Load Analysis For Dabhol RT & Sv/Ip Stations Along Panvel-Dabhol Pipeline Gail (India) Limited
Load Analysis For Dabhol RT & Sv/Ip Stations Along Panvel-Dabhol Pipeline Gail (India) Limited
0318-00-16-50-4701
Page 1 of 4
Rev. No. A
LOAD ANALYSIS
FOR DABHOL RT & SV/IP STATIONS ALONG
PANVEL-DABHOL PIPELINE
GAIL(INDIA) LIMITED
(a) 24V power source i.e.TEG(n+1)/CCVT(1+1) configuration along with battery back-up for
24hours has been considered for meeting the power requirements at the unmanned
stations.
(b) Air conditioning load has not been considered for SV/IP stations.
(c) Air conditioning load is considered only for Control room building at Dabhol.
(d) 24V DC(Floating) 1 no.feeder for Telecom and 1 no.feeder for SCADA shall be provided
at each SV/IP station. Any DC-DC conversion as required shall be in respective
Telecom/SCADA equipment to be supplied & installed by GAIL separately.The efficiency
of dual redundant DC to DC converters ito be provided in SCADA/Telecom equipment is
assumed as 0.7 in power source sizing calculations.
On Power source:-
On Battery:-
(a) New building has been considered at Receipt Terminal at Dabhol. As such
indoor/outdoor lighting, air conditioning loads, etc. have been considered. Power
requirement is envisaged to be met through 2 nos.415V, TPN feeders from existing
power system of LNG Terminal at Dabhol.
CP system(AC
1 UPS load) 0.15 0.15 0.8 0.188 0.75 0.25 0.165
Instt.load at
230V AC (AC
2 UPS load) 1.6 1.6 0.8 2 0.8 2.5 1.5
Instt.Non UPS
3 load 0.4 0.4 0.8 0.5 0.75 0.667 0.441
4 SCADA Load 0.2 0.2 0.8 0.25 0.56 0.446 0.37
Telecom load
at 230V AC
5 (AC UPS load) 1.5 0.4 0.8 0.5 0.8 0.625 0.375
Non UPS
6 Telecom load 0.4 0.4 0.8 0.5 0.75 0.667 0.441
Fire alarm
load(AC UPS
7 load) 0.15 0.15 0.8 0.188 0.8 0.234 0.141
8 Lighting load 5 5 0.8 6.25 0.9 6.944 3.027
Air
conditioning
9 load 35 35 0.8 43.75 0.8 54.69 32.81
UPS battery
charging
load(Consideri
ng 100AH
battery, 291
10 cells) 12 12 0.8 15 0.9 16.67 7.265
TOTAL 56.4 0 69.13 46.54
Electrical Load Assessment:-
Maximum normal running load/Load demand(In terms of KVA) 83.33
Considering 10% margin maximum load demand(In terms of KVA) 91.66
i.e. 92 kVA