Light Circuit (LC) Calculation

Room Identification: Toilet Room


No.of
Total
LC. No. S.No. Appliances Unit Watts Luminaries / Points
Watts
Appliances
1 1 Type 1 Light 26 6 6 156
2 Type 4 Light 17 2 2 34
3 Type 8 Light 10 2 1 20
4 Exhasut Fan 80 3 1 240
10 450

Room Identification: Lavoratory & LHS Entry


No.of
Total
LC. No. S.No. Appliances Unit Watts Luminaries / Points
Watts
Appliances
2 1 Type 3 Light 20 4 2 80
2 Type 4 Light 17 5 2 85
3 Type 5 Light 33 3 1 99
4 Type 8 Light 10 9 3 90
8 354

Room Identification: Dining Hall LHS 1 & 2 Row


No.of
Total
LC. No. S.No. Appliances Unit Watts Luminaries / Points
Watts
Appliances
3 1 Type 7 Light 17 12 6 204
2 Photo Light 4 4 2 16
3 Light Socket 100 2 2 200
10 420

Room Identification: Dining Hall LHS 3 & 4 Row


No.of
Total
LC. No. S.No. Appliances Unit Watts Luminaries / Points
Watts
Appliances
4 1 Type 7 Light 17 24 8 408
2 Photo Light 4 4 2 16
10 424

Room Identification: Entrance LHS


No.of
Total
LC. No. S.No. Appliances Unit Watts Luminaries / Points
Watts
Appliances
5 1 Type 5 Light 33 14 6 462
2 Type 8 Light 10 3 1 30
3 Light Socket 100 1 1 100
8 592
Room Identification: Entrance RHS
No.of
Total
LC. No. S.No. Appliances Unit Watts Luminaries / Points
Watts
Appliances
6 1 Type 5 Light 33 6 2 198
2 Type 8 Light 10 3 1 30
3 Chandelier Point 300 1 1 300
4 Light Socket 100 1 1 100
5 628

Room Identification: Dining Hall RHS 3 & 4 Row


No.of
Total
LC. No. S.No. Appliances Unit Watts Luminaries / Points
Watts
Appliances
7 1 Type 7 Light 17 24 8 408
2 Photo Light 4 4 2 16
10 424

Room Identification: Dining Hall RHS 1 & 2 Row


No.of
Total
LC. No. S.No. Appliances Unit Watts Luminaries / Points
Watts
Appliances
8 1 Type 7 Light 17 12 6 204
2 Photo Light 4 4 2 16
3 Light Socket 100 2 2 200
10 420

Room Identification: Counter RHS Entry


No.of
Total
LC. No. S.No. Appliances Unit Watts Luminaries / Points
Watts
Appliances
9 1 Type 5 Light 33 9 3 297
2 Type 8 Light 10 6 2 60
3 Photo Light 4 2 1 8
4 Light Socket 100 4 4 400
10 765

Room Identification: Store, Refridgeration Room & Kitchen Entry


No.of
Total
LC. No. S.No. Appliances Unit Watts Luminaries / Points
Watts
Appliances
10 1 Type 2 Light 74 1 1 74
2 Type 4 Light 17 4 2 68
3 Type 6 Light 17 4 2 68
4 Type 8 Light 10 6 2 60
5 Light Socket 100 2 2 200
9 470
Room Identification: Kitchen
No.of
Total
LC. No. S.No. Appliances Unit Watts Luminaries / Points
Watts
Appliances
11 1 Type 2 Light 74 6 1 444
2 Type 8 Light 10 5 2 50
3 Light Socket 100 2 2 200
5 694

Total LC Power 5641 Watts

Power Circuit (PC) Calculation


Room Identification: Toilet Room
No.of
Total
PC.No. Appliances Unit Watts Luminaries / Points
Watts
Appliances
1 Burner with Oven 3000 1 1 3000
2 Double Deep Fat Fryer 3000 1 1 3000
3 Salamander 3000 1 1 3000
4 Refrigerated Showcase 3000 1 1 3000
5 Cold Room 3000 1 1 3000
6 Glass Door Refrigerator 1000 1 1 1000
7 Water Heater 2000 1 1 2000
8 Hand Dryer 1000 1 1 1000
9 Power Socket 1000 7 1 7000
26000

Total PC Power 26000 Watts

Total Power Required 31641 Watts

Each Phase 10547 Watts