Projet Name Water Supply Pipe Line

INFLOW SUMP TANK CAPACITY 0.35 MLD 350,000.00 Lts per Day

Discharge Calcuation
Consider Max Pumpring time 18 Hours
Pump Capacity IN Cum/hr 19444.45 Ltr/hr
Pump Capacity in Cum/min 324.08 Ltr/min
Pump Capacity Cum/sec 5.41 Ltr/Sec

Pipe Diameter Design


TAP Point to Sump Tank
Q=AV
Consider V 1 m per sec
Diameter 100 mm
Flow consideration 0.75 Approx for 3/4th FULL
Pipe c/s Area 0.0078539816 SqM
Water Flow area 0.0058904862 SqM
Qty per Hr 21205.76 Ltr/Hr
Qty per min 353.43 Ltr/min
Qty per Sec 5.90 Ltr/Sec
Duration 18 hrs
Qty pumped in specified Duration 381,704 Ltrs

Check PipeDia Selected OK


Head Loss In Pipe Line

Hazen's Williams Formule CH = Coeeficient of Material

V = 0.85 CH R S
0.63 0.54
d= Dia of Pipe
R = d/4 S = Friction dueto Slope
S = HL/L V = Velocity of Liquid

DATA :
DIA "d" = 0.1 mm
Velocity "V" = 1 m/s
Coefficient "CH" = 140 for DI pipe
R= D/4 = 0.025

S = 0.54Ö(V/(0.85XR0.63)
S = 0.010604

HL = SxL

Head Loss for Full Length of Pipeline


L full = L full 1600 M
Start Point to 1st
L Raise = Raise peak point 440
L Remaining = L full- L1 1160

RL at Tap Point = RL START 109.80


RL OF 1stPeak = RL PEAK 114.98
RL at Sump = RL END 99.91

Rise in Start point = RL PEAK- RL START 5.18


Net Fall in remaining portion = RL PEAK- RL END 15.07

Tap Point to Sump Ht difference = RL START-RL END 9.89

HEAD LOSS IN Ist RAISE PORTION


HL = L x S
Head Loss in 1st Raise = 440 x 0.0107 4.67 m
Head loss due to Water Meter = 1m
Head loss at T connection = 0.5 m
Head loss at Valve connection = 0.3 m
Head loss at 90 0 bend = 0.5 m
Head Loss Due to Bends = 3x0.30 1m
Head loss due to level difference = 5.18 m
Total Head = 13.15 m
CALCULATIO OF WATER HORSE POWER (WHP) OF PUMP
WHP = Discharge in Ltr per Min x Total Head in Meters
4500
CASE-1
START POINT TO 1 ST PEAK POINT

WHP1 = 324.08 x 13.15 = 1.420551


. 4500
Break Horse Power = WHP
Eficiency of pump x Efficiency of Motor

Eficiency of pump = 0.85


Efficiency of Motor = 0.65

Break Horse Power = 1.4206 = 2.58 hp


0.85 x 0.65

Min Pump Cap = 5 hp

Capacity Check = 5 hp

Provide Onlone Booster Pump of 5 HP CAPACITY


Hence provide one Stand by pump also

CASE-2
1ST PEAK POINT TO SUMP TANK

Head Loss in Remaining Portion = 1160 x 0.0107 12.30064

HEAD LOSS IN REMAINING PORTION

HL = L x S
Head Loss in 1st Raise = 1160 x 0.0107 12.31 m
Head loss at Valve connection = 0.3 m
Head loss at 90 0 bend = 0.5 m
Head Loss Due to Bends = 3x0.30 1m
Total Head Loss = 14.11 m
Head gain due to level difference = 15.07 m
Net Head Available for flow = 0.96 m

Hence , Water can flow by gravity till sump tank