MANUFACTURER / SUB-CONTRACTOR :
PROJECT :
GENERAL NOTE
1. Equipment Number shall be designated according to Procedure for Plant Identification (KKS)
2. Load Type
M : Motor Load
P : Power (Non-motor) Load
3. Operation
1) Mode
C : Continuous operation
I : Intermittent operaton
S : Stand-by
I(SU) : During plant start-up only (Intermittent)
C(E) : Continuous operation (Emergency load)
I(E) : Intermittent operation (Emergency load)
4. Abbreviation
Ph : Phase (3 phase or 1 phase)
Volt : Rated voltage in V
EFF : Efficiency
PF : Power factor
FLC : Full load current in A
LRC : Motor starting current in A
AC : Alternating current
DC : Direct current
AC(U) : Uninterruptable AC power (UPS)
F5451A13-D-082-02_TT2-CTW-E443-00001_0.xls
ELECTRICAL LOAD LIST
PROJECT NAME : Termo tasajero Unit 2
EQUIPMENT NAME : Cooling Tower Date : 05-13-2014
94,5 0,78
95.0 0,85
94,5 0,78
95.0 0,85
94,5 0,78
95.0 0,85
94,5 0,78
Fan electric motor
4 22PAE40AC001-M M 3 460 ≤ 120 60 132 94,8 0,84 205 1230 continuous 1 WEG fan deck
95.0 0,85
94,5 0,78
95.0 0,85
94,5 0,78
95.0 0,85
F5451A13-D-082-02_TT2-CTW-E443-00001_0.xls
ELECTRICAL LOAD LIST
PROJECT NAME : Termo tasajero Unit 2
EQUIPMENT NAME : Cooling Tower Date : 05-13-2014
Shaft
Rated Power Operation
Load Volt Power Freq. FLC LRC Manu- Installed
No. Equipment No. Equipment Name Ph EFF PF Remark
type [V] Demand [ Hz ] [A] [A] Duty facturer Location
[kW] [KVA] [KW] Mode
factor
(1) Electric motor heater
operation shall be switched
intermittent
Fan electric motor heater ON when the motor is
7 22PAE10AC001 P 1 240 N/A 60 0,14 / / / / (1) SEE Note 1 WEG motor
stopped and switched OFF
22PAE10AC001-H REMARK
when the motor is in
operation
F5451A13-D-082-02_TT2-CTW-E443-00001_0.xls