Chiller Plant Equip Log Sheet J Mall August 2016 Group01
Chiller Plant Equip Log Sheet J Mall August 2016 Group01
Chiller Plant Equip Log Sheet J Mall August 2016 Group01
Design 8:00 9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 0:00
EXISTING CHILLER # 3 - 650 TR - R 123
Compressor % Load, RLA, amps 84.4% 81.7% 90.1% 94.2% 97.0% 97.7% 98.0% 90.9% 96.9% 96.3% 96.2%
Compressor motor input voltage, L1 461 470 472 473 471 475 473 473 475 470 471
Compressor motor input voltage, L2 468 475 479 468 455 479 479 477 479 479 476
Compressor motor input voltage, L3 456 463 461 461 463 467 468 469 469 464 469
Compressor motor load, amps L1 439 439 438 441 444 427 325 418 439 438 436
Compressor motor load, amps L2 450 454 459 454 451 407 341 431 455 453 448
Compressor motor load, amps L3 421 423 430 429 423 381 319 402 430 440 420
Compressor motor load, kw 300 0 0 289 296 299 296 292 275 223 283 301 300 295 0 0 0 0 3149
Evaporator LVG CHW Setpoint Temp, C (F) 44 44 44 44 44 44 44 44 44 44 44
Evaporator LVG CHW Temp, C (F) 47.1 49.1 49.4 48.1 45.6 45.3 49.9 46.7 45.8 44.6 44.1
Evaporator ENT CHW Temp, C (F) 57.7 57.7 57.9 55.9 55.5 53.8 56.6 55 54.9 53.1 52.5
Chilled water temperature rise, C (F) 10 0 0 10.6 8.6 8.5 7.8 9.9 8.5 6.7 8.3 9.1 8.5 8.4 0 0 0 0
Chiller load % 100% 86% 85% 78% 99% 85% 67% 83% 91% 85% 84% 0.0% 0.0% 0.0% 0.0%
Chiller Load Tons 500.0 430.0 425.0 390.0 495.0 425.0 335.0 415.0 455.0 425.0 420.0
Kw/Ton 0.6 0.7 0.7 0.8 0.6 0.6 0.7 0.7 0.7 0.7 0.7
Actual Load Based on Actual Cond. Approach ( Kw ) 289 296 299 296 292 275 223 283 301 300 295
Actual Load Based on Ideal Cond. Approach ( Kw ) 263 269 272 270 266 251 203 258 274 273 268 2,866
Variance Load Savings ( Kw ) 26.1 26.6 26.9 26.7 26.3 24.8 20.1 25.5 27.1 27.0 26.5
COW Pump # 75
COW Pump amps, L1 55 55 55 55 55 55 55 55 55 55 55
COW Pump amps, L2 50 50 50 50 50 50 50 50 50 50 50
Design 8:00 9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 0:00
COW Pump amps, L3 54 54 54 54 54 54 54 54 54 54 54
COW Pump motor kw load 0.0 0.0 37.3 37.9 38.0 37.7 37.4 38.2 38.2 38.2 38.3 38.0 38.1 0.0 417
COW Pump motor frequency, Hz.
COW Pump discharge pressure, psig.
COW Pump suction pressure, psig.
Cooling Tower # 1
# 1 Fan motor amps 4.67 4.67 4.67 4.67 4.67 6.00 5.00 5.00 5.00 5.00 5.00
# 2 Fan motor amps, 3.57 3.57 3.57 3.57 3.57 5.00 4.00 5.00 5.00 5.00 5.00
# 3 Fan motor amps, 3.33 3.33 3.33 3.33 3.33 5.00 4.00 4.00 4.00 4.00 4.00
# 4 Fan motor amps, 4 4 4 4
Fan motor amps load 11.57 11.57 11.57 11.57 11.57 16.00 13.00 18.00 18.00 18.00 18.00
Fan motor kw load 8.1 8.3 8.3 8.2 8.2 11.5 9.4 13.0 13.0 12.9 12.9 114
Cooling Tower # 2
# 1 Fan motor amps 9 9 9 9
# 2 Fan motor amps, 9 9
# 3 Fan motor amps,
# 4 Fan motor amps, 3.93 3.93 3.93 3.93 3.93 8.00 7.00 8.00 8.00 8.00 8.00
Fan motor amps load 3.93 3.93 3.93 3.93 3.93 8.00 7.00 17.00 17.00 26.00 26.00
Fan motor kw load 2.8 2.8 2.8 2.8 2.8 5.8 5.0 12.2 12.3 18.6 18.7 87
Cooling Tower # 3
# 1 Fan motor amps
# 2 Fan motor amps, 20.33 20.33 20.33 20.33
# 3 Fan motor amps,
# 4 Fan motor amps, 15.33 15.33 15.33 15.33
Fan motor amps load
Fan motor kw load 0.0 0.0 0.0 0.0 0
Cooling Tower # 4
# 1 Fan motor amps 5 3 3 3 3 3
# 2 Fan motor amps,
# 3 Fan motor amps, 8 8 8 8
# 4 Fan motor amps,
Fan motor amps load 0 0 0 0 0 5 3 11 11 11 11
Fan motor kw load 0.0 0.0 0.0 0.0 0.0 3.6 2.2 7.9 7.9 7.9 7.9 37
Actual Consumption for all Cooling Towers Kw 10.9 11.1 11.1 11.0 10.9 20.9 16.6 33.1 33.2 39.4 39.5 238
Ideal Cooling Tower for One Chiller Kw 17.6 17.6 17.6 17.6 17.6 17.6 17.6 17.6 17.6 17.6 17.6 194
Savings for Ideal Cooling Tower % -38% -37% -37% -37% -38% 19% -6% 88% 89% 124% 125%
Savings Variance Kw -6.7 -6.5 -6.5 -6.6 -6.7 3.3 -1.0 15.5 15.6 21.8 21.9
Total Kw 0 0 436 444 448 444 439 435 379 455 473 478 473 113 113 113 0
Total Tons 500 430 425 390 495 425 335 415 455 425 420
Actual Load based on Max Chiller Capacity Kw/ton 0.00 0.00 0.87 1.03 1.05 1.14 0.89 1.02 1.13 1.10 1.04 1.12 1.13 0.00
DAILY KWHR FOR WEEKDAYS OPERATION 5243 , Annual KWHR operation 1,363,211 RETROFITTED C.T. & PUMPS DAILY KWHR OPERATION 920 , Annual KWHR operation 239,122
CHILLER COMPRESSOR DAILY KWHR FOR WEEKDAYS 3149 Annual KWHR operation 818,827 CLEAN TUBES CHILLER COMPRESSOR DAILY KWHR OPERATION 2866 , Annual KWHR operation 745,133
PUMPS & COOLING TOWER DAILY KWHR FOR WEEKDAYS 2094 , Annual KWHR operation 544,384 RETROFITTED PUMPS DAILY KWHR OPERATION 726 , Annual KWHR operation 188,786
OPERATION
PUMPS DAILY KWHR OPERATION 1856 , Annual KWHR operation 482,552 RETROFITTED COOLING TOWER DAILY KWHR OPERATION 194 , Annual KWHR operation 50,336
COOLING TOWER DAILY KWHR OPERATION 238 , Annual KWHR operation 61,832
Legend:
COW: Condenser Water ENT: Entering
CHW : Chilled Water LVG: Leaving
CHILLER PLANT EQUIPMENT LOG J MALL CEBU
DATE of Log : 08 06 2016 Daily operation : CHILLER, PUMPS, COOLING TOWER
EXISTING CHILLER # 1 - 650 TR - R 123 Design 8:00 9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 0:00 1:00 2:00 3:00 4:00 5:00 6:00 7:00
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Compressor % Load, RLA, amps 88.5% 94.7% 94.8% 94.6% 95.1% 91.5% 89.4% 86.8% 90.1% 90.2% 89.3%
Compressor motor input voltage, L1 465 469 466 465 470 474 476 475 479 475 470
Compressor motor input voltage, L2 469 472 470 468 474 478 479 475 474 478 471
Compressor motor input voltage, L3 462 466 461 411 466 471 474 473 470 471 464
Compressor motor load, amps L1 410 430 424 464 428 428 417 402 412 407 406
Compressor motor load, amps L2 407 454 454 470 454 452 439 426 432 429 424
Compressor motor load, amps L3 386 409 411 460 412 415 436 411 396 388 485
Compressor motor load, kw 0 0 268 290 287 299 291 294 294 281 282 278 295 0 0 0 0 0 0 0 0 0 0 0 3159
Evaporator LVG CHW Setpoint Temp, C (F) 44 44 44 44 44 44 44 44 44 44 44
Evaporator LVG CHW Temp, C (F) 44 44.7 46.4 46.3 46.9 45.25 43.9 43.95 43.9 43.9 43.9
Evaporator ENT CHW Temp, C (F) 53.4 53.7 54.9 54.8 55.3 53.85 52.3 52.1 52 52 51.8
Chilled water temperature rise, C (F) 10 0 0 9.4 9 8.5 8.5 8.4 8.6 8.4 8.15 8.1 8.1 7.9 0 0 0 0 0 0 0 0 0 0 0
Temp variance from set point, C (F) 0 0 0 -0.7 -2.4 -2.3 -2.9 -1.25 0.1 0.05 0.1 0.1 0.1 0 0 0 0 0 0 0 0 0 0 0
Chiller load 94.0% 90.0% 85.0% 85.0% 84.0% 86.0% 84.0% 81.5% 81.0% 81.0% 79.0%
COW Pump #
COW Pump amps, L1 55 55 55 55 55 55 55 55 55 55 55 55 55 55
COW Pump amps, L2 50 50 50 50 50 50 50 50 50 50 50 50 50 50
COW Pump amps, L3 54 54 54 54 54 54 54 54 54 54 54 54 54 54
COW Pump motor kw load 0.0 0.0 37 37 37 36 37 38 38 38 38 38 37 37 37 37 0 0 0 0 0 0 0 0 522
COW Pump motor frequency, Hz.
COW Pump discharge pressure, psig.
COW Pump suction pressure, psig.
Cooling Tower # 1
# 1 Fan motor amps 33 33 33 33 33 5.00 5 5
# 2 Fan motor amps, 20.33 20.33 20.33 20.33 20.33 3.00 3 3 3 3 3
# 3 Fan motor amps, 15.33 15.33 15.33 15.33 15.33 4.00 4 4
# 4 Fan motor amps, 15.33 15.33 15.33 15.33 15.33 3.00 3 3 3 3 3
Fan motor amps load 84.00 84.00 84.00 84.00 84.00 15 15 15 6 6 6 0 0 0 0 0 0 0 0 0 0 0
Fan motor kw load 59.5 60.0 59.6 57.3 60.1 10.83 10.88 10.83 4.33 4.34 4.28 342
Cooling Tower # 2
# 1 Fan motor amps
# 2 Fan motor amps, 14.00 14 14 12 12 12
# 3 Fan motor amps,
# 4 Fan motor amps, 6.00 6 6 5 5 5
Fan motor amps load 0 0 0 0 0 20 20 20 17 17 17 0 0 0 0 0 0 0 0 0 0 0
Fan motor kw load 14.44 14.50 14.44 12.28 12.28 12.12 80
Cooling Tower # 3
# 1 Fan motor amps
# 2 Fan motor amps, 5 5 5 5 5 5
# 3 Fan motor amps,
# 4 Fan motor amps, 9 9 9 9 9 9
Fan motor amps load 0 0 0 0 0 14 14 14 14 14 14 0 0 0 0 0 0 0 0 0 0 0
Fan motor kw load 10.11 10.15 10.11 10.11 10.12 9.98 61
Cooling Tower # 4
# 1 Fan motor amps 4 4 4 4 4 4
# 2 Fan motor amps,
# 3 Fan motor amps, 7 7 7 7 7 7
# 4 Fan motor amps,
Fan motor amps load 0 0 0 0 0 11 11 11 11 11 11 0 0 0 0 0 0 0 0 0 0 0
Fan motor kw load 0.00 0.00 0.00 0.00 0.00 7.94 7.98 7.94 7.94 7.95 7.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 48
Total Kw 0 0 463 487 483 487 489 476 477 463 455 452 466 113 113 113 0 0 0 0 0 0 0 0
Actual Kw/ton based on Compressor Load % RLA 0.00 0.00 1.05 1.03 1.02 1.03 1.03 1.04 1.07 1.07 1.01 1.00 1.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Actual Kw/ton based on Compressor Load % RLA
Legend:
COW: Condenser Water ENT: Entering Period when second chiller is operated when chilled water supply temperature is high.
CHW : Chilled Water LVG: Leaving Period when the chilled water supply temperature is below the set point of 7 degrees C.
CHILLER PLANT EQUIPMENT LOG J MALL CEBU
DATE of Log : 08 06 2016 Daily operation : CHILLER, PUMPS, COOLING TOWER
Design 8:00 9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 0:00
EXISTING CHILLER # 1 - 650 TR - R 123
Compressor % Load, RLA, amps 88.5% 94.7% 94.8% 94.6% 95.1% 88.2% 87.3% 83.5%
Compressor motor input voltage, L1 465 469 466 465 470 472 477 474
Compressor motor input voltage, L2 469 472 470 468 474 476 479 478
Compressor motor input voltage, L3 462 466 461 411 466 469 474 471
Compressor motor load, amps L1 410 430 424 464 428 431 420 399
Compressor motor load, amps L2 407 454 454 470 454 453 444 423
Compressor motor load, amps L3 386 409 411 460 412 418 474 384
Compressor motor load, kw 300 0 0 284 308 305 317 309 312 324 290 0 0 0 0 0 0 0 2448
Evaporator LVG CHW Setpoint Temp, C (F) 44 44 44 44 44 44 44 44
Evaporator LVG CHW Temp, C (F) 44 44.7 46.4 46.3 46.9 45.2 43.9 44
Evaporator ENT CHW Temp, C (F) 53.4 53.7 54.9 54.8 55.3 53.8 52.4 52.1
Chilled water temperature rise, C (F) 10 0 0 9.4 9 8.5 8.5 8.4 8.6 8.5 8.1 0 0 0 0 0 0 0
Chiller load % 94.0% 90.0% 85.0% 85.0% 84.0% 86.0% 85.0% 81.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0%
Chiller Load Tons 470.0 450.0 425.0 425.0 420.0 430.0 425.0 405.0
Kw/Ton 0.60 0.68 0.72 0.75 0.73 0.73 0.76 0.72
Actual Load Based on Actual Cond. Approach ( Kw ) 284 308 305 317 309 312 324 290
Actual Load Based on Ideal Cond. Approach ( Kw ) 257 278 275 287 279 282 293 263 2,214
Variance Load Savings ( Kw ) 27 29 29 30 30 30 31 28
COW Pump # 75
COW Pump amps, L1 55 55 55 55 55 55 55 55
COW Pump amps, L2 50 50 50 50 50 50 50 50
Design 8:00 9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 0:00
COW Pump amps, L3 54 54 54 54 54 54 54 54
COW Pump motor kw load 0.0 0.0 37.5 37.8 37.6 36.1 37.9 38.1 38.5 38.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 302
COW Pump motor frequency, Hz.
COW Pump discharge pressure, psig.
COW Pump suction pressure, psig.
Cooling Tower # 1
# 1 Fan motor amps 33.0 33.0 33.0 33.0 33.0
# 2 Fan motor amps, 20.3 20.3 20.3 20.3 20.3
# 3 Fan motor amps, 15.3 15.3 15.3 15.3 15.3
# 4 Fan motor amps, 15.3 15.3 15.3 15.3 15.3
Fan motor amps load 84.00 84.00 84.00 84.00 84.00
Fan motor kw load 59.5 60.0 59.6 57.3 60.1 296
Cooling Tower # 2
# 1 Fan motor amps 0.0 0.0 0.0 0.0 0.0
# 2 Fan motor amps, 0.0 0.0 0.0 0.0 0.0
# 3 Fan motor amps, 0.0 0.0 0.0 0.0 0.0
# 4 Fan motor amps, 0.0 0.0 0.0 0.0 0.0
Fan motor amps load
Fan motor kw load 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Cooling Tower # 3
# 1 Fan motor amps 0.0 0.0 0.0 0.0 0.0
# 2 Fan motor amps, 0.0 0.0 0.0 0.0 0.0
# 3 Fan motor amps, 0.0 0.0 0.0 0.0 0.0
# 4 Fan motor amps, 0.0 0.0 0.0 0.0 0.0
Fan motor amps load
Fan motor kw load 0.0 0.0 0.0 0.0 0.0
Cooling Tower # 4
# 1 Fan motor amps 0.0 0.0 0.0 0.0 0.0
# 2 Fan motor amps, 0.0 0.0 0.0 0.0 0.0
# 3 Fan motor amps, 0.0 0.0 0.0 0.0 0.0
# 4 Fan motor amps, 0.0 0.0 0.0 0.0 0.0
Fan motor amps load
Fan motor kw load 0.0 0.0 0.0 0.0 0.0 0.0
Actual Consumption for all Cooling Towers Kw 0.0 0.0 59.5 60.0 59.6 57.3 60.1 0.0 0.0 0.0 0.0 0.0 0.0
Ideal Cooling Tower for One Chiller Kw 17.6 17.6 17.6 17.6 17.6 88
Savings for Ideal Cooling Tower % 238% 241% 238% 226% 242%
Savings Variance Kw 41.9 42.4 42.0 39.7 42.5
Compressor % Load, RLA, amps 94.7% 91.5% 90.0% 90.1% 90.2% 89.3%
Compressor motor input voltage, L1 475 475 476 479 475 470
Compressor motor input voltage, L2 480 479 475 474 478 471
Compressor motor input voltage, L3 473 474 474 470 471 464
Compressor motor load, amps L1 425 413 404 412 407 406
Compressor motor load, amps L2 451 434 429 432 429 424
Compressor motor load, amps L3 412 397 437 396 388 485
Compressor motor load, kw 300 0 0 0 0 0 0 0 311 300 306 298 295 313 0 0 0 0 1824
Evaporator LVG CHW Setpoint Temp, C (F) 44 44 44 44 44 44
Evaporator LVG CHW Temp, C (F) 45.3 43.9 43.9 43.9 43.9 43.9
Evaporator ENT CHW Temp, C (F) 53.9 52.2 52.1 52 52 51.8
Chilled water temperature rise, C (F) 10 0 0 0 0 0 0 0 8.6 8.3 8.2 8.1 8.1 7.9 0 0 0 0
Chiller load % 0.0% 0.0% 0.0% 0.0% 0.0% 86.0% 83.0% 82.0% 81.0% 81.0% 79.0%
Chiller Load Tons 430.0 415.0 410.0 405.0 405.0 395.0
Kw/Ton 0.72 0.72 0.75 0.74 0.73 0.79
Actual Load Based on Actual Cond. Approach ( Kw ) 311 300 306 298 295 313
Actual Load Based on Ideal Cond. Approach ( Kw ) 287 278 283 276 273 290 1,688
Variance Load Savings( Kw ) 24 23 23 22 22 23
Design 8:00 9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 0:00
COW Pump #
COW Pump amps, L1 58 59 59 58 58 58
COW Pump amps, L2 58 59 59 58 58 58
COW Pump amps, L3 58 59 59 58 58 58
COW Pump motor kw load 0 0 0 0 0 0 42 42 42 41 41 41 0 0 0 0 250
COW Pump motor frequency, Hz.
COW Pump discharge pressure, psig.
COW Pump suction pressure, psig.
Cooling Tower # 1
# 1 Fan motor amps 5 5 5 0 0 0
# 2 Fan motor amps, 3 3 3 3 3 3
# 3 Fan motor amps, 4 4 4 0 0 0
# 4 Fan motor amps, 3 3 3 3 3 3
Fan motor amps load 0 0 0 0 0 15 15 15 6 6 6 0 0 0 0
Fan motor kw load 10.87 10.87 10.85 4.33 4.34 4.28 46
Cooling Tower # 2
# 1 Fan motor amps 0 0 0 0 0 0
# 2 Fan motor amps, 14 14 14 12 12 12
# 3 Fan motor amps, 0 0 0 0 0 0
# 4 Fan motor amps, 6 6 6 5 5 5
Fan motor amps load 0 0 0 0 0 20 20 20 17 17 17 0 0 0 0
Design 8:00 9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 0:00
Fan motor kw load 14.49 14.49 14.46 12.28 12.28 12.12 80
Cooling Tower # 3
# 1 Fan motor amps 0 0 0 0 0 0
# 2 Fan motor amps, 5 5 5 5 5 5
# 3 Fan motor amps, 0 0 0 0 0 0
# 4 Fan motor amps, 9 9 9 9 9 9
Fan motor amps load 0 0 0 0 0 14 14 14 14 14 14 0 0 0 0
Fan motor kw load 10.15 10.15 10.12 10.11 10.12 9.98 61
Cooling Tower # 4
# 1 Fan motor amps 4 4 4 4 4 4
# 2 Fan motor amps, 0 0 0 0 0 0
# 3 Fan motor amps, 7 7 7 7 7 7
# 4 Fan motor amps, 0 0 0 0 0 0
Fan motor amps load 0 0 0 0 0 11 11 11 11 11 11 0 0 0 0
Fan motor kw load 0.00 0.00 0.00 0.00 0.00 7.97 7.97 7.95 7.94 7.95 7.84 0.00 0.00 0.00 0.00 48
Actual Consumption for all Cooling Towers Kw 0.0 0.0 59.5 60.0 59.6 57.3 60.1 32.6 43.5 43.4 41.2 34.7 34.3 526
Ideal Cooling Tower for One Chiller Kw 17.6 17.6 17.6 17.6 17.6 17.6 17.6 17.6 17.6 17.6 17.6 194
Savings for Ideal Cooling Tower % 238% 241% 238% 226% 242% 85% 147% 147% 134% 97% 95%
Savings Variance Kw 41.9 42.4 42.0 39.7 42.5 15.0 25.9 25.8 23.6 17.1 16.7
Total Kw 0 0 481 506 501 506 507 976 984 956 502 498 513 135 135 135 0
Total Tons 470 450 425 425 420 860 840 815 405 405 395
Combined Load based on Max Chiller Capacity Kw/ton 0.00 0.00 1.02 1.12 1.18 1.19 1.21 1.14 1.17 1.17 1.24 1.23 1.30 0.00
DAILY KWHR FOR WEEKEND OPERATION 7,337 , Annual KWHR operation 763,029 RETROFITTED C.T. & PUMPS DAILY KWHR OPERATION 1,061 , Annual KWHR operation 110,382
CHILLER COMPRESSOR DAILY KWHR FOR WEEKDAYS 4,272 , Annual KWHR operation 444,244 CLEAM TUBES CHILLER COMPRESSOR DAILY KWHR OPERATION 3,902 , Annual KWHR operation 405,786
PUMPS & COOLING TOWER DAILY KWHR FOR WEEKDAYS 3,065 Annual
, KWHR operation 318,785 RETROFITTED PUMPS DAILY KWHR OPERATION 868 , Annual KWHR operation 90,247
OPERATION
PUMPS DAILY KWHR OPERATION 2535 , Annual KWHR operation 263,628 RETROFITTED COOLING TOWER DAILY KWHR OPERATION 194 , Annual KWHR operation 20,134
COOLING TOWER DAILY KWHR OPERATION 526 , Annual KWHR operation 54,711 ,
Legend:
COW: Condenser Water ENT: Entering
CHW : Chilled Water LVG: Leaving
CHILLER PLANT EQUIPMENT LOG J MALL CEBU
DATE of Log : 08 06 2016 Daily operation : CHILLER, PUMPS, COOLING TOWER
EXISTING CHILLER # 1 - 650 TR - R 123 Design 8:00 9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 0:00
Compressor % Load, RLA, amps 88.5% 94.7% 94.8% 94.6% 95.1% 88.2% 87.3% 83.5%
Compressor motor input voltage, L1 465 469 466 465 470 472 477 474
Compressor motor input voltage, L2 469 472 470 468 474 476 479 478
Compressor motor input voltage, L3 462 466 461 411 466 469 474 471
Compressor motor load, amps L1 410 430 424 464 428 431 420 399
Compressor motor load, amps L2 407 454 454 470 454 453 444 423
Compressor motor load, amps L3 386 409 411 460 412 418 474 384
Compressor motor load, kw 300 0 0 284 308 305 317 309 312 324 290 0 0 0 0 0 0 0 2448
Evaporator LVG CHW Setpoint Temp, C (F) 44 44 44 44 44 44 44 44
Evaporator LVG CHW Temp, C (F) 44 44.7 46.4 46.3 46.9 45.2 43.9 44
Evaporator ENT CHW Temp, C (F) 53.4 53.7 54.9 54.8 55.3 53.8 52.4 52.1
Chilled water temperature rise, C (F) 10 0 0 9.4 9 8.5 8.5 8.4 8.6 8.5 8.1 0 0 0 0 0 0 0
Chiller load % 94.0% 90.0% 85.0% 85.0% 84.0% 86.0% 85.0% 81.0% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0%
Chiller Load Tons 470.0 450.0 425.0 425.0 420.0 430.0 425.0 405.0
Kw/Ton 0.6 0.7 0.7 0.7 0.7 0.7 0.8 0.7
Actual Load Based on Actual Cond. Approach ( Kw ) 284 308 305 317 309 312 324 290
Actual Load Based on Ideal Cond. Approach ( Kw ) 257 278 275 287 279 282 293 263
Variance Load Savings ( Kw ) 27 29 29 30 30 30 31 28
COW Pump # 75
COW Pump amps, L1 55 55 55 55 55 55 55 55
COW Pump amps, L2 50 50 50 50 50 50 50 50
COW Pump amps, L3 54 54 54 54 54 54 54 54
COW Pump motor kw load 0.0 0.0 37.5 37.8 37.6 36.1 37.9 38.1 38.5 38.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 302
COW Pump motor frequency, Hz.
COW Pump discharge pressure, psig.
COW Pump suction pressure, psig.
Cooling Tower # 1
# 1 Fan motor amps 33 33 33 33 33
# 2 Fan motor amps, 20.33 20.33 20.33 20.33 20.33
# 3 Fan motor amps, 15.33 15.33 15.33 15.33 15.33
# 4 Fan motor amps, 15.33 15.33 15.33 15.33 15.33
Fan motor amps load 84.00 84.00 84.00 84.00 84.00
Fan motor kw load 59.5 60.0 59.6 57.3 60.1 296
Cooling Tower # 2
# 1 Fan motor amps
# 2 Fan motor amps,
# 3 Fan motor amps,
# 4 Fan motor amps,
Fan motor amps load
Fan motor kw load 0.0 0.0 0.0 0.0 0.0
Cooling Tower # 3
# 1 Fan motor amps
# 2 Fan motor amps,
# 3 Fan motor amps,
# 4 Fan motor amps,
Fan motor amps load
Fan motor kw load 0.0 0.0 0.0 0.0 0.0
Cooling Tower # 4
# 1 Fan motor amps
# 2 Fan motor amps,
# 3 Fan motor amps,
# 4 Fan motor amps,
Fan motor amps load
Fan motor kw load 0.0 0.0 0.0 0.0 0.0
DAILY KWHR FOR WEEKEND OPERATION 3,841 , Annual KWHR operation 399,502
Legend:
COW: Condenser Water ENT: Entering
CHW : Chilled Water LVG: Leaving
CHILLER PLANT EQUIPMENT LOG J MALL CEBU
DATE of Log : 08 06 2016 Daily operation : CHILLER, PUMPS, COOLING TOWER
EXISTING CHILLER # 3 - 650 TR - R 123 Design 8:00 9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 0:00
Compressor % Load, RLA, amps 94.7% 91.5% 90.0% 90.1% 90.2% 89.3%
Compressor motor input voltage, L1 475 475 476 479 475 470
Compressor motor input voltage, L2 480 479 475 474 478 471
Compressor motor input voltage, L3 473 474 474 470 471 464
Compressor motor load, amps L1 425 413 404 412 407 406
Compressor motor load, amps L2 451 434 429 432 429 424
Compressor motor load, amps L3 412 397 437 396 388 485
Compressor motor load, kw 300 0 0 0 0 0 0 0 311 300 306 298 295 313 0 0 0 0 1824
Evaporator LVG CHW Setpoint Temp, C (F) 44 44 44 44 44 44
Evaporator LVG CHW Temp, C (F) 45.3 43.9 43.9 43.9 43.9 43.9
Evaporator ENT CHW Temp, C (F) 53.9 52.2 52.1 52 52 51.8
Chilled water temperature rise, C (F) 10 0 0 0 0 0 0 0 8.6 8.3 8.2 8.1 8.1 7.9 0 0 0 0
Chiller load % 0.0% 0.0% 0.0% 0.0% 0.0% 86.0% 83.0% 82.0% 81.0% 81.0% 79.0%
Chiller load Tons 430.0 415.0 410.0 405.0 405.0 395.0
Kw/Ton 0.7 0.7 0.7 0.7 0.7 0.8
Actual Load Based on Actual Cond. Approach ( Kw ) 311 300 306 298 295 313
Actual Load Based on Ideal Cond. Approach ( Kw ) 287 278 283 276 273 290
Variance Load Savings ( Kw ) 24 23 23 22 22 23
COW Pump # 75
COW Pump amps, L1 58 59 59 58 58 58
COW Pump amps, L2 58 59 59 58 58 58
COW Pump amps, L3 58 59 59 58 58 58
COW Pump motor kw load 0.0 0.0 0 0 0 0 0 42 43 43 42 42 41 0 253
COW Pump motor frequency, Hz.
COW Pump discharge pressure, psig.
COW Pump suction pressure, psig.
Cooling Tower # 1
# 1 Fan motor amps 5 5 5
# 2 Fan motor amps, 3 3 3 3 3 3
# 3 Fan motor amps, 4 4 4
# 4 Fan motor amps, 3 3 3 3 3 3
Fan motor amps load 0 0 0 0 0 15 15 15 6 6 6 0 0 0 0
Fan motor kw load 10.87 10.87 10.85 4.33 4.34 4.28 46
Cooling Tower # 2
# 1 Fan motor amps
# 2 Fan motor amps, 14.00 14 14 12 12 12
# 3 Fan motor amps,
# 4 Fan motor amps, 6.00 6 6 5 5 5
Fan motor amps load 0 0 0 0 0 20 20 20 17 17 17 0 0 0 0
Fan motor kw load 14.49 14.49 14.46 12.28 12.28 12.12 80
Cooling Tower # 3
# 1 Fan motor amps
# 2 Fan motor amps, 5 5 5 5 5 5
# 3 Fan motor amps,
# 4 Fan motor amps, 9 9 9 9 9 9
Fan motor amps load 0 0 0 0 0 14 14 14 14 14 14 0 0 0 0
Fan motor kw load 10.15 10.15 10.12 10.11 10.12 9.98 61
Cooling Tower # 4
# 1 Fan motor amps 4 4 4 4 4 4
# 2 Fan motor amps,
# 3 Fan motor amps, 7 7 7 7 7 7
# 4 Fan motor amps,
Fan motor amps load 0 0 0 0 0 11 11 11 11 11 11 0 0 0 0
Fan motor kw load 0.00 0.00 0.00 0.00 0.00 7.97 7.97 7.95 7.94 7.95 7.84 0.00 0.00 0.00 0.00 48
Total Kw 0 0 0 0 0 0 0 526 520 527 502 499 514 135 135 135 0
Total Tons 430 415 410 405 405 395
Actual Load based on Max Chiller Capacity Kw/ton 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.22 1.25 1.28 1.24 1.23 1.30 0.00
DAILY KWHR FOR WEEKEND OPERATION 3,492 , Annual KWHR operation 363,186
Legend:
COW: Condenser Water ENT: Entering
CHW : Chilled Water LVG: Leaving
J CENTRE MALL
CHILLERS
Designed Chillers Full Load (Tons) 500 500 1,000
Designed Chillers Full Load, (kw) 300 300 600
Designed Chilled water Temp, Leaving ( C ) 7 7
Designed Chilled water Temp, Return ( C ) 12 12
Designed Condenser Water Temp, Leaving ( C )
Designed Condenser Water Temp, Return ( C )
Designed Chilled Water Flow Rate (GPM) 1200 1200
Designed Condenser Water Flow Rate (GPM) 1500 1500
PUMPS
Primary Chilled Water Pumps Kw 18.5 18.5 37
Primary Chilled Water Pumps VSD (Yes/No) Yes Yes
If yes, what is the average frequency (Hz) 60 60
Secondary Chilled Water Pumps Kw 55 55 110
Secondary Chilled Water Pumps VSD (Yes/No) Yes Yes
If yes, what is the average frequency (Hz) 60 60
Condenser Chilled Water Pumps Kw 75 75 150
Condenser Chilled Water Pumps VSD (Yes/No) Yes Yes
If yes, what is the average frequency (Hz) 60 60
COOLING TOWER
Cooling Tower Fans 22.0 22.0 44
DESIGNED SYSTEM EFFICIENCY
Based on 60% Based on 40%
Existing Design Recommended Recommended
Equipment Kw/Ton Kw/Ton
Kw/Ton
Cooling Tower # 2
# 1 Fan motor Amps
# 2 Fan motor Amps
# 3 Fan motor Amps
# 4 Fan motor Amps 4 4 4
Cooling Tower # 3
# 1 Fan motor Amps
# 2 Fan motor Amps
# 3 Fan motor Amps
# 4 Fan motor Amps
Cooling Tower # 4
# 1 Fan motor Amps
# 2 Fan motor Amps
# 3 Fan motor Amps
# 4 Fan motor Amps
Total Fan ( Kw ) 10.98 11.07 10.99
Cooling Tower # 2
# 1 Fan motor Amps
# 2 Fan motor Amps
# 3 Fan motor Amps
# 4 Fan motor Amps
Cooling Tower # 3
# 1 Fan motor Amps
# 2 Fan motor Amps
# 3 Fan motor Amps
# 4 Fan motor Amps
Cooling Tower # 4
# 1 Fan motor Amps
# 2 Fan motor Amps
# 3 Fan motor Amps
# 4 Fan motor Amps
Total Fan ( Kw ) 0.00 0.00 0.00
Cooling Tower # 2
# 1 Fan motor Amps 0 0 0
# 2 Fan motor Amps 0 0 0
# 3 Fan motor Amps 0 0 0
# 4 Fan motor Amps 0 0 0
Cooling Tower # 3
# 1 Fan motor Amps 0 0 0
# 2 Fan motor Amps 0 0 0
# 3 Fan motor Amps 0 0 0
# 4 Fan motor Amps 0 0 0
Cooling Tower # 4
# 1 Fan motor Amps 0 0 0
# 2 Fan motor Amps 0 0 0
# 3 Fan motor Amps 0 0 0
# 4 Fan motor Amps 0 0 0
Legend:
Fan Operation Duration
Fans of Cooling Tower 1
Fans of Cooling Tower 2
Fans of Cooling Tower 3
Fans of Cooling Tower 4
ation : CHILLER, PUMPS, COOLING TOWER
N SCHEDULE
13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00
5 5 6 5 5 5 5 5
4 4 5 4 5 5 5 5
3 3 5 4 4 4 4 4
4 4 4 4
9 9 9 9
9 9
4 4 8 7 8 8 8 8
0 0 0 0
0 0 0 0
5 3 3 3 3 3
8 8 8 8
10.57 11.09 21.02 16.67 33.26 33.22 39.74 39.21 0.00 0.00
10.57 11.09 21.02 16.67 33.26 33.22 39.74 39.21 0.00 0.00
17.00 17.00 17.00 17.00 17.00 17.00 17.00 17.00
-6.43 -5.91 4.02 -0.33 16.26 16.22 22.74 22.21
5 5 5 0 0 0
3 3 3 3 3 3
4 4 4 0 0 0
3 3 3 3 3 3
0 0 0 0 0 0
14 14 14 12 12 12
0 0 0 0 0 0
6 6 6 5 5 5
0 0 0 0 0 0
5 5 5 5 5 5
0 0 0 0 0 0
9 9 9 9 9 9
4 4 4 4 4 4
0 0 0 0 0 0
7 7 7 7 7 7
0 0 0 0 0 0
0.00 0.00 43.48 43.48 43.39 34.66 34.69 34.22 0.00 0.00
5 5
4 4
3 3
4 4
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
10.91 11.45 0 0 0 0 0 0 0 0
10.91 11.45 43.48 43.48 43.39 34.66 34.69 34.22 0.00 0.00
17.60 17.60 17.60 17.60 17.60 17.60 17.60 17.60
-6.69 -6.15 25.88 25.88 25.79 17.06 17.09 16.62
23:00 0:00 1:00 2:00 3:00 4:00 5:00 6:00 7:00
0.00
0.00
0 0 0 0 0 0 0 0 0
0.00
13.02
DESIGN AND SUBMISSION PHASES
Schematic Design
Design Development
DISCIPLINE
1 ELECTRICAL DESIGN
2 MECHANICAL DESIGN
3 SANITARY AND PLUMBING
4 FIRE PROTECTION
SITE DEVELOPMENT PLUMBING
5 AND DRAINAGE
6 SITE DEVELOPMENT ELECTRICAL
DOCUMENT SUBMITTALS
DRAWING SUBMISSION SCHEDULE Schematic Design
(REVISED) Design Development
1
6 DESIGN CALCULATIONS
DRAFT DESIGN CRITERIA AND 2 SETS
7 PRELIMINARY CALCULATIONS
A 3 CHECK PRINT AND 3 SETS 3 SETS
8 ACCOUNTING AND BILLING
PURPOSES
1 ELECTRICAL DESIGN
2 MECHANICAL DESIGN
3 SANITARY AND PLUMBING
4 FIRE PROTECTION
5 SITE DEVELOPMENT PLUMBING
AND DRAINAGE
6 SITE DEVELOPMENT ELECTRICAL
7 SITE DEVELOPMENT MECHANICAL
DOCUMENT SUBMITTALS
1 DRAWING SUBMISSION SCHEDULE Schematic Design
(REVISED) Design Development
6 DESIGN CALCULATIONS
7 DRAFT DESIGN CRITERIA AND 2 SETS
PRELIMINARY CALCULATIONS
8 A 3 CHECK PRINT AND 3 SETS 3 SETS
ACCOUNTING AND BILLING
PURPOSES
Contract Submission of
Documentation documents for
permit application
3 SETS
ON PHASES
Contract Submission of
Documentation documents for
permit application
signed and sealed.
Contract Submission of
Documentation documents for
permit application
3 SETS