Presentation, Zelio Control - Measurement and

description control relays


Multifunction 3-phase control relays
RM22TA, RM22TU, RM22TR, and RM22TG

Presentation
RM22 Zelio multifunction control relays monitor the following functions on 3-phase
1 supplies:
Functions RM22TA RM22TU RM22TR RM22TG
Sequence of phases L1, L2, and L3
Phase failure with regeneration
Asymmetry
Undervoltage
2 Overvoltage and undervoltage
Function performed
Function not performed
RM22T●●●
Depending on the model RM22T●●● control relays:
b Accept different nominal 3-phase voltages: up to 480 V a
b Monitor their own power supply measured as a true rms value
3 b Are designed for clip-on mounting on DIN rail

They feature:
b Sealable cover to protect the settings
b Diagnostic button for load circuit testing
b Relay output status LED
b Fault detection indication LED

4 b Dial pointer LED indicator for relay power ON status


b Relay output On-delay or Off-delay
Applications
b Control for connection of moving equipment (site equipment, agricultural
equipment, refrigerated trucks)
b Control for protection of persons and equipment against the consequences of
reverse running (lifting, handling, elevators, escalators, etc.)
5 b Control of sensitive 3-phase supplies
b Protection against the risk of a driving load (phase failure)
b Normal/emergency power supply switching

Description
RM22TA RM22TU 1a  Voltage range selector switch

6 L1 L2 L3 L1 L2 L3 1b  Voltage range/On-Off delay selector


2  Time delay adjustment potentiometer Tt
3a  Asymmetry threshold setting
RM22TA31
200
208
RM22TU23
380
400
415 potentiometer Asym
1a 1a
440
220

3b  Undervoltage setting potentiometer <U


240 480

10 20 -8 -14

2 3b
-6 -16
5 25 <U
Tt -4 -18

0,1
10
30s
-2 -20%

3c  Overvoltage setting potentiometer >U


7
8

3a
12

Asym

4  Diagnostic button
Def Def
5 15%
R R

4 DIAGNOSTIC 4 DIAGNOSTIC

12 11 14 12 11 14

22 21 24 22 21 24

8 RM22TR RM22TG
L1 L2 L3 L1 L2 L3

RM22TR31 RM22TG20
200 200

1b
ON DELAY

DELAY

208 208
OFF

9
220 220
240 240
10 20
5 25
Tt
0,1 30s

8 14

3c
6 16
>U
4 18 Un
Def
2 20%
R
-8 -14 R

3b
-6 -16
<U
-4 -18

4
-2

4
-20%
DIAGNOSTIC DIAGNOSTIC

12 11 14 12 11 14

10 22 21 24 22 21 24

Un Green LED: indicates that supply to the relay is on


R Yellow LED: indicates relay output state
DEF Yellow LED: indicates fault detection

2 28614-EN
version: 1.1
Operation Zelio Control - Measurement and
control relays
Multifunction 3-phase control relays
RM22TA, RM22TU, RM22TR, and RM22TG

Operating principle
Multifunction 3-phase supply control relays monitor:
bb Own power supply
bb Correct sequencing of phases L1, L2, and L3
1
bb Fault signaling by LED
bb Phase failure, including in the case of voltage regeneration
bb Undervoltage from - 2…- 20 % of the supply voltage Un
bb Overvoltage from 2…20 % of the supply voltage Un
bb Asymmetry from 5…15 % of the supply voltage Un

Voltage switch operation:


2
vv Set the switch to 3-phase supply voltage Un.
vv The position of this switch is taken into account on energization of the device.
vv If the switch position is changed while the device is operating, all the LEDs flash
but the product continues to operate normally with the voltage selected at the time of
energization preceding the change of position.
vv If the switch is returned to the original position selected prior to the last
energization, the LEDs return to their normal state.
3
Phase + asymmetry control relay: RM22TA
bb The relay monitors its own supply voltage Un:
vv correct sequence of three phases

4
vv failure of at least one of the three phases (U measured < 0.7 x Un)
vv asymmetry adjustable from 5…15 % of Un
bb If a sequencing or phase failure fault is detected, the relay opens instantly.
bb If an asymmetry fault is detected, the relay opens at the end of the time delay set
by the user.
bb On energization of the device with a detected measured fault, the relay stays
open.

Function diagram 5
bb Functions:
vv Sequence of phases L1, L2, L3
vv Phase failure
vv Asymmetry Asym

Phase L1

Phase L2
L3
L2
6
Phase L3

Asymmetry
Hysteresis
0%

Relay R/R1/R2
Outputs Tt Tt 7
Tt: time delay after crossing of threshold (adjustable on front panel)

10

28614-EN 3
version: 1.1
Operation (continued) Zelio Control - Measurement and
control relays
Multifunction 3-phase control relays
RM22TA, RM22TU, RM22TR, and RM22TG

Operating principle (continued)


Phase + undervoltage control relays: RM22TU
1 bb The relay monitors its own supply voltage Un:
vv correct sequence of the three phases
vv failure of at least one of the three phases (U measured < 0.7 x Un)
vv undervoltage adjustable from - 2…- 20 % of Un
bb If a sequencing or phase failure fault is detected, the relay opens instantly.
bb If a voltage fault is detected, the relay opens instantly.
bb On energization of the device with a detected measured fault, the relay stays
2 open.
Function diagrams
bb Functions:
v Sequence of phases L1, L2, L3
v Phase failure

3
30 % Un 30 % Un 30 % Un

Phase L1 L3
Phase L2 L2
Phase L3
Relay R/R1/R2
Outputs

4 vv Undervoltage control <U


L1 L3
L2 L2
L3 L1
Hysteresis
Threshold <U

5
Phases L1/L2/L3

Relays R/R1/R2
Output Tt Tt

Tt: time delay after crossing of threshold

6 Phase + undervoltage/overvoltage control relay: RM22TR


bb The relay monitors its own supply voltage Un:
vv phase failure
vv undervoltage and overvoltage
bb An adjustable time delay, on crossing the thresholds, provides immunity to
transients, and prevents spurious triggering of the output relay.
bb If a voltage fault is detected, the relay opens at the end of the time delay set
7 On-delay or Off-delay by the user.
bb On energization of the device with a detected measured fault, the relay stays
open.
bb In the event of phase failure, the relay opens instantly.
Function diagrams
bb Functions:

8 v Phase failure
30 % Un 30 % Un 30 % Un

Phase L1

Phase L2
Phase L3
Relay R/R1/R2

9
Outputs

vv Overvoltage and undervoltage (Off-delay)


>U
Hysteresis
L1
L2

Hysteresis L3

10 <U
Phases L1/L2/L3

Relay R/R1/R2
Outputs Tt Tt

Tt: time delay after crossing of threshold (adjustable on front panel)

4 28614-EN
version: 1.1
Operation (continued), Zelio Control - Measurement and
references control relays
Multifunction 3-phase control relays
RM22TA, RM22TU, RM22TR, and RM22TG

Operating principle (continued)


Phase control relays: RM22TG
bb The RM22TG relay monitors:
vv correct sequencing of the three phases
1
vv total loss of one or more of the phases
bb When phase sequence and voltages are correct (> 183 V a), the output relays are closed
and the yellow LED is on.
bb When there is a sequencing fault or total loss of one or more phases (detected as soon as
one of the voltages drops below 100 V) the relay opens instantly and the LED goes off.
bb On energization of the device with a detected measured fault, the relay stays open. 2
Function diagram
bb Function:
vv Sequence of phases L1, L2, L3
vv Phase failure

Phase L1
100 %
3
0%
L3
100 %
Phase L2
0%
L2

4
100 %
Phase L3
0%

Relay R/R1/R2
Outputs
Tr Tr Tr Tr

Tr: response time on appearance of a fault


5
References
Function Rated 3-phase Measurement Time delay Output Reference Weight
supply voltage range
V V kg/lb
b Phase 200…240 a 200…240 a Off delay 2 C/O 8 A RM22TA31 0.090/

6
sequence (0.1...30 s) 0.198
b Phase failure
b Asymmetry

380…480 a 380…480 a Off delay 2 C/O 8 A RM22TA33 0.090/


(0.1...30 s) 0.198

b Phase
sequence
200…240 a 200…240 a On/Off delay 2 C/O 8 A
(0.1...30 s)
RM22TR31 0.090/
0.198
7
b Phase failure
b Undervoltage
RM22TA31 RM22TR31 and
overvoltage 380…480 a 380…480 a On/Off delay 2 C/O 8 A RM22TR33 0.090/
(0.1...30 s) 0.198

b Phase 200…240 a 200…240 a No 2 C/O 8 A RM22TU21 0.090/


8
sequence 0.198
b Phase failure
b Undervoltage

380…480 a 380…480 a No 2 C/O 8 A RM22TU23 0.090/

9
0.198

b Phase 208…480 a 183…528 a No 2 C/O 8 A RM22TG20 0.090/


sequence 0.198
RM22TG20 RM22TU21 b Phase failure

10

28614-EN 5
version: 1.1
Presentation, Zelio Control - Measurement and
description control relays
Liquid level control relays
RM22LA and RM22LG

Presentation
RM22LA and RM22LG liquid level control relays control one or two liquid levels, with
1 a fill or empty function:
Functions RM22LA 32MR/32MT RM22LG 11MR/11MT
Level 1/Level 2
Fill operation
Empty operation
Low sensitivity

2 Standard sensitivity
High sensitivity
Function performed
RM22LG11MR RM22LA32MT
Function not performed

RM22 liquid level control relays feature:


b A dial pointer LED indicator for relay power ON status
3 b A relay output status LED
The settings are protected by a sealable cover and the control status is indicated
by an LED. The relays are designed for clip-on mounting on a DIN rail.

Applications
These devices monitor the levels of conductive liquids.

4 They control the actuation of pumps or valves to regulate levels and are also
suitable for protecting submersible pumps against dry running, or protecting tanks
from “overflow”. They can also be used to control dosing of liquids in mixing
processes and to protect heating elements in the event of non-immersion.
They have a transparent, hinged cover on their front panel to avoid any accidental
alteration of the settings. This cover can be directly sealed.

5
b Application examples for compatible liquids:
v spring, town, industrial, and sea water
v metallic salt, acid, or base solutions
v liquid fertilizers
v non-concentrated alcohol (< 40 %)
v liquids in the food-processing industry: milk, beer, coffee, etc.

Description
6 RM22LG11MR RM22LG11MT 1  Configuration: selection of the
A1 A2 NC A1 A2 NC
operating mode (Fill or Empty) and the
sensitivity range (LS/St/HS)
Min Max C Min Max C 2  Sensitivity control potentiometer (kΩ or %)
RM22LG11MR RM22LG11MT
3  Configuration: selection of the number
of levels and theOn/Off time delay
7 1 1
4  Time delay control potentiometer Tt
40 60 40 60
30 70 30 70

2 2
Sens 80
20 Sens 20 80
10 90 10 90
5 100 KΩ 5 100 KΩ

3 Level
2 1 3 Level
2 1
5  Diagnostic button
R R

5 DIAGNOSTIC
5 DIAGNOSTIC

8
12 11 14 12 11 14

RM22LA32MR RM22LA32MT
A1 A2 NC A1 A2 NC

Min Max C Min Max C

9 1
RM22LA32MR
HS
St.
LS
LS
St.
HS
1
RM22LA32MT
HS
St.
LS
LS
St.
HS
40 60 40 60
30 70 30 70

2 2
Sens 20 80 Sens 20 80
10 90 10 90
5 100% 5 100%

3 3
1 1 1 1
DELAY
DELAY

DELAY
DELAY

OFF
OFF

Level Level
ON
ON

2 2 2 2

10 20 R 10 20 R

4 Tt 5 25
4 Tt 5 25

5 5
0,1 30s 0,1 30s

10
DIAGNOSTIC DIAGNOSTIC

12 11 14 12 11 14

22 21 24 22 21 24

R Yellow LED: indicates relay output state

2 28617-EN
version: 1.1
Operation Zelio Control - Measurement and
control relays
Liquid level control relays
RM22LA and RM22LG

Operating principle
Liquid level control relays are designed to measure and control the levels of con-
ductive liquids by means of resistive probes.
The operating principle is based on measurement of the apparent resistance of the
1
liquid between two submerged probes. When this value is less than the threshold
setting on the front panel of the device, the relay changes state. To avoid
electrolytic phenomena, an AC current runs across the probes.
A selector switch on the front panel allows selection of the required function and
the sensitivity range. Control of a single level can be achieved by using the second
selector switch. In this case, the Max. level probe stays up in the air and an adjust-
2
able time delay avoids any wave effect. Both products activate their output relay
when a tank is either emptying or filling.

Level control relays with adjustable sensitivity range

3
A selector switch on the front panel of these relays allows selection of the required
sensitivity range and the empty or fill function. A second switch allows selection of
the number of levels (1 or 2) and the type of time delay in the case of level 1 mode.
The position of these configuration switches is taken into account on energization.
b If the configuration switch is set to an unacceptable position, the product detects a
fault, the output relay stays open, and the LEDs flash to signal the position error.
b If the configuration switch position is changed while the device is operating, all the
LEDs flash, but the product continues to operate normally with the function selected
at the time of energization preceding the change of position.
b If the configuration switch is returned to the original position selected prior to the
4
last energization, the LEDs return to their normal state.

b Control of two levels, empty and fill function


vv Empty function
level: 2, function:
-- LS (Low Sensitivity: 250 W…5 kW) 5
-- St (Standard Sensitivity: 5 kW…100 kW)
-- HS (High Sensitivity: 50 kW…1 MW)
The output relay stays open until the liquid reaches the Max. level probe.
As soon as the Max. level is reached, the contact closes and then allows emptying
of the tank (valve opens, pump starts, ...). When the level drops below the Min.

6
level, the contact opens to stop the emptying process.
vv Fill function
level: 2, function:
-- LS (Low Sensitivity: 250 W…5 kW)
-- St (Standard Sensitivity: 5 kW…100 kW)
-- HS (High Sensitivity: 50 kW…1 MW)
The output relay stays energized until the liquid reaches the Max. level probe.
As soon as the Max. level is reached, the contact opens and the pump stops.
When the level drops below the Min. level, the contact closes again and
7
pumping re-starts to raise the level.

Function diagram
bb Fill/Empty function (2 levels)

Supply Un
8
Max. level

Min. level
Relay
Outputs R/R1/R2

Relay
Outputs
R/R1/R2 9

10

28617-EN 3
version: 1.1
Operation (continued) Zelio Control - Measurement and
control relays
Liquid level control relays
RM22LA and RM22LG

Operating principle (continued)


Level control relays with adjustable sensitivity range (continued)
1 bb Control of one level, empty function
vv level: 1 - on delay functions:
-- LS (Low Sensitivity: 250 W…5 kW)
-- St (Standard Sensitivity: 5 kW…100 kW)
-- HS (High Sensitivity: 50 kW…1 MW)

2 When the liquid level rises above the probe for a time greater than the time delay
value Tt set on the front panel, the relay is energized and stays energized until the
liquid level drops back to the probe.
If the liquid drops back below the set level before the end of the time delay, the relay
does not energize.
Function diagram

3
bb Empty function T on
Supply Un

Level

Relay
R/R1/R2
Outputs
Tt Tt Tt
4
bb Control of one level, empty function
vv level: 1 - off delay functions:
-- LS (Low Sensitivity: 250 W…5 kW)
-- St (Standard Sensitivity: 5 kW…100 kW)

5 -- HS (High Sensitivity: 50 kW…1 MW)

When the liquid level rises above the probe, the relay instantly energizes and stays
energized until the liquid again reaches the probe level for a time Tt set on the front
panel.
If the liquid drops back below the set level before the end of the time delay period,
the relay stays energized.

6 Function diagram
bb Empty function T off
Supply Un

Level

7 Relay
Outputs
R/R1/R2
Tt Tt Tt

bb Control of one level, fill function


vv level: 1 - on delay functions:
-- LS (Low Sensitivity: 250 W…5 kW)
8 -- St (Standard Sensitivity: 5 kW…100 kW)
-- HS (High Sensitivity: 50 kW…1 MW)

When the liquid level drops below the probe for a time greater than the time delay
value Tt set on the front panel, the relay is energized and stays energized until the
liquid level rises back up to the probe.
If the liquid rises back above the set level before the end of the time delay period, the
9 relay does not energize.
Function diagram
bb Fill function T on
Supply Un

10
Level

Relay
R/R1/R2
Outputs
Tt Tt Tt
Tt: time delay after crossing of threshold

4 28617-EN
version: 1.1
Operation (continued), Zelio Control - Measurement and
references control relays
Liquid level control relays
RM22LA and RM22LG

Operating principle (continued)


Level control relays with adjustable sensitivity range (continued)
vv level: 1 - off delay functions: 1
-- LS (Low Sensitivity: 250 W…5 kW)
-- St (Standard Sensitivity: 5 kW…100 kW)
-- HS (High Sensitivity: 50 kW…1 MW)

When the liquid level drops below the probe, the relay instantly energizes and stays

2
energized until the liquid level again reaches the probe level and stays above it for
a time greater than the time delay period Tt set on the front panel.
If the liquid drops back below the set level before the end of the time delay period,
the relay stays energized.

Function diagram
bb Fill function T off
Supply Un
3
Level

Relay R/R1/R2
Outputs
Tt Tt Tt

Tt: time delay after crossing of threshold 4


References
Function Rated supply Measurement Time Output Reference Weight
voltage range delay
V Ω kg/lb
b Level 1/
Level 2
24…240 z 5 K…100 K No 1 C/O 8 A RM22LG11MR 0.100/
0.220
5
b Fill
operation
b Empty
operation

380…415 a 5 K…100 K No 1 C/O 8 A RM22LG11MT 0.100/


0.220 6
RM22LG11MR RM22LG11MT

24…240 z 250...1 M On/Off 2 C/O 8 A RM22LA32MR 0.110/


delay
(0.1...30 s)
0.242
7

380…415 a 250...1 M On/Off 2 C/O 8 A RM22LA32MT 0.110/


delay 0.242
(0.1...30 s)
8
RM22LA32MR RM22LA32MT

10

28617-EN 5
version: 1.1
Presentation, Zelio Control - Measurement and
description control relays
1-phase or DC voltage control relays
RM22UA and RM22UB

Presentation
RM22UA and RM22UB 1-phase or DC voltage control relays monitor the following
1 functions:
Functions RM22 UA2●MR UA3●MR UA33MT UB34
Overvoltage (without memory)
Undervoltage (with/without memory)
Overvoltage (with/without memory)

2
Overvoltage or undervoltage
(windows mode)
Function performed
RM22UA21MR RM22UA31MR Function not performed

RM22 control relays enable:


b Automatic AC or DC recognition

3 b Selection between overvoltage and undervoltage


b Monitoring their own supply voltage measured as true rms value
b Selectable memory function

They feature:
b Dial pointer LED indicator for relay power ON status
b Relay output status LED

4 The settings are protected by a sealable cover and the control status is indicated
by an LED. The relays are designed for clip-on mounting on a DIN rail.

Applications
b Protection of electronic or electromechanical devices against overvoltage and
undervoltage
5 b Normal/emergency power supply switching
b DC motor overspeed control
b Monitoring of AC or DC supplies
b Battery and speed monitoring (with tacho-generator)

Description

6 RM22UA2●MR
A1 A2 M
RM22UA3●MR
A1 A2 M
1  Configuration: selection of operating
mode <U (undervoltage), >U
(overvoltage), >U> (overvoltage and
E1 E2 E3 E1 E2 E3
undervoltage), MEMORY - NO
MEMORY (with or without memory)
RM22UA23MR RM22UA31MR

1 2a  Voltage threshold setting potentiometer


>U > > U>
MEMORY

MEMORY
NO

>U >U
<U <U

40 70 40 70
U value
2c 2a
30 80

7
30 80
U
>U 20 90 Value 20 90
Value 10 100% 10 100%

20 35 20 35
2b  Undervoltage setting potentiometer <U
4a 4b
15 40 Hys/ 15 40
Hys
10 45 >U> 10 45

2c Overvoltage setting potentiometer >U


5 50% 5 50%
R 10 20 R

3 Tt 5 25

3  Time delay adjustment potentiometer Tt


0,1

5
30s

5 DIAGNOSTIC DIAGNOSTIC

4a Hysteresis adjustment potentiometer


12 11 14 12 11 14
Hys
4b  Hysteresis/overvoltage and
8
22 21 24 22 21 24

undervoltage window mode adjustment


potentiometer Hys/>U>
RM22UA33MT RM22UB34
A1 A2 M A1+ A2-
5 Diagnostic button
6 Configuration: selection of On-delay or
E1 E2 E3 Off-delay

9
RM22UA33MT RM22UB34

1 6
>U > > U>
MEMORY

DELAY
MEMORY

DELAY
OFF
ON
NO

>U >U
<U <U

40 70 160 220
140 240

2a 2c
U 30 80
>U 120 260
Value 20 90
100 280
10 100%
80 300V
20 35 160 220

4b 2b
15 40 140 240
Hys/
<U 120 260
>U> 10 45
100 280
5 50% 80 300V
10 20 R 10 20 R

3 Tt 5 25
3 Tt 5 25

5
0,1 30s

5
0,1 30s
DIAGNOSTIC DIAGNOSTIC

10 12 11 14 12 11 14

22 21 24 22 21 24

R Yellow LED: indicates relay output state

2 28615-EN
version: 1.1
Operation Zelio Control - Measurement and
control relays
1-phase or DC voltage control relays
RM22UA and RM22UB

Operating principle
1-phase or DC voltage control relays monitor:
bb the voltage of 1-phase and DC supplies
bb their own supply voltage for the RM22UB model
1
An adjustable time delay, on crossing the thresholds, provides immunity to
transients, and prevents spurious triggering of the output relay.

Overvoltage + undervoltage control relays with/without memory: RM22


UA2●MR/ UA3●MR/UA33MT
The operating mode is fixed by the user:
2
bb Undervoltage with or without memory
bb Overvoltage with or without memory

The position of the configuration switch and the operating mode is read by the
product on energization:
bb If the configuration switch is set to an unacceptable position, the product detects
a fault, the output relay stays open, and the LEDs flash to indicate the position error. 3
bb If the configuration switch position is changed while the device is operating, all
the LEDs flash, but the product continues to operate normally with the function
selected at the time of energization before position change.
bb If the configuration switch is returned to the original position selected prior to the
last energization, the LEDs return to their normal state.

The undervoltage or overvoltage threshold value is set by means of a 4


potentiometer graduated as a percentage of the scale value of U to be monitored.
The hysteresis is adjusted by means of a potentiometer graduated from 5…50 %
of the threshold setting. The hysteresis value must not exceed the limit values of
the measuring range.

bb Overvoltage without memory


If the voltage controlled exceeds the threshold setting for a time greater than that 5
set on the front panel (0.1…30 s), the output relay opens and LED R goes off.
During the time delay, this LED flashes.
As soon as the voltage drops below the value of the threshold setting minus the
hysteresis, the relay instantly closes.

bb Undervoltage without memory


If the voltage controlled falls below the threshold setting for a time greater than 6
that set on the front panel (0.1…30 s), the output relay opens and LED R goes off.
During the time delay, this LED flashes.
As soon as the voltage rises above the value of the threshold setting plus the
hysteresis, the relay instantly closes.

7
bb Overvoltage/undervoltage with memory
If “Memory” mode is selected, the relay opens when crossing of the threshold is
detected and then stays in that position. The power must be switched off to reset
the product.
Function diagram
bb Function: Overvoltage control > U
vv Without memory
Supply Un 8
Threshold >U
Hysteresis
U
Relay R/R1/R2
Outputs
Tt
9
vv With memory
Supply Un

Threshold >U
Hysteresis

Relay R/R1/R2
U
10
Outputs
Tt

Tt: time delay after crossing of threshold

28615-EN 3
version: 1.1
Operation (continued) Zelio Control - Measurement and
control relays
1-phase or DC voltage control relays
RM22UA and RM22UB

Operating principle (continued)


Overvoltage + undervoltage control relays with/without memory: RM22
1 UA2●MR/ UA3●MR/UA33MT (continued)
Function diagrams (continued)
bb Function: Undervoltage control < U
vv Without memory
Supply Un

U
2 Hysteresis
Threshold <U

Relay R/R1/R2
Outputs
Tt

vv With memory

3 Supply Un

Hysteresis
U
Threshold <U

Relay
R/R1/R2
Outputs
Tt

4 Tt: time delay after crossing of threshold

Overvoltage + undervoltage control relay in window mode: RM22 UA3●MR/


UA33MT/UB34
These relays operate in window mode where they check that the voltage controlled
5 stays between a minimum and a maximum threshold.
bb The undervoltage or overvoltage threshold values are set by means of two
graduated potentiometers clearly indicating the Un to be monitored. The hysteresis
is fixed at 5 % of the threshold setting.
bb If the voltage controlled exceeds the high threshold setting or falls below the low
threshold setting for a time greater than that set time on the front panel (0.1…30 s),
the output relay opens and LED R goes off. During the time delay, this LED flashes.
6 bb As soon as the voltage falls below the high threshold setting value minus the
hysteresis, or rises above the low threshold setting value plus the hysteresis, the
relay instantly closes.
bb On energization of the device with a detected measured fault, the relay stays
open.

Function diagrams

7 bb Functions: Overvoltage and undervoltage control in window mode <U<


Supply Un

Threshold >U
Hysteresis
Hysteresis U
8 Threshold <U
Relay R/R1/R2
Ouputs Tt Tt
Tt: time delay after crossing of threshold

10

4 28615-EN
version: 1.1
References Zelio Control - Measurement and
control relays
1-phase or DC voltage control relays
RM22UA and RM22UB

References
Function Rated supply Measurement Time delay Output Reference Weight
voltage
V
range
V kg/lb
1
b Overvoltage 24…240 z 0.05…5 z No 2 C/O 8 A RM22UA21MR 0.110/
without memory 0.242

24…240 z 1…100 z No 2 C/O 8 A RM22UA22MR 0.110/


0.242
2
24…240 z 15…500 z No 2 C/O 8 A RM22UA23MR 0.110/
0.242

RM22UA23MR RM22UA33MR b Overvoltage and 24…240 z 0.05…5 z Off delay 2 C/O 8 A RM22UA31MR 0.110/
undervoltage with/ (0.1...30 s) 0.242
without memory
b Overvoltage and
undervoltage with 24…240 z 1…100 z Off delay 2 C/O 8 A RM22UA32MR 0.110/
3
memory window (0.1...30 s) 0.242

24…240 z 15…500 z Off delay 2 C/O 8 A RM22UA33MR 0.110/


(0.1...30 s) 0.242

380…415 a 15…500 a Off delay 2 C/O 8 A RM22UA33MT 0.110/


4
(0.1...30 s) 0.242

b Overvoltage and 110…240 z 80…300 z On/Off delay 2 C/O 8 A RM22UB34 0.090/


undervoltage (0.1...30 s) 0.198
RM22UA33MT RM22UB34 without memory

10

28615-EN 5