CHILLER PLANT EQUIPMENT LOG J MALL CEBU

DATE of Log : 08 05 2016 Daily operation : CHILLER, PUMPS, COOLING TOWER

Design 8:00 9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 0:00
EXISTING CHILLER # 3 - 650 TR - R 123
Compressor % Load, RLA, amps 84.4% 81.7% 90.1% 94.2% 97.0% 97.7% 98.0% 90.9% 96.9% 96.3% 96.2%
Compressor motor input voltage, L1 461 470 472 473 471 475 473 473 475 470 471
Compressor motor input voltage, L2 468 475 479 468 455 479 479 477 479 479 476
Compressor motor input voltage, L3 456 463 461 461 463 467 468 469 469 464 469
Compressor motor load, amps L1 439 439 438 441 444 427 325 418 439 438 436
Compressor motor load, amps L2 450 454 459 454 451 407 341 431 455 453 448
Compressor motor load, amps L3 421 423 430 429 423 381 319 402 430 440 420
Compressor motor load, kw 300 0 0 289 296 299 296 292 275 223 283 301 300 295 0 0 0 0 3149
Evaporator LVG CHW Setpoint Temp, C (F) 44 44 44 44 44 44 44 44 44 44 44
Evaporator LVG CHW Temp, C (F) 47.1 49.1 49.4 48.1 45.6 45.3 49.9 46.7 45.8 44.6 44.1
Evaporator ENT CHW Temp, C (F) 57.7 57.7 57.9 55.9 55.5 53.8 56.6 55 54.9 53.1 52.5
Chilled water temperature rise, C (F) 10 0 0 10.6 8.6 8.5 7.8 9.9 8.5 6.7 8.3 9.1 8.5 8.4 0 0 0 0

Chiller load % 100% 86% 85% 78% 99% 85% 67% 83% 91% 85% 84% 0.0% 0.0% 0.0% 0.0%
Chiller Load Tons 500.0 430.0 425.0 390.0 495.0 425.0 335.0 415.0 455.0 425.0 420.0
Kw/Ton 0.6 0.7 0.7 0.8 0.6 0.6 0.7 0.7 0.7 0.7 0.7

Actual Load Based on Actual Cond. Approach ( Kw ) 289 296 299 296 292 275 223 283 301 300 295
Actual Load Based on Ideal Cond. Approach ( Kw ) 263 269 272 270 266 251 203 258 274 273 268 2,866
Variance Load Savings ( Kw ) 26.1 26.6 26.9 26.7 26.3 24.8 20.1 25.5 27.1 27.0 26.5

New chiller kw/ton at varied load


New chiller power, kw 0

Evaporator Sat. Ref. Pressure, psig


Evaporator Sat. Ref. Temp, C (F) 45.7 47 47.1 43.9 43.7 43.3 47.8 44.9 43.7 42.4 41.9
Evaporator Approach Temp, C (F) 1.4 2.1 2.3 4.2 1.9 2 2.1 1.8 2.1 2.2 2.2
Evaporator LVG CHW pressure, psig. 20 20 20 20 20 20 20 20 20 20 20
Evaporator ENT CHW pressure, prig. 22 22 22 22 22 22 22 22 22 22 22
Condenser LVG COW Temp, C (F) 92.6 93.3 93.1 90 89.5 93.4 90.1 95.5 91.7 90.2 89.8
Condenser ENT COW Temp, C * (F) 85 85.7 85.6 83.4 82.3 86.6 83.4 88.6 84.1 82.1 82.3
Condenser Sat. Ref. Pressure, psig
Condenser Saturated Temp, C (F) 98.8 99.7 99.1 95.9 95.7 99.1 95.7 100.6 98 96.5 96.1
Condenser Approach Temp, C (F) 6.2 6.4 6 5.9 6.2 5.7 5.6 5.1 6.3 6.3 6.3
Condenser LVG COW pressure, psig.
Condenser ENT COW pressure, psig. 30 30 30 30 30 30 30 30 30 30 30

Primary CHW Pump # 18.5


CHW Pump amps, L1 30 30 30 30 30 30 30 30 30 30 30 55 55 55
CHW Pump amps, L2 28 28 28 28 28 28 28 28 28 28 28 50 50 50
CHW Pump amps, L3 37 37 37 37 37 37 37 37 37 37 37 54 54 54
CHW Pump motor kw load 0.0 0.0 21.5 21.9 21.9 21.8 21.6 22.1 22.0 22.0 22.1 21.9 22.0 37.1 37.1 37.1 0.0 352
CHW Pump motor frequency, Hz.
CHW Pump discharge pressure, psig.
CHW Pump suction pressure, psig.

New Primary Pump motor kw load 11 11 11 11 11 11 11 11 11 11 11 11 11 11 154


New Primary Pump motor % Savings 49% 50% 50% 49% 49% 50% 50% 50% 50% 50% 50% 70% 70% 70%
Savings Kw Load 10 11 11 11 11 11 11 11 11 11 11 26 26 26

Secondary CHW Pump # 55


CHW Pump amps, L1 109 109 109 109 109 109 109 109 109 109 109 109 109 109
CHW Pump amps, L2 110 110 110 110 110 110 110 110 110 110 110 110 110 110
CHW Pump amps, L3 108 108 108 108 108 108 108 108 108 108 108 108 108 108
CHW Pump motor kw load 0.0 0.0 76.6 77.9 78.1 77.6 76.8 78.6 78.5 78.5 78.7 78.2 78.3 76.3 76.3 76.3 0.0 1087
CHW Pump discharge pressure, psig.
CHW Pump suction pressure, psig.

New Secondary Pump motor kw load 18 18 18 18 18 18 18 18 18 18 18 18 18 18 252


New Secondary Pump motor % Savings 77% 77% 77% 77% 77% 77% 77% 77% 77% 77% 77% 76% 76% 76%
Savings Kw Load 58.6 59.9 60.1 59.6 58.8 60.6 60.5 60.5 60.7 60.2 60.3 58.3 58.3 58.3

COW Pump # 75
COW Pump amps, L1 55 55 55 55 55 55 55 55 55 55 55
COW Pump amps, L2 50 50 50 50 50 50 50 50 50 50 50
Design 8:00 9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 0:00
COW Pump amps, L3 54 54 54 54 54 54 54 54 54 54 54
COW Pump motor kw load 0.0 0.0 37.3 37.9 38.0 37.7 37.4 38.2 38.2 38.2 38.3 38.0 38.1 0.0 417
COW Pump motor frequency, Hz.
COW Pump discharge pressure, psig.
COW Pump suction pressure, psig.

New COW Pump motor kw load 29 29 29 29 29 29 29 29 29 29 29 320


New COW Pump motor % Savings 22% 23% 23% 23% 22% 24% 24% 24% 24% 23% 24%
Savings Kw Load 8 9 9 9 8 9 9 9 9 9 9

Cooling Tower # 1
# 1 Fan motor amps 4.67 4.67 4.67 4.67 4.67 6.00 5.00 5.00 5.00 5.00 5.00
# 2 Fan motor amps, 3.57 3.57 3.57 3.57 3.57 5.00 4.00 5.00 5.00 5.00 5.00
# 3 Fan motor amps, 3.33 3.33 3.33 3.33 3.33 5.00 4.00 4.00 4.00 4.00 4.00
# 4 Fan motor amps, 4 4 4 4
Fan motor amps load 11.57 11.57 11.57 11.57 11.57 16.00 13.00 18.00 18.00 18.00 18.00
Fan motor kw load 8.1 8.3 8.3 8.2 8.2 11.5 9.4 13.0 13.0 12.9 12.9 114

Cooling Tower # 2
# 1 Fan motor amps 9 9 9 9
# 2 Fan motor amps, 9 9
# 3 Fan motor amps,
# 4 Fan motor amps, 3.93 3.93 3.93 3.93 3.93 8.00 7.00 8.00 8.00 8.00 8.00
Fan motor amps load 3.93 3.93 3.93 3.93 3.93 8.00 7.00 17.00 17.00 26.00 26.00
Fan motor kw load 2.8 2.8 2.8 2.8 2.8 5.8 5.0 12.2 12.3 18.6 18.7 87

Cooling Tower # 3
# 1 Fan motor amps
# 2 Fan motor amps, 20.33 20.33 20.33 20.33
# 3 Fan motor amps,
# 4 Fan motor amps, 15.33 15.33 15.33 15.33
Fan motor amps load
Fan motor kw load 0.0 0.0 0.0 0.0 0

Cooling Tower # 4
# 1 Fan motor amps 5 3 3 3 3 3
# 2 Fan motor amps,
# 3 Fan motor amps, 8 8 8 8
# 4 Fan motor amps,
Fan motor amps load 0 0 0 0 0 5 3 11 11 11 11
Fan motor kw load 0.0 0.0 0.0 0.0 0.0 3.6 2.2 7.9 7.9 7.9 7.9 37

Actual Consumption for all Cooling Towers Kw 10.9 11.1 11.1 11.0 10.9 20.9 16.6 33.1 33.2 39.4 39.5 238
Ideal Cooling Tower for One Chiller Kw 17.6 17.6 17.6 17.6 17.6 17.6 17.6 17.6 17.6 17.6 17.6 194
Savings for Ideal Cooling Tower % -38% -37% -37% -37% -38% 19% -6% 88% 89% 124% 125%
Savings Variance Kw -6.7 -6.5 -6.5 -6.6 -6.7 3.3 -1.0 15.5 15.6 21.8 21.9

Total Kw 0 0 436 444 448 444 439 435 379 455 473 478 473 113 113 113 0
Total Tons 500 430 425 390 495 425 335 415 455 425 420
Actual Load based on Max Chiller Capacity Kw/ton 0.00 0.00 0.87 1.03 1.05 1.14 0.89 1.02 1.13 1.10 1.04 1.12 1.13 0.00

DAILY KWHR as per amps reading 5243

DAILY KWHR FOR WEEKDAYS OPERATION 5243 , Annual KWHR operation 1,363,211 RETROFITTED C.T. & PUMPS DAILY KWHR OPERATION 920 , Annual KWHR operation 239,122
CHILLER COMPRESSOR DAILY KWHR FOR WEEKDAYS 3149 Annual KWHR operation 818,827 CLEAN TUBES CHILLER COMPRESSOR DAILY KWHR OPERATION 2866 , Annual KWHR operation 745,133
PUMPS & COOLING TOWER DAILY KWHR FOR WEEKDAYS 2094 , Annual KWHR operation 544,384 RETROFITTED PUMPS DAILY KWHR OPERATION 726 , Annual KWHR operation 188,786
OPERATION
PUMPS DAILY KWHR OPERATION 1856 , Annual KWHR operation 482,552 RETROFITTED COOLING TOWER DAILY KWHR OPERATION 194 , Annual KWHR operation 50,336
COOLING TOWER DAILY KWHR OPERATION 238 , Annual KWHR operation 61,832

Legend:
COW: Condenser Water ENT: Entering
CHW : Chilled Water LVG: Leaving
CHILLER PLANT EQUIPMENT LOG J MALL CEBU
DATE of Log : 08 06 2016 Daily operation : CHILLER, PUMPS, COOLING TOWER

EXISTING CHILLER # 1 - 650 TR - R 123 Design 8:00 9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 0:00 1:00 2:00 3:00 4:00 5:00 6:00 7:00
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Compressor % Load, RLA, amps 88.5% 94.7% 94.8% 94.6% 95.1% 91.5% 89.4% 86.8% 90.1% 90.2% 89.3%
Compressor motor input voltage, L1 465 469 466 465 470 474 476 475 479 475 470
Compressor motor input voltage, L2 469 472 470 468 474 478 479 475 474 478 471
Compressor motor input voltage, L3 462 466 461 411 466 471 474 473 470 471 464
Compressor motor load, amps L1 410 430 424 464 428 428 417 402 412 407 406
Compressor motor load, amps L2 407 454 454 470 454 452 439 426 432 429 424
Compressor motor load, amps L3 386 409 411 460 412 415 436 411 396 388 485
Compressor motor load, kw 0 0 268 290 287 299 291 294 294 281 282 278 295 0 0 0 0 0 0 0 0 0 0 0 3159
Evaporator LVG CHW Setpoint Temp, C (F) 44 44 44 44 44 44 44 44 44 44 44
Evaporator LVG CHW Temp, C (F) 44 44.7 46.4 46.3 46.9 45.25 43.9 43.95 43.9 43.9 43.9
Evaporator ENT CHW Temp, C (F) 53.4 53.7 54.9 54.8 55.3 53.85 52.3 52.1 52 52 51.8
Chilled water temperature rise, C (F) 10 0 0 9.4 9 8.5 8.5 8.4 8.6 8.4 8.15 8.1 8.1 7.9 0 0 0 0 0 0 0 0 0 0 0

Temp variance from set point, C (F) 0 0 0 -0.7 -2.4 -2.3 -2.9 -1.25 0.1 0.05 0.1 0.1 0.1 0 0 0 0 0 0 0 0 0 0 0
Chiller load 94.0% 90.0% 85.0% 85.0% 84.0% 86.0% 84.0% 81.5% 81.0% 81.0% 79.0%

New chiller kw/ton at varied load


New chiller power, kw 0

Evaporator Sat. Ref. Pressure, psig


Evaporator Sat. Ref. Temp, C (F)
Evaporator LVG CHW pressure, psig. 12 12 12 12 12 12 12
Evaporator ENT CHW pressure, prig. 25 30 30 30 30 30 30 30
Condenser LVG COW Temp, C (F) 89.5 91.4 92.3 92.2 92.9 91.1 84.9 88.9
Condenser ENT COW Temp, C * (F) 82.1 83.1 84.3 84.3 85 83.1 81.5 81.4
Condenser Sat. Ref. Pressure, psig
Condenser Saturated Temp, C (F) 94.8 96.9 98 98 98.6 96.9 95.1 94.4
Condenser LVG COW pressure, psig. 20 20 20 20 20 20 20 20
Condenser ENT COW pressure, psig. 23 25 25 25 25 25 25 25

Primary CHW Pump #


CHW Pump amps, L1 30 30 30 30 30 30 30 30 30 30 30
CHW Pump amps, L2 28 28 28 28 28 28 28 28 28 28 28
CHW Pump amps, L3 37 37 37 37 37 37 37 37 37 37 37
CHW Pump motor kw load 0.0 0.0 22 22 22 21 22 22 22 22 22 22 22 0 0 0 0 0 0 0 0 0 0 0 240
CHW Pump motor frequency, Hz.
CHW Pump discharge pressure, psig.
CHW Pump suction pressure, psig.

Secondary CHW Pump #


CHW Pump amps, L1 109 109 109 109 109 109 109 109 109 109 109 109 109 109
CHW Pump amps, L2 110 110 110 110 110 110 110 110 110 110 110 110 110 110
CHW Pump amps, L3 108 108 108 108 108 108 108 108 108 108 108 108 108 108
CHW Pump motor kw load 0 77 78 77 74 78 79 79 79 79 79 78 76 76 76 0 0 0 0 0 0 0 0 1085
CHW Pump discharge pressure, psig.
CHW Pump suction pressure, psig.

COW Pump #
COW Pump amps, L1 55 55 55 55 55 55 55 55 55 55 55 55 55 55
COW Pump amps, L2 50 50 50 50 50 50 50 50 50 50 50 50 50 50
COW Pump amps, L3 54 54 54 54 54 54 54 54 54 54 54 54 54 54
COW Pump motor kw load 0.0 0.0 37 37 37 36 37 38 38 38 38 38 37 37 37 37 0 0 0 0 0 0 0 0 522
COW Pump motor frequency, Hz.
COW Pump discharge pressure, psig.
COW Pump suction pressure, psig.

Cooling Tower # 1
# 1 Fan motor amps 33 33 33 33 33 5.00 5 5
# 2 Fan motor amps, 20.33 20.33 20.33 20.33 20.33 3.00 3 3 3 3 3
# 3 Fan motor amps, 15.33 15.33 15.33 15.33 15.33 4.00 4 4
# 4 Fan motor amps, 15.33 15.33 15.33 15.33 15.33 3.00 3 3 3 3 3
Fan motor amps load 84.00 84.00 84.00 84.00 84.00 15 15 15 6 6 6 0 0 0 0 0 0 0 0 0 0 0
Fan motor kw load 59.5 60.0 59.6 57.3 60.1 10.83 10.88 10.83 4.33 4.34 4.28 342

Cooling Tower # 2
# 1 Fan motor amps
# 2 Fan motor amps, 14.00 14 14 12 12 12
# 3 Fan motor amps,
# 4 Fan motor amps, 6.00 6 6 5 5 5
Fan motor amps load 0 0 0 0 0 20 20 20 17 17 17 0 0 0 0 0 0 0 0 0 0 0
Fan motor kw load 14.44 14.50 14.44 12.28 12.28 12.12 80
Cooling Tower # 3
# 1 Fan motor amps
# 2 Fan motor amps, 5 5 5 5 5 5
# 3 Fan motor amps,
# 4 Fan motor amps, 9 9 9 9 9 9
Fan motor amps load 0 0 0 0 0 14 14 14 14 14 14 0 0 0 0 0 0 0 0 0 0 0
Fan motor kw load 10.11 10.15 10.11 10.11 10.12 9.98 61

Cooling Tower # 4
# 1 Fan motor amps 4 4 4 4 4 4
# 2 Fan motor amps,
# 3 Fan motor amps, 7 7 7 7 7 7
# 4 Fan motor amps,
Fan motor amps load 0 0 0 0 0 11 11 11 11 11 11 0 0 0 0 0 0 0 0 0 0 0
Fan motor kw load 0.00 0.00 0.00 0.00 0.00 7.94 7.98 7.94 7.94 7.95 7.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 48

Total Kw 0 0 463 487 483 487 489 476 477 463 455 452 466 113 113 113 0 0 0 0 0 0 0 0
Actual Kw/ton based on Compressor Load % RLA 0.00 0.00 1.05 1.03 1.02 1.03 1.03 1.04 1.07 1.07 1.01 1.00 1.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Actual Kw/ton based on Compressor Load % RLA

DAILY KWHR as per amps reading 5536

Legend:
COW: Condenser Water ENT: Entering Period when second chiller is operated when chilled water supply temperature is high.
CHW : Chilled Water LVG: Leaving Period when the chilled water supply temperature is below the set point of 7 degrees C.
CHILLER PLANT EQUIPMENT LOG J MALL CEBU
DATE of Log : 08 06 2016 Daily operation : CHILLER, PUMPS, COOLING TOWER

Design 8:00 9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 0:00
EXISTING CHILLER # 1 - 650 TR - R 123
Compressor % Load, RLA, amps 88.5% 94.7% 94.8% 94.6% 95.1% 88.2% 87.3% 83.5%
Compressor motor input voltage, L1 465 469 466 465 470 472 477 474
Compressor motor input voltage, L2 469 472 470 468 474 476 479 478
Compressor motor input voltage, L3 462 466 461 411 466 469 474 471
Compressor motor load, amps L1 410 430 424 464 428 431 420 399
Compressor motor load, amps L2 407 454 454 470 454 453 444 423
Compressor motor load, amps L3 386 409 411 460 412 418 474 384
Compressor motor load, kw 300 0 0 284 308 305 317 309 312 324 290 0 0 0 0 0 0 0 2448
Evaporator LVG CHW Setpoint Temp, C (F) 44 44 44 44 44 44 44 44
Evaporator LVG CHW Temp, C (F) 44 44.7 46.4 46.3 46.9 45.2 43.9 44
Evaporator ENT CHW Temp, C (F) 53.4 53.7 54.9 54.8 55.3 53.8 52.4 52.1
Chilled water temperature rise, C (F) 10 0 0 9.4 9 8.5 8.5 8.4 8.6 8.5 8.1 0 0 0 0 0 0 0

Chiller load % 94.0% 90.0% 85.0% 85.0% 84.0% 86.0% 85.0% 81.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0%
Chiller Load Tons 470.0 450.0 425.0 425.0 420.0 430.0 425.0 405.0
Kw/Ton 0.60 0.68 0.72 0.75 0.73 0.73 0.76 0.72

Actual Load Based on Actual Cond. Approach ( Kw ) 284 308 305 317 309 312 324 290
Actual Load Based on Ideal Cond. Approach ( Kw ) 257 278 275 287 279 282 293 263 2,214
Variance Load Savings ( Kw ) 27 29 29 30 30 30 31 28

New chiller kw/ton at varied load


New chiller power, kw 0

Evaporator Sat. Ref. Pressure, psig


Evaporator Sat. Ref. Temp, C (F) 43.1 43.7 45.4 45.5 46 44.2 42.8 43
Evaporator Approach Temp, C (F) 0.9 1 1 0.8 0.9 1 1.1 1
Evaporator LVG CHW pressure, psig. 0 12 12 12 12 12 12 12
Evaporator ENT CHW pressure, prig. 25 30 30 30 30 30 30 30
Condenser LVG COW Temp, C (F) 89.5 91.4 92.3 92.2 92.9 91.1 84.9 88.9
Condenser ENT COW Temp, C * (F) 82.1 83.1 84.3 84.3 85 83.1 81.5 81.4
Condenser Sat. Ref. Pressure, psig 0 0 0 0 0 0 0 0
Condenser Saturated Temp, C (F) 94.8 96.9 98 98 98.6 96.9 95.1 94.4
Condenser Approach Temp, C (F) 5.3 5.5 5.7 5.8 5.7 5.8 10.2 5.5
Condenser LVG COW pressure, psig. 20 20 20 20 20 20 20 20
Condenser ENT COW pressure, psig. 23 25 25 25 25 25 25 25

Primary CHW Pump # 18.5


CHW Pump amps, L1 30 30 30 30 30 30 30 30
CHW Pump amps, L2 28 28 28 28 28 28 28 28
CHW Pump amps, L3 37 37 37 37 37 37 37 37
CHW Pump motor kw load 0.0 0.0 22.4 22.6 22.4 21.6 22.7 22.8 23.0 22.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 180
CHW Pump motor frequency, Hz.
CHW Pump discharge pressure, psig.
CHW Pump suction pressure, psig.

New Primary Pump motor kw load 11 11 11 11 11 11 11 11 0 0 0 88


New Primary Pump motor % Savings 49% 50% 49% 47% 50% 50% 50% 50% 0% 0% 0%
Savings Kw Load 11 11 11 10 11 11 11 11 0 0 0

Secondary CHW Pump # 55


CHW Pump amps, L1 109 109 109 109 109 109 109 109
CHW Pump amps, L2 110 110 110 110 110 110 110 110
CHW Pump amps, L3 108 108 108 108 108 108 108 108
CHW Pump motor kw load 0.0 0.0 77.2 77.8 77.3 74.3 78.0 78.4 79.1 78.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 621
CHW Pump discharge pressure, psig.
CHW Pump suction pressure, psig.

New Secondary Pump motor kw load 18 18 18 18 18 18 18 18 144


New Secondary Pump motor % Savings 77% 77% 77% 76% 77% 77% 77% 77%
Savings Kw Load 59.2 59.8 59.3 56.3 60.0 60.4 61.1 60.7

COW Pump # 75
COW Pump amps, L1 55 55 55 55 55 55 55 55
COW Pump amps, L2 50 50 50 50 50 50 50 50
Design 8:00 9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 0:00
COW Pump amps, L3 54 54 54 54 54 54 54 54
COW Pump motor kw load 0.0 0.0 37.5 37.8 37.6 36.1 37.9 38.1 38.5 38.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 302
COW Pump motor frequency, Hz.
COW Pump discharge pressure, psig.
COW Pump suction pressure, psig.

New COW Pump motor kw load 29 29 29 29 29 29 29 29 233


New COW Pump motor % Savings 22% 23% 22% 19% 23% 24% 24% 24%
Savings Kw Load 8 9 8 7 9 9 9 9

Cooling Tower # 1
# 1 Fan motor amps 33.0 33.0 33.0 33.0 33.0
# 2 Fan motor amps, 20.3 20.3 20.3 20.3 20.3
# 3 Fan motor amps, 15.3 15.3 15.3 15.3 15.3
# 4 Fan motor amps, 15.3 15.3 15.3 15.3 15.3
Fan motor amps load 84.00 84.00 84.00 84.00 84.00
Fan motor kw load 59.5 60.0 59.6 57.3 60.1 296

Cooling Tower # 2
# 1 Fan motor amps 0.0 0.0 0.0 0.0 0.0
# 2 Fan motor amps, 0.0 0.0 0.0 0.0 0.0
# 3 Fan motor amps, 0.0 0.0 0.0 0.0 0.0
# 4 Fan motor amps, 0.0 0.0 0.0 0.0 0.0
Fan motor amps load
Fan motor kw load 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Cooling Tower # 3
# 1 Fan motor amps 0.0 0.0 0.0 0.0 0.0
# 2 Fan motor amps, 0.0 0.0 0.0 0.0 0.0
# 3 Fan motor amps, 0.0 0.0 0.0 0.0 0.0
# 4 Fan motor amps, 0.0 0.0 0.0 0.0 0.0
Fan motor amps load
Fan motor kw load 0.0 0.0 0.0 0.0 0.0

Cooling Tower # 4
# 1 Fan motor amps 0.0 0.0 0.0 0.0 0.0
# 2 Fan motor amps, 0.0 0.0 0.0 0.0 0.0
# 3 Fan motor amps, 0.0 0.0 0.0 0.0 0.0
# 4 Fan motor amps, 0.0 0.0 0.0 0.0 0.0
Fan motor amps load
Fan motor kw load 0.0 0.0 0.0 0.0 0.0 0.0

Actual Consumption for all Cooling Towers Kw 0.0 0.0 59.5 60.0 59.6 57.3 60.1 0.0 0.0 0.0 0.0 0.0 0.0
Ideal Cooling Tower for One Chiller Kw 17.6 17.6 17.6 17.6 17.6 88
Savings for Ideal Cooling Tower % 238% 241% 238% 226% 242%
Savings Variance Kw 41.9 42.4 42.0 39.7 42.5

EXISTING CHILLER # 3 - 650 TR - R 123

Compressor % Load, RLA, amps 94.7% 91.5% 90.0% 90.1% 90.2% 89.3%
Compressor motor input voltage, L1 475 475 476 479 475 470
Compressor motor input voltage, L2 480 479 475 474 478 471
Compressor motor input voltage, L3 473 474 474 470 471 464
Compressor motor load, amps L1 425 413 404 412 407 406
Compressor motor load, amps L2 451 434 429 432 429 424
Compressor motor load, amps L3 412 397 437 396 388 485
Compressor motor load, kw 300 0 0 0 0 0 0 0 311 300 306 298 295 313 0 0 0 0 1824
Evaporator LVG CHW Setpoint Temp, C (F) 44 44 44 44 44 44
Evaporator LVG CHW Temp, C (F) 45.3 43.9 43.9 43.9 43.9 43.9
Evaporator ENT CHW Temp, C (F) 53.9 52.2 52.1 52 52 51.8
Chilled water temperature rise, C (F) 10 0 0 0 0 0 0 0 8.6 8.3 8.2 8.1 8.1 7.9 0 0 0 0

Chiller load % 0.0% 0.0% 0.0% 0.0% 0.0% 86.0% 83.0% 82.0% 81.0% 81.0% 79.0%
Chiller Load Tons 430.0 415.0 410.0 405.0 405.0 395.0
Kw/Ton 0.72 0.72 0.75 0.74 0.73 0.79

Actual Load Based on Actual Cond. Approach ( Kw ) 311 300 306 298 295 313
Actual Load Based on Ideal Cond. Approach ( Kw ) 287 278 283 276 273 290 1,688
Variance Load Savings( Kw ) 24 23 23 22 22 23
Design 8:00 9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 0:00

New chiller kw/ton at varied load


New chiller power, kw 0

Evaporator Sat. Ref. Pressure, psig


Evaporator Sat. Ref. Temp, C (F) 44.3 42.9 42.9 42.9 42.8 43
Evaporator Approach Temp, C (F) 1 1 1 1 1.1 0.9
Evaporator LVG CHW pressure, psig. 17 17 17 17 17 17
Evaporator ENT CHW pressure, prig. 24 24 24 24 24 24
Condenser LVG COW Temp, C (F) 91 89.6 89 89.8 89.9 89.6
Condenser ENT COW Temp, C * (F) 82.9 81.9 81.4 82.3 82.4 82.2
Condenser Sat. Ref. Pressure, psig
Condenser Saturated Temp, C (F) 96.7 95.1 94.5 95.4 95.4 95
Condenser Approach Temp, C (F) 0 0 0 0 0 5.7 5.5 5.5 5.6 5.5 5.4
Condenser LVG COW pressure, psig. 14 14 14 14 14 14
Condenser ENT COW pressure, psig. 33 33 33 33 33 33

Primary CHW Pump #


CHW Pump amps, L1 44 44 44 41 41 41 58 58 58
CHW Pump amps, L2 44 44 44 41 41 41 58 58 58
CHW Pump amps, L3 44 44 44 41 41 41 58 58 58
CHW Pump motor kw load 0.0 0.0 0 0 0 0 0 32 32 32 30 30 29 41 41 41 0 306
CHW Pump motor frequency, Hz.
CHW Pump discharge pressure, psig.
CHW Pump suction pressure, psig.

New Primary Pump motor kw load 11 11 11 11 11 11 66


New Primary Pump motor % Savings 65% 65% 65% 63% 63% 62%
Savings Kw Load 21 21 21 19 19 18

Secondary CHW Pump #


CHW Pump amps, L1 134 140 142 135 135 135 135 135 135
CHW Pump amps, L2 134 140 142 135 135 135 135 135 135
CHW Pump amps, L3 134 140 142 135 135 135 135 135 135
CHW Pump motor kw load 0 0 0 0 0 0 97 101 103 97 98 96 95 95 95 0 876
CHW Pump discharge pressure, psig.
CHW Pump suction pressure, psig.

New Secondary Pump motor kw load 18 18 18 18 18 18 18 18 18 162


New Secondary Pump motor % Savings 81% 82% 82% 82% 82% 81% 81% 81% 81%
Savings Kw Load 79.1 83.5 84.7 79.5 79.6 78.3 76.5 76.5 76.5

COW Pump #
COW Pump amps, L1 58 59 59 58 58 58
COW Pump amps, L2 58 59 59 58 58 58
COW Pump amps, L3 58 59 59 58 58 58
COW Pump motor kw load 0 0 0 0 0 0 42 42 42 41 41 41 0 0 0 0 250
COW Pump motor frequency, Hz.
COW Pump discharge pressure, psig.
COW Pump suction pressure, psig.

New COW Pump motor kw load 29 29 29 29 29 29 0 175


New COW Pump motor % Savings 31% 32% 32% 30% 31% 30% 0%
Savings Kw Load 13 14 14 13 13 12 0

Cooling Tower # 1
# 1 Fan motor amps 5 5 5 0 0 0
# 2 Fan motor amps, 3 3 3 3 3 3
# 3 Fan motor amps, 4 4 4 0 0 0
# 4 Fan motor amps, 3 3 3 3 3 3
Fan motor amps load 0 0 0 0 0 15 15 15 6 6 6 0 0 0 0
Fan motor kw load 10.87 10.87 10.85 4.33 4.34 4.28 46

Cooling Tower # 2
# 1 Fan motor amps 0 0 0 0 0 0
# 2 Fan motor amps, 14 14 14 12 12 12
# 3 Fan motor amps, 0 0 0 0 0 0
# 4 Fan motor amps, 6 6 6 5 5 5
Fan motor amps load 0 0 0 0 0 20 20 20 17 17 17 0 0 0 0
Design 8:00 9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 0:00
Fan motor kw load 14.49 14.49 14.46 12.28 12.28 12.12 80

Cooling Tower # 3
# 1 Fan motor amps 0 0 0 0 0 0
# 2 Fan motor amps, 5 5 5 5 5 5
# 3 Fan motor amps, 0 0 0 0 0 0
# 4 Fan motor amps, 9 9 9 9 9 9
Fan motor amps load 0 0 0 0 0 14 14 14 14 14 14 0 0 0 0
Fan motor kw load 10.15 10.15 10.12 10.11 10.12 9.98 61

Cooling Tower # 4
# 1 Fan motor amps 4 4 4 4 4 4
# 2 Fan motor amps, 0 0 0 0 0 0
# 3 Fan motor amps, 7 7 7 7 7 7
# 4 Fan motor amps, 0 0 0 0 0 0
Fan motor amps load 0 0 0 0 0 11 11 11 11 11 11 0 0 0 0
Fan motor kw load 0.00 0.00 0.00 0.00 0.00 7.97 7.97 7.95 7.94 7.95 7.84 0.00 0.00 0.00 0.00 48

Actual Consumption for all Cooling Towers Kw 0.0 0.0 59.5 60.0 59.6 57.3 60.1 32.6 43.5 43.4 41.2 34.7 34.3 526
Ideal Cooling Tower for One Chiller Kw 17.6 17.6 17.6 17.6 17.6 17.6 17.6 17.6 17.6 17.6 17.6 194
Savings for Ideal Cooling Tower % 238% 241% 238% 226% 242% 85% 147% 147% 134% 97% 95%
Savings Variance Kw 41.9 42.4 42.0 39.7 42.5 15.0 25.9 25.8 23.6 17.1 16.7

Total Kw 0 0 481 506 501 506 507 976 984 956 502 498 513 135 135 135 0
Total Tons 470 450 425 425 420 860 840 815 405 405 395
Combined Load based on Max Chiller Capacity Kw/ton 0.00 0.00 1.02 1.12 1.18 1.19 1.21 1.14 1.17 1.17 1.24 1.23 1.30 0.00

DAILY KWHR as per amps reading 7337

DAILY KWHR FOR WEEKEND OPERATION 7,337 , Annual KWHR operation 763,029 RETROFITTED C.T. & PUMPS DAILY KWHR OPERATION 1,061 , Annual KWHR operation 110,382
CHILLER COMPRESSOR DAILY KWHR FOR WEEKDAYS 4,272 , Annual KWHR operation 444,244 CLEAM TUBES CHILLER COMPRESSOR DAILY KWHR OPERATION 3,902 , Annual KWHR operation 405,786
PUMPS & COOLING TOWER DAILY KWHR FOR WEEKDAYS 3,065 Annual
, KWHR operation 318,785 RETROFITTED PUMPS DAILY KWHR OPERATION 868 , Annual KWHR operation 90,247
OPERATION
PUMPS DAILY KWHR OPERATION 2535 , Annual KWHR operation 263,628 RETROFITTED COOLING TOWER DAILY KWHR OPERATION 194 , Annual KWHR operation 20,134
COOLING TOWER DAILY KWHR OPERATION 526 , Annual KWHR operation 54,711 ,

Legend:
COW: Condenser Water ENT: Entering
CHW : Chilled Water LVG: Leaving
CHILLER PLANT EQUIPMENT LOG J MALL CEBU
DATE of Log : 08 06 2016 Daily operation : CHILLER, PUMPS, COOLING TOWER

EXISTING CHILLER # 1 - 650 TR - R 123 Design 8:00 9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 0:00

Compressor % Load, RLA, amps 88.5% 94.7% 94.8% 94.6% 95.1% 88.2% 87.3% 83.5%
Compressor motor input voltage, L1 465 469 466 465 470 472 477 474
Compressor motor input voltage, L2 469 472 470 468 474 476 479 478
Compressor motor input voltage, L3 462 466 461 411 466 469 474 471
Compressor motor load, amps L1 410 430 424 464 428 431 420 399
Compressor motor load, amps L2 407 454 454 470 454 453 444 423
Compressor motor load, amps L3 386 409 411 460 412 418 474 384
Compressor motor load, kw 300 0 0 284 308 305 317 309 312 324 290 0 0 0 0 0 0 0 2448
Evaporator LVG CHW Setpoint Temp, C (F) 44 44 44 44 44 44 44 44
Evaporator LVG CHW Temp, C (F) 44 44.7 46.4 46.3 46.9 45.2 43.9 44
Evaporator ENT CHW Temp, C (F) 53.4 53.7 54.9 54.8 55.3 53.8 52.4 52.1
Chilled water temperature rise, C (F) 10 0 0 9.4 9 8.5 8.5 8.4 8.6 8.5 8.1 0 0 0 0 0 0 0

Chiller load % 94.0% 90.0% 85.0% 85.0% 84.0% 86.0% 85.0% 81.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0%
Chiller Load Tons 470.0 450.0 425.0 425.0 420.0 430.0 425.0 405.0
Kw/Ton 0.6 0.7 0.7 0.7 0.7 0.7 0.8 0.7

Actual Load Based on Actual Cond. Approach ( Kw ) 284 308 305 317 309 312 324 290
Actual Load Based on Ideal Cond. Approach ( Kw ) 257 278 275 287 279 282 293 263
Variance Load Savings ( Kw ) 27 29 29 30 30 30 31 28

New chiller kw/ton at varied load


New chiller power, kw 0

Evaporator Sat. Ref. Pressure, psig


Evaporator Sat. Ref. Temp, C (F) 43.1 43.7 45.4 45.5 46 44.2 42.8 43
Evaporator Approach Temp, C (F) 0.9 1 1 0.8 0.9 1 1.1 1
Evaporator LVG CHW pressure, psig. 12 12 12 12 12 12 12
Evaporator ENT CHW pressure, prig. 25 30 30 30 30 30 30 30
Condenser LVG COW Temp, C (F) 89.5 91.4 92.3 92.2 92.9 91.1 84.9 88.9
Condenser ENT COW Temp, C * (F) 82.1 83.1 84.3 84.3 85 83.1 81.5 81.4
Condenser Sat. Ref. Pressure, psig
Condenser Saturated Temp, C (F) 94.8 96.9 98 98 98.6 96.9 95.1 94.4
Condenser Approach Temp, C (F) 5.3 5.5 5.7 5.8 5.7 5.8 10.2 5.5
Condenser LVG COW pressure, psig. 20 20 20 20 20 20 20 20
Condenser ENT COW pressure, psig. 23 25 25 25 25 25 25 25

Primary CHW Pump # 18.5


CHW Pump amps, L1 30 30 30 30 30 30 30 30 30 30 30
CHW Pump amps, L2 28 28 28 28 28 28 28 28 28 28 28
CHW Pump amps, L3 37 37 37 37 37 37 37 37 37 37 37
CHW Pump motor kw load 0.0 0.0 21.7 21.8 21.7 20.9 21.9 22.0 22.2 22.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 174
CHW Pump motor frequency, Hz.
CHW Pump discharge pressure, psig.
CHW Pump suction pressure, psig.

New Primary Pump motor kw load 11 11 11 11 11 11 11 11


New Primary Pump motor % Savings 49% 50% 49% 47% 50% 50% 50% 50%
Savings Kw Load 11 11 11 10 11 11 11 11

Secondary CHW Pump # 55


CHW Pump amps, L1 109 109 109 109 109 109 109 109
CHW Pump amps, L2 110 110 110 110 110 110 110 110
CHW Pump amps, L3 108 108 108 108 108 108 108 108
CHW Pump motor kw load 0.0 0.0 77.2 77.8 77.3 74.3 78.0 78.4 79.1 78.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 621
CHW Pump discharge pressure, psig.
CHW Pump suction pressure, psig.

New Secondary Pump motor kw load 18 18 18 18 18 18 18 18


New Secondary Pump motor % Savings 77% 77% 77% 76% 77% 77% 77% 77%
Savings Kw Load 59 60 59 56 60 60 61 61

COW Pump # 75
COW Pump amps, L1 55 55 55 55 55 55 55 55
COW Pump amps, L2 50 50 50 50 50 50 50 50
COW Pump amps, L3 54 54 54 54 54 54 54 54
COW Pump motor kw load 0.0 0.0 37.5 37.8 37.6 36.1 37.9 38.1 38.5 38.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 302
COW Pump motor frequency, Hz.
COW Pump discharge pressure, psig.
COW Pump suction pressure, psig.

New COW Pump motor kw load 29 29 29 29 29 29 29 29


New COW Pump motor % Savings 22% 23% 22% 19% 23% 24% 24% 24%
Savings Kw Load 8 9 8 7 9 9 9 9

Cooling Tower # 1
# 1 Fan motor amps 33 33 33 33 33
# 2 Fan motor amps, 20.33 20.33 20.33 20.33 20.33
# 3 Fan motor amps, 15.33 15.33 15.33 15.33 15.33
# 4 Fan motor amps, 15.33 15.33 15.33 15.33 15.33
Fan motor amps load 84.00 84.00 84.00 84.00 84.00
Fan motor kw load 59.5 60.0 59.6 57.3 60.1 296

Cooling Tower # 2
# 1 Fan motor amps
# 2 Fan motor amps,
# 3 Fan motor amps,
# 4 Fan motor amps,
Fan motor amps load
Fan motor kw load 0.0 0.0 0.0 0.0 0.0

Cooling Tower # 3
# 1 Fan motor amps
# 2 Fan motor amps,
# 3 Fan motor amps,
# 4 Fan motor amps,
Fan motor amps load
Fan motor kw load 0.0 0.0 0.0 0.0 0.0

Cooling Tower # 4
# 1 Fan motor amps
# 2 Fan motor amps,
# 3 Fan motor amps,
# 4 Fan motor amps,
Fan motor amps load
Fan motor kw load 0.0 0.0 0.0 0.0 0.0

Total Kw 0 0 480 505 501 506 507 451 463 429 0 0 0 0 0 0 0


Total Tons 470 450 425 425 420 430 425 405
Actual Load based on Max Chiller Capacity Kw/ton 0.00 0.00 1.02 1.12 1.18 1.19 1.21 1.05 1.09 1.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00

DAILY KWHR as per amps reading 3841

DAILY KWHR FOR WEEKEND OPERATION 3,841 , Annual KWHR operation 399,502

Legend:
COW: Condenser Water ENT: Entering
CHW : Chilled Water LVG: Leaving
CHILLER PLANT EQUIPMENT LOG J MALL CEBU
DATE of Log : 08 06 2016 Daily operation : CHILLER, PUMPS, COOLING TOWER

EXISTING CHILLER # 3 - 650 TR - R 123 Design 8:00 9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 0:00

Compressor % Load, RLA, amps 94.7% 91.5% 90.0% 90.1% 90.2% 89.3%
Compressor motor input voltage, L1 475 475 476 479 475 470
Compressor motor input voltage, L2 480 479 475 474 478 471
Compressor motor input voltage, L3 473 474 474 470 471 464
Compressor motor load, amps L1 425 413 404 412 407 406
Compressor motor load, amps L2 451 434 429 432 429 424
Compressor motor load, amps L3 412 397 437 396 388 485
Compressor motor load, kw 300 0 0 0 0 0 0 0 311 300 306 298 295 313 0 0 0 0 1824
Evaporator LVG CHW Setpoint Temp, C (F) 44 44 44 44 44 44
Evaporator LVG CHW Temp, C (F) 45.3 43.9 43.9 43.9 43.9 43.9
Evaporator ENT CHW Temp, C (F) 53.9 52.2 52.1 52 52 51.8
Chilled water temperature rise, C (F) 10 0 0 0 0 0 0 0 8.6 8.3 8.2 8.1 8.1 7.9 0 0 0 0

Chiller load % 0.0% 0.0% 0.0% 0.0% 0.0% 86.0% 83.0% 82.0% 81.0% 81.0% 79.0%
Chiller load Tons 430.0 415.0 410.0 405.0 405.0 395.0
Kw/Ton 0.7 0.7 0.7 0.7 0.7 0.8

Actual Load Based on Actual Cond. Approach ( Kw ) 311 300 306 298 295 313
Actual Load Based on Ideal Cond. Approach ( Kw ) 287 278 283 276 273 290
Variance Load Savings ( Kw ) 24 23 23 22 22 23

New chiller kw/ton at varied load


New chiller power, kw 0

Evaporator Sat. Ref. Pressure, psig


Evaporator Sat. Ref. Temp, C (F) 44.3 42.9 42.9 42.9 42.8 43
Evaporator Approach Temp, C (F) 1 1 1 1 1.1 0.9
Evaporator LVG CHW pressure, psig. 17 17 17 17 17 17
Evaporator ENT CHW pressure, prig. 24 24 24 24 24 24
Condenser LVG COW Temp, C (F) 91 89.6 89 89.8 89.9 89.6
Condenser ENT COW Temp, C * (F) 82.9 81.9 81.4 82.3 82.4 82.2
Condenser Sat. Ref. Pressure, psig
Condenser Saturated Temp, C (F) 96.7 95.1 94.5 95.4 95.4 95
Condenser Approach Temp, C (F) 5.7 5.5 5.5 5.6 5.5 5.4
Condenser LVG COW pressure, psig. 14 14 14 14 14 14
Condenser ENT COW pressure, psig. 33 33 33 33 33 33

Primary CHW Pump # 18.5


CHW Pump amps, L1 44 44 44 41 41 41 58 58 58
CHW Pump amps, L2 44 44 44 41 41 41 58 58 58
CHW Pump amps, L3 44 44 44 41 41 41 58 58 58
CHW Pump motor kw load 0.0 0.0 0 0 0 0 0 32 32 32 30 30 29 41 41 41 0.0 306
CHW Pump motor frequency, Hz.
CHW Pump discharge pressure, psig.
CHW Pump suction pressure, psig.

New Primary Pump motor kw load 11 11 11 11 11 11


New Primary Pump motor % Savings 65% 65% 65% 63% 63% 62%
Savings Kw Load 21 21 21 19 19 18

Secondary CHW Pump # 55


CHW Pump amps, L1 134 140 142 135 135 135 135 135 135
CHW Pump amps, L2 134 140 142 135 135 135 135 135 135
CHW Pump amps, L3 134 140 142 135 135 135 135 135 135
CHW Pump motor kw load 0 0 0 0 0 0 97 101 103 97 98 96 95 95 95 0 876
CHW Pump discharge pressure, psig.
CHW Pump suction pressure, psig.

New Secondary Pump motor kw load 18 18 18 18 18 18 18 18 18


New Secondary Pump motor % Savings 81% 82% 82% 82% 82% 81% 81% 81% 81%
Savings Kw Load 79 83 85 79 80 78 77 77 77

COW Pump # 75
COW Pump amps, L1 58 59 59 58 58 58
COW Pump amps, L2 58 59 59 58 58 58
COW Pump amps, L3 58 59 59 58 58 58
COW Pump motor kw load 0.0 0.0 0 0 0 0 0 42 43 43 42 42 41 0 253
COW Pump motor frequency, Hz.
COW Pump discharge pressure, psig.
COW Pump suction pressure, psig.

New COW Pump motor kw load 29 29 29 29 29 29


New COW Pump motor % Savings 31% 32% 32% 30% 31% 30%
Savings Kw Load 13 14 14 13 13 12

Cooling Tower # 1
# 1 Fan motor amps 5 5 5
# 2 Fan motor amps, 3 3 3 3 3 3
# 3 Fan motor amps, 4 4 4
# 4 Fan motor amps, 3 3 3 3 3 3
Fan motor amps load 0 0 0 0 0 15 15 15 6 6 6 0 0 0 0
Fan motor kw load 10.87 10.87 10.85 4.33 4.34 4.28 46

Cooling Tower # 2
# 1 Fan motor amps
# 2 Fan motor amps, 14.00 14 14 12 12 12
# 3 Fan motor amps,
# 4 Fan motor amps, 6.00 6 6 5 5 5
Fan motor amps load 0 0 0 0 0 20 20 20 17 17 17 0 0 0 0
Fan motor kw load 14.49 14.49 14.46 12.28 12.28 12.12 80

Cooling Tower # 3
# 1 Fan motor amps
# 2 Fan motor amps, 5 5 5 5 5 5
# 3 Fan motor amps,
# 4 Fan motor amps, 9 9 9 9 9 9
Fan motor amps load 0 0 0 0 0 14 14 14 14 14 14 0 0 0 0
Fan motor kw load 10.15 10.15 10.12 10.11 10.12 9.98 61

Cooling Tower # 4
# 1 Fan motor amps 4 4 4 4 4 4
# 2 Fan motor amps,
# 3 Fan motor amps, 7 7 7 7 7 7
# 4 Fan motor amps,
Fan motor amps load 0 0 0 0 0 11 11 11 11 11 11 0 0 0 0
Fan motor kw load 0.00 0.00 0.00 0.00 0.00 7.97 7.97 7.95 7.94 7.95 7.84 0.00 0.00 0.00 0.00 48

Total Kw 0 0 0 0 0 0 0 526 520 527 502 499 514 135 135 135 0
Total Tons 430 415 410 405 405 395
Actual Load based on Max Chiller Capacity Kw/ton 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.22 1.25 1.28 1.24 1.23 1.30 0.00

DAILY KWHR as per amps reading 3492

DAILY KWHR FOR WEEKEND OPERATION 3,492 , Annual KWHR operation 363,186

Legend:
COW: Condenser Water ENT: Entering
CHW : Chilled Water LVG: Leaving
J CENTRE MALL

Chiller Chiller Sub-Total


System # 1 System # 3 Kw

CHILLERS
Designed Chillers Full Load (Tons) 500 500 1,000
Designed Chillers Full Load, (kw) 300 300 600
Designed Chilled water Temp, Leaving ( C ) 7 7
Designed Chilled water Temp, Return ( C ) 12 12
Designed Condenser Water Temp, Leaving ( C )
Designed Condenser Water Temp, Return ( C )
Designed Chilled Water Flow Rate (GPM) 1200 1200
Designed Condenser Water Flow Rate (GPM) 1500 1500
PUMPS
Primary Chilled Water Pumps Kw 18.5 18.5 37
Primary Chilled Water Pumps VSD (Yes/No) Yes Yes
If yes, what is the average frequency (Hz) 60 60
Secondary Chilled Water Pumps Kw 55 55 110
Secondary Chilled Water Pumps VSD (Yes/No) Yes Yes
If yes, what is the average frequency (Hz) 60 60
Condenser Chilled Water Pumps Kw 75 75 150
Condenser Chilled Water Pumps VSD (Yes/No) Yes Yes
If yes, what is the average frequency (Hz) 60 60
COOLING TOWER
Cooling Tower Fans 22.0 22.0 44
DESIGNED SYSTEM EFFICIENCY
Based on 60% Based on 40%
Existing Design Recommended Recommended
Equipment Kw/Ton Kw/Ton
Kw/Ton

0.6 0.6 0.6

0.04 0.03 0.03

0.11 0.04 0.06

0.15 0.07 0.11

0.04 0.04 0.03


0.94 0.79 0.83
CHILLER PLANT EQUIPMENT LOG J MALL CEBU
DATE of Log : 08 05 2016 Daily operation : CHILLER, PUMPS, COO
OPERATION SCHEDULE
EXISTING CHILLER # 3 - 650 TR - R 123 8:00 9:00 10:00 11:00 12:00
Cooling Tower # 1
# 1 Fan motor Amps 5 5 5
# 2 Fan motor Amps 4 4 4
# 3 Fan motor Amps 3 3 3
# 4 Fan motor Amps

Cooling Tower # 2
# 1 Fan motor Amps
# 2 Fan motor Amps
# 3 Fan motor Amps
# 4 Fan motor Amps 4 4 4

Cooling Tower # 3
# 1 Fan motor Amps
# 2 Fan motor Amps
# 3 Fan motor Amps
# 4 Fan motor Amps

Cooling Tower # 4
# 1 Fan motor Amps
# 2 Fan motor Amps
# 3 Fan motor Amps
# 4 Fan motor Amps
Total Fan ( Kw ) 10.98 11.07 10.99

Total Daily Operation of Cooling Towers Kw 10.98 11.07 10.99


Ideal Daily Operation of Cooling Tower Kw 17.00 17.00 17.00
Variace Savings Kw -6.02 -5.93 -6.01

DATE of Log : 08 06 2016


EXISTING CHILLER # 3 - 650 TR - R 123
Cooling Tower # 1
# 1 Fan motor Amps
# 2 Fan motor Amps
# 3 Fan motor Amps
# 4 Fan motor Amps

Cooling Tower # 2
# 1 Fan motor Amps
# 2 Fan motor Amps
# 3 Fan motor Amps
# 4 Fan motor Amps

Cooling Tower # 3
# 1 Fan motor Amps
# 2 Fan motor Amps
# 3 Fan motor Amps
# 4 Fan motor Amps

Cooling Tower # 4
# 1 Fan motor Amps
# 2 Fan motor Amps
# 3 Fan motor Amps
# 4 Fan motor Amps
Total Fan ( Kw ) 0.00 0.00 0.00

DATE of Log : 08 06 2016


EXISTING CHILLER # 1 - 650 TR - R 123
Cooling Tower # 1
# 1 Fan motor Amps 5 5 5
# 2 Fan motor Amps 4 4 4
# 3 Fan motor Amps 3 3 3
# 4 Fan motor Amps 4 4 4

Cooling Tower # 2
# 1 Fan motor Amps 0 0 0
# 2 Fan motor Amps 0 0 0
# 3 Fan motor Amps 0 0 0
# 4 Fan motor Amps 0 0 0

Cooling Tower # 3
# 1 Fan motor Amps 0 0 0
# 2 Fan motor Amps 0 0 0
# 3 Fan motor Amps 0 0 0
# 4 Fan motor Amps 0 0 0

Cooling Tower # 4
# 1 Fan motor Amps 0 0 0
# 2 Fan motor Amps 0 0 0
# 3 Fan motor Amps 0 0 0
# 4 Fan motor Amps 0 0 0

Total Fan ( Kw ) 11.33 11.42 11.34

Total Daily Operation of Cooling Towers Kw 11.33 11.42 11.34


Ideal Daily Operation of Cooling Tower Kw 17.60 17.60 17.60
Variance Savings Kw -6.27 -6.18 -6.26

Legend:
Fan Operation Duration
Fans of Cooling Tower 1
Fans of Cooling Tower 2
Fans of Cooling Tower 3
Fans of Cooling Tower 4
ation : CHILLER, PUMPS, COOLING TOWER
N SCHEDULE
13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00

5 5 6 5 5 5 5 5
4 4 5 4 5 5 5 5
3 3 5 4 4 4 4 4
4 4 4 4

9 9 9 9
9 9

4 4 8 7 8 8 8 8

0 0 0 0

0 0 0 0

5 3 3 3 3 3

8 8 8 8

10.57 11.09 21.02 16.67 33.26 33.22 39.74 39.21 0.00 0.00

10.57 11.09 21.02 16.67 33.26 33.22 39.74 39.21 0.00 0.00
17.00 17.00 17.00 17.00 17.00 17.00 17.00 17.00
-6.43 -5.91 4.02 -0.33 16.26 16.22 22.74 22.21

5 5 5 0 0 0
3 3 3 3 3 3
4 4 4 0 0 0
3 3 3 3 3 3

0 0 0 0 0 0
14 14 14 12 12 12
0 0 0 0 0 0
6 6 6 5 5 5

0 0 0 0 0 0
5 5 5 5 5 5
0 0 0 0 0 0
9 9 9 9 9 9

4 4 4 4 4 4
0 0 0 0 0 0
7 7 7 7 7 7
0 0 0 0 0 0
0.00 0.00 43.48 43.48 43.39 34.66 34.69 34.22 0.00 0.00

5 5
4 4
3 3
4 4

0 0
0 0
0 0
0 0

0 0
0 0
0 0
0 0

0 0
0 0
0 0
0 0

10.91 11.45 0 0 0 0 0 0 0 0

10.91 11.45 43.48 43.48 43.39 34.66 34.69 34.22 0.00 0.00
17.60 17.60 17.60 17.60 17.60 17.60 17.60 17.60
-6.69 -6.15 25.88 25.88 25.79 17.06 17.09 16.62
23:00 0:00 1:00 2:00 3:00 4:00 5:00 6:00 7:00

0.00
0.00

0 0 0 0 0 0 0 0 0

0.00
13.02
DESIGN AND SUBMISSION PHASES
Schematic Design
Design Development
DISCIPLINE

1 ELECTRICAL DESIGN
2 MECHANICAL DESIGN
3 SANITARY AND PLUMBING
4 FIRE PROTECTION
SITE DEVELOPMENT PLUMBING
5 AND DRAINAGE
6 SITE DEVELOPMENT ELECTRICAL

7 SITE DEVELOPMENT MECHANICAL

DOCUMENT SUBMITTALS
DRAWING SUBMISSION SCHEDULE Schematic Design
(REVISED) Design Development
1

2 E-FILE, CD 1 COPY 1 COPY


3 A 0 DRAWING SIZE
4 A 1 DRAWING SIZE 2 SETS 2 SETS
TECHNICAL SPECIFICATIONS
5

6 DESIGN CALCULATIONS
DRAFT DESIGN CRITERIA AND 2 SETS
7 PRELIMINARY CALCULATIONS
A 3 CHECK PRINT AND 3 SETS 3 SETS
8 ACCOUNTING AND BILLING
PURPOSES

ADJUSTED DESIGN CRITERIA, FINAL 2 SETS


CALCULATIONS AND DRAFT
9 TECHNICAL SPECIFICATIONS

DESIGN AND SUBMISSION PHASES


DISCIPLINE Schematic Design
Design Development

1 ELECTRICAL DESIGN
2 MECHANICAL DESIGN
3 SANITARY AND PLUMBING
4 FIRE PROTECTION
5 SITE DEVELOPMENT PLUMBING
AND DRAINAGE
6 SITE DEVELOPMENT ELECTRICAL
7 SITE DEVELOPMENT MECHANICAL

DOCUMENT SUBMITTALS
1 DRAWING SUBMISSION SCHEDULE Schematic Design
(REVISED) Design Development

2 E-FILE, CD 1 COPY 1 COPY


3 A 0 DRAWING SIZE

4 A 1 DRAWING SIZE 2 SETS 2 SETS


5 TECHNICAL SPECIFICATIONS

6 DESIGN CALCULATIONS
7 DRAFT DESIGN CRITERIA AND 2 SETS
PRELIMINARY CALCULATIONS
8 A 3 CHECK PRINT AND 3 SETS 3 SETS
ACCOUNTING AND BILLING
PURPOSES

9 ADJUSTED DESIGN CRITERIA, FINAL 2 SETS


CALCULATIONS AND DRAFT
TECHNICAL SPECIFICATIONS
ON PHASES
Contract Submission of
Documentation documents for
permit application

Contract Submission of
Documentation documents for
permit application

6 SETS, FOR 8 SETS, SIGNED AND


BIDDING SEALED

6 SETS FOR 8 SETS, SIGNED AND


BIDDING SEALED

3 SETS

ON PHASES
Contract Submission of
Documentation documents for
permit application
signed and sealed.

Contract Submission of
Documentation documents for
permit application

6 SETS, FOR 8 SETS, SIGNED AND


BIDDING SEALED

6 SETS FOR 8 SETS, SIGNED AND


BIDDING SEALED

3 SETS

You might also like