GENERAL NOTES

1. ALL ELECTRICAL WORKS HEREIN SHALL COMPLY WITH THE LATEST EDITION OF THE
PHILIPPINE ELECTRICAL CODE, THE RULES AND REGULATIONS OF THE LOCAL UTILITY
COMPANY AND THE LAWS AND ORDINANCES OF THE LOCAL ENFORCING AUTHORITIES
CONCERNED. THE ELECTRICAL WORKS SHALL BE UNDER THE IMMEDIATE SUPERVISION
OF COMPETENT DULY LICENSED ELECTRICAL ENGINEER AND REGISTERED MASTER
ELECTRICIAN.
2. POWER SERVICE ENTRANCE VOLTAGE SHALL BE 230V, 60HERTZ, SINGLE PHASE, 3 WIRE
AS SHAWN ON DRAWING.
3. MINIMUM SIZE OF CONDUCTOR AND CONDUIT TO BE USED SHALL BE 3.5mm2 TYPE
THHN STRANDED AND 15mm NOMINAL DIAMETER Ø, RESPECTIVELY.
4. ALL PIPE SLEEVES SHALL BE PROVIDED WITH PROPER SUPPORT OR ANCHORAGE
NECESSARY FOR PERMANENT CONNECTIONS WITH CONCRETE WALLING OR BEAMS.
5. ALL SERVICE ENTRANCE EQUIPMENT, SWITCHES, PANELBOARDS, LIGHTING FIXTURES
AND ALL NON-CURRENT CARRYING METAL PARTS SHALL BE PROPERLY GROUNDED IN
ACCORDANCE WITH THE LATEST EDITION OF PHILIPPINE ELECTRICAL LOAD.
6. SERVICE ENTRANCE CONDUIT SHALL BE IN RIGID STEEL CONDUIT.
7. NO BRANCH CIRCUIT, POWER AND SPECIAL OUTLET SHALL HAVE A LOAD MORE THAN
80% OF ITS RATING.
8. UNLESS OTHERWISE SPECIFIED, PULL BOXES OR JUNCTION BOXES SHALL BE PROVIDED
WHENEVER REQUIRED AND NECESSARY, ALTHOUGH SUCH BOXES ARE NOT INDICATED
ON PLANS.
9. ALL MATERIALS TO BE USED AND EQUIPMENT TO BE INSTALLED SHALL BE BRAND NEW
AND MUST BE ON THE APPROVED TYPE AND MODEL. ALL DISCREPANCY IN LOCATIONS
AND RATINGS OF EQUIPMENT AND APPARATUS SHALL BE VERIFIED WITH THE OWNER
OR HIS REPRESENTATIVES AND THEN CHANGES SHALL BE MADE ACCORDINGLY.
10. ALL CONVENIENCE OUTLET SHOULD BE 3-PRONG TYPE, PROVIDED WITH GROUNDING
TERMINAL. ALL EXTERIOR CONVENIENCE OUTLET SHOULD BE WEATHERPROFF ‘CROUSE-
HINDS’ BRAND.