X = 00,00 t Press & to enter the OFF LINE menu from the main
L = 63,56 % program.
Password
Enter 4 digit password which is stored in the configuration and
Enter password : press to access the OFF LINE menu
Password
Enter password : Y If TUC shows “Y” the password is correct. Password is wrong
it shows “N”. If password is wrong again go to password menu
to enter the correct password. If password is correct press
to go to CALIBRATION menu.
CALIBRATION LOAD LHS counts (auto) w.r.t load cell mV & RHS counts determined
the calibration percentage. LHS counts will increase w.r.t to
0000 => 0000 d
increment of the mV from Tare mV. After study state of
counts enter the “d” counts in RHS w.r.t to calibration
CALIBRATION LOAD percentage. Press to complete the calibration & close the
Keep the test
2756 => 15000 d weight on the bin calibration menu.
Note: 1% calibration = 20 d counts
SYSTEM DATA Press to run the main program while main program menu
MAINPROGRAM in bottom line.
X = 00,00 t Press & to enter the OFF LINE menu from the main
L = 63,56 % program.
Password
Enter 4 digit password which is stored in the configuration and
Enter password : press to access the OFF LINE menu
Password
If TUC shows “Y” the password is correct. Password is wrong
Enter password : Y
it shows “N”. If password is wrong again go to password menu
to enter the correct password. If password is correct press
to go to CALIBRATION menu.
TARE MV
Enter the Tare mV, which is generated by the load cell w.r.t
2.125 bin dead weight. Press proceed the span mV calibration.
SYSTEM DATA
Press to run the main program while main program menu
MAINPROGRAM in bottom line.