Heat Load Computations: Fourth Floor - South Wing, PUP Main Academic Building

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 10

HEAT LOAD COMPUTATIONS

Fourth Floor – South Wing, PUP Main Academic Building


Room: 4 - 23
Usage: ITSO MANAGER OFFICE
Floor Area: 𝟑𝟎. 𝟑𝟕𝟓 𝒎𝟐 (𝟑𝟐𝟔. 𝟕𝟖𝟔 𝒇𝒕𝟐)
Number of Occupants: 20 persons
Total Wall Area: 𝟕𝟏. 𝟓𝟓 𝒎𝟐 (𝟕𝟔𝟗. 𝟕𝟔𝟒 𝒇𝒕𝟐)
Window Area: 𝟐. 𝟑𝟕𝟓 𝒎𝟐 (𝟐𝟓. 𝟓𝟓 𝒇𝒕𝟐)

I. LOAD SOURCE: EXTERNAL LOAD

1. ROOF – 0
2. WALLS
𝑄𝑤 = 𝑈𝑤𝐴𝑤(𝐶𝐿𝑇𝐷′𝑤)

a. West-facing Wall

Wall Area: 𝐴𝑤 = (3.18𝑚)(6.75𝑚) = 21.47 𝑚2


𝑊
Overall Heat Transfer: 𝑈𝑤 = 1.3652 𝑚2.𝐾 , (See note #2)
Cooling Load Temperature Difference: 𝐶𝐿𝑇𝐷𝑤 = 22 °𝐶 , (See Note #3)
𝐶𝐿𝑇𝐷′𝑤 = 𝐶𝐿𝑇𝐷𝑤 + (25.5 − 𝑡𝑖𝑛) + (𝑡𝑜𝑚 − 29.4)

Where: tin = 23 °C , (See Note #4)


tom = 13.70 °C , (See Note #5)
𝐶𝐿𝑇𝐷 𝑤 = 𝐶𝐿𝑇𝐷𝑤 + (25.5 − 23) + (13.70 − 29.4)

𝐶𝐿𝑇𝐷′𝑤 = 8.8°𝐶 = 8.8𝐾


𝑄𝑤 = 𝑈𝑤𝐴𝑤(𝐶𝐿𝑇𝐷′𝑤)
𝑊
𝑄𝑤 = (1.3652 2 )(21.47𝑚 2)(8.8𝐾)
𝑚 −𝐾
𝐵𝑇𝑈
𝑄𝑤 = 257.88 𝑊 𝑥 3.412
ℎ𝑟−𝑊
𝐵𝑇𝑈
𝑄𝑤 = 879.92 ℎ𝑟

b. East-facing Wall

Wall Area: 𝐴𝑤 = (3.18𝑚)(6.75 𝑚) = 21.47 𝑚2


𝑊
Overall Heat Transfer: 𝑈𝑤 = 1.3652 𝑚2.𝐾
Cooling Load Temperature Difference: 𝐶𝐿𝑇𝐷𝑤 = 22 °𝐶
𝐶𝐿𝑇𝐷′𝑤 = 𝐶𝐿𝑇𝐷𝑤 + (25.5 − 𝑡𝑖𝑛) + (𝑡𝑜𝑚 − 29.4)

Where: tin = 23 °C
tom = 13.70 °C

𝐶𝐿𝑇𝐷′𝑤 = 𝐶𝐿𝑇𝐷𝑤 + (25.5 − 23) + (13.70 − 29.4)


𝐶𝐿𝑇𝐷′𝑤 = 8.8°𝐶 = 8.8𝐾
𝑄𝑤 = 𝑈𝑤𝐴𝑤(𝐶𝐿𝑇𝐷′𝑤)
HEAT LOAD COMPUTATIONS
Fourth Floor – South Wing, PUP Main Academic Building
𝑊
𝑄𝑤 = (1.3652 2 )(21.47𝑚 2)(8.8𝐾)
𝑚 −𝐾
𝐵𝑇𝑈
𝑄𝑤 = 257.88 𝑊 𝑥 3.412
ℎ𝑟−𝑊
𝐵𝑇𝑈
𝑄𝑤 = 879.92 ℎ𝑟

c. North-facing Wall

Wall Area: 𝐴𝑤 = (3.18𝑚)(4.5𝑚) = 14.31 𝑚2


𝑊
Overall Heat Transfer: 𝑈𝑤 = 1.3652 𝑚2.𝐾
Cooling Load Temperature Difference: 𝐶𝐿𝑇𝐷𝑤 = 22 °𝐶
𝐶𝐿𝑇𝐷′𝑤 = 𝐶𝐿𝑇𝐷𝑤 + (25.5 − 𝑡𝑖𝑛) + (𝑡𝑜𝑚 − 29.4)

Where: tin = 23 °C
tom = 13.70 °C

𝐶𝐿𝑇𝐷′𝑤 = 𝐶𝐿𝑇𝐷𝑤 + (25.5 − 23) + (13.70 − 29.4)


𝐶𝐿𝑇𝐷′𝑤 = 8.8°𝐶 = 8.8𝐾
𝑄𝑤 = 𝑈𝑤𝐴𝑤(𝐶𝐿𝑇𝐷′𝑤)
𝑊
𝑄𝑤 = (1.3652 2 )(14.31𝑚 2− 2.375𝑚 )(8.8𝐾)
2
𝑚 −𝐾
𝐵𝑇𝑈
𝑄𝑤 = 143.3866 𝑊 𝑥 3.412
𝐵𝑇𝑈 ℎ𝑟−𝑊
𝑄𝑤 = 489.264 ℎ𝑟

d. South-facing Wall

Wall Area: 𝐴𝑤 = (3.18𝑚)(4.5𝑚) = 14.31𝑚2


𝑊
Overall Heat Transfer: 𝑈𝑤 = 1.3652 𝑚2.𝐾
Cooling Load Temperature Difference: 𝐶𝐿𝑇𝐷𝑤 = 22 °𝐶
𝐶𝐿𝑇𝐷′𝑤 = 𝐶𝐿𝑇𝐷𝑤 + (25.5 − 𝑡𝑖𝑛) + (𝑡𝑜𝑚 − 29.4)

Where: tin = 23 °C
tom = 13.70 °C

𝐶𝐿𝑇𝐷′𝑤 = 𝐶𝐿𝑇𝐷𝑤 + (25.5 − 23) + (13.70 − 29.4)


𝐶𝐿𝑇𝐷′𝑤 = 8.8°𝐶 = 8.8𝐾
𝑄𝑤 = 𝑈𝑤𝐴𝑤(𝐶𝐿𝑇𝐷′𝑤)
𝑊
𝑄𝑤 = (1.3652 2 )(14.31 𝑚 2)(8.8𝐾)
𝑚 −𝐾
𝐵𝑇𝑈
𝑄𝑤 = 171.9169 𝑊 𝑥 3.4122
ℎ𝑟−𝑊
𝐵𝑇𝑈
𝑄𝑤 = 586.615
ℎ𝑟
HEAT LOAD COMPUTATIONS
Fourth Floor – South Wing, PUP Main Academic Building
3. GLASS CONDUCTION
𝑄𝑐𝑜𝑛𝑑−𝑔 = 𝑈𝑔𝐴𝑔(𝐶𝐿𝑇𝐷′ ) 𝑔

Window Area: 2.375 𝑚2


𝑊
Overall Heat Transfer Coefficient: 𝑈𝑔 = 5.902 , (See Note #7)
𝑚2−𝐾
𝐶𝐿𝑇𝐷𝑔 = 8°𝐶 @ 1500 ℎ𝑟. ( 𝑓𝑟𝑜𝑚 𝑇𝑎𝑏𝑙𝑒 34, 1997 𝐴𝑆𝐻𝑅𝐴𝐸 𝐻𝑎𝑛𝑑𝑏𝑜𝑜𝑘)
𝐶𝐿𝑇𝐷′𝑔 = (8 + 1.67)°𝐶 = 9.67 ℃ = 9.67𝐾 (Table 10 Rule (a) for Glass)

Therefore,
𝑄𝑐𝑜𝑛𝑑−𝑔 = 𝑈𝑔𝐴𝑔(𝐶𝐿𝑇𝐷′ )𝑔
𝑊
𝑄𝑐𝑜𝑛𝑑−𝑔 = 5.902 (2.375 𝑚²)(9.67𝐾)
𝑚2.𝐾
𝐵𝑇𝑈
𝑄𝑐𝑜𝑛𝑑−𝑔 = 135.5353 𝑊 𝑥 3.4122
ℎ𝑟−𝑊
𝐵𝑇𝑈
𝑄𝑐𝑜𝑛𝑑−𝑔 = 462.4736
ℎ𝑟

4. SOLAR HEAT GAIN


𝑄𝑠𝑜𝑙−𝑔 = 𝐴𝑔(𝑀𝑆𝐻𝐺𝐹)(𝐶𝐿𝐹)(𝑆𝐶)

Window Area: 2.375 𝑚2


MSHGF:
For North-Facing Glass Windows,
𝑊
𝑀𝑆𝐻𝐺𝐹 = 164.04 (𝑆𝑒𝑒 𝑛𝑜𝑡𝑒 #8)
𝑚2
Cooling Load Factor: 𝐶𝐿𝐹 = 0.82 (𝑆𝑒𝑒 𝑁𝑜𝑡𝑒 #9)
Shading Coefficient of Glass Window: 𝑆𝐶 = 0.55 (𝑆𝑒𝑒 𝑁𝑜𝑡𝑒#11)
Therefore,
𝑄𝑠𝑜𝑙−𝑔 = 𝐴𝑔(𝑀𝑆𝐻𝐺𝐹)(𝐶𝐿𝐹)(𝑆𝐶)
𝑊
𝑄𝑠𝑜𝑙−𝑔 = (2.375 𝑚 ) (164.04 𝑚)(0.82)(0.55)
2
2
𝐵𝑇𝑈
𝑄𝑠𝑜𝑙−𝑔 = 175.6924 𝑊 𝑥 3.4122
ℎ𝑟 − 𝑊
𝐵𝑇𝑈
𝑄𝑠𝑜𝑙−𝑔 = 599.498
ℎ𝑟

5. CEILING – 0
6. PARTITION WALLS – 0

𝑩𝑻𝑼
𝐓𝐎𝐓𝐀𝐋 𝐇𝐄𝐀𝐓 𝐋𝐎𝐀𝐃(𝐄𝐗𝐓𝐄𝐑𝐍𝐀𝐋) = 𝟑𝟖𝟗𝟕. 𝟔𝟗
𝒉𝒓
HEAT LOAD COMPUTATIONS
Fourth Floor – South Wing, PUP Main Academic Building
II. INTERNAL LOADS

A. SENSIBLE HEAT LOAD

1. LIGHTS
𝑄𝑙 = 𝑁 𝑥 𝑃𝑖𝑛 𝑥 𝐹𝑢𝑙 𝑥 𝐹𝑠𝑎 𝑥 𝐶𝐿𝐹
Number of Lights: 𝑁 = 6
Power Input: 𝑃 = 60 W
Lighting Use Factor: 𝐹𝑢𝑙 = 1.0 (𝑆𝑒𝑒 𝑁𝑜𝑡𝑒 #16)
Special Allowance Factor: 𝐹𝑠𝑎 = 1.20 (𝑆𝑒𝑒 𝑁𝑜𝑡𝑒 #17)
Cooling Load Factor: 𝐶𝐿𝐹 = 1.0

Therefore,
𝑄𝑙 = 𝑁 𝑥 𝑃𝑖𝑛 𝑥 𝐹𝑢𝑙 𝑥 𝐹𝑠𝑎 𝑥 𝐶𝐿𝐹
𝑄𝑙 = 6𝑥 60𝑊 𝑥 1.0 𝑥 1.20 𝑥 1.0
𝐵𝑇𝑈
𝑄𝑙 = 432𝑊 𝑥 3.4122
ℎ𝑟
𝐵𝑇𝑈
1474.07
𝑄𝑙 = ℎ𝑟

2. PEOPLE
𝑄𝑠𝑒𝑛𝑠−𝑜𝑐𝑐 = 𝑁(𝐻𝑠𝑒𝑛𝑠−𝑜𝑐𝑐)(𝐶𝐿𝐹)

Number of Occupants: 𝑁 = 20
Sensible Heat Gain: 𝐻𝑠𝑒𝑛𝑠−𝑜𝑐𝑐 = 75 𝑊 (𝑆𝑒𝑒 𝑁𝑜𝑡𝑒 #14)
Cooling Load Factor: 𝐶𝐿𝐹 = 1.0 (𝑆𝑒𝑒 𝑁𝑜𝑡𝑒 #15)
Therefore,
𝑄𝑠𝑒𝑛𝑠−𝑜𝑐𝑐 = 𝑁(𝐻𝑠𝑒𝑛𝑠−𝑜𝑐𝑐)(𝐶𝐿𝐹)
𝑄𝑠𝑒𝑛𝑠−𝑜𝑐𝑐 = 20(75 𝑊)(1.0)
𝐵𝑇𝑈
𝑄𝑠𝑒𝑛𝑠−𝑜𝑐𝑐 = 1500𝑊 𝑥 3.4122
𝐵𝑇𝑈 ℎ𝑟−𝑊
5118.3
𝑄𝑠𝑒𝑛𝑠−𝑜𝑐𝑐 = ℎ𝑟

3. APPLIANCES
a. Fan Motors
𝑃𝑖𝑛
𝑄=𝑁× ×𝐹 ×𝐹
𝑓 𝑢𝑚 𝑙𝑚
𝜂𝑚

Number of Fan: 𝑁 =3
Input Power: 𝑃𝑖𝑛 = 65 𝑊 (𝑀𝑜𝑡𝑜𝑟 𝑃𝑜𝑤𝑒𝑟 𝐼𝑛𝑝𝑢𝑡)
Mechanical Efficiency: 𝜂𝑚 = 70% (𝑈𝑠𝑢𝑎𝑙𝑙𝑦 𝑓𝑜𝑟 𝑠𝑚𝑎𝑙𝑙 𝑓𝑎𝑛 𝑎𝑝𝑝𝑙𝑖𝑐𝑎𝑡𝑖𝑜𝑛)
Motor Use Factor: 𝐹𝑢𝑚 = 1.0 (𝐹𝑜𝑟 𝑔𝑒𝑛𝑒𝑟𝑎𝑙 𝑎𝑝𝑝𝑟𝑜𝑥𝑖𝑚𝑎𝑡𝑖𝑜𝑛)
Motor Load Factor: 𝐹𝑙𝑚 = 1.0 (𝐹𝑜𝑟 𝑔𝑒𝑛𝑒𝑟𝑎𝑙 𝑎𝑝𝑝𝑟𝑜𝑥𝑖𝑚𝑎𝑡𝑖𝑜𝑛)
HEAT LOAD COMPUTATIONS
Fourth Floor – South Wing, PUP Main Academic Building
Therefore,
𝑃𝑖𝑛
𝑄=𝑁× ×𝐹 ×𝐹
𝑓 𝑢𝑚 𝑙𝑚
𝜂𝑚
65𝑊
𝑄𝑓 = 3 × 𝑥 1.0 𝑥 1.0
0.70
𝐵𝑇𝑈
𝑄𝑓 = 278.57𝑊 𝑥 3.4122
ℎ𝑟 − 𝑊
𝑄𝑓 = 950.5414 𝐵𝑇𝑈
ℎ𝑟

b. Personal Computer
𝑄𝑠𝑒𝑛𝑠−𝑝𝑐 = 𝑃𝑖𝑛 × 𝐶𝐿𝐹

Number of Set: 𝑁 =2
Input Power: 𝑃𝑖𝑛 = 480 𝑊 × 0.50 (see note #18)
𝑃𝑖𝑛 = 240 𝑊

Cooling Load Factor: 𝐶𝐿𝐹 = 1.0 (see note #17)


𝑄𝑠𝑒𝑛𝑠−𝑃𝐶 = (240 𝑊 × 1.0 × 4)
3.4122 𝐵𝑇𝑈𝐻
𝑄𝑠𝑒𝑛𝑠−𝑃𝐶 = 480𝑊 ×
𝑊
𝐵𝑇𝑈
𝑄𝑠𝑒𝑛𝑠−𝑝𝑐 = 1637.856
ℎ𝑟
c. Printer

𝑄𝑠𝑒𝑛𝑠−𝑎𝑝𝑝 = 𝐶𝑠 × 𝑁 × 𝑃𝑖𝑛 × 𝐶𝐿𝐹

CS = 0.33 (unhooded electric appliance)


Number of Unit/s: N=1
Input Power: 𝑃𝑖𝑛 = 300 𝑊
CLF = 0.89 (8hrs operation)
𝑄𝑠𝑒𝑛𝑠−𝑎𝑝𝑝 = (0.33) (1) (300 W) (0.89)
𝑄𝑠𝑒𝑛𝑠−𝑎𝑝𝑝 = 88.11W × 3.4122 𝐵𝑇𝑈
ℎ𝑟 𝑊

𝐵𝑇𝑈
𝑄𝑠𝑒𝑛𝑠−𝑎𝑝𝑝 = 300.65
ℎ𝑟

4. SAFETY FACTOR (5% of #5)


𝐵𝑇𝑈
𝑆𝑎𝑓𝑒𝑡𝑦 𝐹𝑎𝑐𝑡𝑜𝑟 = (0.05 𝑥 9955.49)
ℎ𝑟
𝐵𝑇𝑈
𝑆𝑎𝑓𝑒𝑡𝑦 𝐹𝑎𝑐𝑡𝑜𝑟 = 497.77
ℎ𝑟
HEAT LOAD COMPUTATIONS
Fourth Floor – South Wing, PUP Main Academic Building
5. ROOM SENSIBLE HEAT LOAD
𝛴 𝑁𝑜𝑠. 1 − 3 𝑥 (1.05)
𝐵𝑇𝑈
𝑅𝑆𝐻𝐿 = (1474.07 + 5118.30 + 2889.05) 𝑥 1.05
ℎ𝑟
𝐵𝑇𝑈
∴ 𝑅𝑆𝐻𝐿 = 9955.49
ℎ𝑟
6. DUCT HEAT GAIN (8% of #5)
𝐵𝑇𝑈
𝐷𝑢𝑐𝑡 𝐻𝑒𝑎𝑡 𝐺𝑎𝑖𝑛 = (0.08 𝑥 9955.49)
ℎ𝑟
𝐵𝑇𝑈
𝐷𝑢𝑐𝑡 𝐻𝑒𝑎𝑡 𝐺𝑎𝑖𝑛 = 796.44
ℎ𝑟
7. DUCT LEAKAGE LOSSES (10% of #5)
𝐵𝑇𝑈
𝐷𝑢𝑐𝑡 𝐿𝑒𝑎𝑘𝑎𝑔𝑒 𝐿𝑜𝑠𝑠𝑒𝑠 = (0.10 𝑥 9955.49)
ℎ𝑟
𝐵𝑇𝑈
𝐷𝑢𝑐𝑡 𝐿𝑒𝑎𝑘𝑎𝑔𝑒 𝐿𝑜𝑠𝑠𝑒𝑠 = 995.55
ℎ𝑟
8. FAN HORSEPOWER (3% of #5)
𝐵𝑇𝑈
𝐹𝑎𝑛 𝐻𝑜𝑟𝑠𝑒𝑝𝑜𝑤𝑒𝑟 = (0.3 𝑥 9955.49)
𝐵𝑇𝑈 ℎ𝑟
𝐹𝑎𝑛 𝐻𝑜𝑟𝑠𝑒𝑝𝑜𝑤𝑒𝑟 = 298.66
ℎ𝑟
9. VENTILATION
𝑊 𝑐𝑓𝑚
𝐻𝑠𝑒𝑛𝑠−𝑣𝑒𝑛 = 0.58025 × × 𝑁 × (𝑡𝑜𝑚𝑎𝑥 − 𝑡𝑖𝑛)
𝑐𝑓𝑚 ∙ °𝐶 𝑝𝑒𝑟𝑠𝑜𝑛

CFM per Person: 𝐶𝐹𝑀


= 20 (𝑆𝑒𝑒 𝑁𝑜𝑡𝑒 #20)
𝑝𝑒𝑟𝑠𝑜𝑛
Number of Occupants: 𝑁 = 20
Temperatures: 𝑡𝑖𝑛 = 23°𝐶
𝑡𝑜𝑚𝑎𝑥 = 33.2°𝐶
Therefore,
𝑊 𝑐𝑓𝑚
𝐻𝑠𝑒𝑛𝑠−𝑣𝑒𝑛 = 0.58025 × × 𝑁 × (𝑡𝑜𝑚𝑎𝑥 − 𝑡𝑖𝑛)
𝑐𝑓𝑚 ∙ °𝐶 𝑝𝑒𝑟𝑠𝑜𝑛
𝑊 𝑐𝑓𝑚
𝐻𝑠𝑒𝑛𝑠−𝑣𝑒𝑛 = 0.58025 × 20 × 20 × (33.2°𝐶 − 23°𝐶)
𝑐𝑓𝑚 ∙ °𝐶 𝑝𝑒𝑟𝑠𝑜𝑛
𝐵𝑇𝑈
𝐻𝑠𝑒𝑛𝑠−𝑣𝑒𝑛 = 2367.42𝑊 𝑥 3.4122
ℎ𝑟 − 𝑊
𝐻𝑠𝑒𝑛𝑠−𝑣𝑒𝑛 = 8078.111 𝐵𝑇𝑈
ℎ𝑟

𝑩𝑻𝑼
𝐄𝐟𝐟𝐞𝐜𝐭𝐢𝐯𝐞 𝐑𝐨𝐨𝐦 𝐒𝐞𝐧𝐬𝐢𝐛𝐥𝐞 𝐇𝐞𝐚𝐭 𝐋𝐨𝐚𝐝(𝐒𝐮𝐦𝐦𝐚𝐭𝐢𝐨𝐧 𝐨𝐟 #"𝐬 𝟏 − 𝟗) = 𝟑𝟎𝟏𝟎𝟑. 𝟒𝟒
𝒉𝒓
HEAT LOAD COMPUTATIONS
Fourth Floor – South Wing, PUP Main Academic Building
B. LATENT HEAT COMPONENTS
1. PEOPLE
𝑄𝑙𝑎𝑡−𝑜𝑐𝑐 = 𝑁 × 𝐻𝑙𝑎𝑡−𝑜𝑐𝑐 × 𝐶𝐿𝐹
Number of Occupants: 𝑁 = 20
Latent Heat Gain: 𝐻𝑙𝑎𝑡−𝑜𝑐𝑐 = 55 𝑊 (𝑆𝑒𝑒 𝑁𝑜𝑡𝑒 #13)
Cooling Load Factor: 𝐶𝐿𝐹 = 1.0 (𝑆𝑒𝑒 𝑁𝑜𝑡𝑒 #14)
Therefore,
𝑄𝑙𝑎𝑡−𝑜𝑐𝑐 = 𝑁 × 𝐻𝑙𝑎𝑡−𝑜𝑐𝑐 × 𝐶𝐿𝐹
𝑄𝑙𝑎𝑡−𝑜𝑐𝑐 = 20 × 55 𝑊 × 1.0
𝐵𝑇𝑈
𝑄𝑙𝑎𝑡−𝑜𝑐𝑐 = 1100𝑊 𝑥 3.4122
ℎ𝑟−𝑊
𝐵𝑇𝑈
𝑄𝑙𝑎𝑡−𝑜𝑐𝑐 = 3753.42 ℎ𝑟

2. APPLIANCES
a. Fan Motors
𝑃𝑖𝑛
𝑄=𝑁× ×𝐹 ×𝐹
𝑓 𝑢𝑚 𝑙𝑚
𝜂𝑚
Number of Fan: 𝑁 =3
Input Power: 𝑃𝑖𝑛 = 65 𝑊 (𝑀𝑜𝑡𝑜𝑟 𝑃𝑜𝑤𝑒𝑟 𝐼𝑛𝑝𝑢𝑡)
Mechanical Efficiency: 𝜂𝑚 = 70% (𝑈𝑠𝑢𝑎𝑙𝑙𝑦 𝑓𝑜𝑟 𝑠𝑚𝑎𝑙𝑙 𝑓𝑎𝑛 𝑎𝑝𝑝𝑙𝑖𝑐𝑎𝑡𝑖𝑜𝑛)
Motor Use Factor: 𝐹𝑢𝑚 = 1.0 (𝐹𝑜𝑟 𝑔𝑒𝑛𝑒𝑟𝑎𝑙 𝑎𝑝𝑝𝑟𝑜𝑥𝑖𝑚𝑎𝑡𝑖𝑜𝑛)
Motor Load Factor: 𝐹𝑙𝑚 = 1.0 (𝐹𝑜𝑟 𝑔𝑒𝑛𝑒𝑟𝑎𝑙 𝑎𝑝𝑝𝑟𝑜𝑥𝑖𝑚𝑎𝑡𝑖𝑜𝑛)

Therefore,
𝑃𝑖𝑛
𝑄=𝑁× ×𝐹 ×𝐹
𝑓 𝑢𝑚 𝑙𝑚
𝜂𝑚
65𝑊
𝑄𝑓 = 3 × 𝑥 1.0 𝑥 1.0
0.70
𝐵𝑇𝑈
𝑄𝑓 = 278.57𝑊 𝑥 3.4122
ℎ𝑟 − 𝑊
𝐵𝑇𝑈
𝑄𝑓 = 950.54
ℎ𝑟
HEAT LOAD COMPUTATIONS
Fourth Floor – South Wing, PUP Main Academic Building
b. Personal Computer

𝑄𝑙 = 𝐶𝑙 × 𝑁 × 𝑃𝑖𝑛 × 𝐶𝐿𝐹

CL: 0.17 (unhooded electric appliance)


Number of Unit/s: N=2
Input Power: 𝑃𝑖𝑛 = 240𝑊
CLF: 0.95
Therefore,
𝑄𝑙 = 𝐶𝑙 × 𝑁 × 𝑃𝑖𝑛 × 𝐶𝐿𝐹
𝑄𝑙 = 0.17 × 2 × 240𝑊 × 0.95
𝐵𝑇𝑈
𝑄𝑙 = 77.52𝑊 × 3.4122
ℎ𝑟 − 𝑊
𝐵𝑇𝑈
𝑄𝑙 = 264.5137
ℎ𝑟
c. Printer

𝑄𝑙 = 𝐶𝑙 × 𝑁 × 𝑃𝑖𝑛 × 𝐶𝐿𝐹

CL: 0.17 (unhooded electric appliance)


Number of Unit/s: N=1
Input Power: 𝑃𝑖𝑛 = 300𝑊
CLF: 0.89
Therefore,
𝑄𝑙 = 𝐶𝑙 × 𝑁 × 𝑃𝑖𝑛 × 𝐶𝐿𝐹
𝑄𝑙 = 0.17 × 1 × 300𝑊 × 0.89
𝐵𝑇𝑈
𝑄𝑙 = 45.39𝑊 × 3.4122
ℎ𝑟 − 𝑊
𝐵𝑇𝑈
𝑄𝑙 = 154.879
ℎ𝑟
HEAT LOAD COMPUTATIONS
Fourth Floor – South Wing, PUP Main Academic Building
3. SAFETY FACTOR (5% of #4)
𝐵𝑇𝑈
𝑆𝑎𝑓𝑒𝑡𝑦 𝐹𝑎𝑐𝑡𝑜𝑟 = (0.05 𝑥 5379.52)
ℎ𝑟
𝐵𝑇𝑈
𝑆𝑎𝑓𝑒𝑡𝑦 𝐹𝑎𝑐𝑡𝑜𝑟 = 268.98
ℎ𝑟

4. ROOM LATENT HEAT LOAD = ∑ 𝒐𝒇 𝑵𝒐𝒔. 𝟏 − 𝟐 𝒙 (𝟏. 𝟎𝟓)


𝑅𝑜𝑜𝑚 𝐿𝑎𝑡𝑒𝑛𝑡 𝐻𝑒𝑎𝑡 𝐿𝑜𝑎𝑑 = (3753.42 + 1369.93) 𝐵𝑇𝑈𝐻 × 1.05

𝐵𝑇𝑈
𝑅𝑜𝑜𝑚 𝐿𝑎𝑡𝑒𝑛𝑡 𝐻𝑒𝑎𝑡 𝐿𝑜𝑎𝑑 = 5379.52
ℎ𝑟

5. DUCT HEAT GAIN (10% of #4)


𝐵𝑇𝑈
𝐷𝑢𝑐𝑡 𝐻𝑒𝑎𝑡 𝐺𝑎𝑖𝑛 = (5379.52) × 0.10
ℎ𝑟
𝐵𝑇𝑈
𝐷𝑢𝑐𝑡 𝐻𝑒𝑎𝑡 𝐺𝑎𝑖𝑛 = 537.95
ℎ𝑟

6. SUPPLY DUCT LEAKAGE (5% of #4)


𝐵𝑇𝑈
𝑆𝑢𝑝𝑝𝑙𝑦 𝐷𝑢𝑐𝑡 𝐿𝑒𝑎𝑘𝑎𝑔𝑒 = (0.05 𝑥 5379.52)
ℎ𝑟
𝐵𝑇𝑈
𝑆𝑢𝑝𝑝𝑙𝑦 𝐷𝑢𝑐𝑡 𝐿𝑒𝑎𝑘𝑎𝑔𝑒 = 268.98
ℎ𝑟

7. VENTILATION

𝑊 𝑐𝑓𝑚
𝐻𝑙𝑎𝑡−𝑣𝑒𝑛 = 1418.3889 × × 𝑁 × (∆𝑊)
𝑐𝑓𝑚 𝑝𝑒𝑟𝑠𝑜𝑛
𝑐𝑓𝑚
CFM per person: 20 (𝑆𝑒𝑒 𝑁𝑜𝑡𝑒 #20)
𝑝𝑒𝑟𝑠𝑜𝑛
Number of Occupants: 𝑁 = 20
Humidity Ratios:
At initial, using 𝑡𝑖𝑛 =23°𝐶 and RH = 55%
𝑘𝑔 𝑤. 𝑣.
𝑊1 = 0.00875
𝑘𝑔 𝑑. 𝑎.
At final, using 𝑡𝑜𝑚𝑎𝑥 =33.2°𝐶 for dry-bulb & 26.10°𝐶 for wet-bulb
(see note #21)
HEAT LOAD COMPUTATIONS
Fourth Floor – South Wing, PUP Main Academic Building
𝑘𝑔 𝑤. 𝑣.
𝑊2 = 0.01975
𝑘𝑔 𝑑. 𝑎.
∆𝑊 = 𝑊2 − 𝑊1
𝑘𝑔 𝑤. 𝑣.
∆𝑊 = (0.01975 − 0.00875)
𝑘𝑔 𝑑. 𝑎.
𝑘𝑔 𝑤.𝑣.
∆𝑊 = 0.011
𝑘𝑔 𝑑.𝑎.
𝑊
𝐻 = (1418.3889 ×
20 𝑐𝑓𝑚
× 20 × 0.011
𝑘𝑔 𝑤.𝑣.
)
𝑙𝑎𝑡−𝑣𝑒𝑛 𝑐𝑓𝑚 𝑝𝑒𝑟𝑠𝑜𝑛 𝑘𝑔 𝑑.𝑎.
𝐵𝑇𝑈
𝐻𝑙𝑎𝑡−𝑣𝑒𝑛 = 6240.911𝑊 × 3.4122
ℎ𝑟−𝑊
𝐵𝑇𝑈
21295.24
𝐻𝑙𝑎𝑡−𝑣𝑒𝑛 =
ℎ𝑟

𝑩𝑻𝑼
𝐄𝐟𝐟𝐞𝐜𝐭𝐢𝐯𝐞 𝐑𝐨𝐨𝐦 𝐋𝐚𝐭𝐞𝐧𝐭 𝐇𝐞𝐚𝐭 𝐋𝐨𝐚𝐝(𝐒𝐮𝐦𝐦𝐚𝐭𝐢𝐨𝐧 𝐨𝐟 #"𝐬 𝟒 − 𝟕) = 𝟐𝟕𝟒𝟖𝟏. 𝟔𝟗
𝒉𝒓

SUMMARY:
A. Total Internal Heat Load = ERSHL + ERLHL 57585.13 BTUH
B. Return Duct Heat Gain = 6% of A 3455.11 BTUH
C. Return Duct Leakage Losses = 3% of A 1727.55 BTUH

Grand Total Internal Load = Summation of A-C 62767.79 BTUH


Total Room Heat Load = External Heat Load + GTIHL 66665.49 BTUH
TOTAL ROOM REQUIREMENT = TRHL/12000BTUH/ton 5.56TR
= TR x 400 CFM/TR 2222.18 CFM