Technical Information

Cerabar T PMC131, PMP131, PMP135


Pressure Transducer
With ceramic and metal sensors
For absolute pressure and gauge pressure measurement up to 400 bar
Extremely stable, overload-resistant and reliable

Application
Cerabar T is a pressure transducer for measuring absolute
pressure and gauge pressure in gases, vapors, liquids and
dusts.
Hygienic and threaded connections are available as
process connections.
Your benefits
This compact pressure transducer impresses with its
well-engineered construction:
• High reproducibility and long-term stability.
• Finely graduated measuring ranges from vacuum up to
400 bar/6000 psi.
• Ceraphire® ceramic sensor: corrosion-proof, abrasion-
proof and extremely overload-resistant.
• Deployed for pressure monitoring up to SIL 2 as per
IEC 61508/IEC 61511-1
• Sensors
– Dry capacitance ceramic sensor (Ceraphire®) for
measuring ranges up to 40 bar:
overload-resistant, vacuum-proof, stable against
alternating load
– Piezoresistive sensor with metal diaphragm for
measuring ranges up to 400 bar

TI415P/00/en
Cerabar T

Table of contents

Function and system design. . . . . . . . . . . . . . . . . . . . . 3 Operating conditions (process) . . . . . . . . . . . . . . . . . 11


Device selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Process temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Measuring principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Overload resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Measuring system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Vacuum resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Pressure specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Measured variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Mechanical construction . . . . . . . . . . . . . . . . . . . . . . 12
Measuring range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 PMC131 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
PMP131 and PMP135 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
PMP131 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
PMP135 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Output current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Operating elements . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Switch frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Operating elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Input PLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Inductive loads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Certificates and approvals . . . . . . . . . . . . . . . . . . . . . 17
CE mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Ex approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
PMC131 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Pressure Equipment Directive (PED) . . . . . . . . . . . . . . . . . . . . . 17
PMP131 and PMP135 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Functional safety SIL 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
PMP131 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Suitability for hygenic processes . . . . . . . . . . . . . . . . . . . . . . . . . 17
Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 TSE Certificate of Suitability . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Residual ripple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Standards and guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Cable entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Registered trademarks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Performance characteristics. . . . . . . . . . . . . . . . . . . . . 8 Ordering information. . . . . . . . . . . . . . . . . . . . . . . . . 18


Reference operating PMC131 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 PMC131 (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Long-term stability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 PMP131 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Maximum measured error PMP131 (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
of analog output PMP135 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
(under reference operating conditions) . . . . . . . . . . . . . . . . . . . . . 8
Switch point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Rise time (T90) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Welding neck with
Settling time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
sealing taper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Thermal change of the lower range value and the span . . . . . . . . . 9
Welding neck with
Temperature coefficient (TK) for lower range value and span . . . . . 9
sealing surface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Plug-in jack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Operating conditions (Installation instructions). . . . . . 9 Plug-on display
Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 PHX20/PHX21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Location dependence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Field of Activities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Operating conditions (environment) . . . . . . . . . . . . . 10 Technical Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Ambient temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Storage temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Functional Safety Manual (SIL) . . . . . . . . . . . . . . . . . . . . . . . . . 24
Climate class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Vibration resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Electromagnetic compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

2 Endress+Hauser
Cerabar T

Function and system design


Device selection Cerabar T PMC131 PMP131 PMP135

ENDRESS+HAUSER
CERABAR T

ENDRESS+HAUSER
CERABAR T
ENDRESS+HAUSER
CERABAR T

P01-PMC131xx-14-xx-xx-xx-000 P01-PMP131xx-14-xx-xx-xx-000 P01-PMP135xx-14-xx-xx-xx-000

With capacitive measuring With piezoresistive With piezoresistive measuring cell


cell and ceramic measuring measuring cell and metallic and metallic measuring
diaphragm (Ceraphire®) measuring diaphragm diaphragm for hygienic
applications

Field of Absolute pressure and gauge Absolute pressure and gauge Absolute pressure and gauge pressure
application pressure pressure in hygienic processes

Output Current output 4 to 20 mA – Current output 4 to 20 mA – 4 to 20 mA


– Voltage output 0 to 10 V – Switch output PNP
– Switch output PNP
Process Thread: Thread: Hygiene:
connection – G½ – G½ – Clamp DN 22 (¾")
– ½ MNPT and ¼ FNPT – ½ MNPT and ¼ FNPT – Tri-Clamp DN 25 to 38 (1" to 1½")
– G ½, bore 11 mm – ½ MNPT, bore 4 mm – Tri-Clamp DN 40 to 51 (2")
– G¼ – G1
– ¼ MNPT, bore 3.5 mm – SMS 1½"
– M 20 x 1.5

Measuring –1 to 0 bar/–100 to 0 kPa 0 to 1 bar/0 to 100 kPa 0 to 1 bar/0 to 100 kPa


range up to up to up to
0 to 40 bar/0 to 4 MPa 0 to 400 bar/0 to 40 MPa 0 to 40 bar/0 to 4 MPa

Process –20 to +100 °C –25 °C to +70 °C –25 to +100 °C


temperature (+135 °C for max. 1 hour)

Measuring principle PMC131


The measuring pressure causes a slight deflection of the ceramic diaphragm of the sensor. The pressure-
proportional change in capacitance is measured at the electrodes of the ceramic sensor. The ceramic sensor is
a dry sensor, i.e. no fill fluid is required for the pressure transfer. This makes the sensor completely suitable for
vacuums. Extremely high stability, comparable with the material Alloy, is achieved by using ultrapure
Ceraphire® as the ceramic.

PMP131 and PMP135 with analog output


The process pressure acting upon the metallic separating diaphragm of the sensor is transmitted to a resistance
bridge via a fluid. The pressure-proportional change of the bridge output voltage is measured and processed
further.

PMP131 and PMP135 with switch output


The process pressure acting upon the metallic separating diaphragm of the sensor is transmitted to a resistance
bridge via a fluid. A differential amplifier creates a standard signal from the pressure-proportional change in
output voltage of the bridge. A comparator with an adjustable hysteresis compares this signal with the pre-set
switch point and then activates the transistor output.

Endress+Hauser 3
Cerabar T

Measuring system
1 2
4...20 mA

+ – – +


p p

3 4
+ 0...10 V 4...20 mA

+ –


p

p
P01-PMx13xxx-14-xx-xx-xx-002

1 PMP131, PMP135: current output with transmitter power supply unit, e.g. RN 221N from Endress+Hauser
2 PMP131, PMP135: switch output with load, e.g. PLC, DCS, relay
3 PMC131: voltage output with transmitter power supply unit, e.g. RIA452 from Endress+Hauser
4 PMC131: current output with transmitter power supply unit, e.g. RN 221N from Endress+Hauser

Input
Measured variable Absolute pressure or gauge pressure

Measuring range up to 400 bar/6000 psi, see Page 18, "Ordering information" section

Output
Analog output (PMC131, PMP131, PMP135)

Output signal 4 to 20 mA

Load PMC131
RLmax [Ω] ≤ (US – 1 V) / 0.02 A

PMP131 and PMP135 (current output)


RLmax [Ω] ≤ (US – 12 V) / 0.02 A (RLmax: Maximum load resistance, US: Supply voltage)
PMP131 (voltage output)
Load resistance RLmax ≥5 kΩ, current consumption ≤6 mA

Switch output (PMP131, PMP135)

Output signal PNP switch output (positive voltage signal), rate depends on power supply voltage

Output current • Switch status ON: Ia ≤ 500 mA


• Switch status OFF: Ia ≤ 1 mA

4 Endress+Hauser
Cerabar T

Power max. 6 W

Switch frequency max. 10 Hz

Input PLC • Input resistance Ri ≤ 2 kΩ


• Input current Ii ≥ 10 mA

Inductive loads To prevent electrical interference, only operate an inductive load (relays, contactors, solenoid valves) when
directly connected to a protective circuit (free-wheeling diode or capacitor).

Power supply
PMC131 Plug/cable connection

2 1

ENDRESS+HAUSER ENDRESS+HAUSER ENDRESS+HAUSER


CERABAR T CERABAR T CERABAR T

M16 / ½ NPT M12x1 5 m/25 m


P01-PMC131xx-04-xx-xx-xx-001

Plug M 16 x 1.5 (DIN 43650/A), ½ NPT Plug M 12x1 5 m/25 m cable

➀ Plug-in housing ➀ Reference pressure line

➁ Gasket

Electrical connection: Analog/current output

1 + 2 +
– 12...30 V – 12...30 V
3-
4...20 mA 4...20 mA

2
1+ 2

+
3 – 12...30 V
1+ 2–
4...20 mA

+

PE
gnye
bk
rd

P01-PMC131xx-04-xx-xx-xx-002

1 Plug M 16 x 1.5 (DIN 43650/A), ½ NPT


2 Plug M 12 x 1
3 Cable (rd = red, bk = black, gnye = green-yellow)

Endress+Hauser 5
Cerabar T

PMP131 and PMP135 Plug/cable connection

1 1
3

4 2

5 3

DIN 43 650/A (M16 / ½ NPT) M12x1 5m


DIN 43650/C
P01-PMP13xxx-04-xx-xx-xx-001

Plug M 16 x 1.5 (DIN 43650/A), ½ NPT Plug M 12x1 5 m cable, only analog output
Plug DIN 43650/C

➀ Plug-in housing ➀ Coupling nut ➀ Reference pressure line

➁ Plug-in jack with gasket ➁ Connector with gasket

➂ Coupling nut ➂ Operating potentiometer (inner)

➃ Plug with O-ring

➄ Operating potentiometer (inner)

Electrical connection: Analog/current output

+ +
1 2
– 12...30 V – 12...30 V

4...20 mA 4...20 mA

2 3-
1+

3
+
3 3 – 12...30 V
1+ 2–
4...20 mA

+

PE
wh
gn
rd

P01-PMP13xxx-04-xx-xx-xx-002

1 Plug M 16 x 1.5 (DIN 43650/A), ½ NPT and plug DIN 43650/C


2 Plug M 12 x 1
3 Cable (rd = red, wh = white, gn = green)

For electrical connection provided by customer use only shielded cable

6 Endress+Hauser
Cerabar T

Electrical connection (switch output)

1 R 2
+ +
– 18...32 V 18...32 V –
3
2-

1 3+
1+ 2–
2 R

3 1+
P01-PMP13xxx-04-xx-xx-xx-003

1 Plug M 16 x 1.5 (DIN 43650/A), ½ NPT


2 Plug M 12 x 1
R External load, e.g. relay, programmable logic controller, distributed control system
For electrical connection provided by customer use only shielded cable

PMP131 Electrical connection: Analog-/voltage output

1 0...10 V 2 0...10 V 3 0...10 V

+ + +
– 15...30 V – 15...30 V –
15...30 V
3-

+
+
PE

1+

wh
gn
bk
rd
2-
2+
3+ 1+

P01-PMP131xx-04-xx-xx-xx-001

1 Plug M 16 x 1,5 (DIN 43650/A), ½ NPT and plug DIN 43 650/C


2 Plug M 12 x 1
3 Cable (rd = red, wh = white, gn = green)
For electrical connection provided by customer use only shielded cable

Supply voltage PMC131


11 to 30 V DC

PMP131 and PMP135 (current output, 2-wire version)


• For non-hazardous areas: 12 to 30 V DC
• Ex i: no-load voltage ≤ 26 V DC, short-circuit current ≤ 100 mA, power consumption ≤ 0.8 W

PMP131 (voltage output, 3-wire version)


• 15...30 V DC

PMP131 and PMP135 (switch output)


• 18 to 32 V DC, current consumption without load < 20 mA, with reverse polarity protection

Residual ripple • Analog output: max. 5 % of supply voltage


• Switch output: max. 10 % of supply voltage

Cable entry → See Page 18, "Ordering information" section.

Endress+Hauser 7
Cerabar T

Performance characteristics
Reference operating as per DIN IEC 60770, TU = 25 °C
conditions

Long-term stability ≤ 0.15 % of URL per year

Maximum measured error The measured error comprises the non-linearity including hysteresis and non-reproducibility in accordance
of analog output with the limit point method as per IEC 60770.
(under reference operating
conditions) PMC131
• ≤ 0.5 % of (URL - LRL) x TD1)

Example: PMC131 version "A1R"


• Nominal value = 10 bar 1
• Upper range value (URV) = 6 bar
• Lower range value (LRV) = 0 bar LRL = LRV URV URL

Turn down (is set at factory):


• Nominal value / (URV – LRV)⏐= 10 bar/6 bar = 10:6 0 bar +6 bar +10 bar

3
P01-PMx13xxx-05-xx-xx-xx-001

Example: PMC131 version "A1R"


set span: 0 to 6 bar; nominal value = 10 bar
1 Span set and calibrated at the factory (measuring
range)
2 Nominal value i Upper Range Limit (URL)
3 Sensor measuring range
LRL Lower Range Limit
URL Upper Range Limit
LRV Lower Range Value
URV Upper Range Value

PMP131 and PMP135


• ≤ 0.5 % of URL

Switch point PMP131 and PMP135


• Deviation: ≤ 1 % of URL
• Non-reproducibility: ≤ 0.5 % of URL

Rise time (T90) PMC131


20 ms

Settling time PMP131 and PMP135


2 to 5 ms

1) extended specifications apply to customer-specific measuring ranges

8 Endress+Hauser
Cerabar T

Thermal change of the lower PMC1312)


range value and the span
Zero output, −20 to +85 °C:
• typically 1.5 % of URL
Output span, −20 to +85 °C:
• Nominal value 0.4 to 40 bar: typically 0.8 % of URL
• Nominal value 0.1bar: typically 1.0 % of URL

Temperature coefficient (TK) PMP131 and PMP135 (analog output)


for lower range value and span
Zero output:
• typically: 0.2 % of URL/10 K
• max.: 0.5 % of URL/10 K
• Nominal value ≤ 6 bar: by 0.1 % of URL/10 K higher
Output signal:
• typically: 0.2 % of URL/10 K
• max.: 0.5 % of URL/10 K

PMP131 and PMP135 (switch output)


Switch point:
• typically: 0.2 % of URL/10 K
• max.: 0.5 % of URL/10 K

Operating conditions (Installation instructions)


Orientation anywhere

Installation instructions PMP131


Process connection G 1/2 flush-mounted, max. torque 40 Nm

Location dependence PMC131


without influence

PMP131 and PMP135


Position-dependent zero point shift can be corrected by potentiometer setting, see also Page 16.

2) for customer-specific measuring-ranges: values are doubled

Endress+Hauser 9
Cerabar T

Operating conditions (environment)

Ambient temperature range PMC131


–20 to +85 °C

PMP131 and PMP135


• For non-hazardous areas: –25 to +70 °C
• Ex i: –25 to +65 °C

Storage temperature range PMC131


–50 to +100 °C

PMP131 and PMP135


–40 to +85 °C

Climate class PMC131


4K4H as per DIN EN 60721-3

PMP131 and PMP135


4Z
with Z = 70 °C as per VDI/VDE 3540

Degree of protection PMC131


• Plug M 16 x 1,5 (DIN 43650/A), ½ NPT: IP 65/NEMA 4X
• Plug M12x1: IP 65/ NEMA 4
• Cable: IP 68/NEMA 6P (1 mWS/24 h)

PMP131 and PMP135


• Plug M 16 x 1,5 (DIN 43650/A), ½ NPT: IP 65/NEMA 4X
• Plug M 12x1 and gauge pressure sensors: IP 65/NEMA 4X
• Plug M 12x1 and absolute pressure sensors: IP 68/NEMA 6P (1 mWS/24 h)
• Cable: IP 68/NEMA 6P (1 mWS/24 h)

Vibration resistance 4M5 as per DIN EN 60721-3

Electromagnetic compatibility PMC131


Interference emission as per EN 61326 electrical device class B,
Interference immunity as per EN 61326 appendix A (industrial use).

PMP131 and PMP135


Electromagnetic combatibility according to EN 61326;
For details refer to the declaration of conformity (see ATEX Safety Instructions XA142P)

10 Endress+Hauser
Cerabar T

Operating conditions (process)

Process temperature range PMC131


• –20 to +100 °C
• Devices for oxygen application: −10 to +60 °C
(Version "S" for feature 30 "Sensor gasket")
PMP131
–25 to +70 °C
PMP135
–25 to +100 °C (+135 °C for max. 1 hour)
Extreme jumps in temperature can result in temporary measuring errors. Temperature compensation takes
effect after several minutes. Internal temperature compensation is faster the smaller the temperature jump and
the longer the time interval.

Overload resistance → See Page 18, "Ordering information" section.

Vacuum resistance PMC131


• with URV > 200 mbar/> 80 inH2O/> 1.5 psi: 0 mbarabs
• with URV = 200 mbar/= 50 inH2O or 80 inH2O: 500 mbarabs
(Versions "D12", "D38", "W6O", "S4N")
• with URV = 20 mbar or 100 mbar/=1.5 psi/=15 inH2O or 30 inH2O: 700 mbarabs
(Versions "D10", "D3W", "D31", "Q4D", "V6F", "W6N", "W6R")
PMP131 and PMP135
10 mbarabs

Pressure specifications • The MWP (maximum working pressure) of the device is specified on the nameplate. It depends on the
weakest element, with regard to pressure, of the selected components. See the following sections:
– → Page 18 ff, "Ordering information" section, feature 50 "Measuring range; MWP; Nominal value; OPL"
or "Sensor range; MWP; OPL".
– → Page 12 ff, "Mechanical construction" section.
The MWP specification on the nameplate is based on a reference temperature of +20 °C and can be present
over an unlimited period of time.
• The test pressure corresponds to the overload limit of the measuring device (Over Pressure Limit OPL) and
must only be present for a limited period of time.

Endress+Hauser 11
Cerabar T

Mechanical construction
PMC131 Housing

1 2 3
32

Pg 11

101
ENDRESS+HAUSER ENDRESS+HAUSER

91
ENDRESS+HAUSER
CERABAR T CERABAR T
CERABAR T

73
SW 41 SW 41 SW 41
A

A
P01-PMC131xx-06-xx-xx-xx-001

Housing PMC131; Material AISI 304 (1.4301)


1 Versions A1, A2, B1, C1, C2: Plug M 16 or ½ NPT (ISO 4400), IP 65
2 Versions A5, B5, C5: Plug M 12, IP 65
3 Versions A3, A4, B3, C3: 5 m or 25 m cable, IP 68

→ See the following diagram for the height of process connection A

Process connections

1 2 3
H

H
20

17

20
25
12
A

6 ¼ NPT ø11
3

G½ ½ NPT ø17

P01-PMC131xx-06-xx-xx-xx-002

Process connections PMC131; Material AISI 304 (1.4301)


1 Version 1: Thread ISO 228 G ½
2 Version 2: Thread ANSI ½ MNPT ¼ FNPT
3 Version 5: Thread ISO 228 G ½, bore 11 mm

→ See respective housing for installation height H (previous figure)

12 Endress+Hauser
Cerabar T

PMP131 and PMP135 Housings

1 2 3 4 5 6

54
36

15
54
36

15

110
H=110

110
ø26.5 ø26.5 ø26.5
ø26.5 ø26.5 ø26.5 ø33
85

89
89
H
A

A
A
P01-PMP13xxx-06-xx-xx-xx-002

Housings PMP131 and PMP135; Material AISI 304 (1.4301)


1...3 PMP131 and PMP135 with sensor range up to 100 bar
4...6 PMP131 with sensor range up to 400 bar
1 + 4 Versions A1, A2: Plug M 16 (DIN 43650/A) or ½ NPT (ISO 4400), IP 65; dimension x = 52 mm
Version A5: Plug DIN 43650/C, IP 65; dimension x = 42 mm
2 + 5 Version A3: 5 m cable, IP 68
3 + 6 Version A4: Plug M 12, IP 65

→ See the following figure for the dimensions of process connection A

PMP131 Process connections


A

P01-PMP131xx-06-xx-xx-xx-002

Process connections PMP131; Material AISI 304 (1.4301)


1 Version 1: Thread ISO 228 G ½
2 Version 2: Thread ANSI ½ MNPT ¼ FNPT
3 Version 3: Thread ANSI ½ MNPT, bore 4 mm female
4 Version 4: Thread ISO 228 G ¼
5 Version 5: Thread ANSI ¼ MNPT, bore 3.5 mm female
6 Version 6: Thread M 20 x 1.5

→ See respective housing for installation height H (figure above)


→ Process connections with AF 27 mm

Endress+Hauser 13
Cerabar T

1 2 mm (inch)

27

H
(1.1)

(0.1)
2.5

(0.7)
(0.5)
17
14

(0.5)

(0.9)
14

22

ø26
(1)
P01-PMP131xx-06-09-xx-xx-002

Process connection PMP131; Material AISI 304 (1.4301)


1 Version B: Thread ISO 228 G ½, Gasket DIN 3852-A flush-mounted
2 Dimensions for tapped hole G ½ as per DIN 3852-11 form X

→ See respective housing for installation height H

PMP135 Process connections

1 2 3
H

H
33

33

33
M M M

ø27.5 ø43.5 ø56.5

ø34 ø50.5 ø64

4 5 6
H

H
H

39
46.6
33

27
29.5

M M
M

ø55 ø29 G1A


G1A
P01-PMP135xx-06-xx-xx-xx-001

Process connections PMP135; Material AISI 316L (1.4435); Surface roughness of the surfaces in contact with the medium
Ra ≤ 0.8 μm
M = Diaphragm diameter 17.2 mm
1 Version F: Clamp ¾" (ISO 2852) or DN 22 (DIN 32676), 3A
2 Version G: Tri-Clamp 1" to 1½" (ISO 2852) or DN 25 to DN 40 (DIN 32676), 3A
3 Version H: Tri-Clamp 2" (ISO 2852) or DN 50 (DIN 32676), 3A
4 Version S: SMS 1½" PN 25, 3A
5 Version N : G1A (ISO 228), with sealing surface for flush-mounted installation
6 Version M: G1A (ISO 228), with metallic sealing taper, flush-mounted

→ See respective housing for installation height H

14 Endress+Hauser
Cerabar T

Weights • PMC131: approx. 0.32 kg


• PMP131: approx. 0.24 kg
• PMP135: approx. 0.34 kg

Material • Process connection:


– PMC131: AISI 304 (1.4301)
– PMP131: AISI 304 (1.4301)
– PMP135: AISI 316L (1.4435)
• Sensor diaphragm:
– PMC131: Ceraphire® (99.9 % Al2O3), FDA number 21-CFR 186.1256
– PMP131, PMP135: AISI 316L (1.4435)
• Fill oil:
– PMP131: Tegiloxan 3
– PMP135: Mineral oil, FDA number 21-CFR 172.882
• Housing
AISI 304 (1.4301)
• Electrical connection
Plug M12: Polyamide (PA)
Valve connector: Sheathing made of polyamide (PA)
Cable: Sheathing made of polyurethane (PUR/UL94, V0, UV-resistant)

Operating elements
Operating elements Position of operating elements
The potentiometer for operating the
Cerabar T PMP131 and PMP135 with analog or
switch output is located below the base of the plug.

P01-PMx13xxx-19-xx-xx-xx-003

Analog output: Zero point adjustment


The zero point can be corrected for the Cerabar T
PMP131 and PMP135 with analog output and plug
version.

P01-PMx13xxx-19-xx-xx-xx-001

1 Potentiometer for zero point correction by ±5 % of URL

Endress+Hauser 15
Cerabar T

Switch output: Switch point and hysteresis adjustment


For the Cerabar T PMP131 and PMP135 with
switch output, both the switch point and hysteresis
can be adjusted.
3 This can also be carried out at atmospheric pressure
using the enclosed test cable and a voltmeter.
1

2 + –
4

P01-PMx13xxx-19-xx-xx-xx-002

1 Hysteresis adjustment 1.5 to 20 % of URL;


Factory setting 10 % of URL
2 Switch point adjustment 0 to 100 % of URL;
Factory setting 50 % of URL
3 LED color code for checking the switch status:
green = off; red = on
4 Connect voltmeter to test pins:
0 to 1 V corresponds to 0 to 100 % of URL

Uout
Hysteresis
1.5...20 %
ON = red LED
on

Switch Switch
on off

off
OFF = green LED

p
Switch point
0...100 %
P01-PMP13xxx-05-xx-xx-en-001

Instructions for switch point and hysteresis (the percentage values refer to the URL)
Ua Output voltage
p Acting pressure

16 Endress+Hauser
Cerabar T

Certificates and approvals


CE mark The device meets the legal requirements of the EC directives. Endress+Hauser confirms that the device has
been successfully tested by applying the CE mark.

Ex approvals All explosion protection data are given in separate documentation which is available upon request. The Ex
documentation is supplied as standard with all devices approved for use in explosion hazardous areas.
→ See also Page 22, "Safety Instructions" section.

Pressure Equipment Directive This measuring device corresponds to Article 3 (3) of the EC directive 97/23/EC (Pressure Equipment
(PED) Directive) and has been designed and manufactured according to good engineering practice.

Functional safety SIL 2 The Cerabar T PMP131 and PMP135 pressure transducers with 4 to 20 mA electronics have been assessed by
an independent body according to the standards IEC 61508/IEC 61511-1. These devices can be used for
monitoring process pressure up to SIL 2.
→ For a detailed description of safety functions with Cerabar T, settings and characteristic quantities for
functional safety, see the "Functional Safety Manual – Cerabar T SD160P".

Suitability for hygenic The Cerabar T PMP135 is suitable for the employment in hygenic
processes processes.
An overview of permitted process connections on page 14.
Many versions meet the requirements of 3A-Sanitary Standard No. 74
and are certified by the EHEDG.
! Note!
The gap-free connections can be cleaned without residue using the
TYPE EL
usual cleaning methods. October 2007

74 -

TSE Certificate of Suitability Cerabar T PMP135


The following applies to wetted device components: They do not contain any materials derived from animals.
No auxiliaries or operating materials derived from animals are used in production or processing. Process wetted
device components are listed in the “Mechanical construction” and “Ordering information” sections.

Standards and guidelines DIN EN 60770 (IEC 60770):


Transmitters for controlling in systems used in industrial process technology
Part 1: Methods for evaluating the operating behavior.
DIN EN 61003-1, Edition:1993-12
Systems used in industrial process technology;
Devices with analog inputs and two-point or multi-point behavior;
Part 1: Methods for evaluating the operating behavior.
DIN 16086:
Electrical pressure measuring devices, pressure sensors, transmitters, pressure measuring devices
Terms, specifications in data sheets.
IEC 60592
Degrees of protection provided by enclosures (IP-Code).
EN 61326:
Electrical equipment for control technology and laboratory application – EMC requirements.
IEC 61010
Safety requirements for electrical equipment for measurement, control and laboratory use.
NAMUR
Association for Standards for Control and Regulation in the Chemical Industry.

Registered trademarks Ceraphire®


Registered trademark of Endress+Hauser GmbH+Co. KG, Maulburg, Germany
(→ see also www.endress.com/ceraphire)

Endress+Hauser 17
Cerabar T

Ordering information
PMC131 10 Electrical connection:
A1 Plug ISO 4400, M 16, IP 65/NEMA 4X
A2 Plug ISO 4400, ½ NPT, IP 65/NEMA 4X
A3 5 m cable, IP 68/NEMA 6P
A4 25 m cable, IP 68/NEMA 6P
A5 Plug M 12, IP 65/NEMA 4
B1 Plug ISO 4400, M 16, IP 65, ATEX II 3 G EEx nA II T4
B3 5 m cable, IP 68, ATEX II 3 G EEx nA II T4
B5 Plug M 12, IP 65, ATEX II 3 G EEx nA II T4
C1 Plug ISO 4400, M 16, NEMA 4X, CSA GP
C2 Plug ISO 4400, ½ NPT, NEMA 4X, CSA GP
C3 5m cable, IP 68/NEMA 6P, CSA GP
C5 Plug M12, IP 65/NEMA 4, CSA GP

20 Process connection:
1 Thread ISO 228 G ½, AISI 304
2 Thread ANSI ½ MNPT ¼ FNPT, AISI 304
5 Thread ISO 228 G ½ bore 11 mm, AISI 304

30 Sensor seal:
F FKM Viton
S FKM Viton, oxygen application

40 Additional options:
1 Without additional equipment
S GL (German Lloyd) marine certificate
2 Final inspection report

50 Measuring range; MWP; Nominal value; OPL:


Measuring range MWP Nominal OPL
(Maximum value (Over Pressure
Working Limit)
Pressure)
Sensors for gauge pressure
A1G 0 to 1 bar / 0 to 100 kPa 6.7 bar 1 bar 10 bar / 1 MPa
A1H 1) 0 to 1.6 bar / 0 to 160 kPa 12 bar 2 bar 18 bar / 1.8 MPa
A1K 0 to 2 bar / 0 to 200 kPa 12 bar 2 bar 18 bar / 1.8 MPa
A1Q 0 to 4 bar / 0 to 400 kPa 16.7 bar 4 bar 25 bar / 2.5 MPa
A1R 1) 0 to 6 bar / 0 to 600 kPa 26.7 bar 10 bar 40 bar / 4 MPa
A1S 0 to 10 bar / 0 to 1 MPa 26.7 bar 10 bar 40 bar / 4 MPa
A1T 1) 0 to 16 bar / 0 to 1.6 MPa 26.7 bar 20 bar 40 bar / 4 MPa
A1V 0 to 20 bar / 0 to 2 MPa 26.7 bar 20 bar 40 bar / 4 MPa
A1W 1) 0 to 25 bar / 0 to 2.5 MPa 40 bar 40 bar 60 bar / 6 MPa
A1X 0 to 40 bar / 0 to 4 MPa 40 bar 40 bar 60 bar / 6 MPa
A3C 1) −1 to 0 bar / −100 to 0 kPa 6.7 bar 2 bar 10 bar / 1 MPa
A3E 1) −1 to 1 bar / −100 to 100 kPa 6.7 bar 2 bar 10 bar / 1 MPa
A3G 1) −1 to 3 bar / −100 to 300 kPa 16.7 bar 4 bar 25 bar / 2.5 MPa
A3K 1) −1 to 9 bar / −100 to 900 kPa 26.7 bar 10 bar 40 bar / 4 MPa
A3N 1) −1 to 15 bar / −0.1 to 1.5 MPa 26.7 bar 20 bar 40 bar / 4 MPa
D10 0 to 100 mbar / 0 to 10 kPa 2.7 bar 0.1 bar 4 bar / 400 kPa
D12 1) 0 to 200 mbar / 0 to 20 kPa 3.3 bar 0.2 bar 5 bar / 500 kPa
D14 0 to 400 mbar / 0 to 40 kPa 5.3 bar 0.4 bar 8 bar / 800 kPa
D3W −20 to 20 mbar / −2 to 2 kPa 2.7 bar 0.2 bar 4 bar / 400 kPa
D31 1) −100 to 100 mbar / −10 to 10 3.3 bar 0.2 bar 5 bar / 500 kPa
kPa
D38 1) −200 to 200 mbar / −20 to 20 3.3 bar 0.4 bar 5 bar / 500 kPa
kPa
D39 1) −300 to 300 mbar / −30 to 30 5.3 bar 1 bar 8 bar / 800 kPa
kPa

PMC131 Order code

→ For continuation of ordering information of PMC131, see the following page.

1) Span set and calibrated at the factory

18 Endress+Hauser
Cerabar T

PMC131 (continued) 50 Measuring range; MWP; Nominal value; OPL:


Measuring range MWP Nominal OPL
(Maximum value (Over Pressure
Working Limit)
Pressure)
Sensors for gauge pressure
Q4D 0 to 1.5 psi 40 psi 1.5 psi 60 psi
Q4F 1) 0 to 5 psi 80 psi 6 psi 120 psi
Q4H 0 to 15 psi 100 psi 15 psi 150 psi
Q4K 0 to 30 psi 180 psi 30 psi 270 psi
Q4N 1) 0 to 50 psi 250 psi 60 psi 375 psi
Q4R 0 to 150 psi 400 psi 150 psi 600 psi
Q4S 0 to 300 psi 400 psi 300 psi 600 psi
Q4T 1) 0 to 500 psi 600 psi 600 psi 900 psi
V6F 1) −1.5 to 1.5 psi 50 psi 3 psi 75 psi
V6N 1) −15 to 15 psi 100 psi 30 psi 150 psi
V6R 1) −15 to 30 psi 250 psi 60 psi 375 psi
V6S −15 to 60 psi 250 psi 60 psi 375 psi
V6V −15 to 150 psi 400 psi 150 psi 600 psi
S4N 1) 0 to 50 inH2O 50 psi 3 psi 75 psi
S4Q 1) 0 to 100 inH2O 80 psi 6 psi 120 psi
W6N 1) −15 to 15 inH2O 40 psi 3 psi 60 psi
W6O 1) −80 to 80 inH2O 50 psi 6 psi 75 psi
W6R 1) −15 to 30 inH2O 50 psi 3 psi 75 psi
Sensors for absolute
pressure
A2G 0 to 1 bar / 0 to 100 kPa 6.7 bar 1 bar 10 bar / 1 MPa
A2H 1) 0 to 1.6 bar / 0 to 160 kPa 12 bar 2 bar 18 bar / 1.8 MPa
A2K 0 to 2 bar / 0 to 200 kPa 12 bar 2 bar 18 bar / 1.8 MPa
A2Q 0 to 4 bar / 0 to 400 kPa 16.7 bar 4 bar 25 bar / 2.5 MPa
A2R 1) 0 to 6 bar / 0 to 600 kPa 26.7 bar 10 bar 40 bar / 4 MPa
A2S 0 to 10 bar / 0 to 1 MPa 26.7 bar 10 bar 40 bar / 4 MPa
A2T 1) 0 to 16 bar / 0 to 1.6 MPa 26.7 bar 20 bar 40 bar / 4 MPa
A2V 0 to 20 bar / 0 to 2 MPa 26.7 bar 20 bar 40 bar / 4 MPa
A2W 1) 0 to 25 bar / 0 to 2.5 MPa 40 bar 40 bar 60 bar / 6 MPa
A2X 0 to 40 bar / 0 to 4 MPa 40 bar 40 bar 60 bar / 6 MPa
D20 1) 0 to 100 mbar / 0 to 10 kPa 3.3 bar 0.2 bar 5 bar / 500 kPa
D22 0 to 200 mbar / 0 to 20 kPa 3.3 bar 0.2 bar 5 bar / 500 kPa
D24 0 to 400 mbar / 0 to 40 kPa 5.3 bar 0.4 bar 8 bar / 800 kPa
R4D 1) 0 to 1.5 psi 50 psi 3 psi 75 psi
R4F 1) 0 to 5 psi 80 psi 6 psi 120 psi
R4H 0 to 15 psi 100 psi 15 psi 150 psi
R4K 0 to 30 psi 180 psi 30 psi 270 psi
R4N 1) 0 to 50 psi 250 psi 60 psi 375 psi
R4R 0 to 150 psi 400 psi 150 psi 600 psi
R4S 0 to 300 psi 400 psi 300 psi 600 psi
R4T 1) 0 to 500 psi 600 psi 600 psi 900 psi

PMC131 Complete order code

1) Span set and calibrated at the factory

Endress+Hauser 19
Cerabar T

PMP131 10 Electrical connection:


A1 Plug ISO 4400, M 16, IP 65/NEMA 4X (DIN 43650/A)
A2 Plug ISO 4400, ½ NPT, IP 65/NEMA 4X
A3 5 m cable, IP 68/NEMA 6P
A4 Plug M 12, IP 65/NEMA 4X
A5 Plug DIN 43650/C, IP65, NEMA 4X

20 Process connection:
B Thread ISO 228 G ½, Seal DIN 3852, AISI 304, flush-mounted
1 Thread ISO 228 G ½, AISI 304
2 Thread ANSI ½ MNPT ¼ FNPT, AISI 304
3 Thread ANSI ½ MNPT bore 4 mm, AISI 304
4 Thread ISO 228 G ¼, AISI 304
5 Thread ANSI ¼ MNPT bore 3.5 mm, AISI 304
6 Thread M 20 x 1.5

30 Output:
0 Analog current output 4 to 20 mA, SIL
D Analog current output 4 to 20 mA, SIL, ATEX II 1/2 G EEx ib IIC T6
1 Analog current output 4 to 20 mA, SIL, ATEX II 2 G EEx ib IIC T6
5 Analog current output 4 to 20 mA, SIL, ATEX II 3 G EEx nA II T6
2 Switch output PNP, 3-wire
3 Switch output PNP, 3-wire, ATEX II 3 G EEx nA II T6
6 Analog voltage output 0...10 V

40 Additional options:
1 Without additional equipment
S GL/RINA marine approval
2 Final inspection report

50 Sensor range; MWP; OPL:


Sensor range MWP (maximum working OPL (over pressure limit)
pressure)
Sensors for gauge pressure
A1G 0 to 1 bar / 0 to 100 kPa 2.7 bar 4 bar / 400 kPa
A1H 0 to 1.6 bar / 0 to 160 kPa 4 bar 6.4 bar / 640 kPa
A1N 0 to 2.5 bar / 0 to 250 kPa 6.7 bar 10 bar / 1 MPa
A1Q 0 to 4 bar / 0 to 400 kPa 10.7 bar 16 bar / 1.6 MPa
A1R 0 to 6 bar / 0 to 600 kPa 16 bar 24 bar / 2.4 MPa
A1S 0 to 10 bar / 0 to 1 MPa 25 bar 40 bar / 4 MPa
A1T 0 to 16 bar / 0 to 1.6 MPa 25 bar 64 bar / 6.4 MPa
A1W 0 to 25 bar / 0 to 2.5 MPa 25 bar 100 bar / 10 MPa
A1X 0 to 40 bar / 0 to 4 MPa 60 bar 160 bar / 16 MPa
A1Z 0 to 60 bar / 0 to 6 MPa 60 bar 240 bar / 24 MPa
A70 0 to 100 bar / 0 to 10 MPa 100 bar 400 bar / 40 MPa
A71 0 to 160 bar / 0 to 16 MPa 160 bar 600 bar / 60 MPa
A73 0 to 250 bar / 0 to 25 MPa 250 bar 600 bar / 60 MPa
A74 0 to 400 bar / 0 to 40 MPa 400 bar 600 bar / 60 MPa
Q4H 0 to 15 psi 40 psi 60 psi
Q4K 0 to 30 psi 100 psi 150 psi
Q4N 0 to 50 psi 160 psi 240 psi
Q4R 0 to 150 psi 400 psi 600 psi
Q4S 0 to 300 psi 400 psi 1500 psi
Q4T 0 to 500 psi 1000 psi 2400 psi
Q4V 0 to 1000 psi 1000 psi 3600 psi
Q70 0 to 1500 psi 1500 psi 6000 psi
Q73 0 to 3000 psi 3000 psi 9000 psi
Q74 0 to 6000 psi 6000 psi 9000 psi

PMP131 Order code

→ For continuation of ordering information of PMP131, see the following page.

20 Endress+Hauser
Cerabar T

PMP131 (continued) 50 Sensor range; MWP; OPL:


Sensor range MWP (maximum working OPL (over pressure limit)
pressure)
Sensors for absolute pres-
sure
A2G 0 to 1 bar / 0 to 100 kPa 2.7 bar 4 bar / 400 kPa
A2H 0 to 1.6 bar / 0 to 160 kPa 4 bar 6.4 bar / 640 kPa
A2N 0 to 2.5 bar / 0 to 250 kPa 6.7 bar 10 bar / 1 MPa
A2Q 0 to 4 bar / 0 to 400 kPa 10.7 bar 16 bar / 1.6 MPa
A2R 0 to 6 bar / 0 to 600 kPa 16 bar 24 bar / 2.4 MPa
A2S 0 to 10 bar / 0 to 1 MPa 25 bar 40 bar / 4 MPa
A2T 0 to 16 bar / 0 to 1.6 MPa 25 bar 64 bar / 6.4 MPa
A2W 0 to 25 bar / 0 to 2.5 MPa 25 bar 100 bar / 10 MPa
A2X 0 to 40 bar / 0 to 4 MPa 60 bar 160 bar / 16 MPa
A2Z 0 to 60 bar / 0 to 6 MPa 60 bar 240 bar / 24 MPa
B70 0 to 100 bar / 0 to 10 MPa 100 bar 400 bar / 40 MPa
B71 0 to 160 bar / 0 to 16 MPa 160 bar 600 bar / 60 MPa
B73 0 to 250 bar / 0 to 25 MPa 250 bar 600 bar / 60 MPa
B74 0 to 400 bar / 0 to 40 MPa 400 bar 600 bar / 60 MPa
R4H 0 to 15 psi 40 psi 60 psi
R4K 0 to 30 psi 100 psi 150 psi
R4N 0 to 50 psi 160 psi 240 psi
R4R 0 to 150 psi 400 psi 600 psi
R4S 0 to 300 psi 400 psi 1500 psi
R4T 0 to 500 psi 1000 psi 2400 psi
R4V 0 to 1000 psi 1000 psi 3600 psi
R70 0 to 1500 psi 1500 psi 6000 psi
R73 0 to 3000 psi 3000 psi 9000 psi
R74 0 to 6000 psi 6000 psi 9000 psi

PMP131 Complete order code

Endress+Hauser 21
Cerabar T

PMP135 10 Electrical connection:


A1 Plug ISO 4400, M 16, IP 65/NEMA 4X
A2 Plug ISO 4400, ½ NPT, IP 65/NEMA 4X
A3 5 m cable, IP 68/NEMA 6P
A4 Plug M 12, IP 65/NEMA 4X

20 Process connection:
F Clamp ISO 2852, DN 22 (¾"), AISI 316L, 3A, DIN 32676 DN 20, EHEDG
G Tri-Clamp ISO 2852, DN 25 to 38 (1" to 1½"), AISI 316L, 3A, DIN 32676 DN 25 to 40, EHEDG
H Tri-Clamp ISO 2852, DN 40 to 51 (2"), AISI 316L, 3A, DIN 32676 DN 50, EHEDG
M Thread ISO 228, G 1, with metallic sealing taper, AISI 316L, flush-mounted, adapter 52005087
N Thread ISO 228, G 1, with sealing surface for flush-mounted installation, AISI 316L, adapter 52001051
S SMS 1½", PN 25, AISI 316L, 3A, EHEDG

30 Output:
0 Analog 4 to 20 mA, SIL
D Analog 4 to 20 mA, SIL, ATEX II 1/2 G EEx ib IIC T6
1 Analog 4 to 20 mA, SIL, ATEX II 2 G EEx ib IIC T6
5 Analog 4 to 20 mA, SIL, ATEX II 3 G EEx nA II T6
2 Switch output PNP, 3-wire
3 Switch output PNP, ATEX II 3 G EEx nA II T6

40 Additional options:
1 Without additional equipment
C EN10204-3.1 material (wetted) inspection certificate
2 Final inspection report

50 Sensor range; MWP; OPL:


Sensor range MWP (maximum working OPL (over pressure limit)
pressure)
Sensors for gauge pressure
A1G 0 to 1 bar / 0 to 100 kPa 2.7 bar 4 bar / 400 kPa
A1H 0 to 1.6 bar / 0 to 160 kPa 4 bar 6.4 bar / 640 kPa
A1N 0 to 2.5 bar / 0 to 250 kPa 6.7 bar 10 bar / 1 MPa
A1Q 0 to 4 bar / 0 to 400 kPa 10.7 bar 16 bar / 1.6 MPa
A1R 0 to 6 bar / 0 to 600 kPa 16 bar 24 bar / 2.4 MPa
A1S 0 to 10 bar / 0 to 1 MPa 25 bar 40 bar / 4 MPa
A1T 0 to 16 bar / 0 to 1.6 MPa 25 bar 64 bar / 6.4 MPa
A1W 0 to 25 bar / 0 to 2.5 MPa 25 bar 100 bar / 10 MPa
A1X 0 to 40 bar / 0 to 4 MPa 60 bar 160 bar / 16 MPa
Q4H 0 to 15 psi 40 psi 60 psi
Q4K 0 to 30 psi 100 psi 150 psi
Q4N 0 to 50 psi 160 psi 240 psi
Q4R 0 to 150 psi 400 psi 600 psi
Q4S 0 to 300 psi 400 psi 1500 psi
Q4T 0 to 500 psi 1000 psi 2400 psi
Sensors for absolute pres-
sure
A2G 0 to 1 bar / 0 to 100 kPa 2.7 bar 4 bar / 400 kPa
A2H 0 to 1.6 bar / 0 to 160 kPa 4 bar 6.4 bar / 640 kPa
A2N 0 to 2.5 bar / 0 to 250 kPa 6.7 bar 10 bar / 1 MPa
A2Q 0 to 4 bar / 0 to 400 kPa 10.7 bar 16 bar / 1.6 MPa
A2R 0 to 6 bar / 0 to 600 kPa 16 bar 24 bar / 2.4 MPa
A2S 0 to 10 bar / 0 to 1 MPa 25 bar 40 bar / 4 MPa
A2T 0 to 16 bar / 0 to 1.6 MPa 25 bar 64 bar / 6.4 MPa
A2W 0 to 25 bar / 0 to 2.5 MPa 25 bar 100 bar / 10 MPa
A2X 0 to 40 bar / 0 to 4 MPa 60 bar 160 bar / 16 MPa
R4H 0 to 15 psi 40 psi 60 psi
R4K 0 to 30 psi 100 psi 150 psi
R4N 0 to 50 psi 160 psi 240 psi
R4R 0 to 150 psi 400 psi 600 psi
R4S 0 to 300 psi 400 psi 1500 psi
R4T 0 to 500 psi 1000 psi 2400 psi

PMP135 Complete order code

22 Endress+Hauser
Cerabar T

Accessories
Welding neck with • Welding neck for flush-mounted installation of the
mm (inch)
sealing taper process connection G1 A with metallic sealing
taper (PMP135, version M)
Material: AISI 316L (1.4435)

(1.1)
27.5

(1.2)
30
Order number: 52005087
• with inspection certificate 3.1 50
Order number: 52010171 (2)
P01-PMP135xx-00-xx-00-xx-002

• Pressure sensor dummy for welding the welding


neck without any problems with order number
52005087 or 52010171
Material: CuZn
Order number: 52005272

Welding neck with • Welding neck for flush-mounted installation of the ø41 (1.6) mm (inch)
sealing surface process connection G1 A with sealing surface
G1
(PMP135, version N) ISO 228
Material: AISI 316L (1.4435)

24.6

(1.2)
29.6
(1)
Gasket (enclosed): silicone O-ring
Order number: 52001051
Ø60 –0.4
• Optional with inspection certificate 3.1 (2.4–0.02 )
Order number: 52011896 P01-PMP13xxx-00-xx-00-xx-005

Plug-in jack • Plug-in jack M 12x1, straight


Self-made connection to M 12x1 housing plug
Material: Handle body PA; Coupling nut CuZn,
nickel-plated, degree of protection (inserted): IP 67
Order number: 52006263

P01-PMP13xxx-00-xx-00-xx-003

Plug-on display • 4-digit red LED display for looping into 4 to 20 mA


PHX20/PHX21 circuit via elbow plug
DIN 43650, rotatable in 90° steps, programmable
via 2 keys
42 (1.7)

Display range: –1999 to +9999


Degree of protection: IP 65 42
Material: Housing Pa6 GF30, front screen PMMA
Voltage drop: ≤5 V (corresponds to max. 250 Ω
load) 42 42
(1.7) 48 48
(1.9)
Approval for PHX21: ATEX II 2G
Order number PHX20: 52022914 P01-PHX2xxxx-06-xx-xx-xx-002

Order number PHX21: 52022915

Endress+Hauser 23
Documentation
Field of Activities • Pressure measurement, powerful measuring devices for process pressure, differential pressure, level
and flow: FA004P/00/en

Technical Information • EMC test procedures: TI241F/00/en

Operating Instructions • Cerabar T PMC131: KA085P/00/a3


• Cerabar T PMP131: KA103P/00/a3
• Cerabar T PMP135: KA198P/00/a3

Functional Safety Manual (SIL) • Cerabar T PMP131, PMP135: SD160P/00/en

Safety Instructions Cerabar T PMC131


• ATEX II 3 G EEx nA II T4: XA191P/00/a3
Cerabar T PMP131
• ATEX II 1/2 G or 2 G EEx ib IIC T6: XA142P/00/a3
• ATEX II 3 G EEx nA II T6: XA191P/00/a3
Cerabar T PMP135
• ATEX II 1/2 G or 2 G EEx ib IIC T6: XA142P/00/a3
• ATEX II 3 G EEx nA II T6: XA191P/00/a3

Instruments International

Endress+Hauser
Instruments International AG
Kaegenstrasse 2
4153 Reinach
Switzerland

Tel. +41 61 715 81 00


Fax +41 61 715 25 00
www.endress.com
info@ii.endress.com

TI415P/00/en/07.08
71082613
CCS/FM+SGML 6.0