Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 76

PROJECT:

Construction of 66/11kV subsation (New) in Institutional Area at


Village Sarangpur on behalf of EDUTC

CUSTOMER: POWER GRID CORPORATION OF INDIA LTD

CONTRACTOR BHARAT BIJLEE LTD., MUMBAI

Client PO N2JM/C&M/CS/22(10)/EDUTC/LOA-I/386 Dated.18.01.2012

Construction of 66/11kV subsation (New) in Institutional Area at Village


PROJECT: Sarangpur on behalf of EDUTC

Consultant: DRN. NAME SIGN DATE


PRPD A.K. 4.7.12
M/s. Alif Engineers & Planners, Mumbai CHKD S.A 4.7.12
APPD S.A 4.7.12

TITLE

CONTROL ROOM BUILDING DOC. NO. REV. NO.


FOUNDATION (F1) - DESIGN 3VIN.BBL.A4.11.C.404 1
CALCULATIONS
DOC: 3 VIN BBL A4 11 C -404
ALIF ENGINEERS &
PLANNERS DESIGN OF FOOTING - F1
REV : R0

DESIGN OF BI-AXIAL ISOLATED RCC FOOTING (IS 456, 2000)

LOADS FROM ANALYSIS - SUPPORT REACTIONS

Load (T) Moments (T.M)


Load Case MX( @X ) MZ( @Z )
P TM TM
Joint 1
5 23 0.58 -0.80
6 18 0.63 4.24
7 19 -9.58 -0.70
8 28 0.53 -5.85
9 27 10.74 -0.91
Joint 6
5 27 0.6144 1.5085
6 31 0.5993 6.2836
7 22 -13.41 1.6133
8 24 0.6295 -3.2667
9 33 14.641 1.4037

0.90
COLUMN/PEDESTAL 0.90
Depth of footing from NGL = 1.5
Length (l, dim. || Z axis ) = 600 mm
Breadth (b, dim. || X axis) = 300 mm global
X
Depth of filling = 1
Height of pedestal = 2.1 m Breadth 2.1 m

global
FOOTING global
Z
Z
Foot length (L, dim. || Z axis) = 2.4 m
Foot Breadth (B, dim. || X axis) = 2.1 m
Thickness of footing (t) = 400 mm global
Clear cover to Reinforcement = 50 mm X
Main bar dia of footing = 12 mm
Effective depth of footing = 344 mm Length 2.4 m
Selfweight of the footing = 5.04 T Footing Dimensions
Area of Footing(A) = 5.04 m2
Sect mod of foot about Z axis (Zz) = 1.76 m3
Sec mod of foot about X axis (Zx) = 2.02 m3

MATERIALS OF CONSTRUCTION
Grade of concrete fck = 20 N/mm2
Grade of steel fy = 415 N/mm2

Safe NET bearing pressure = 14 T/m2


Safe gross bearing pr. = 16.55 T/m2 (net pr. + depth of foot * soil unit wt)
Allowable Bearing pressure 20.69 T/m2
Factor of overstressing 1
Unit wt of soil = 1.7 T/m3
Weight of soil retained above foot = 17.35 T

Bharat Bijlee Ltd.


DOC: 3 VIN BBL A4 11 C -404
ALIF ENGINEERS &
PLANNERS DESIGN OF FOOTING - F1
REV : R0

CALCULATION OF PRESSURES

P (T) Moments (T.M) Soil


Pmax Pmin Actual /
Load Case (Incl self wt overstress
(T/m2) (T/m2) Allowable
+ soil wt MX(@X) MZ(@Z) Factor

Joint 1
5 45.39 0.581 0.803 1 9.75 8.26 0.70
6 40.39 0.630 4.241 1.25 10.73 5.30 0.61
7 41.39 9.581 0.698 1.25 13.36 3.06 0.76
8 50.39 0.531 5.846 1.25 13.58 6.42 0.78
9 49.39 10.742 0.907 1.25 15.64 3.96 0.89
Joint 6
5 49.39 0.614 1.509 1 10.96 8.64 0.78
6 53.39 0.599 6.284 1.25 14.45 6.73 0.83
7 44.39 13.413 1.613 1.25 16.38 1.24 0.94
8 46.39 0.630 3.267 1.25 11.37 7.04 0.65
9 55.39 14.641 1.404 1.25 19.05 2.93 1.09

OK 0.89

Maximum bearing pressure = 19.05 T/m2 P M y Mx


± ±
Minimum bearing pressure = 1.24 T/m2 A Zy Zx
Hence footing is safe against max gross bearing pr.

Bharat Bijlee Ltd.


DOC: 3 VIN BBL A4 11 C -404
ALIF ENGINEERS &
PLANNERS DESIGN OF FOOTING - F1
REV : R0

FOR DESIGN OF FOOTINGS


Maximum effective soil pressure pe max
( Pu/Area+ Muz/Zz + Mux/Zx) = 19.05 T/m2
Design of footing is done using above maximum effective soil pressure

CALCULATION FOR BOTTOM STEEL


Mu about X1 X1 = ( pe max x length 2/2)= 7.71 T-m per meter
Mulimit = 32.68 T-m per meter
A st =
fy [ √
0. 5 f ck
1− 1−
4.6 Mu
f ck bd
2]bd The section is singly reinforced

Hence, Ast = 646.68 mm2


Min Ast = 412.80 mm2 (0.12 % for slab, cl 26.5.2.1)
Spacing = 174.89 mm (considering max of above two calculated values of Ast)
Provide spacing = 150 mm
pt provided = 0.22 %
Hence provide 12 mm dia bar @ 150 mm c/c parellel to length of footing ( || to Z)

Mu about N1 N1 = ( pe max x length2/2)= 7.71 T-m per meter


Calc. Ast = 646.68 mm 2
The section is singly reinforced
Min Ast = 412.8 mm2 (0.12 % for slab, cl 26.5.2.1)
Spacing = 174.89 mm (considering max of above two calculated values of Ast)
Provide spacing = 150 mm
pt provided = 0.22 %
Hence provide 12 mm dia bar @ 150 mm c/c parellel to breadth of footing ( || to X)
Arrangement of bottom reinforcement as per above design is shown below

Al
ar
as
12 mm dia bar @ 150 mm c/c ne

12 mm dia bar @ 150 mm c/c

1 1

Footing Length 2400 mm Breadth 2100 mm

Sec 1-1

Bharat Bijlee Ltd.


DOC: 3 VIN BBL A4 11 C -404
ALIF ENGINEERS &
PLANNERS DESIGN OF FOOTING - F1
REV : R0

944 300
644
L1 X1 X

a a

Z Z
N1 N1
a a

L2 L2

556 X1 X
L1 Breadth 2100 mm
600
Footing Length 2400 mm 556
PLAN

CHECK FOR ONE WAY SHEAR :


One way shear at critical section L1- L1 Instead of calcula
accurate pressure
Distance of critical sec. from edge of footing = 0.556 m ordinate at L1-L1
Shear force Vs =pe max x 0.556 x 1m width of footing = 10.591 T have used "pema
conservative side
Shear stress tv = Vs/bd = 0.308 N/mm2
tc = 0.34 N/mm2
tv < tc Hence O.K.

One way shear at critical section L2- L2


Distance of critical sec. from edge of footing = 0.556 m
Shear force Vs =pe max x 0.556 x 1m width of footing = 10.591 T
Shear stress v t = Vs/bd = 0.308 N/mm 2

tc = 0.34 N/mm2
tv < tc Hence O.K.

CHECK FOR TWO WAY SHEAR


Ref. cl 34.2.4 and cl.31.6.3 of IS 456 : 2000
Allowable shear stress tv allowable = kstc
ks = ( 0.5 + bc) = 1.64286 >1
Hence, ks= 1
tc = 0.25 (fck) 0.5
= 1.11803 N/mm2
tv allowable = ks x tc = 1.11803 N/mm2
Shear force Vs = 19.048 ( 2.4 x 2.1 - 0.944 x 0.644) = 84.42 T
Length of critical section = 2 x ( 944 + 644) = 3176 mm
Area of the critical section (length of critical sec x eff. d ) = 1092544 mm2
Hence shear stress tv = 0.773 N/mm2
tv < allowable Hence O.K.

Bharat Bijlee Ltd.


NUCLEAR POWER CORPORATION OF INDIA LTD.

DESIGN OF BI-AXIAL ISOLATED RCC FOOTING (IS 456, 2000)


Project name
Building name
global Z and X axis are assumed
X as two horizontal Global
Breadth 6.5 m axis of building.
If this moment is very high
try to reduce moment by
Hence, input the
global dimensions of footing easily changing footing size.
global Higher moment will require
Z Z by inputing footing length
parallel to global Z and higher steel and section
may be doubly reinforced. Instead of calculating
footing breadth parallel to Instead of calculating
global global X. This design is done as accurate pressure ordinate accurate pressure ordinate
X singly reinforced section. at L1-L 1 we have used at L2-L 2 we have used
Input pedestal height = 0 if Design of footing is done
Length 6.75 m self wt of footing & soil wt is "pemax" on conserv ative "pemax" on conservative

[ √ ]
wt. of pedestal/column is using above max imum
not to be considered. not considered in Pu. effective soil pressure 0 . 5 f ck 4. 6 M u side. side.
Footing Dimensions A st = 1− 1− bd
fy f ck bd
2

Column/Pedestal Footing size Footing Properties Materials of Const CHECK FOR GROSS BEARING PRESSURE FACTORED DESIGN FORCES EFFECTIVE SOIL PRESSURE CALCULATION FOR BOTTOM STEEL CHECK FOR ONE WAY SHEAR CHECK FOR TWO WAY SHEAR (Ref. cl 34.2.4 and cl.31.6.3 of IS 456 : 2000)
Length (l, Breadth Height of Weight Foot Foot Thickness Clear Main Effective Self Area of Sect mod Sec mod Grade of Grade of Safe NET Safe gross Unfactored Axial Moment Moment Depth Unit wt Weight P = (P1+ Maximum Minimum Check if Factored Axial Moment Moment Maximum Minimum Mu about X1 Mulimit Check type Ast Min Ast = Spacing pt Bar Dia Mu about N1 Check type Ast Min Ast Spacing pt Bar Dia Distance Shear Shear tc Check for Distance of Shear force Shear stress tc Check for k s = If k s >1 tc = Allowable Shear Length of Area of the Hence Check for two way
dim. || Z (b, dim. || Pedestal of length Breadth of footing cover bar dia depth of weight of Footing of foot of foot concrete steel fy bearing bearing pr. load case load about Z about X of top of soil of soil soil + bearing bearing footing is load load: about Z about X effective soil effective soil X1 = ( pe max of section (0.12 % (considering provided /Spacing of N1 = ( pe of section = (0.12 (considering provided /Spacing of of critical force Vs stress one way critical sec. Vs =pe max tv = Vs/bd one way ( 0.5 + 0.25 shear stres force critical critical shear shear
then Ks =1
axis ) X axis) pedestal (L, dim. (B, dim. || (t) to of footing footing (A) about Z about X f ck pressure (net pr. + number from axis (Mz) axis (Mx) of foot. retained Pedestal pressure pressure safe comb. no. (Pu) axis (Muz) axis (Mux) pressure p e max = ( pressure pe min = x length 2/2) singly / for slab, max of two Reinf. max x singly / % for max of two Reinf. Parallel sec. L1- =pe max tv = shear at L2- L2 from x dist of L2- shear at bc) (fck) 0.5 tv allowable = ks x Vs section section stress tv
|| Z axis) X axis) Reinf footing axis (Zz) axis (Zx) depth of foot output from above + foot against Pu/Area+ Muz/Zz ( Pu/Area - doubly cl calculated Parallel to length 2/2) doubly slab, cl calculated to breadth of L1 from x dist of Vs/bd Critical edge of L2 x 1m Critical else Ks=Ks
= tc (length of
* soil unit wt) (P1) ground footing self wt) M M max gross + Mux/Zx) Muz/Zz - reinforced. 26.5.2.1) values of length of reinforced. 26.5.2.1) values of footing (|| to edge of L1-L1 x section L1- footing width of section L2- critical sec
P
± y± x bearing pr Mux/Zx) Ast) foot. (|| to Z) Ast) X) footing 1m width L1 footing L2 x eff. d )
A Zy Zx of footing

KN-m per KN-m per KN-m per


mm mm m KN m m mm mm mm mm KN m2 m3 m3 N/mm2 N/mm2 KN/m2 KN/m2 KN KN-m KN-m m KN/m3 KN KN KN/m2 KN/m2 KN KN-m KN-m KN/m2 KN/m2 meter meter mm2 mm2 mm % mm meter mm2 mm2 mm % m KN N/mm2 N/mm2 m KN N/mm2 N/mm2 N/mm2 N/mm2 KN mm mm2 N/mm2
500 600 0 0 6.75 6.5 750 75 16 667 822.66 43.88 47.53 49.36 20 415 1650 1702.25 215 721.07 200 2000 2 19 1655.85 3199.58 117.65 28.20 SAFE 18 100 100 5 4.48 0.07 21.90 1228.80 Singly reinf 91.23 800.40 251.20 0.12 16@251c/c 19.51 Singly reinf 81.27 800.4 251.20 0.12 16@251c/c 2.458 11.023 0.017 0.26 tv < tc O.K. 2.283 10.238 0.015 0.26 tv < tc O.K. 1.53846154 1 1.118 1.118033989 190.12 4868 3246956 0.05855 tv < allowable O.K.
700 600 0 0 6.75 6.5 750 75 16 667 822.66 43.88 47.53 49.36 20 415 1650 1702.25 215 721.07 200 2000 2 19 1651.29 3195.02 117.55 28.09 SAFE 18 100 100 5 4.48 0.07 20.52 1228.80 Singly reinf 85.47 800.40 251.20 0.12 16@251c/c 19.51 Singly reinf 81.27 800.4 251.20 0.12 16@251c/c 2.358 10.574 0.016 0.26 tv < tc O.K. 2.283 10.238 0.015 0.26 tv < tc O.K. 1.53846154 1 1.118 1.118033989 188.99 5268 3513756 0.05378 tv < allowable O.K.
700 600 0 0 6.75 6.5 750 75 16 667 822.66 43.88 47.53 49.36 20 415 1650 1702.25 215 721.07 200 2000 2 19 1651.29 3195.02 117.55 28.09 SAFE 18 100 100 5 4.48 0.07 20.52 1228.80 Singly reinf 85.47 800.40 251.20 0.12 16@251c/c 19.51 Singly reinf 81.27 800.4 251.20 0.12 16@251c/c 2.358 10.574 0.016 0.26 tv < tc O.K. 2.283 10.238 0.015 0.26 tv < tc O.K. 1.53846154 1 1.118 1.118033989 188.99 5268 3513756 0.05378 tv < allowable O.K.
700 600 0 0 6.75 6.5 750 75 16 667 822.66 43.88 47.53 49.36 20 415 1650 1702.25 215 721.07 200 2000 2 19 1651.29 3195.02 117.55 28.09 SAFE 18 100 100 5 4.48 0.07 20.52 1228.80 Singly reinf 85.47 800.40 251.20 0.12 16@251c/c 19.51 Singly reinf 81.27 800.4 251.20 0.12 16@251c/c 2.358 10.574 0.016 0.26 tv < tc O.K. 2.283 10.238 0.015 0.26 tv < tc O.K. 1.53846154 1 1.118 1.118033989 188.99 5268 3513756 0.05378 tv < allowable O.K.
700 600 0 0 6.75 6.5 750 75 16 667 822.66 43.88 47.53 49.36 20 415 1650 1702.25 215 721.07 200 2000 2 19 1651.29 3195.02 117.55 28.09 SAFE 18 100 100 5 4.48 0.07 20.52 1228.80 Singly reinf 85.47 800.40 251.20 0.12 16@251c/c 19.51 Singly reinf 81.27 800.4 251.20 0.12 16@251c/c 2.358 10.574 0.016 0.26 tv < tc O.K. 2.283 10.238 0.015 0.26 tv < tc O.K. 1.53846154 1 1.118 1.118033989 188.99 5268 3513756 0.05378 tv < allowable O.K.
700 600 0 0 6.75 6.5 750 75 16 667 822.66 43.88 47.53 49.36 20 415 1650 1702.25 215 721.07 200 2000 2 19 1651.29 3195.02 117.55 28.09 SAFE 18 100 100 5 4.48 0.07 20.52 1228.80 Singly reinf 85.47 800.40 251.20 0.12 16@251c/c 19.51 Singly reinf 81.27 800.4 251.20 0.12 16@251c/c 2.358 10.574 0.016 0.26 tv < tc O.K. 2.283 10.238 0.015 0.26 tv < tc O.K. 1.53846154 1 1.118 1.118033989 188.99 5268 3513756 0.05378 tv < allowable O.K.
700 600 0 0 6.75 6.5 750 75 16 667 822.66 43.88 47.53 49.36 20 415 1650 1702.25 215 721.07 200 2000 2 19 1651.29 3195.02 117.55 28.09 SAFE 18 100 100 5 4.48 0.07 20.52 1228.80 Singly reinf 85.47 800.40 251.20 0.12 16@251c/c 19.51 Singly reinf 81.27 800.4 251.20 0.12 16@251c/c 2.358 10.574 0.016 0.26 tv < tc O.K. 2.283 10.238 0.015 0.26 tv < tc O.K. 1.53846154 1 1.118 1.118033989 188.99 5268 3513756 0.05378 tv < allowable O.K.
700 600 0 0 6.75 6.5 750 75 16 667 822.66 43.88 47.53 49.36 20 415 1650 1702.25 215 721.07 200 2000 2 19 1651.29 3195.02 117.55 28.09 SAFE 18 100 100 5 4.48 0.07 20.52 1228.80 Singly reinf 85.47 800.40 251.20 0.12 16@251c/c 19.51 Singly reinf 81.27 800.4 251.20 0.12 16@251c/c 2.358 10.574 0.016 0.26 tv < tc O.K. 2.283 10.238 0.015 0.26 tv < tc O.K. 1.53846154 1 1.118 1.118033989 188.99 5268 3513756 0.05378 tv < allowable O.K.
700 600 0 0 6.75 6.5 750 75 16 667 822.66 43.88 47.53 49.36 20 415 1650 1702.25 215 721.07 200 2000 2 19 1651.29 3195.02 117.55 28.09 SAFE 18 100 100 5 4.48 0.07 20.52 1228.80 Singly reinf 85.47 800.40 251.20 0.12 16@251c/c 19.51 Singly reinf 81.27 800.4 251.20 0.12 16@251c/c 2.358 10.574 0.016 0.26 tv < tc O.K. 2.283 10.238 0.015 0.26 tv < tc O.K. 1.53846154 1 1.118 1.118033989 188.99 5268 3513756 0.05378 tv < allowable O.K.
700 600 0 0 6.75 6.5 750 75 16 667 822.66 43.88 47.53 49.36 20 415 1650 1702.25 215 721.07 200 2000 2 19 1651.29 3195.02 117.55 28.09 SAFE 18 100 100 5 4.48 0.07 20.52 1228.80 Singly reinf 85.47 800.40 251.20 0.12 16@251c/c 19.51 Singly reinf 81.27 800.4 251.20 0.12 16@251c/c 2.358 10.574 0.016 0.26 tv < tc O.K. 2.283 10.238 0.015 0.26 tv < tc O.K. 1.53846154 1 1.118 1.118033989 188.99 5268 3513756 0.05378 tv < allowable O.K.
700 600 0 0 6.75 6.5 750 75 16 667 822.66 43.88 47.53 49.36 20 415 1650 1702.25 215 721.07 200 2000 2 19 1651.29 3195.02 117.55 28.09 SAFE 18 100 100 5 4.48 0.07 20.52 1228.80 Singly reinf 85.47 800.40 251.20 0.12 16@251c/c 19.51 Singly reinf 81.27 800.4 251.20 0.12 16@251c/c 2.358 10.574 0.016 0.26 tv < tc O.K. 2.283 10.238 0.015 0.26 tv < tc O.K. 1.53846154 1 1.118 1.118033989 188.99 5268 3513756 0.05378 tv < allowable O.K.
700 600 0 0 6.75 6.5 750 75 16 667 822.66 43.88 47.53 49.36 20 415 1650 1702.25 215 721.07 200 2000 2 19 1651.29 3195.02 117.55 28.09 SAFE 18 100 100 5 4.48 0.07 20.52 1228.80 Singly reinf 85.47 800.40 251.20 0.12 16@251c/c 19.51 Singly reinf 81.27 800.4 251.20 0.12 16@251c/c 2.358 10.574 0.016 0.26 tv < tc O.K. 2.283 10.238 0.015 0.26 tv < tc O.K. 1.53846154 1 1.118 1.118033989 188.99 5268 3513756 0.05378 tv < allowable O.K.

446521818.xls
NUCLEAR POWER CORPORATION OF INDIA LTD.

All drawings on this sheet


are updated automatically
as per design changes and
need not be edited.
16 mm dia bar @ 251 mm c/c

16 mm dia bar @ 251 mm c/c

1 1

Footing Length 6750 mm Breadth 6500 mm

446521818.xls
NUCLEAR POWER CORPORATION OF INDIA LTD.

Sec 1-1

1167 600
1267
L1 X1 X

a a

Z Z
N1 N1
a a

L2 L2

2458 X1 X
L1 Breadth 6500 mm
500
Footing Length 6750 mm 2283
PLAN

446521818.xls
NUCLEAR POWER CORPORATION OF INDIA LTD.

DESIGN OF BI-AXIAL ISOLATED RCC FOOTING (IS 456, 2000)


Building Name
Footing Number:
Node number

COLUMN
Length (l, dim. || Z axis ) = 700 mm
Breadth (b, dim. || X axis) = 600 mm global
X Input pedestal height = 0 if
Height of pedestal = 1 m Breadth 3 m wt. of pedestal/column is
Weight of pedestal/column = 10.50 KN not to be considered.

FOOTING
global
Foot length (L, dim. || Z axis) = 5 m global
Z
Foot Breadth (B, dim. || X axis) = 3 m Z Z and X axis are assumed
Thickness of footing (t) = 750 mm as two horizontal Global
global
Clear cover to Reinforcement = 75 mm X axis of building.
Main bar dia of footing = 16 mm
Hence, input the
Effective depth of footing = 667 mm Length 5 m dimensions of footing easily
Selfweight of the footing = 281.25 KN by inputing footing length
Footing Dimensions parallel to global Z and
Area of Footing(A) = 15.00 m2
footing breadth parallel to
Sect mod of foot about Z axis (Zz) = 7.50 m3 global X.
Sec mod of foot about X axis (Zx) = 12.50 m3

MATERIALS OF CONSTRUCTION
Grade of concrete fck = 20 N/mm2
Grade of steel fy = 415 N/mm2

CHECK FOR GROSS BEARING PRESSURE


Safe NET bearing pressure = 1650 KN/m2
Safe gross bearing pr. = 1702.25 KN/m2 (net pr. + depth of foot * soil unit wt)
Unfactored load case number = 215 To perform successful
iteration do not input '0'
Axial load from output (P1) = 10 KN these cells. Atleast input
Moment about Z axis (Mz) = 500 KN-m 0.1 to these cells when
there is no moment.
Moment about X axis (Mx) = 450 KN-m
Depth of top of foot. from ground = 2 m
Unit wt of soil = 19 KN/m3
Weight of soil retained above foot = 554.04 KN If min pressure is negat
P = (P1+soil+pedestal+foot selfwt) = 855.79 KN then to recalculate
pressure use solver of
Maximum bearing pressure = 159.72 KN/m2 P M y Mx sheet1.
Minimum bearing pressure = -45.61 KN/m2 ± ±
A Zy Zx
Recalculation of max pressure done below as min pressure is negative.
Recalculated max bearing press. = 170.80 KN/m2 Max bearing pressure is safe
Minimum bearing pressure = 0 KN/m2
Hide this two rows befor
DESIGN FORCES print out if they are
highlighted.
Factored load comb. no. 18
Axial load:(Pu) = 150 KN
Moment about Z axis (Muz) = 150 KN-m
Moment about X axis (Mux) = 150 KN-m self wt of footing & soil
is not to be considered i
Maximum effective soil pressure pe max Pu.
( Pu/Area+ Muz/Zz + Mux/Zx) = 42.00 KN/m2
Minimum effective soil pressure p e min If min pressure is nega
then to recalculate pres
( Pu/Area - Muz/Zz - Mux/Zx) = -22.00 KN/m 2
use solver of sheet2.
Recalculation of maximum effective pressure done below as min pressure is negative.

446521818.xls
NUCLEAR POWER CORPORATION OF INDIA LTD. If min pressure is nega
then to recalculate pres
use solver of sheet2.

Maximum effective soil pressure pe max 75.15 KN/m2


Minimum effective soil pressure p e min 0 KN/m2
Hide this two rows befo
print out if they are
highlighted.

446521818.xls
NUCLEAR POWER CORPORATION OF INDIA LTD.

Hide this two rows befo


CALCULATION FOR BOTTOM STEEL print out if they are
Mu about X1 X1 = ( pe max x length2/2)= 173.68 KN-m per meter highlighted.
Mulimit = 1228.80 KN-m per meter
A st =
fy [ √
0. 5 f ck
1− 1−
4.6 Mu
f ck bd
2
bd
] The section is singly reinforced If this moment is very
try to reduce moment
changing footing size.
Higher moment will re
Hence, Ast = 738.53 mm2 higher steel and sectio
Min Ast = 800.40 mm2 (0.12 % for slab, cl 26.5.2.1) may be doubly reinforc
This design is done as
Spacing = 251.20 mm (considering max of above two calculated values of Ast) singly reinforced sectio
pt provided = 0.12 %
Hence provide 16 mm dia bar @ 251 mm c/c parellel to length of footing ( || to Z) at bottom

Mu about N1 N1 = ( pe max x length2/2)= 54.10 KN-m per meter


Calc. Ast = 226.38 mm 2
The section is singly reinforced
Min Ast = 800.40 mm2 (0.12 % for slab, cl 26.5.2.1)
Spacing = 251.20 mm (considering max of above two calculated values of Ast)
pt provided = 0.12 %
Hence provide 16 mm dia bar @ 251 mm c/c parellel to breadth of footing ( || to X) at bottom
Arrangement of bottom reinforcement as per above design is shown below

All drawings on this sheet


16 mm dia bar @ 251 mm c/c
are updated automatically
as per design changes and
need not be edited.

16 mm dia bar @ 251 mm c/c

1 1

Footing Length 5000 mm Breadth 3000 mm

Sec 1-1

1367 600
1267
L1 X1 X

a a

Z Z
N1 N1
a a

L2 L2

1483 X1 X
L1 Breadth 3000 mm
700
Footing Length 5000 mm 533
PLAN

446521818.xls
NUCLEAR POWER CORPORATION OF INDIA LTD.

CHECK FOR ONE WAY SHEAR :


One way shear at critical section L1- L1
Distance of critical sec. from edge of footing = 1.483 m
Shear force Vs =pe max x 1.483 x 1m width of footing = 111.44 KN Instead of calculating
accurate pressure
Shear stress tv = Vs/bd = 0.167 N/mm 2
ordinate at L1-L1 we
tc = have used "pemax" on
0.26 N/mm2
conservative side.
tv < tc hence O.K.

One way shear at critical section L2- L2


Distance of critical sec. from edge of footing = 0.533 m
Shear force Vs =pe max x 0.533 x 1m width of footing = 40.05 KN
Shear stress tv = Vs/bd = 0.060 N/mm2
tc = 0.26 N/mm2
tv < tc hence O.K.

CHECK FOR TWO WAY SHEAR


Ref. cl 34.2.4 and cl.31.6.3 of IS 456 : 2000
Allowable shear stress tv allowable = kstc
ks = ( 0.5 + bc) = 2.16667 >1
Hence, ks= 1
tc = 0.25 (fck)0.5 = 1.11803 N/mm2
tv allowable = ks x tc = 1.11803 N/mm2
Shear force Vs = 42 ( 5 x 3 - 1.367 x 1.267) = 557.26 KN
Length of critical section = 2 x ( 1367 + 1267) = 5268 mm
Area of the critical section (length of critical sec x eff. d ) = 3513756 mm2
Hence shear stress tv = 0.159 N/mm2
tv < allowable hence O.K.

446521818.xls
uniaxial

-32.5209652
4.218141515

Page 14
biaxial

1.00E+30
-32.5209652
4.218141515

Page 15
UNI

-233.931624
2.604476613

Page 16
B

1.00E+30
-32.5209652
4.218141515

Page 17
B1

1.00E+30
-233.931624
2.604476613

Page 18
DOC: 3 VIN BBL A4 11 C -404
ALIF ENGINEERS &
PLANNERS DESIGN OF FOOTING - F1
REV : R0

LOADS FROM ANALYSIS - SUPPORT REACTIONS

Load (T) Moments (T.M)


Load Case MX( @X ) MZ( @Z )
P TM TM
Joint 15
5 25 -0.102 -0.5796
6 20 -0.08 7.9806
7 25 -3.467 -0.6021
8 29 -0.123 -9.1397
9 24 3.2636 -0.557
Joint 17
5 20 -2.452 0.9204
6 24 -2.597 4.6971
7 29 -10.28 0.9205
8 17 -2.306 -2.8563
9 11 5.3792 0.9203
Joint 23
5 28 0.1384 0.8294
6 31 0.2547 4.7489
7 23 -7.668 0.8381
8 24 0.0221 -3.09
9 32 7.9446 0.8208
Joint 24
5 22 -0.891 -0.7849
6 18 -0.861 3.5664
7 26 -7.469 -0.9039
8 26 -0.922 -5.1362
9 18 5.6861 -0.6659
Joint 29
5 29 -1.1911 1.506
6 31 -1.208 5.6833
7 33 -9.991 1.3998
8 26 -1.174 -2.6714
9 24 7.6092 1.6121
Input pedestal heigh
wt. of pedestal/colum
COLUMN/PEDESTAL not to be considered
Depth of footing from NGL = 1.5
Length (l, dim. || Z axis ) = 500 mm
Breadth (b, dim. || X axis) = 300 mm global
X
Depth of filling = 1
Z and X axis are assum
Height of pedestal = 2.1 m Breadth 2.1 m as two horizontal Globa
axis of building.
global Hence, input the
FOOTING global
Z dimensions of footing e
Z
Foot length (L, dim. || Z axis) = 2.4 m by inputing footing leng
Foot Breadth (B, dim. || X axis) = 2.1 m parallel to global Z and
global footing breadth parallel
Thickness of footing (t) = 400 mm global X.
Clear cover to Reinforcement = 50 mm X

Bharat Bijlee Ltd.


Hence, input the
dimensions of footing e
by Cinputing
DOC: 3 VIN BBL A4 11 -404 footing leng
ALIF ENGINEERS & parallel to global Z and
PLANNERS DESIGN OF FOOTING - F1 footing breadth parallel
global X.
REV : R0
Main bar dia of footing = 12 mm
Effective depth of footing = 344 mm Length 2.4 m
Selfweight of the footing = 5.04 T Footing Dimensions
Area of Footing(A) = 5.04 m2
Sect mod of foot about Z axis (Zz) = 1.76 m3
Sec mod of foot about X axis (Zx) = 2.02 m3

Bharat Bijlee Ltd.


DOC: 3 VIN BBL A4 11 C -404
ALIF ENGINEERS &
PLANNERS DESIGN OF FOOTING - F1
REV : R0

MATERIALS OF CONSTRUCTION
Grade of concrete fck = 20 N/mm2
Grade of steel fy = 415 N/mm2
`
Safe NET bearing pressure = 14 T/m2

Safe gross bearing pr. = 16.55 T/m2 (net pr. + depth of foot * soil unit wt)
Allowable Bearing pressure 20.69 T/m2
Factor of overstressing 1
Unit wt of soil = 1.7 T/m3
Weight of soil retained above foot = 17.46 T

CALCULATION OF PRESSURES

P (T) Moments (T.M) Soil


Pmax Pmin Actual /
Load Case (Incl self wt overstress
(T/m2) (T/m2) Allowable
+ soil wt MX@X MZ@Z Factor
Joint 15
5 47.50 -0.102 -0.580 1 9.80 9.05 0.59
6 42.50 -0.080 7.981 1.25 13.00 3.87 0.63
7 47.50 -3.467 -0.602 1.25 11.49 7.36 0.56
8 51.50 -0.123 -9.140 1.25 15.46 4.98 0.75
9 46.50 3.264 -0.557 1.25 11.16 7.29 0.54
Joint 17
5 42.50 -2.452 0.920 1 10.17 6.69 0.61
6 46.50 -2.597 4.697 1.25 13.18 5.27 0.64
7 51.50 -10.282 0.921 1.25 15.84 4.60 0.77
8 39.50 -2.306 -2.856 1.25 10.60 5.07 0.51
9 33.50 5.379 0.920 1.25 9.84 3.46 0.48
Joint 23
5 50.50 0.138 0.829 1 10.56 9.48 0.64
6 53.50 0.255 4.749 1.25 13.43 7.80 0.65
7 45.50 -7.668 0.838 1.25 13.31 4.75 0.64
8 46.50 0.022 -3.090 1.25 10.99 7.46 0.53
9 54.50 7.945 0.821 1.25 15.22 6.41 0.74
Joint 24
5 44.50 -0.891 -0.785 1 9.72 7.94 0.59
6 40.50 -0.861 3.566 1.25 10.48 5.59 0.51
7 48.50 -7.469 -0.904 1.25 13.84 5.41 0.67
8 48.50 -0.922 -5.136 1.25 12.99 6.25 0.63
9 40.50 5.686 -0.666 1.25 11.23 4.84 0.54
Joint 29
5 51.50 -1.191 1.506 1 11.66 8.77 0.70
6 53.50 -1.208 5.683 1.25 14.44 6.79 0.70
7 55.50 -9.991 1.400 1.25 16.76 5.26 0.81
8 48.50 -1.174 -2.671 1.25 11.72 7.53 0.57
9 46.50 7.609 1.612 1.25 13.91 4.54 0.67

OK 0.72

Maximum bearing pressure = 16.76 T/m2 P M y Mx


Minimum bearing pressure = 3.46 T/m2
± ±
A Zy Zx
Hence footing is safe against max gross bearing pr.
Bharat Bijlee Ltd.
DOC: 3 VIN BBL A4 11 C -404
ALIF ENGINEERS &
PLANNERS DESIGN OF FOOTING - F1
REV : R0

FOR DESIGN OF FOOTINGS


Maximum effective soil pressure pe max If this moment is v
try to reduce mom
( Pu/Area+ Muz/Zz + Mux/Zx) = 16.76 T/m2 changing footing s
Design of footing is done using above maximum effective soil pressure Higher moment wi
higher steel and se
may be doubly rein
CALCULATION FOR BOTTOM STEEL This design is done
Mu about X1 X1 = ( pe max x length 2/2)= 7.56 T-m per meter singly reinforced se
Mulimit = 32.68 T-m per meter
A st =
fy [ √
0. 5 f ck
1− 1−
4.6 Mu
f ck bd 2]bd The section is singly reinforced

Hence, Ast = 633.47 mm2


Min Ast = 412.80 mm2 (0.12 % for slab, cl 26.5.2.1)
Spacing = 178.54 mm (considering max of above two calculated values of Ast)
Provide spacing = 150 mm
pt provided = 0.22 %
Hence provide 12 mm dia bar @ 150 mm c/c parallel to length of footing ( || to Z)

Mu about N1 N1 = ( pe max x length2/2)= 6.79 T-m per meter


Calc. Ast = 566.15 mm2 The section is singly reinforced
Min Ast = 412.8 mm2 (0.12 % for slab, cl 26.5.2.1)
Spacing = 199.76 mm (considering max of above two calculated values of Ast) All drawings on this
are updated automa
Provide spacing = 150 mm as per design chang
pt provided = 0.22 % need not be edited.
Hence provide 12 mm dia bar @ 150 mm c/c parallel to breadth of footing ( || to X)
Arrangement of bottom reinforcement as per above design is shown below

12 mm dia bar @ 150 mm c/c

12 mm dia bar @ 150 mm c/c

1 1

Footing Length 2400 mm Breadth 2100 mm

Sec 1-1

Bharat Bijlee Ltd.


DOC: 3 VIN BBL A4 11 C -404
ALIF ENGINEERS &
PLANNERS DESIGN OF FOOTING - F1
REV : R0

844 300
644
L1 X1 X

a a

Z Z
N1 N1
a a

L2 L2

606 X1 X
L1 Breadth 2100 mm
Instead of calculatin
500 accurate pressure
Footing Length 2400 mm 556 ordinate at L1-L1 we
have used "pemax"
PLAN
conservative side.

CHECK FOR ONE WAY SHEAR :


One way shear at critical section L1- L1
Distance of critical sec. from edge of footing = 0.606 m
Shear force Vs =pe max x 0.606 x 1m width of footing = 10.157 T
Shear stress tv = Vs/bd = 0.295 N/mm 2

tc = 0.34 N/mm2
tv < tc Hence O.K.

One way shear at critical section L2- L2


Distance of critical sec. from edge of footing = 0.556 m
Shear force Vs =pe max x 0.556 x 1m width of footing = 9.319 T
Shear stress tv = Vs/bd = 0.271 N/mm2
tc = 0.34 N/mm2
tv < tc Hence O.K.

CHECK FOR TWO WAY SHEAR


Ref. cl 34.2.4 and cl.31.6.3 of IS 456 : 2000
Allowable shear stress tv allowable = kstc
ks = ( 0.5 + bc) = 1.64286 >1
Hence, ks= 1
tc = 0.25 (fck) 0.5
= 1.11803 N/mm2
tv allowable = ks x tc = 1.11803 N/mm2
Shear force Vs = 16.76 ( 2.4 x 2.1 - 0.844 x 0.644) = 75.36 T
Length of critical section = 2 x ( 844 + 644) = 2976 mm
Area of the critical section (length of critical sec x eff. d ) = 1023744 mm2
Hence shear stress tv = 0.736 N/mm2
tv < Allowable Hence O.K.

Bharat Bijlee Ltd.


Input pedestal height = 0 if
wt. of pedestal/column is
not to be considered.
0.9

0.95

Z and X axis are assumed


as two horizontal Global
axis of building.

Hence, input the


dimensions of footing easily
by inputing footing length
parallel to global Z and
footing breadth parallel to
global X.

Bharat Bijlee Ltd.


Hence, input the
dimensions of footing easily
by inputing footing length
parallel to global Z and
footing breadth parallel to
global X.

Bharat Bijlee Ltd.


If this moment is very high
try to reduce moment by
changing footing size.
Higher moment will require
higher steel and section
may be doubly reinforced.
This design is done as
singly reinforced section.

All drawings on this sheet


are updated automatically
as per design changes and
need not be edited.

Bharat Bijlee Ltd.


Instead of calculating
accurate pressure
ordinate at L1-L1 we
have used "pemax" on
conservative side.

Bharat Bijlee Ltd.


DOC: 3 VIN BBL A4 11 C -404
ALIF ENGINEERS &
PLANNERS DESIGN OF FOOTING - F2
REV : R0

LOADS FROM ANALYSIS - SUPPORT REACTIONS


Load (T) Moments (T.M)
Load Case MX( @X ) MZ( @Z )
P TM TM
Joint 3
5 32 7.293 0.3578
6 28 7.272 6.3399
7 31 -1.1149 0.4842
8 37 7.314 -5.6243
9 33 15.701 0.2314
Joint 4
5 29 7.0388 -0.3266
6 33 6.9535 5.6936
7 28 -2.942 -0.1996
8 25 7.1242 -6.3467
9 30 17.019 -0.4536
Joint 7
5 34 -0.1119 -2.8347
6 32 -0.096 10.9322
7 35 -4.038 -2.875
8 35 -0.128 -16.602
9 32 3.8138 -2.7944
Joint 8
5 35 -0.142 3.4418
6 37 -0.145 18.1733
7 37 -5.644 3.5456
8 34 -0.139 -11.29
9 33 5.3597 3.338

Bharat Bijlee Ltd.


DOC: 3 VIN BBL A4 11 C -404
ALIF ENGINEERS &
PLANNERS DESIGN OF FOOTING - F2
REV : R0

COLUMN/PEDESTAL
Depth of footing from NGL = 1.5 Input pedestal height = 0 if
Length (l, dim. || Z axis ) = 600 mm wt. of pedestal/column is
global not to be considered.
Breadth (b, dim. || X axis) = 300 mm
X
Depth of filling = 1
Height of pedestal = 2.05 m Breadth 2.2 m

global
FOOTING global Z and X axis are assumed
Z
Z as two horizontal Global
Foot length (L, dim. || Z axis) = 2.5 m axis of building.
Foot Breadth (B, dim. || X axis) = 2.2 m
Thickness of footing (t) = 450 mm global Hence, input the
X dimensions of footing easily
Clear cover to Reinforcement = 50 mm by inputing footing length
Main bar dia of footing = 12 mm parallel to global Z and
Effective depth of footing = 394 mm Length 2.5 m footing breadth parallel to
global X.
Selfweight of the footing = 6.19 T Footing Dimensions
Area of Footing(A) = 5.50 m2
Sect mod of foot about Z axis (Zz) = 2.02 m3
Sec mod of foot about X axis (Zx) = 2.29 m3

MATERIALS OF CONSTRUCTION
Grade of concrete fck = 20 N/mm2
Grade of steel fy = 415 N/mm2

Safe NET bearing pressure = 14 T/m2


Safe gross bearing pr. = 16.55 T/m2 (net pr. + depth of foot * soil unit wt)
Allowable Bearing pressure 20.69 T/m2
Factor of overstressing 1
Unit wt of soil = 1.7 T/m3
Weight of soil retained above foot = 18.54 T

Bharat Bijlee Ltd.


DOC: 3 VIN BBL A4 11 C -404
ALIF ENGINEERS &
PLANNERS DESIGN OF FOOTING - F2
REV : R0

CALCULATION OF PRESSURES

P (T) Moments (T.M) Soil


Pmax Pmin Actual /
Load Case (Incl self wt overstress
(T/m2) (T/m2) Allowable
+ soil wt MX(@X) MZ(@Z) Factor

Joint 3
5 56.73 7.293 0.358 1 13.67 6.95 0.83
6 52.73 7.272 6.340 1.25 15.90 3.27 0.77
7 55.73 -1.115 0.484 1.25 10.86 9.41 0.52
8 61.73 7.314 -5.624 1.25 17.20 5.24 0.83
9 57.73 15.701 0.231 1.25 17.46 3.53 0.84
Joint 4
5 53.73 7.039 -0.327 1 13.00 6.54 0.79
6 57.73 6.954 5.694 1.25 16.35 4.64 0.79
7 52.73 -2.942 -0.200 1.25 10.97 8.20 0.53
8 49.73 7.124 -6.347 1.25 15.30 2.79 0.74
9 54.73 17.019 -0.454 1.25 17.60 2.30 0.85
Joint 7
5 58.73 -0.112 -2.835 1 12.13 9.22 0.73
6 56.73 -0.096 10.932 1.25 15.78 4.85 0.76
7 59.73 -4.038 -2.875 1.25 14.05 7.67 0.68
8 59.73 -0.128 -16.602 1.25 19.15 2.57 0.93
9 56.73 3.814 -2.794 1.25 13.36 7.26 0.65
Joint 8
5 59.73 -0.142 3.442 1 12.63 9.09 0.76
6 61.73 -0.145 18.173 1.25 20.30 2.15 0.98
7 61.73 -5.644 3.546 1.25 15.44 7.00 0.75
8 58.73 -0.139 -11.290 1.25 16.34 5.02 0.79
9 57.73 5.360 3.338 1.25 14.49 6.50 0.70
OK

Bharat Bijlee Ltd.


DOC: 3 VIN BBL A4 11 C -404
ALIF ENGINEERS &
PLANNERS DESIGN OF FOOTING - F2
REV : R0
0.98
Maximum bearing pressure = 20.30 T/m2 P M y Mx
± ±
Minimum bearing pressure = 2.15 T/m2 A Zy Zx
Hence footing is safe against max gross bearing pr.

FOR DESIGN OF FOOTINGS


Maximum effective soil pressure pe max
( Pu/Area+ Muz/Zz + Mux/Zx) = 20.30 T/m2
Design of footing is done using above maximum effective soil pressure If this moment is very high
try to reduce moment by
CALCULATION FOR BOTTOM STEEL changing footing size.
Higher moment will require
Mu about X1 X1 = ( pe max x length2/2)= 9.16 T-m per meter higher steel and section
Mulimit = 42.88 T-m per meter may be doubly reinforced.

A st =
fy [ √
0. 5 f ck
1− 1−
4.6 Mu
f ck bd
2]bd The section is singly reinforced This design is done as
singly reinforced section.

Hence, Ast = 667.68 mm2


Min Ast = 472.80 mm2 (0.12 % for slab, cl 26.5.2.1)
Spacing = 169.39 mm (considering max of above two calculated values of Ast)
Provide spacing = 150 mm
pt provided = 0.19 %
Hence provide 12 mm dia bar @ 150 mm c/c parallel to length of footing ( || to Z)

Mu about N1 N1 = ( pe max x length2/2)= 9.16 T-m per meter


Calc. Ast = 667.68 mm2 The section is singly reinforced
Min Ast = 472.8 mm2 (0.12 % for slab, cl 26.5.2.1)
Spacing = 169.39 mm (considering max of above two calculated values of Ast)
Provide spacing = 150 mm
pt provided = 0.19 %
Hence provide 12 mm dia bar @ 150 mm c/c parallel to breadth of footing ( || to X)
Arrangement of bottom reinforcement as per above design is shown below
All drawings on this sheet
are updated automatically
as per design changes and
need not be edited.
12 mm dia bar @ 150 mm c/c

12 mm dia bar @ 150 mm c/c

1 1

Footing Length 2500 mm Breadth 2200 mm

Sec 1-1

Bharat Bijlee Ltd.


DOC: 3 VIN BBL A4 11 C -404
ALIF ENGINEERS &
PLANNERS DESIGN OF FOOTING - F2
REV : R0

994 300
694
L1 X1 X

a a

Z Z
N1 N1
a a

L2 L2 Instead of calculating
accurate pressure
ordinate at L1-L1 we
556 X1 X have used "pemax" on
L1 Breadth 2200 mm conservative side.
600
Footing Length 2500 mm 556
PLAN

CHECK FOR ONE WAY SHEAR :


One way shear at critical section L1- L1
Distance of critical sec. from edge of footing = 0.556 m
Shear force Vs =pe max x 0.556 x 1m width of footing = 11.286 T
Shear stress tv = Vs/bd = 0.286 N/mm 2

tc = 0.32 N/mm2
tv < tc Hence O.K.

One way shear at critical section L2- L2


Distance of critical sec. from edge of footing = 0.556 m
Shear force Vs =pe max x 0.556 x 1m width of footing = 11.286 T
Shear stress tv = Vs/bd = 0.286 N/mm2
tc = 0.32 N/mm2
tv < tc Hence O.K.

CHECK FOR TWO WAY SHEAR


Ref. cl 34.2.4 and cl.31.6.3 of IS 456 : 2000
Allowable shear stress tv allowable = kstc
ks = ( 0.5 + bc) = 1.63636 >1
Hence, ks= 1
tc = 0.25 (fck)0.5 = 1.11803 N/mm2
tv allowable = ks x tc = 1.11803 N/mm2
Shear force Vs = 20.297 ( 2.5 x 2.2 - 0.994 x 0.694) = 97.64 T
Length of critical section = 2 x ( 994 + 694) = 3376 mm
Area of the critical section (length of critical sec x eff. d ) = 1330144 mm2
Hence shear stress tv = 0.734 N/mm2
tv < Allowable Hence O.K.

Bharat Bijlee Ltd.


DOC: 3 VIN BBL A4 11 C -404
ALIF ENGINEERS &
PLANNERS DESIGN OF FOOTING - F3
REV : R0

LOADS FROM ANALYSIS - SUPPORT REACTIONS


Load (T) Moments (T.M)
Load Case MX( @X ) MZ( @Z )
P TM TM
Joint 14
5 41 0.0568 1.1322
6 45 0.0548 12.2784
7 41 -4.364 1.1633
8 36 0.0587 -10.014
9 40 4.477 1.101
Joint 18
5 38 -0.832 -1.1538
6 31 -0.802 8.9136
7 39 -5.636 -1.1698
8 46 -0.862 -11.221
9 38 3.9718 -1.1378
Joint 19
5 65 -1.245 -1.2281
6 69 -1.235 10.1167
7 66 -7.074 -1.2455
8 62 -1.255 -12.573
9 65 4.5849 -1.2107
Joint 20
5 44 -0.014 1.5771
6 48 -0.024 11.0707
7 43 -4.667 1.5637
8 40 -0.003 -7.9165
9 46 4.6399 1.5905
Joint 22
5 44 0.063 0.0567
6 45 0.0828 4.7392
7 40 -7.293 0.069
8 43 0.0432 -4.6258
9 47 7.4186 0.0444
Joint 25
5 39 -1.417 0.0051
6 40 -1.398 5.0136
7 45 -8.704 -0.1276
8 38 -1.437 -5.0034
9 32 5.8695 0.1378
Joint 28
5 47 -3.734 -0.6569
6 48 -3.715 4.264
7 52 -14.16 -0.7881
8 46 -3.752 -5.5778
9 41 6.6917 -0.5258
Input pedestal height =
COLUMN/PEDESTAL wt. of pedestal/column i
Depth of footing from NGL = 1.5 1.05 not to be considered.

Length (l, dim. || Z axis ) = 500 mm 1.05


Breadth (b, dim. || X axis) = 300 mm global
X Z and X axis are assume
Depth of filling = 1
as two horizontal Global
Height of pedestal = 2.05 m Breadth 2.4 m
axis of building.

global Hence, input the


FOOTING global dimensions of footing ea
Z by inputing footing lengt
Z
Foot length (L, dim. || Z axis) = 2.6 m parallel to global Z and
Foot Breadth (B, dim. || X axis) = 2.4 m footing breadth parallel
Thickness of footing (t) = 450 mm global global X.

Clear cover to Reinforcement = 50 mm X


Main bar dia of footing = 12 mm
Effective depth of footing = 394 mm Length 2.6 m
Selfweight of the footing = 7.02 T Footing Dimensions
Area of Footing(A) = 6.24 m2
Sect mod of foot about Z axis (Zz) = 2.50 m3
Sec mod of foot about X axis (Zx) = 2.70 m3

MATERIALS OF CONSTRUCTION
Grade of concrete fck = 20 N/mm2
Grade of steel fy = 415 N/mm2

Safe NET bearing pressure = 14 T/m2


Safe gross bearing pr. = 16.55 T/m2 (net pr. + depth of foot * soil unit wt)
Allowable Gross Bearing pressure 20.69 T/m2
Factor of overstressing 1
Unit wt of soil = 1.7 T/m3
Weight of soil retained above foot = 21.22 T
CALCULATION OF PRESSURES

P (T) Moments (T.M) Soil


Pmax Pmin Actual /
Load Case (Incl self wt overstress
(T/m2) (T/m2) Allowable
+ soil wt MX(@X) MZ(@Z) Factor

Joint 14
5 69.24 0.057 1.132 1 11.57 10.62 0.70
6 73.24 0.055 12.278 1.25 16.68 6.80 0.81
7 69.24 -4.364 1.163 1.25 13.18 9.02 0.64
8 64.24 0.059 -10.014 1.25 14.33 6.26 0.69
9 68.24 4.477 1.101 1.25 13.03 8.84 0.63
Joint 18
5 66.24 -0.832 -1.154 1 11.39 9.85 0.69
6 59.24 -0.802 8.914 1.25 13.36 5.63 0.65
7 67.24 -5.636 -1.170 1.25 13.33 8.22 0.64
8 74.24 -0.862 -11.221 1.25 16.71 7.08 0.81
9 66.24 3.972 -1.138 1.25 12.54 8.69 0.61
Joint 19
5 93.24 -1.245 -1.228 1 15.90 13.99 0.960
6 97.24 -1.235 10.117 1.25 20.09 11.07 0.97
7 94.24 -7.074 -1.246 1.25 18.22 11.99 0.88
8 90.24 -1.255 -12.573 1.25 19.96 8.96 0.96
9 93.24 4.585 -1.211 1.25 17.12 12.76 0.83
Joint 20
5 72.24 -0.014 1.577 1 12.21 10.94 0.74
6 76.24 -0.024 11.071 1.25 16.66 7.77 0.81
7 71.24 -4.667 1.564 1.25 13.77 9.06 0.67
8 68.24 -0.003 -7.917 1.25 14.11 7.76 0.68
9 74.24 4.640 1.591 1.25 14.25 9.54 0.69
Joint 22
5 72.24 0.063 0.057 1 11.62 11.53 0.70
6 73.24 0.083 4.739 1.25 13.67 9.81 0.66
7 68.24 -7.293 0.069 1.25 13.66 8.21 0.66
8 71.24 0.043 -4.626 1.25 13.29 9.55 0.64
9 75.24 7.419 0.044 1.25 14.82 9.30 0.72
Joint 25
5 67.24 -1.417 0.005 1 11.30 10.25 0.68
6 68.24 -1.398 5.014 1.25 13.46 8.41 0.65
7 73.24 -8.704 -0.128 1.25 15.01 8.47 0.73
8 66.24 -1.437 -5.003 1.25 13.15 8.08 0.64
9 60.24 5.870 0.138 1.25 11.88 7.43 0.57
Joint 28
5 75.24 -3.734 -0.657 1 13.70 10.41 0.83
6 76.24 -3.715 4.264 1.25 15.30 9.14 0.74
7 80.24 -14.159 -0.788 1.25 18.41 7.31 0.89
8 74.24 -3.752 -5.578 1.25 15.52 8.28 0.75
9 69.24 6.692 -0.526 1.25 13.78 8.41 0.67
OK
0.97
Maximum bearing pressure = 20.09 T/m2 P My Mx
Minimum bearing pressure = 5.63 T/m2
± ±
A Zy Zx
Hence footing is safe against max gross bearing pr.
If this moment is very h
FOR DESIGN OF FOOTINGS try to reduce moment by
changing footing size.
Maximum effective soil pressure pe max Higher moment will requ
( Pu/Area+ Muz/Zz + Mux/Zx) = 20.09 T/m2 higher steel and section
may be doubly reinforce
Design of footing is done using above maximum effective soil pressure This design is done as
singly reinforced section
may be doubly reinforce
This design is done as
singly reinforced section
CALCULATION FOR BOTTOM STEEL
Mu about X1 X1 = ( pe max x length 2/2)= 11.08 T-m per meter
Mulimit = 42.88 T-m per meter
A st =
fy [ √
0. 5 f ck
1− 1−
4.6 Mu
]
f ck bd 2
bd The section is singly reinforced

Hence, Ast = 813.94 mm2


Min Ast = 472.80 mm2 (0.12 % for slab, cl 26.5.2.1)
Spacing = 138.95 mm (considering max of above two calculated values of Ast)
Provide spacing = 125 mm
pt provided = 0.23 %
Hence provide 12 mm dia bar @ 125 mm c/c parallel to length of footing ( || to Z)

Mu about N1 N1 = ( pe max x length2/2)= 11.08 T-m per meter


Calc. Ast = 813.94 mm 2
The section is singly reinforced
Min Ast = 472.8 mm2 (0.12 % for slab, cl 26.5.2.1)
Spacing = 138.95 mm (considering max of above two calculated values of Ast)
Provide spacing = 125 mm All drawings on this shee
pt provided = 0.23 % are updated automatical
Hence provide 12 mm dia bar @ 125 mm c/c parallel to breadth of footing ( || to X) as per design changes a
need not be edited.
Arrangement of bottom reinforcement as per above design is shown below

12 mm dia bar @ 125 mm c/c

12 mm dia bar @ 125 mm c/c

1 1

Footing Length 2600 mm Breadth 2400 mm

Sec 1-1
894 300
694
L1 X1 X

a a

Z Z
N1 N1
a a

L2 L2

656 X1 X Instead of calculating


accurate pressure
L1 Breadth 2400 mm ordinate at L1-L1 we
500 have used "pemax" o
Footing Length 2600 mm 656 conservative side.
PLAN

CHECK FOR ONE WAY SHEAR :


One way shear at critical section L1- L1
Distance of critical sec. from edge of footing = 0.656 m
Shear force Vs =pe max x 0.656 x 1m width of footing = 13.182 T
Shear stress tv = Vs/bd = 0.335 N/mm2
tc = 0.35 N/mm2
tv < tc Hence O.K.

One way shear at critical section L2- L2


Distance of critical sec. from edge of footing = 0.656 m
Shear force Vs =pe max x 0.656 x 1m width of footing = 13.182 T
Shear stress tv = Vs/bd = 0.335 N/mm 2

tc = 0.35 N/mm2
tv < tc Hence O.K.

CHECK FOR TWO WAY SHEAR


Ref. cl 34.2.4 and cl.31.6.3 of IS 456 : 2000
Allowable shear stress tv allowable = kstc
ks = ( 0.5 + bc) = 1.58333 >1
Hence, ks= 1
tc = 0.25 (fck)0.5 = 1.11803 N/mm2
tv allowable = ks x tc = 1.11803 N/mm2
Shear force Vs = 20.093 ( 2.6 x 2.4 - 0.894 x 0.694) = 112.92 T
Length of critical section = 2 x ( 894 + 694) = 3176 mm
Area of the critical section (length of critical sec x eff. d ) = 1251344 mm2
Hence shear stress tv = 0.902 N/mm2
tv < Allowable Hence O.K.
Input pedestal height = 0 if
wt. of pedestal/column is
not to be considered.

Z and X axis are assumed


as two horizontal Global
axis of building.

Hence, input the


dimensions of footing easily
by inputing footing length
parallel to global Z and
footing breadth parallel to
global X.
If this moment is very high
try to reduce moment by
changing footing size.
Higher moment will require
higher steel and section
may be doubly reinforced.
This design is done as
singly reinforced section.
may be doubly reinforced.
This design is done as
singly reinforced section.

All drawings on this sheet


are updated automatically
as per design changes and
need not be edited.
Instead of calculating
accurate pressure
ordinate at L1-L1 we
have used "pemax" on
conservative side.
DOC: 3 VIN BBL A4 11 C -404
ALIF ENGINEERS &
PLANNERS DESIGN OF FOOTING - F3
REV : R0

LOADS FROM ANALYSIS - SUPPORT REACTIONS


Load (T) Moments (T.M)
Load Case MX( @X ) MZ( @Z )
P TM TM
Joint 11
5 42 -2.805 1.0901
6 47 -3.034 5.8805
7 31 -14.67 1.1262
8 37 -2.577 -3.7002
9 52 9.0634 1.0541
Joint 12
5 42 -1.646 -0.9869
6 35 -1.596 5.1853
7 39 -15.26 -0.9668
8 50 -1.696 -7.159
9 46 11.969 -1.0069

COLUMN/PEDESTAL 1
Depth of footing from NGL = 1.5 1.05
Length (l, dim. || Z axis ) = 600 mm
Breadth (b, dim. || X axis) = 300 mm global Input pedestal height = 0 if
X wt. of pedestal/column is
Depth of filling = 1 not to be considered.
Height of pedestal = 2.05 m Breadth 2.4 m

global
FOOTING global Z and X axis are assumed
Z
Z as two horizontal Global
Foot length (L, dim. || Z axis) = 2.6 m axis of building.
Foot Breadth (B, dim. || X axis) = 2.4 m
Thickness of footing (t) = 450 mm global Hence, input the
Clear cover to Reinforcement = 50 mm X dimensions of footing easily
by inputing footing length
Main bar dia of footing = 12 mm parallel to global Z and
Effective depth of footing = 394 mm Length 2.6 m footing breadth parallel to
global X.
Selfweight of the footing = 7.02 T Footing Dimensions
Area of Footing(A) = 6.24 m2
Sect mod of foot about Z axis (Zz) = 2.50 m3
Sec mod of foot about X axis (Zx) = 2.70 m3

MATERIALS OF CONSTRUCTION
Grade of concrete fck = 20 N/mm2
Grade of steel fy = 415 N/mm2

Safe NET bearing pressure = 14 T/m2


Safe gross bearing pr. = 16.55 T/m2 (net pr. + depth of foot * soil unit wt)
Allowable Gross Bearing pressure 20.69 T/m2
Factor of overstressing 1
Unit wt of soil = 1.7 T/m3
Weight of soil retained above foot = 21.12 T

Bharat Bijlee Ltd.


DOC: 3 VIN BBL A4 11 C -404
ALIF ENGINEERS &
PLANNERS DESIGN OF FOOTING - F3
REV : R0

CALCULATION OF PRESSURES

P (T) Moments (T.M) Soil


Pmax Pmin Actual /
Load Case (Incl self wt overstress
(T/m2) (T/m2) Allowable
+ soil wt MX(@X) MZ(@Z) Factor

Joint 11
5 70.14 -2.805 1.090 1 12.71 9.77 0.77
6 75.14 -3.034 5.881 1.25 15.52 8.56 0.75
7 59.14 -14.674 1.126 1.25 15.36 3.60 0.74
8 65.14 -2.577 -3.700 1.25 12.87 8.00 0.62
9 80.14 9.063 1.054 1.25 16.62 9.07 0.80
Joint 12
5 70.14 -1.646 -0.987 1 12.24 10.24 0.74
6 63.14 -1.596 5.185 1.25 12.79 7.45 0.62
7 67.14 -15.261 -0.967 1.25 16.79 4.73 0.81
8 78.14 -1.696 -7.159 1.25 16.02 9.03 0.77
9 74.14 11.969 -1.007 1.25 16.71 7.05 0.81
OK
0.81
Maximum bearing pressure = 16.79 T/m2 P M y Mx
± ±
Minimum bearing pressure = 3.60 T/m2 A Zy Zx
Footing is not safe against max bearing pressure.

FOR DESIGN OF FOOTINGS


Maximum effective soil pressure pe max
( Pu/Area+ Muz/Zz + Mux/Zx) = 16.79 T/m2
Design of footing is done using above maximum effective soil pressure If this moment is very high
try to reduce moment by
changing footing size.
CALCULATION FOR BOTTOM STEEL Higher moment will require
Mu about X1 X1 = ( pe max x length2/2)= 8.40 T-m per meter higher steel and section
Mulimit = 42.88 T-m per meter may be doubly reinforced.

[ √ ]
0. 5 f ck 4.6 Mu This design is done as
The section is singly reinforced singly reinforced section.
A st = 1− 1− 2
bd
fy f ck bd
Hence, Ast = 610.06 mm2
Min Ast = 472.80 mm2 (0.12 % for slab, cl 26.5.2.1)
Spacing = 185.39 mm (considering max of above two calculated values of Ast)
Provide spacing = 125 mm
pt provided = 0.23 %
Hence provide 12 mm dia bar @ 125 mm c/c parallel to length of footing ( || to Z)

Mu about N1 N1 = ( pe max x length2/2)= 9.26 T-m per meter


Calc. Ast = 674.97 mm 2
The section is singly reinforced
Min Ast = 472.8 mm2 (0.12 % for slab, cl 26.5.2.1)
Spacing = 167.56 mm (considering max of above two calculated values of Ast)
Provide spacing = 125 mm
pt provided = 0.23 %
Hence provide 12 mm dia bar @ 125 mm c/c parallel to breadth of footing ( || to X)
Arrangement of bottom reinforcement as per above design is shown below

Bharat Bijlee Ltd.


DOC: 3 VIN BBL A4 11 C -404
ALIF ENGINEERS &
PLANNERS DESIGN OF FOOTING - F3
REV : R0

All drawings on this sheet


are updated automatically
12 mm dia bar @ 125 mm c/c as per design changes and
need not be edited.

12 mm dia bar @ 125 mm c/c

1 1

Footing Length 2600 mm Breadth 2400 mm

Sec 1-1

994 300
694
L1 X1 X

a a

Z Z
N1 N1
a a

L2 L2

606 X1 X
L1 Breadth 2400 mm Instead of calculating
accurate pressure
600 ordinate at L1-L1 we
Footing Length 2600 mm 656 have used "pemax" on
PLAN conservative side.

Bharat Bijlee Ltd.


Instead of calculating
DOC: 3 VIN BBL A4 accurate
11 C -404 pressure
ALIF ENGINEERS & ordinate at L1-L1 we
PLANNERS DESIGN OF FOOTING - F3 have used "pemax" on
REV : R0 conservative side.

CHECK FOR ONE WAY SHEAR :


One way shear at critical section L1- L1
Distance of critical sec. from edge of footing = 0.606 m
Shear force Vs =pe max x 0.606 x 1m width of footing = 10.175 T
Shear stress tv = Vs/bd = 0.258 N/mm 2

tc = 0.35 N/mm2
tv < tc Hence O.K.

One way shear at critical section L2- L2


Distance of critical sec. from edge of footing = 0.656 m
Shear force Vs =pe max x 0.656 x 1m width of footing = 11.015 T
Shear stress tv = Vs/bd = 0.280 N/mm 2

tc = 0.35 N/mm2
tv < tc Hence O.K.

CHECK FOR TWO WAY SHEAR


Ref. cl 34.2.4 and cl.31.6.3 of IS 456 : 2000
Allowable shear stress tv allowable = kstc
ks = ( 0.5 + bc) = 1.58333 >1
Hence, ks= 1
tc = 0.25 (fck)0.5 = 1.11803 N/mm2
tv allowable = ks x tc = 1.11803 N/mm2
Shear force Vs = 16.79 ( 2.6 x 2.4 - 0.994 x 0.694) = 93.19 T
Length of critical section = 2 x ( 994 + 694) = 3376 mm
Area of the critical section (length of critical sec x eff. d ) = 1330144 mm2
Hence shear stress tv = 0.701 N/mm2
tv < Allowable Hence O.K.

Bharat Bijlee Ltd.


Input pedestal height = 0 if
wt. of pedestal/column is
not to be considered.

Z and X axis are assumed


as two horizontal Global
axis of building.

Hence, input the


dimensions of footing easily
by inputing footing length
parallel to global Z and
footing breadth parallel to
global X.

Bharat Bijlee Ltd.


If this moment is very high
try to reduce moment by
changing footing size.
Higher moment will require
higher steel and section
may be doubly reinforced.
This design is done as
singly reinforced section.

Bharat Bijlee Ltd.


All drawings on this sheet
are updated automatically
as per design changes and
need not be edited.

Instead of calculating
accurate pressure
ordinate at L1-L1 we
have used "pemax" on
conservative side.

Bharat Bijlee Ltd.


Instead of calculating
accurate pressure
ordinate at L1-L1 we
have used "pemax" on
conservative side.

Bharat Bijlee Ltd.


DOC: 3 VIN BBL A4 11 C -404
ALIF ENGINEERS &
PLANNERS DESIGN OF FOOTING - F4
REV : R0

DESIGN OF BI-AXIAL ISOLATED RCC FOOTING (IS 456, 2000)

LOADS FROM ANALYSIS - SUPPORT REACTIONS

Load (T) Moments (T.M)


Load Case MX( @X ) MZ( @Z )
P TM TM
Joint 2
5 45 9.8901 -0.0117
6 47 10.473 11.3841
7 44 -0.61 0.2192
8 44 9.3068 -11.407
9 47 20.39 -0.2426
Joint 5
5 53 11.216 -0.9909
6 54 10.828 10.2129
7 51 -5.089 -0.7567
8 52 11.604 -12.195
9 55 27.521 -1.225
Joint 10
5 62 -3.954 0.5466
6 64 -4.134 11.5524
7 51 -18.8 0.6328
8 60 -3.774 -10.459
9 73 10.894 0.4604
Joint 13
5 79 -4.1134 -1.5584
6 81 -4.082 12.1014
7 75 -25.51 -1.5193
8 77 -4.145 -15.218
9 83 17.286 -1.5975

COLUMN/PEDESTAL 1.2
Depth of footing from NGL = 1.5 1.2
Input pedestal height = 0 if
Length (l, dim. || Z axis ) = 600 mm wt. of pedestal/column is
Breadth (b, dim. || X axis) = 400 mm global not to be considered.
X
Depth of filling = 1
Height of pedestal = 1.95 m Breadth 2.8 m
Z and X axis are assumed
as two horizontal Global
global axis of building.
FOOTING global
Z
Z
Foot length (L, dim. || Z axis) = 3 m Hence, input the
Foot Breadth (B, dim. || X axis) = 2.8 m dimensions of footing easily
by inputing footing length
Thickness of footing (t) = 550 mm global
parallel to global Z and
Clear cover to Reinforcement = 50 mm X footing breadth parallel to
Main bar dia of footing = 12 mm global X.
Effective depth of footing = 494 mm Length 3 m
Selfweight of the footing = 11.55 T Footing Dimensions
Area of Footing(A) = 8.40 m2
Sect mod of foot about Z axis (Zz) = 3.92 m3
Sec mod of foot about X axis (Zx) = 4.20 m3
Bharat Bijlee Ltd.
DOC: 3 VIN BBL A4 11 C -404
ALIF ENGINEERS &
PLANNERS DESIGN OF FOOTING - F4
REV : R0

MATERIALS OF CONSTRUCTION
Grade of concrete fck = 20 N/mm2
Grade of steel fy = 415 N/mm2

Safe NET bearing pressure = 14 T/m2


Safe gross bearing pr. = 16.55 T/m2 (net pr. + depth of foot * soil unit wt)
Allowable gross bearing pressure 20.69 T/m2
Factor of overstressing 1
Unit wt of soil = 1.7 T/m3
Weight of soil retained above foot = 27.05 T

CALCULATION OF PRESSURES

P (T) Moments (T.M) Soil


Pmax Pmin Actual /
Load Case (Incl self wt overstress
(T/m2) (T/m2) Allowable
+ soil wt MX(@X) MZ(@Z) Factor

Joint 2
5 83.60 9.890 -0.012 1 12.31 7.59 0.74
6 85.60 10.473 11.384 1.25 15.59 4.79 0.75
7 82.60 -0.610 0.219 1.25 10.03 9.63 0.49
8 82.60 9.307 -11.407 1.25 14.96 4.71 0.72
9 85.60 20.390 -0.243 1.25 15.11 5.27 0.73
Joint 5
5 91.60 11.216 -0.991 1 13.83 7.98 0.84
6 92.60 10.828 10.213 1.25 16.21 5.84 0.78
7 89.60 -5.089 -0.757 1.25 12.07 9.26 0.58
8 90.60 11.604 -12.195 1.25 16.66 4.91 0.81
9 93.60 27.521 -1.225 1.25 18.01 4.28 0.87
Joint 10
5 100.60 -3.954 0.547 1 13.06 10.90 0.79
6 102.60 -4.134 11.552 1.25 16.15 8.28 0.78
7 89.60 -18.801 0.633 1.25 15.30 6.03 0.74
8 98.60 -3.774 -10.459 1.25 15.30 8.17 0.74
9 111.60 10.894 0.460 1.25 16.00 10.57 0.77
Joint 13
5 117.60 -4.113 -1.558 1 15.38 12.62 0.93
6 119.60 -4.082 12.101 1.25 18.30 10.18 0.88
7 113.60 -25.513 -1.519 1.25 19.99 7.06 0.97
8 115.60 -4.145 -15.218 1.25 18.63 8.89 0.90
9 121.60 17.286 -1.598 1.25 19.00 9.95 0.92
OK
0.97
Maximum bearing pressure = 19.99 T/m 2
P My Mx
Minimum bearing pressure = 4.28 T/m2
± ±
A Zy Zx
Hence footing is safe against max gross bearing pr.

FOR DESIGN OF FOOTINGS


Maximum effective soil pressure pe max
( Pu/Area+ Muz/Zz + Mux/Zx) = 19.99 T/m2 If this moment is very high
Design of footing is done using above maximum effective soil pressure try to reduce moment by
changing footing size.
Higher moment will require
higher steel and section
may be doubly reinforced.
This design is done as
singly reinforced section.
Bharat Bijlee Ltd.
DOC: 3 VIN BBL A4 11 C -404
ALIF ENGINEERS &
PLANNERS DESIGN OF FOOTING - F4
If this moment is very high
REV : R0 try to reduce moment by
changing footing size.
Higher moment will require
CALCULATION FOR BOTTOM STEEL higher steel and section
Mu about X1 X1 = ( pe max x length 2/2)= 14.39 T-m per meter may be doubly reinforced.
This design is done as
Mulimit = 67.40 T-m per meter

[ √ ]
singly reinforced section.
0. 5 f ck 4.6 Mu The section is singly reinforced
A st = 1− 1− 2
bd
fy f ck bd
Hence, Ast = 836.59 mm2
Min Ast = 592.80 mm2 (0.12 % for slab, cl 26.5.2.1)
Spacing = 135.19 mm (considering max of above two calculated values of Ast)
Provide spacing = 125 mm
pt provided = 0.18 %
Hence provide 12 mm dia bar @ 125 mm c/c parallel to length of footing ( || to Z)

Mu about N1 N1 = ( pe max x length2/2)= 14.39 T-m per meter


Calc. Ast = 836.59 mm2 The section is singly reinforced
Min Ast = 592.8 mm2 (0.12 % for slab, cl 26.5.2.1)
Spacing = 135.19 mm (considering max of above two calculated values of Ast)
Provide spacing = 125 mm
pt provided = 0.18 %
Hence provide 12 mm dia bar @ 125 mm c/c parallel to breadth of footing ( || to X)
Arrangement of bottom reinforcement as per above design is shown below All drawings on this sheet
are updated automatically
as per design changes and
need not be edited.

12 mm dia bar @ 125 mm c/c

12 mm dia bar @ 125 mm c/c

1 1

Footing Length 3000 mm Breadth 2800 mm

Sec 1-1

Bharat Bijlee Ltd.


DOC: 3 VIN BBL A4 11 C -404
ALIF ENGINEERS &
PLANNERS DESIGN OF FOOTING - F4
REV : R0

1094 400
894
L1 X1 X

a a

Z Z
N1 N1
a a

L2 L2

706 X1 X
L1 Breadth 2800 mm
600
Footing Length 3000 mm 706
Instead of calculating
PLAN accurate pressure
ordinate at L1-L1 we
CHECK FOR ONE WAY SHEAR : have used "pemax" on
conservative side.
One way shear at critical section L1- L1
Distance of critical sec. from edge of footing = 0.706 m
Shear force Vs =pe max x 0.706 x 1m width of footing = 14.110 T
Shear stress tv = Vs/bd = 0.286 N/mm2
tc = 0.31 N/mm2
tv < tc Hence O.K.

One way shear at critical section L2- L2


Distance of critical sec. from edge of footing = 0.706 m
Shear force Vs =pe max x 0.706 x 1m width of footing = 14.110 T
Shear stress tv = Vs/bd = 0.286 N/mm2
tc = 0.31 N/mm2
tv < tc Hence O.K.

CHECK FOR TWO WAY SHEAR


Ref. cl 34.2.4 and cl.31.6.3 of IS 456 : 2000
Allowable shear stress tv allowable = kstc
ks = ( 0.5 + bc) = 1.57143 >1
Hence, ks= 1
tc = 0.25 (fck)0.5 = 1.11803 N/mm2
tv allowable = ks x tc = 1.11803 N/mm2
Shear force Vs = 19.985 ( 3 x 2.8 - 1.094 x 0.894) = 148.33 T
Length of critical section = 2 x ( 1094 + 894) = 3976 mm
Area of the critical section (length of critical sec x eff. d ) = 1964144 mm2
Hence shear stress tv = 0.755 N/mm2
tv < Allowable Hence O.K.

Bharat Bijlee Ltd.


Input pedestal height = 0 if
wt. of pedestal/column is
not to be considered.

Z and X axis are assumed


as two horizontal Global
axis of building.

Hence, input the


dimensions of footing easily
by inputing footing length
parallel to global Z and
footing breadth parallel to
global X.

Bharat Bijlee Ltd.


If this moment is very high
try to reduce moment by
changing footing size.
Higher moment will require
higher steel and section
may be doubly reinforced.
This design is done as
singly reinforced section.
Bharat Bijlee Ltd.
If this moment is very high
try to reduce moment by
changing footing size.
Higher moment will require
higher steel and section
may be doubly reinforced.
This design is done as
singly reinforced section.

All drawings on this sheet


are updated automatically
as per design changes and
need not be edited.

Bharat Bijlee Ltd.


Instead of calculating
accurate pressure
ordinate at L1-L1 we
have used "pemax" on
conservative side.

Bharat Bijlee Ltd.


DOC: 3 VIN BBL A4 11 C -404
ALIF ENGINEERS &
PLANNERS DESIGN OF FOOTING - F2
REV : R0

LOADS FROM ANALYSIS - SUPPORT REACTIONS


Load (T) Moments (T.M)
Load Case MX( @X ) MZ( @Z )
P TM TM
Joint 9
5 30 -0.26 -0.3941
6 24 -0.245 8.6856
7 28 -3.543 -0.3199
8 36 -0.275 -9.4737
9 32 3.0234 -0.4683
Joint 16
5 32 -2.581 0.1515
6 33 -2.672 4.6803
7 42 -10.31 0.1402
8 32 -2.491 -4.3772
9 23 5.1437 0.1629
Joint 21
5 30 0.0897 -0.8184
6 26 0.1071 8.046
7 30 -3.345 -0.7933
8 34 0.0723 -9.6828
9 30 3.5239 -0.8436

Joint 26
5 32 -1.399 0.3162
6 27 -1.294 5.3698
7 37 -9.057 0.1901
8 36 -1.503 -4.7373
9 26 6.26 0.4423
Joint 27
5 31 -2.88 -0.2907
6 35 -2.811 4.7775
7 34 -11.5 -0.4213
8 26 -2.949 -5.3589
9 28 5.7389 -0.1601

COLUMN/PEDESTAL 1
Depth of footing from NGL = 1.5 0.95 Input pedestal height = 0
Length (l, dim. || Z axis ) = 500 mm wt. of pedestal/column is
Breadth (b, dim. || X axis) = 300 mm global not to be considered.
X
Depth of filling = 1
Height of pedestal = 2.05 m Breadth 2.2 m
Z and X axis are assumed
as two horizontal Global
axis of building.

Hence, input the


dimensions of footing eas
Z and X axis are assumed
as two horizontal Global
global
FOOTING global axis of building.
Z
Z
Foot length (L, dim. || Z axis) = 2.5 m Hence, input the
Foot Breadth (B, dim. || X axis) = 2.2 m dimensions of footing eas
global by inputing footing length
Thickness of footing (t) = 450 mm parallel to global Z and
Clear cover to Reinforcement = 50 mm X
footing breadth parallel to
Main bar dia of footing = 12 mm global X.
Effective depth of footing = 394 mm Length 2.5 m
Selfweight of the footing = 6.19 T Footing Dimensions
Area of Footing(A) = 5.50 m2
Sect mod of foot about Z axis (Zz) = 2.02 m3
Sec mod of foot about X axis (Zx) = 2.29 m3

MATERIALS OF CONSTRUCTION
Grade of concrete fck = 20 N/mm2
Grade of steel fy = 415 N/mm2

Safe NET bearing pressure = 14 T/m2


Safe gross bearing pr. = 16.55 T/m2 (net pr. + depth of foot * soil unit wt)
Allowable safe bearing pressure 20.69 T/m2
Factor of overstressing 1
Unit wt of soil = 1.7 T/m3
Weight of soil retained above foot = 18.64 T

CALCULATION OF PRESSURES

P (T) Moments (T.M) Soil


Pmax Pmin Actual /
Load Case (Incl self wt overstress
(T/m2) (T/m2) Allowable
+ soil wt MX(@X) MZ(@Z) Factor

Joint 9
5 54.83 -0.260 -0.394 1 10.28 9.66 0.62
6 48.83 -0.245 8.686 1.25 13.29 4.46 0.64
7 52.83 -3.543 -0.320 1.25 11.31 7.90 0.55
8 60.83 -0.275 -9.474 1.25 15.88 6.24 0.77
9 56.83 3.023 -0.468 1.25 11.88 8.78 0.57
Joint 16
5 56.83 -2.581 0.152 1 11.53 9.13 0.70
6 57.83 -2.672 4.680 1.25 14.00 7.03 0.68
7 66.83 -10.307 0.140 1.25 16.72 7.58 0.81
8 56.83 -2.491 -4.377 1.25 13.59 7.08 0.66
9 47.83 5.144 0.163 1.25 11.02 6.37 0.53
Joint 21
5 54.83 0.090 -0.818 1 10.41 9.52 0.63
6 50.83 0.107 8.046 1.25 13.28 5.21 0.64
7 54.83 -3.345 -0.793 1.25 11.82 8.12 0.57
8 58.83 0.072 -9.683 1.25 15.53 5.86 0.75
9 54.83 3.524 -0.844 1.25 11.93 8.01 0.58

Joint 26
5 56.83 -1.399 0.316 1 11.10 9.57 0.67
6 51.83 -1.294 5.370 1.25 12.65 6.20 0.61
7 61.83 -9.057 0.190 1.25 15.29 7.20 0.74
8 60.83 -1.503 -4.737 1.25 14.07 8.06 0.68
9 50.83 6.260 0.442 1.25 12.19 6.29 0.59
Joint 27
5 55.83 -2.880 -0.291 1 11.55 8.75 0.70
6 59.83 -2.811 4.778 1.25 14.47 7.28 0.70
7 58.83 -11.499 -0.421 1.25 15.92 5.47 0.77
8 50.83 -2.949 -5.359 1.25 13.19 5.30 0.64
9 52.83 5.739 -0.160 1.25 12.19 7.02 0.59
OK
0.81
Maximum bearing pressure = 16.72 T/m2 P M y Mx
± ±
Minimum bearing pressure = 4.46 T/m2 A Zy Zx
Hence footing is safe against max gross bearing pr.

FOR DESIGN OF FOOTINGS


Maximum effective soil pressure pe max
If this moment is very hig
( Pu/Area+ Muz/Zz + Mux/Zx) = 16.72 T/m2 try to reduce moment by
changing footing size.
Design of footing is done using above maximum effective soil pressure Higher moment will requi
higher steel and section
CALCULATION FOR BOTTOM STEEL may be doubly reinforced
This design is done as
Mu about X1 X1 = ( pe max x length 2/2)= 8.36 T-m per meter singly reinforced section.
Mulimit = 42.88 T-m per meter
A st =
fy [ √
0. 5 f ck
1− 1−
4.6 Mu
f ck bd
2]bd
The section is singly reinforced

Hence, Ast = 607.34 mm2


Min Ast = 472.80 mm2 (0.12 % for slab, cl 26.5.2.1)
Spacing = 186.22 mm (considering max of above two calculated values of Ast)
Provide spacing = 150 mm
pt provided = 0.19 %
Hence provide 12 mm dia bar @ 150 mm c/c parallel to length of footing ( || to Z)
Mu about N1 N1 = ( pe max x length2/2)= 7.54 T-m per meter
Calc. Ast = 546.31 mm 2
The section is singly reinforced
Min Ast = 472.8 mm2 (0.12 % for slab, cl 26.5.2.1)
Spacing = 207.02 mm (considering max of above two calculated values of Ast)
Provide spacing = 150 mm All drawings on this shee
pt provided = 0.19 are updated automaticall
as per design changes an
Hence provide 12 mm dia bar @ 150 mm c/c parallel to breadth of footing ( || to X)
need not be edited.
Arrangement of bottom reinforcement as per above design is shown below

12 mm dia bar @ 150 mm c/c

12 mm dia bar @ 150 mm c/c

1 1
Footing Length 2500 mm Breadth 2200 mm

Sec 1-1

894 300
694
L1 X1 X

a a

Z Z
N1 N1
a a

L2 L2

606 X1 X
L1 Breadth 2200 mm
500
Footing Length 2500 mm 556
PLAN Instead of calculating
accurate pressure
ordinate at L1-L1 we
CHECK FOR ONE WAY SHEAR : have used "pemax" on
One way shear at critical section L1- L1 conservative side.
Distance of critical sec. from edge of footing = 0.606 m
Shear force Vs =pe max x 0.606 x 1m width of footing = 10.131 T
Shear stress v t = Vs/bd = 0.257 N/mm 2

tc = 0.32 N/mm2
tv < tc Hence O.K.

One way shear at critical section L2- L2


Distance of critical sec. from edge of footing = 0.556 m
Shear force Vs =pe max x 0.556 x 1m width of footing = 9.295 T
Shear stress tv = Vs/bd = 0.236 N/mm2
tc = 0.32 N/mm2
tv < tc Hence O.K.

CHECK FOR TWO WAY SHEAR


Ref. cl 34.2.4 and cl.31.6.3 of IS 456 : 2000
Allowable shear stress tv allowable = kstc
ks = ( 0.5 + bc) = 1.63636 >1
Hence, ks= 1
tc = 0.25 (fck)0.5 = 1.11803 N/mm2
tv allowable = ks x tc = 1.11803 N/mm2
Shear force Vs = 16.718 ( 2.5 x 2.2 - 0.894 x 0.694) = 81.58 T
Length of critical section = 2 x ( 894 + 694) = 3176 mm
Area of the critical section (length of critical sec x eff. d ) = 1251344 mm2
Hence shear stress tv = 0.652 N/mm2
tv < Allowable Hence O.K.
DOC: 3 VIN BBL A4 11 C -404

REV : R0

Input pedestal height = 0 if


wt. of pedestal/column is
not to be considered.

Z and X axis are assumed


as two horizontal Global
axis of building.

Hence, input the


dimensions of footing easily
Z and X axis are assumed
as two horizontal Global
axis of building.

Hence, input the


dimensions of footing easily
by inputing footing length
parallel to global Z and
footing breadth parallel to
global X.
If this moment is very high
try to reduce moment by
changing footing size.
Higher moment will require
higher steel and section
may be doubly reinforced.
This design is done as
singly reinforced section.

All drawings on this sheet


are updated automatically
as per design changes and
need not be edited.
Instead of calculating
accurate pressure
ordinate at L1-L1 we
have used "pemax" on
conservative side.
Vertical Moment
Node L/C Fy Mton Mxtm
1 5 COMBINATION LOAD CASE 5 (DL + LL) 23 0.58
6 COMBINATION LOAD CASE 6 (DL + LL + EQX) 18 0.63
7 COMBINATION LOAD CASE 7 (DL + LL + EQZ) 19 -9.58
8 COMBINATION LOAD CASE 8 (DL + LL - EQX) 28 0.53
9 COMBINATION LOAD CASE 9 (DL + LL - EQZ) 27 10.74

2 5 COMBINATION LOAD CASE 5 (DL + LL) 45 9.8901


6 COMBINATION LOAD CASE 6 (DL + LL + EQX) 47 10.4734
7 COMBINATION LOAD CASE 7 (DL + LL + EQZ) 44 -0.6095
8 COMBINATION LOAD CASE 8 (DL + LL - EQX) 44 9.3068
9 COMBINATION LOAD CASE 9 (DL + LL - EQZ) 47 20.3898

3 5 COMBINATION LOAD CASE 5 (DL + LL) 32 7.293


6 COMBINATION LOAD CASE 6 (DL + LL + EQX) 28 7.272
7 COMBINATION LOAD CASE 7 (DL + LL + EQZ) 31 -1.1149
8 COMBINATION LOAD CASE 8 (DL + LL - EQX) 37 7.314
9 COMBINATION LOAD CASE 9 (DL + LL - EQZ) 33 15.701

4 5 COMBINATION LOAD CASE 5 (DL + LL) 29 7.0388


6 COMBINATION LOAD CASE 6 (DL + LL + EQX) 33 6.9535
7 COMBINATION LOAD CASE 7 (DL + LL + EQZ) 28 -2.9416
8 COMBINATION LOAD CASE 8 (DL + LL - EQX) 25 7.1242
9 COMBINATION LOAD CASE 9 (DL + LL - EQZ) 30 17.0193

5 5 COMBINATION LOAD CASE 5 (DL + LL) 53 11.2159


6 COMBINATION LOAD CASE 6 (DL + LL + EQX) 54 10.8278
7 COMBINATION LOAD CASE 7 (DL + LL + EQZ) 51 -5.0893
8 COMBINATION LOAD CASE 8 (DL + LL - EQX) 52 11.6041
9 COMBINATION LOAD CASE 9 (DL + LL - EQZ) 55 27.5211

6 5 COMBINATION LOAD CASE 5 (DL + LL) 27 0.6144


6 COMBINATION LOAD CASE 6 (DL + LL + EQX) 31 0.5993
7 COMBINATION LOAD CASE 7 (DL + LL + EQZ) 22 -13.413
8 COMBINATION LOAD CASE 8 (DL + LL - EQX) 24 0.6295
9 COMBINATION LOAD CASE 9 (DL + LL - EQZ) 33 14.6414

7 5 COMBINATION LOAD CASE 5 (DL + LL) 34 -0.1119


6 COMBINATION LOAD CASE 6 (DL + LL + EQX) 32 -0.0956
7 COMBINATION LOAD CASE 7 (DL + LL + EQZ) 35 -4.0375
8 COMBINATION LOAD CASE 8 (DL + LL - EQX) 35 -0.1282
9 COMBINATION LOAD CASE 9 (DL + LL - EQZ) 32 3.8138

8 5 COMBINATION LOAD CASE 5 (DL + LL) 35 -0.142


6 COMBINATION LOAD CASE 6 (DL + LL + EQX) 37 -0.1448
7 COMBINATION LOAD CASE 7 (DL + LL + EQZ) 37 -5.6437
8 COMBINATION LOAD CASE 8 (DL + LL - EQX) 34 -0.1392
9 COMBINATION LOAD CASE 9 (DL + LL - EQZ) 33 5.3597

9 5 COMBINATION LOAD CASE 5 (DL + LL) 30 -0.2599


6 COMBINATION LOAD CASE 6 (DL + LL + EQX) 24 -0.2446
7 COMBINATION LOAD CASE 7 (DL + LL + EQZ) 28 -3.5432
8 COMBINATION LOAD CASE 8 (DL + LL - EQX) 36 -0.2752
9 COMBINATION LOAD CASE 9 (DL + LL - EQZ) 32 3.0234

10 5 COMBINATION LOAD CASE 5 (DL + LL) 62 -3.9539


6 COMBINATION LOAD CASE 6 (DL + LL + EQX) 64 -4.1338
7 COMBINATION LOAD CASE 7 (DL + LL + EQZ) 51 -18.801
8 COMBINATION LOAD CASE 8 (DL + LL - EQX) 60 -3.7739
9 COMBINATION LOAD CASE 9 (DL + LL - EQZ) 73 10.8936

11 5 COMBINATION LOAD CASE 5 (DL + LL) 42 -2.8054


6 COMBINATION LOAD CASE 6 (DL + LL + EQX) 47 -3.0342
7 COMBINATION LOAD CASE 7 (DL + LL + EQZ) 31 -14.674
8 COMBINATION LOAD CASE 8 (DL + LL - EQX) 37 -2.5767
9 COMBINATION LOAD CASE 9 (DL + LL - EQZ) 52 9.0634

12 5 COMBINATION LOAD CASE 5 (DL + LL) 42 -1.6459


6 COMBINATION LOAD CASE 6 (DL + LL + EQX) 35 -1.5957
7 COMBINATION LOAD CASE 7 (DL + LL + EQZ) 39 -15.261
8 COMBINATION LOAD CASE 8 (DL + LL - EQX) 50 -1.6961
9 COMBINATION LOAD CASE 9 (DL + LL - EQZ) 46 11.9688

13 5 COMBINATION LOAD CASE 5 (DL + LL) 79 -4.1134


6 COMBINATION LOAD CASE 6 (DL + LL + EQX) 81 -4.0819
7 COMBINATION LOAD CASE 7 (DL + LL + EQZ) 75 -25.513
8 COMBINATION LOAD CASE 8 (DL + LL - EQX) 77 -4.1449
9 COMBINATION LOAD CASE 9 (DL + LL - EQZ) 83 17.286

14 5 COMBINATION LOAD CASE 5 (DL + LL) 41 0.0568


6 COMBINATION LOAD CASE 6 (DL + LL + EQX) 45 0.0548
7 COMBINATION LOAD CASE 7 (DL + LL + EQZ) 41 -4.3635
8 COMBINATION LOAD CASE 8 (DL + LL - EQX) 36 0.0587
9 COMBINATION LOAD CASE 9 (DL + LL - EQZ) 40 4.477

15 5 COMBINATION LOAD CASE 5 (DL + LL) 25 -0.1018


6 COMBINATION LOAD CASE 6 (DL + LL + EQX) 20 -0.0804
7 COMBINATION LOAD CASE 7 (DL + LL + EQZ) 25 -3.4672
8 COMBINATION LOAD CASE 8 (DL + LL - EQX) 29 -0.1231
9 COMBINATION LOAD CASE 9 (DL + LL - EQZ) 24 3.2636

16 5 COMBINATION LOAD CASE 5 (DL + LL) 32 -2.5814


6 COMBINATION LOAD CASE 6 (DL + LL + EQX) 33 -2.6723
7 COMBINATION LOAD CASE 7 (DL + LL + EQZ) 42 -10.307
8 COMBINATION LOAD CASE 8 (DL + LL - EQX) 32 -2.4905
9 COMBINATION LOAD CASE 9 (DL + LL - EQZ) 23 5.1437

17 5 COMBINATION LOAD CASE 5 (DL + LL) 20 -2.4515


6 COMBINATION LOAD CASE 6 (DL + LL + EQX) 24 -2.5973
7 COMBINATION LOAD CASE 7 (DL + LL + EQZ) 29 -10.282
8 COMBINATION LOAD CASE 8 (DL + LL - EQX) 17 -2.3057
9 COMBINATION LOAD CASE 9 (DL + LL - EQZ) 11 5.3792

18 5 COMBINATION LOAD CASE 5 (DL + LL) 38 -0.8318


6 COMBINATION LOAD CASE 6 (DL + LL + EQX) 31 -0.8016
7 COMBINATION LOAD CASE 7 (DL + LL + EQZ) 39 -5.6355
8 COMBINATION LOAD CASE 8 (DL + LL - EQX) 46 -0.862
9 COMBINATION LOAD CASE 9 (DL + LL - EQZ) 38 3.9718

19 5 COMBINATION LOAD CASE 5 (DL + LL) 65 -1.2447


6 COMBINATION LOAD CASE 6 (DL + LL + EQX) 69 -1.2349
7 COMBINATION LOAD CASE 7 (DL + LL + EQZ) 66 -7.0744
8 COMBINATION LOAD CASE 8 (DL + LL - EQX) 62 -1.2546
9 COMBINATION LOAD CASE 9 (DL + LL - EQZ) 65 4.5849

20 5 COMBINATION LOAD CASE 5 (DL + LL) 44 -0.0135


6 COMBINATION LOAD CASE 6 (DL + LL + EQX) 48 -0.0244
7 COMBINATION LOAD CASE 7 (DL + LL + EQZ) 43 -4.6669
8 COMBINATION LOAD CASE 8 (DL + LL - EQX) 40 -0.0027
9 COMBINATION LOAD CASE 9 (DL + LL - EQZ) 46 4.6399

21 5 COMBINATION LOAD CASE 5 (DL + LL) 30 0.0897


6 COMBINATION LOAD CASE 6 (DL + LL + EQX) 26 0.1071
7 COMBINATION LOAD CASE 7 (DL + LL + EQZ) 30 -3.3445
8 COMBINATION LOAD CASE 8 (DL + LL - EQX) 34 0.0723
9 COMBINATION LOAD CASE 9 (DL + LL - EQZ) 30 3.5239

22 5 COMBINATION LOAD CASE 5 (DL + LL) 44 0.063


6 COMBINATION LOAD CASE 6 (DL + LL + EQX) 45 0.0828
7 COMBINATION LOAD CASE 7 (DL + LL + EQZ) 40 -7.2926
8 COMBINATION LOAD CASE 8 (DL + LL - EQX) 43 0.0432
9 COMBINATION LOAD CASE 9 (DL + LL - EQZ) 47 7.4186

23 5 COMBINATION LOAD CASE 5 (DL + LL) 28 0.1384


6 COMBINATION LOAD CASE 6 (DL + LL + EQX) 31 0.2547
7 COMBINATION LOAD CASE 7 (DL + LL + EQZ) 23 -7.6678
8 COMBINATION LOAD CASE 8 (DL + LL - EQX) 24 0.0221
9 COMBINATION LOAD CASE 9 (DL + LL - EQZ) 32 7.9446

24 5 COMBINATION LOAD CASE 5 (DL + LL) 22 -0.8914


6 COMBINATION LOAD CASE 6 (DL + LL + EQX) 18 -0.8605
7 COMBINATION LOAD CASE 7 (DL + LL + EQZ) 26 -7.4689
8 COMBINATION LOAD CASE 8 (DL + LL - EQX) 26 -0.9222
9 COMBINATION LOAD CASE 9 (DL + LL - EQZ) 18 5.6861

25 5 COMBINATION LOAD CASE 5 (DL + LL) 39 -1.4172


6 COMBINATION LOAD CASE 6 (DL + LL + EQX) 40 -1.3979
7 COMBINATION LOAD CASE 7 (DL + LL + EQZ) 45 -8.7039
8 COMBINATION LOAD CASE 8 (DL + LL - EQX) 38 -1.4365
9 COMBINATION LOAD CASE 9 (DL + LL - EQZ) 32 5.8695

26 5 COMBINATION LOAD CASE 5 (DL + LL) 32 -1.3987


6 COMBINATION LOAD CASE 6 (DL + LL + EQX) 27 -1.2943
7 COMBINATION LOAD CASE 7 (DL + LL + EQZ) 37 -9.0574
8 COMBINATION LOAD CASE 8 (DL + LL - EQX) 36 -1.5032
9 COMBINATION LOAD CASE 9 (DL + LL - EQZ) 26 6.26

27 5 COMBINATION LOAD CASE 5 (DL + LL) 31 -2.8802


6 COMBINATION LOAD CASE 6 (DL + LL + EQX) 35 -2.811
7 COMBINATION LOAD CASE 7 (DL + LL + EQZ) 34 -11.4993
8 COMBINATION LOAD CASE 8 (DL + LL - EQX) 26 -2.9494
9 COMBINATION LOAD CASE 9 (DL + LL - EQZ) 28 5.7389

28 5 COMBINATION LOAD CASE 5 (DL + LL) 47 -3.7335


6 COMBINATION LOAD CASE 6 (DL + LL + EQX) 48 -3.7151
7 COMBINATION LOAD CASE 7 (DL + LL + EQZ) 52 -14.159
8 COMBINATION LOAD CASE 8 (DL + LL - EQX) 46 -3.7519
9 COMBINATION LOAD CASE 9 (DL + LL - EQZ) 41 6.6917

29 5 COMBINATION LOAD CASE 5 (DL + LL) 29 -1.1911


6 COMBINATION LOAD CASE 6 (DL + LL + EQX) 31 -1.2082
7 COMBINATION LOAD CASE 7 (DL + LL + EQZ) 33 -9.9913
8 COMBINATION LOAD CASE 8 (DL + LL - EQX) 26 -1.1739
9 COMBINATION LOAD CASE 9 (DL + LL - EQZ) 24 7.6092

30 5 COMBINATION LOAD CASE 5 (DL + LL) 5 -0.8304


6 COMBINATION LOAD CASE 6 (DL + LL + EQX) 3 -0.6355
7 COMBINATION LOAD CASE 7 (DL + LL + EQZ) 7 -4.688
8 COMBINATION LOAD CASE 8 (DL + LL - EQX) 8 -1.0252
9 COMBINATION LOAD CASE 9 (DL + LL - EQZ) 4 3.0273

31 5 COMBINATION LOAD CASE 5 (DL + LL) 5 -1.0765


6 COMBINATION LOAD CASE 6 (DL + LL + EQX) 7 -1.2518
7 COMBINATION LOAD CASE 7 (DL + LL + EQZ) 6 -5.7261
8 COMBINATION LOAD CASE 8 (DL + LL - EQX) 3 -0.9012
9 COMBINATION LOAD CASE 9 (DL + LL - EQZ) 4 3.5731
Moment
Mz tm
-0.80
4.24
-0.70
-5.85
-0.91

-0.0117
11.3841
0.2192
-11.4074
-0.2426

0.3578
6.3399
0.4842
-5.6243
0.2314

-0.3266
5.6936
-0.1996
-6.3467
-0.4536

-0.9909
10.2129
-0.7567
-12.195
-1.225

1.5085
6.2836
1.6133
-3.2667
1.4037

-2.8347
10.9322
-2.875
-16.602
-2.7944

3.4418
18.1733
3.5456
-11.2896
3.338

-0.3941
8.6856
-0.3199
-9.4737
-0.4683

0.5466
11.5524
0.6328
-10.459
0.4604

1.0901
5.8805
1.1262
-3.7002
1.0541

-0.9869
5.1853
-0.9668
-7.159
-1.0069

-1.5584
12.1014
-1.5193
-15.218
-1.5975

1.1322
12.2784
1.1633
-10.014
1.101

-0.5796
7.9806
-0.6021
-9.1397
-0.557

0.1515
4.6803
0.1402
-4.3772
0.1629

0.9204
4.6971
0.9205
-2.8563
0.9203

-1.1538
8.9136
-1.1698
-11.2212
-1.1378

-1.2281
10.1167
-1.2455
-12.573
-1.2107

1.5771
11.0707
1.5637
-7.9165
1.5905

-0.8184
8.046
-0.7933
-9.6828
-0.8436

0.0567
4.7392
0.069
-4.6258
0.0444

0.8294
4.7489
0.8381
-3.09
0.8208

-0.7849
3.5664
-0.9039
-5.1362
-0.6659

0.0051
5.0136
-0.1276
-5.0034
0.1378

0.3162
5.3698
0.1901
-4.7373
0.4423

-0.2907
4.7775
-0.4213
-5.3589
-0.1601

-0.6569
4.264
-0.7881
-5.5778
-0.5258

1.506
5.6833
1.3998
-2.6714
1.6121

-0.0697
1.7236
-0.3084
-1.8629
0.1691

-0.0713
1.7221
-0.3099
-1.8647
0.1674

You might also like