COATED INSULATION

DIAMOND PATTERN PAPER


A DENNISONTM Product

OIL COMPATIBILITY:

The coated paper is compatible with transformer oil when thermally aged and tested per ASTM D3455.
This procedure includes tests for dissipation factor, neutralization number, interfacial tension and
dielectric strength.

BONDING:

The coated paper shall bond firmly and evenly to a conductor or other insulation provided that there is
adequate time, temperature and contact.

BOND TEST: A sample specimen is prepared by using two strips of clean and flattened
aluminum or copper 0.015 to 0.030 inch (.38 to .76 mm) thickness and 2 inches (51 mm) by 6
inches (152 mm) in size; sandwiched on top of four layers of 2 inch (51 mm) squares of coated
paper and then bonded at 2 PSI, 120 C for 1 hour.

The bonded samples are then tested for tensile shear at 100 C with a pull rate of 6 inches (152
mm) per minute and must achieve a shear strength of 40 PSI minimum average; 30 PSI
minimum individual based on 3 samples each.

SHELF LIFE:

When stored in a controlled atmosphere, the "B Stage" coated paper will have an extended shelf life. For
paper stored in normal warehouse conditions, out of direct sunlight and away from direct moisture, we
recommend that it be used within 12 months.

PACKAGING:

Coated paper is supplied in sheets or rolls. Rolls are wound on a 3 inch (76 mm) ID core and wrapped
with a poly lined kraft paper (moisture barrier). Rolls are packaged vertically on pallets and banded
vertically and horizontally.

LABELING:

Each roll is marked to the customer specification.

RETENTION OF BURSTING STRENGTH:

Initial Bursting Strength is determined per ASTM D202, using Model C tester for thicknesses 0.005 and
0.007 inch (0.127 & 0.178 mm) and Model A tester for thicknesses 0.010 and 0.015 inch (0.250 & 0.380
mm).

Permissible changes in the Bursting Strength after aging in oil is measured per ASTM D774.

THERMAL UPGRADING CONTENT:

1.5 to 2.0% Nitrogen Content by weight when using approved thermal upgrading chemicals per ASTM
D982 or other methods approved by purchaser. Thermal upgrading content is 1.5 times organic nitrogen
content.
TYPICAL VALUES
Caliper: (inch) 0.003 0.005 0.007 0.010 0.015 0.020
(millimeter) 0.075 0.125 0.175 0.250 0.380 0.500
Basis Weight:
lbs. per 3000 sq.ft. 46 80 110 160 230 310
Apparent Density: .9 to 1.1, all thicknesses
Moisture Content, % 4.0 to 7.0%, all thicknesses
pH Water Extract: 6.0 to 8.0, all thicknesses
Ash Content, % 1% Maximum
Nitrogen Content: 1.5% to 2.0%, Coleman, by weight
Tear Strength, grams/inch,
Machine Direction: 60 120 200 300 500 750
Cross Machine Direction: 85 180 240 400 650 850
Tensile Strength, lbs./inch,
Machine Direction: 45 85 100 160 200 250
Cross Machine Direction: 15 20 25 40 80 120
Mullen Burst Strength:
45 90 120 175 275 330
(lbs./inch square)
Dielectric Breakdown*:
900 1,300 1,700 2,100 3,000 3,300
(Volts, Dry Test)
Dielectric Breakdown*:
5.5 8.5 10.5 14.0 20.0 23.5
(Kilovolts, Oil Test)
Bond Strength: Minimum 40 psi shear strength, tested at 100 degrees C.

*Dielectric Values Based on Tests Made According to ASTM D-202, Section 143

All data shown represents Nominal, or Typical Values only and should not be construed
as minimum or maximum values unless specifically stated.

WEIDMANN SYSTEMS INTERNATIONAL A Member of the WICOR Group

Neue Jonastrasse 60 One Gordon Mills Way, PO Box 799 Unit 3, 15/F, The Center
CH-8640 Rapperswil, Switzerland St. Johnsbury, VT 05819-0799 USA 99 Queen’s Road Central, Hong Kong
Phone 41 55 221 4630 Phone 802 748 3936 Phone 852 2799 2199
Fax 41 55 221 4631 Fax 802 748 8630 Fax 852 2795 8984
e-mail wsi.sales@weidmann-systems.ch e-mail service@weidmann-systems.com e-mail customer.service@weidmann.com.hk
www.weidmann-systems.com

ipaa0103

You might also like