Professional Documents
Culture Documents
General Description: Click For Detailed Diagram Collection and Mixing of Outdoor Air and Air From The Building
General Description: Click For Detailed Diagram Collection and Mixing of Outdoor Air and Air From The Building
The air handling unit is an integrated piece of equipment consisting of fans, heating and cooling
coils, air-control dampers, filters and silencers. The purpose of this equipment is to collect and
mix outdoor air with that returning from the building space. The air mixture is then cooled or
heated, after which it is discharged into the building space through a duct system made up of
five-feet diameter pipes.
1. Collection and Mixing of Outdoor Air and Air from the Building
2. Heating and Cooling System for the Air Handling Unit
1. Heating System
1. Steam Heated Coil
2. Baseboard Radiators
3. Reheat Coils
4. Solar Radiation and Heat Generated by the Equipments and the Building's
Occupants
2. Cooling System
1. Direct Evaporative Cooling
2. Indirect Cooling
3. Economiser or Free Cooling
Collection and Mixing of Outdoor Air and Air from the Building
plot no 0x002
24hr 72 http://blt.itll.cu.int/
The mixed air is filtered before entering the supply fan. The airfoil type centrifugal supply fan
pushes the air through the heating and cooling stages of the AHU. The air is then distributed
through a system of ductwork to all areas of the building.
The main energy source for heating the ITLL is the main power plant on campus. Burning
natural gas to boil water, the plant provides steam to the ITLL building. The heating coil in the
AHU uses steam made by a heat exchanger in the ITLL mechanical room.
The ITLL building is heated in different ways: the steam heated coil in the main AHU, the
baseboard radiators, reheat coils in the ducts, solar radiation and building equipment and
occupants.
a. Steam Heated Coil
b. Baseboard Radiators
c. Reheat Coils.
d. Solar Radiation and Heat Generated by Building Equipment and Occupants
The Steam Heated Coil in the Main Air Handling Unit (AHU)
Baseboard Radiators
Reheat Coils
In the early fall, before the cooling system has been shut down for the season, cool air is still
being supplied to the rooms. The reheat coils re-heat the air before it enters rooms which may
require heating. This way, other rooms in the building with high heat gain from equipment and
occupants can continue to be cooled. It may seem like a waste of energy to cool the air in the
AHU and then reheat it, but outside air from outside must be continuously supplied during
occupied hours to maintain acceptable air quality.
Rooms with more people and equipment require less additional heat to keep the room warm.
Individual thermostats (e.g. Room 160) detect this temperature rise and reduce the heating to
such rooms.
Cooling System
Although there is no local cooling for any of the rooms except the computer rooms, the variable
air volume (VAV) system allows different amounts of cooling in each zone (rooms or areas
sharing a single thermostat).
Indirect Cooling
A drip pan piped to drain below the indirect cooling coil carries away any moisture which may
collect on the coil when the air is dehumidified. The fluid cooler also requires low outside air
humidity to function, since it cools the glycol solution through evaporation of water on the
outside of its cooling coil. Because of this, these systems are not used in climates where high
humidity conditions occur.
Operations
The main air handler unit serving the ITLL building is of the variable air volume (VAV) type.
This means that as the overall building airflow requirements increase or decrease, the main fans
in the air handler speed up and slow down, to provide only as much air as is required.
Due in part to special variable speed motor controllers used to control the fan speeds, the initial
costs of installing a VAV system are somewhat higher than a traditional constant volume system.
However, the money saved when these big fans are running below maximum speed quickly pays
off.
The pre-programmed Direct Digital Control (DDC) system operates the equipment differently
during occupied and unoccupied periods. This is another energy-saving strategy which allows
the air conditioning equipment to "rest" during periods when the building is unoccupied.
Many sensors installed in the air handler give the DDC system the information it needs to control
the fans, dampers, etc.
a. System Operation during Occupied Periods
b. System Operation during Unoccupied Periods
c. General System Operation during All Modes
The (adjustable) discharge air temperature setpoint is reset based on the outside air temperature
(99 Outside.Air.Temperature.1) (OAT) according to the following schedule:
For an OAT of 55°F (12.77°C), the discharge air temperature is 55°F (12.77°C).
For an OAT of 20°F (-6.66°C), the discharge air temperature is 65°F (18.33°C).
Supply Fan
Return Fan
0x002 24hr 96
Whenever the supply fan is running, the return fan
also operates (113 Return.Fan.Status.2) and its speed (86 Return.Air.Flow.Rate) is controlled to
plot
maintain 0.10 in. static pressure (109 Return.Static) in the return air plenum.
no 0x002 24hr 92
It is virtually impossible to have a situation that when the building requires cooling on a hot day,
the economizer heating activates; this is not, therefore, part of the control system programming.
This section consists of a two honeycomb type porous pads (4 in. and 8 in. thick) over which
water is sprayed by the two sump pumps. When air is blown through the holes, some of the water
evaporates and cools the air stream in the same way sweating cools the body on a breezy day.
Sump Schedule
If the outside air temperature drops below 40°F (4.44°C), the water sump is drained; it is filled
when the outside air temperature rises above 55°F (12.77°C), and the evaporative cooler is
needed to meet the cooling requirements. The sump is drained on Sunday mornings, if it has not
been drained for the previous 4 days, while a daily 60-minute pad dry-out period runs from 5
a.m. to 6 a.m. if the cooler has not been off for at least one hour in the last 24 hours.
Sump Pumps
The sump pumps cycle in sequence (pump #1 to 4 in. pad, pump 2 to 8 in. pad, and both pumps
on) to maintain the AHU air discharge temperature setpoint; minimum on-off cycle timers
prevent the pumps from short-cycling. To allow the evaporative cooler discharge temperature to
stabilize, a 10-minute time delay between pump stages is used. The pumps only operate if the
outside air damper is completely open, the supply fan is still running and the sump has been
filled.
Humidity Control
The fans are de-energized, the outside air and exhaust air dampers are closed and the steam coil
control valve is opened to the coil.
Baseboard Radiators
The radiation heating valves are controlled to maintain a temperature of 65°F (18.33°C) in each
zone. If this temperature drops below 63°F or 17.22°C (with a 5°F or 2.77°C deadband), the
AHU cycles on to maintain the zone temperature using supply air at a maximum temperature of
85°F (29.44°C).
A thermostat stops the supply fan, starts the return fan, starts the condenser water pump, opens
the control valves to the heating coil and indirect cooling coil and closes the outside air damper if
it senses an outside air temperature below 40°F (4.44°C). Glycol solution is circulated in the
cooling coil during this time to prevent the solution from freezing in the coil.
Smoke Detectors
Smoke detectors located at the supply duct in the air handling unit act to stop the supply and
return fans and close the outside air, exhaust air and smoke dampers if smoke is detected. These
detectors are integrated with the fire alarm system.
Technical Specifications
The Fan coil unit Compact option simulates a 4 pipe fan coil unit with hot water heating coil,
chilled water cooling coil, and an outside air mixer. The fan coil units are zone equipment units
which are assembled from other components. Fan coils contain an outdoor air mixer, a fan, a
simple heating coil and a cooling coil. The fan coil unit is connected to a hot water loop (demand
side) through its hot water coil and to a chilled water loop (demand side) through its cooling coil.
The unit is controlled to meet the zone (remaining) heating or cooling demand. If there is a
heating demand, the cooling coil is off and the hot water flow through the heating coil is throttled
to meet the demand. The hot water control node must be specified (same as the hot water coil
inlet node) as well as maximum and minimum possible hot water volumetric flow rates. If there
is a cooling demand from the zone, the hot water coil is off and the chilled water flow through
the cooling coil is throttled to meet the load.
You can model Fan coil unit systems with or without outside air. If you include Mechanical
ventilation with your Fan coil unit system then heating and cooling will only operate when the
Mechanical ventilation operation schedule is on.
If you do not want to include outside air in your system, you should uncheck the Mechanical
ventilation 'On' check box. In this case heating/cooling availability is determined entirely from
the heating/cooling operation schedules under the Heating and Cooling headers.
Unlike the Unitary multizone and CAV and VAV Compact HVAC types, Fan coil unit zone
systems take all their data from the zone level.
Note 1: Fan coil supply fans run continuously at full speed whenever the availability schedules are > 0 so
fan coil outside air flow can be 'fully on' or 'fully off' but cannot reduce to fractional values in between. You
may therefore get higher outside air delivery rates than with other systems if you are using Schedules and
your Mechanical ventilation operation schedule has fractional values.
Limitations
1. Fan coil units cannot be used in the same simulation as Unitary multizone Compact
HVAC type.
2. Outside air flow rate is either off, or on at a fixed flow rate depending on the value of the
Fan operation schedule..
3. Fan coil units cannot incorporate economisers and variable speed fans.
Technical EnergyPlus
EnergyPlus needs both the heating coil and cooling coil to be defined so even if heating or
cooling is not selected in the input, DesignBuilder will schedule the appropriate coil to be off to
mimic a 2-pipe system.