×
R P
2 4 B
2 T
⅜"
2
]

"

F X
F Q
5
In 0
Ld
1 V
1 4
4.1. Piping Out 1
FP R
S Q
2
In 5
2 A
d P V
1
5 .0
m[ 2
]
¼"× ½
" ×⅜"

In d
3
F P
E Q
K 28 AV
1

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 4
5. Wiring Diagrams
P1P2 = Please select the cable type and size in accordance with the databook.
F1F2 = Please select the cable type and size in accordance with the databook.

L,N
Ou t1
R ZQP 6AV 1
INF 1,F 2
2 .1A9 1p h
F1, F2
Ind 1
P 1,P2
FX 50Q LV1 4L
,N 0.3 A1p hBRC

Ind 2 P ,P21 BRC 1E6 42


FPR Q2S 5AP 1V
1E6 2
5.1. Wiring Out 1
F1, F2 L ,N .40 4A1 ph
P 1,P2
Ind 3 63A 62
FPE Q2K 8AV 1L
F1, F2 ,N 0.6 A1p hBRC

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 5
6. Device Options
6.1. Indoor Unit Options
Model Description Used by
BYEKP28AY1E Decoration panel Ind 3 [FPEKQ28AV1]
BYCP125K-W1 Decoration panel Ind 1 [FXFQ50LV14]

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.