Feeder Motor Protection Relay VAMP 40 PDF
Feeder Motor Protection Relay VAMP 40 PDF
Protection Relay
VAMP 40
Feeder/Motor Protection Relay
2
Measurement and Functionality
Monitoring Functions Protection functions
IEEE no IEC symbol Function name
The VAMP 40 offers a complete set of measurement 50/51 3I>, 3I>>, 3I>> Overcurrent protection
50N/51N I0>, I0>>, I02>, I02>> Earth fault protection
functions to replace the conventional metering 67N Iϕ>, Ioϕ>> Directional earth fault protection (1
functions of traditional switchgear and control REF I0REF Restricted earth fault protection
gear installations. The measurement functions 46 I2 / I 1 > Broken conductor protection
46 I2 > Unbalance protection
cover currents, residual or phase to phase or phase 47 I2 >> Phase reversal /
to earth voltages. The voltage measurement vary incorrect phase sequence protection
48 Ist> Stall protection
according to the connected voltage that is either 66 N> Frequent start protection
residual voltage (U0 ), phase to earth voltage 37 I< Undercurrent protection
(UL1) or phase to phase voltage (U12) 49 T> Overload protection
32 P Reverse power, 1 phase
connection. The measured information can be read 59N U0>, U0>> Residual voltage protection (1
via the communication bus or display. 59 U>, U>>, U>>> Overvoltage protection, 1-phase (2, (4
27 U<, U<<, U<<< Undervoltage protection, 1-phase (2, (4
Besides the measurement functions VAMP 40 also 68 2.ha Second harmonic stage /inrush
encompasses a set of system supervision functions. 79 Auto reclose function
50BF CBFP Circuit-breaker failure protection
All current circuits are continuously supervised, 50AR ArcI> Arc fault protection (3, (4
as are the trip circuits from the relay to the circuit Capacitor bank unbalance protection
86 Latched trip
breaker trip coils. The wear and tear of the circuit Programable stages 1 … 8
breaker is also continuously monitored providing
Measurement and monitoring functions
an alarm when the circuit breaker needs mainte-
3I Three-phase current
nance. lo Neutral current
I2 Current unbalance
IL Average and maximum demand current
Uo Residual voltage
Power Quality UL1 / U12
P
Q
Phase to earth and phase to phase voltages (2, (4
Active power (2, (4
Reactive power (2, (4
Assessment S
E +, E -
Apparent power (2, (4
Active energy, exported / imported (2, (4
Eq +, Eq - Reactive energy, exported / imported (2, (4
The power quality of electrical networks has PF Power factor
f System frequency
become increasingly important in modern society. Phasor diagram views of currents,
Sophisticated loads, such as computers and residual (1 or phase or line voltages (2
automation systems, require an uninterrupted 2nd to 15th harmonics and THD of currents
Condition monitoring CB wear
supply of “clean” electricity. Condition monitoring CT supervision
Trip Circuit Supervision (TCS)
The VAMP 40 feeder and motor protection relay is Disturbance recorder
provided with integrated power quality measuring Temperature
and analyzing functions, which help catching CB control
possible variations in the quality of the distributed Communication
power. The relay supervises harmonics of phase IEC 60870-5-103
currents and one voltage from the 2nd to 15th order Modbus TCP
Modbus RTU
and the THD (Total Harmonic Distortion). Profibus DP
SPA-bus
DNP 3.0
Many functions in modern society rely heavily on DNP 3.0 TCP
electric energy and therefore the quality of the energy Human Machine Interface, display
supply is gaining increased importance Human Machine Interface, PC
Migration path to IEC 61850 (4
Hardware
Number of phase current CT’s 3
Number of residual current CT’s 2
Number of voltage input VT’s 1
Number of digital inputs 2
Number of trip outputs 4
Number of alarm outputs 1
Internal Failure, IF (NO/NC) 1
RTD inputs 4-16 (3
1) with residual voltage connection
Example of harmonics content 2) with phase to phase or phase to earth voltage connection
obtained from a VAMP 40 relay. 3) option 4) future software release
3
Feeder/Motor Protection Relay
Arc Protection
Whether the time-grading or blocking based protection measure light via arc sensor channels monitoring the
coordination principle is used, the traditional pro- whole switchgear. Should an arcing fault occur in the
tection systems may not provide fast enough protection switchgear the arc protection system provides an
of substation faults. Further, high-impedance type of extremely fast tripping of the circuit breaker.
earth-faults may cause prolonged operation times of
earth-fault relays leading to the significant release of
the arcing energy. These facts pose a considerable risk Traditional protection relay systems
to human beings and economical assets. By applying do not provide fast enough
protection in an arc-fault situations.
a modern, high-speed arc protection system the damage
may be considerably reduced. Such an arc protection The VAMP 40 protection relay with
system is an optional feature incorporatable in all integrated arc protection also
provide a cost efficient high-speed
current measuring VAMP relays. MV busbar protection.
The VAMP relays measure the fault current. If the arc
protection interface option is selected the relays also
As a regular
feature of the
VAMP relays
The phase sequences for
standard
currents and residual
COMTRADE type
voltages can be read on-
disturbance
line from the clear and
recording files can
explicit screen windows for
be uploaded for
easy commissioning of the
subsequent
relay system.
evaluation of any
network event
recorded.
4
Connection Diagrams
Connection for L1
overcurrent, L2
directional earth L3
fault and +
1 -
residual voltage
protection
X2:15 ~ VAMP40 - 0
Protection functions X1
Front
X2:16
50/51 67N 50N/51N
X4
I> Remote
3I> I>
0
0
I>>
0
3I>> I>>
0
X6:1
IL1 3I>>> X2:14
X6:2 T1
X2:13
X6:3 +
X6:4 IL2
59N T2 X2:12
U>0
X2:11
X6:5 U>0 +
IL3
T3 X2:10
X6:6
X2:9
X6:7
I01 50AR 48 50BF
T4 X2:8
X6:8 5A
ArcI> Ist> CBFP X2:7
*
1A
X6:9
X6:10 49 47 37
I02
X6:11 1A
0.2A
T> I2>> 3I< A1 X2:4
X6:12 X2:6
46 66 X2:5
X6:13
U0 U0/UL1/U12 I>
2 If2> N
>
X6:14
79
VAM 255 AutoReclose IF X2:1
P X2:3
X2:2
Autorecloser Blocking and
matrix output matrix
X9:1DI1+
X9:2DI1- DI
-
X9:4DI2+
X9:5Di2-
-
Connection for L1
overcurrent, L2
phase to phase L3
or phase to earth +
voltage 1 -
protection
X2:15 ~
VAMP40 - 0
Protection functions X1
Front
X2:16
50/51 50N/51N
X4
I> Remote
3I> 0
I>>
0
3I>>
X6:1
IL1 3I>>> X2:14
X6:2 T1
X2:13
X6:3
59
+
X6:4 IL2 U
27 T2 X2:12
U
X2:11
X6:5
>
U>
<
U<
+
IL3 > < T3 X2:10
X6:6 U>> U<<
> < X2:9
X6:7
I01 50AR 48 50BF
T4 X2:8
X6:8 5A
ArcI> Ist> CBFP X2:7
*
1A
X6:9
X6:10 49 47 37
I02
X6:11 1A
0.2A
T> I2>> 3I< A1 X2:4
X6:12 X2:6
46 66 X2:5
U12 X6:13 U0/UL1/U12 I>
2 If2> N
X6:14 >
79
UL1 VAM 255 AutoReclose IF X2:1
P X2:3
X2:2
Autorecloser Blocking and
matrix output matrix
Connection for
phase to earth voltage at
voltage transformer secondary. X9:1DI1+
X9:2DI1- DI
-
X9:4DI2+
X9:5Di2-
-
*) Note 1. The residual current can be derived
from three phase CTs connected in parallel, from
a core balance cable CT or it can be calculated
from the three phase currents.
5
Feeder/Motor Protection Relay
Applications
VAMP 40 VAMP 40
Typical application Typical VAMP 40
3
VAMP 40
50,51,50N,
application 3 50, 51, 50N,
51N, 46,
51N,67N,
46,49,68,59N with integrated 49, 68, 79
3 3
3
VAMP 40
3
VAMP 40
3
VAMP 40 VAMP 40 VAMP 40
50, 51, 50N, 50, 51, 50N,
1 50,51,50N,51N, 50,51,50N,51N, 50,51,50N, 51N, 46, 51N, 46,
49,46,37, 49M,46,47,48, 51N,67N, 49, 68, 79 49, 68, 79
UNBALANCE 66,67N,37 46,49,68,59N,
79
L>
ARC INTERFACE ARC INTERFACE
BIO BIO
RTD 1 2 in out 1 2 in out
M
38,39
1
Dimensional Drawings
The slim casing gives a possibility to install this relay to the secondary
equipment compartment which has limited space.
Order Codes
Order Code Explanation Note
VAMP 40 Feeder / motor protection relay VAMP Ltd Panel
Accessories cut-out
VEA 3 CG Ethernet Interface Module VAMP Ltd
VPA 3 CG Profibus Interface Module VAMP Ltd
VSE001 Fiber optic Interface Module VAMP Ltd
VSE002 RS485 Interface Module VAMP Ltd
VX003-3 Programming Cable Cable length 3m
(VAMPSET,VEA3CG+200-series)
VP40 Arc option (1 Vamp Ltd
VA1DA-6 Arc Sensor, cable lenght 6 m VAMP Ltd
DI-934MB RTD Input module (2 DataQ Instruments Inc.
Adam 4015-B RTD Input module (2 Advantech Co., Ltd
1) future software release
2) disable use of remote protocol communication
6
Technical Data,
Tests and Environmental Conditions
Measuring circuitry Casing
Rated current In 1…10 A (software parameter) Dimensions (W x H x D) 280 x 195 x 55
- Current measuring range 0…250 A (0…50) x In [In=5 A]; Weight
0…250 x In [In=1 A] (Terminal, Package and Manual) 5 kg
- Thermal withstand 20 A (continuously)
100 A (for 10 s) Disturbance tests
500 A (for 1 s) Emission
- Burden < 0.2 VA - Conducted EN 55022B 0.15 - 30 MHz
- Emitted (CISPR 11) 30 - 1 000 MHz
Rated current Ion 1/ 5 A
- Current measuring range 0…10 A (0…10) x Ion Immunity
- Static discharge (ESD) IEC 60255-22-2, class III
Rated current Io2n 0.2 / 1 A 6 kV contact discharge
- Current measuring range 0…50 A (0…10) x Io2n 8 kV air discharge
- Fast transients (EFT) IEC 60255-22-4, class B
Rated voltage Uon / Un 50 - 120 V (configurable) 2 kV, 5/50 ns, 5 kHz, +/-
- Voltage measuring range 0 - 175 V (100 V/110 V) - Surge IEC 60255-22-5
- Continuous voltage withstand 250 V 2 kV, 1.2/50 µs, line-to-earth
- Burden < 0.5V A 1 kV, 1.2/50 µs, line-to-line
- Conducted HF field IEC 60255-22-6
Rated frequency fn 50 / 60 Hz (45 - 65 Hz) 0.15 - 80 MHz, 10 V/m
- Frequency measuring range 16 - 75 Hz - Emitted HF field IEC 60255-22-3
80 - 1000 MHz, 10 V/m
Terminal block: Maximum wire dimension: - GSM test ENV 50204
- Solid or stranded wire 4 mm2 (10-12 AWG) 900 MHz, 10 V/m, pulse modulated
7
Vamp Ltd is a Finnish company specialized in developing
and manufacturing protection relays for electrical power
generation and distribution systems. Vamp Ltd offers
complete MV protection and arc-protection family.