R.D.Mill
SMP FOR
Fire Hydrant System
1
Hindustan Zinc Limited
R.D.Mill
A. Purpose – To minimize the risk of accident/hazard/fatality due to Fire by using fire hydrant system
B. Scope – Standard Operating Procedure for use of fire hydrant system
C. Competency Skill and Knowledge
VTC Trained fitter, welder, helper with ITI or 4 years of experience
D. PREREQUISITES:-
1. Basic Qualification – Experience as Fitter, Mechanic, Welder.
2. Basic Safety Training – VTC Training as per HZL rules
3. Mandatory PPEs – Safety Helmet, Safety Shoes, Dust Mask, Reflector Jacket, Welding Goggles, Hand Gloves.
4. Tools / Equipment’s –
General Tools.
D. Activities :
PTW and LOTOTO
1. Hot work permit to be taken for in case of any maintenance in the pipeline network.
2. Electrical isolation of the pump is to be taken.
3. All valves at the suction lines of the pumps to be closed and plugs at the suction nipple to be removed
for complete draining.
Working principle
A fire hydrant system is a water supply with a sufficient pressure and flow delivered through pipes
throughout the plant to strategically located network of valves for fire-fighting purposes.
In some circumstances, water from a reticulated fire hydrant system can also be shared with other safety
measures such as automatic fire sprinkler systems or fire hose reels.
System comprised of one main pump and one jockey pump and distribution line with hydrant landing valve
that can be connected with Non-percolating flexible hose.
Both the pumps are connected in Parallel type so as to maintain the required pressure in the pipeline. Both
have the provision of running in Auto mode as well as manual mode. And one pressure gauge and two nos.
of pressure switch are mounted in the line for each pump to measure and maintain the pressure.
For additional safety of the pressurized line on PRV (Pressure Release Valve) is also installed and is set at
10.0 Kg/cm2. If the line pressure exceeds the desired limit the PRV will automatically open up to release
the pressure.
The two Pressure switch are set on the following limits
Main Pump Jockey Pump
Max. Pressure (kg/cm2) 8 8
Min. Pressure (kg/cm2) 4 6
2
Hindustan Zinc Limited
R.D.Mill
Max pressure indicates that as the pressure reaches to that pressure pump will automatically stop in auto
mode and as soon as the pressure touches the min limit pump will start.
Jockey pump’s pressure is set as to just maintain the required pressure in case like small water out. Main
pump will start automatically when jockey is unable to maintain the required pressure in case of High
volume of water being taken out in case of emergency.
Precaution
Do not close the main line valve (8” line valve)
Do not close discharge butterfly valve of both the pumps.
Before starting of the pump ensure line inlet and discharge valves are in open condition.
Check regularly the line pressure in manual mode operation.
Close the water discharge valve after use and fold the flexible hoses.
3
Hindustan Zinc Limited
R.D.Mill
Strainer Strainer
Pressure Pressure
Transmitter Transmitter