Professional Documents
Culture Documents
TDi Installation Instructions 080219
TDi Installation Instructions 080219
Installation Package
ProNet, 8000, and 5000 Systems
This installation package has been put together by the NDC Project Management
Department in order to assist you in preparing for your gauging system.
NDC provides a wide selection of sensors that can interface with our ProNet (9000),
8000, or 5000 electronic packages. Refer to the attached Installation Drawing to
determine which system, sensors, and options apply to your installation.
Field Engineering Note: Exercise care when installing inputs (air and water) and
tightening the Swagelok couplings to assure that the
supporting fittings and connections for the scanners and
sensors are not twisted or bent.
Note: Please ensure that orientations are per drawing and that access space per drawing
is available.
TDi_Installation_Instructions_080219.doc Page 1 of 20
1.2.2 Air/Water/Cooling Inputs
The customer shall provide appropriate air/water/cooling to the scanner(s) and/or
sensor(s) as noted in Sections 3 and 4. Standard TDi scanners include five (5) inputs.
Typical tubing Colors and Usage/Applications are noted below:
A site survey will be performed by NDC upon installation of X-Ray, Beta, or Gamma
gauges. The NDC Field Service Engineer will provide a copy of the gauge’s radiation
profile for the customer’s records. The profile should be kept on site for review by
regulatory and safety officials.
NDC recommends that access controls are fitted to ensure that radiation levels are
maintained as low as reasonably achievable (ALARA) based on the radiation survey for
each gauge.
Additional radiation safety information is located in the User Manual for each sensor.
TDi_Installation_Instructions_080219.doc Page 2 of 20
Idler rolls are required on the in-feed and out-feed positions of the scanner. For idler
spacing, refer to Scanner drawings in your Installation Booklet. Idler rolls are used to
minimize flutter (± 1/8" (3.175 mm) and for fine adjustments to the web path. If the
rollers are set and cannot be adjusted, adjustments can be made by adjusting the pads or
shimming the feet.
Installation must allow for thermal expansion of the frame per the Frame Installation
Manuals.
Air Quality: Clean, instrument grade air or nitrogen only. Air must be oil free
and water free. Plant utility compressed air without substantial
filtering is not acceptable.
4 Sensor Information
Sensor information provided below is based on nominal operating and environmental
conditions. Some of the values (e.g. flow rates) may be adjusted during the installation
process by the NDC Engineer to assure proper operation of the equipment based on the
specific site installation and conditions.
Note: Infrared sensors are typically referred to as 710, IR, or NIR sensors in the
Installation Package.
TDi_Installation_Instructions_080219.doc Page 3 of 20
4.1.1 Air Purge Window
The IR sensor comes equipped with an air purge window used to keep dust, debris, and
moisture from collecting on the sensor window.
Air Quality: Clean, instrument grade air only. Air must be oil free and
water free. A 1-5 micron coalescing filter combined with a
drying filter is recommended. Plant utility compressed air
without substantial filtering is not acceptable.
Pressure: 6 – 10 PSI
The water should be clean, preferably demineralized, and set up to the following
specifications:
Pressure: 30 – 50 PSI
Connection: Connect water supply lines (Input & Output) to the 6mm quick-
disconnect tube fittings supplied at the scanner (scanning
system) or sensor (fixed system).
TDi_Installation_Instructions_080219.doc Page 4 of 20
XRB Sensors ordered with MiniTrak-Single scanners include a stationary XRB shield
to be mounted by the customer (on the opposite side of the web from the scanner).
XRB Sensors ordered with AccuTrak and MiniTrak-O scanners include an XRB shield
that is mounted to the scanner carriage and travels with the sensor.
Air Quality: Clean, instrument grade air only. Air must be oil free and
water free. A 1-5 micron coalescing filter combined with a
drying filter is recommended. Plant utility compressed air
without substantial filtering is not acceptable.
Pressure: 35 – 60 PSI
Air Quality: Clean, instrument grade air only. Air must be oil free and
water free. A 1-5 micron coalescing filter combined with a
drying filter is recommended. Plant utility compressed air
without substantial filtering is not acceptable.
Pressure: 6 – 10 PSI
4.2.4 Cooling
Water cooling is required on all X-ray sensors. Higher temperature applications may
require additional protection as outlined below.
Temperature Range Definition: The temperature conditions noted below represent the
highest expected temperature approximately 1 inch
(25mm) from the web at the measurement location
during operation of the customer’s production line.
This should take into account all potential seasonal
changes in the operating conditions.
TDi_Installation_Instructions_080219.doc Page 5 of 20
4.2.4.1 Nominal Conditions (<50°C)
Nominal conditions are for operating temperatures that are maintained below 50°C.
The customer shall provide water to the scanner set up to the following specifications:
Connection: Connect water supply lines (Input & Output) to the 6mm quick-
disconnect tube fittings supplied at the scanner (scanning
system) or sensor (fixed system).
Connection: Connect water supply lines (Input & Output) to the 6mm quick-
disconnect tube fittings supplied at the scanner (scanning
system) or sensor (fixed system).
TDi_Installation_Instructions_080219.doc Page 6 of 20
Insulating Jacket: The X-ray sensor requires the addition of an insulating
jacket.
Air Quality: Clean, instrument grade air only. Air must be oil free and
water free. A 1-5 micron coalescing filter combined with a
drying filter is recommended. Plant utility compressed air
without substantial filtering is not acceptable.
Pressure: 35 – 60 PSI
Air Quality: Clean, instrument grade air only. Air must be oil free and
water free. A 1-5 micron coalescing filter combined with a
drying filter is recommended. Plant utility compressed air
without substantial filtering is not acceptable.
TDi_Installation_Instructions_080219.doc Page 7 of 20
Pressure: 35 – 60 PSI
The water should be clean, preferably demineralized, and set up to the following
specifications:
Connection: Connect water supply lines (Input & Output) to the 6mm quick-
disconnect tube fittings supplied at the scanner (scanning
system) or sensor (fixed system). Exercise care in tightening the
Swagelok couplings to assure that the steel tube on the sensor is
not twisted or bent.
Water Supply: It is recommended that minimum 10mm (3/8”) O.D. supply tubing
be provided to the end of the scanner then reduced to 6mm to
ensure proper flow.
Air Quality: Clean, instrument grade air only. Air must be oil free and
water free. A 1-5 micron coalescing filter combined with a
TDi_Installation_Instructions_080219.doc Page 8 of 20
drying filter is recommended. Plant utility compressed air
without substantial filtering is not acceptable.
Pressure: 1 – 3 PSI
The jackets are bridged on the outside so that there is no possibility of leakage inside
the sensor. All wetted materials are Tygon (Polyurethane) or Stainless Steel. The IN
and OUT labels are arbitrary; the water can flow in either direction without affecting
the cooling function.
TDi_Installation_Instructions_080219.doc Page 9 of 20
The water should be clean, preferably demineralized, and set up to the following
specifications:
Pressure: 30 – 50 PSI
Connection: Connect water supply lines (Input & Output) to the 6mm quick-
disconnect tube fittings supplied at the scanner (scanning
system) or at the sensor (fixed system). Exercise care in
tightening the Swagelok couplings to assure that the steel tube on
the sensor is not twisted or bent.
Air Quality: Clean, instrument grade air only. Air must be oil free and
water free. A 1-5 micron coalescing filter combined with a
drying filter is recommended. Plant utility compressed air
without substantial filtering is not acceptable.
Pressure: 35 – 60 PSI
• The roll must be precision ground, with a roughness height rating of 63 micro
inches or less. There should be no more than 3 mils (76.2 microns) of total runout
when the roll is mounted.
TDi_Installation_Instructions_080219.doc Page 10 of 20
• The roll must be wider than the maximum sheet width by 7" (177.8 mm) on each
side. This provides the laser gauge with room to standardize.
• The sheet should wrap 1" (25.4 mm) around the roll on each side from the
measurement spot of the sensor (see Figure 3 - Sheet wrap around roll).
The air input for the GBS Auto Shutter should be set up to the following specifications:
Air Quality: Clean, instrument grade air only. Air must be oil free and
water free. A 1-5 micron coalescing filter combined with a
drying filter is recommended. Plant utility compressed air
without substantial filtering is not acceptable.
Pressure: 70 – 90 PSI
TDi_Installation_Instructions_080219.doc Page 11 of 20
4.5.2.2 Water Cooling
Water cooling is required if the area around the sensor face will exceed temperatures
greater than 50°C (120°F).
The water should be clean, preferably demineralized, and set up to the following
specifications:
Pressure: 30 – 50 PSI
Connection: Connect water supply lines (Input & Output) to the 6mm quick-
disconnect tube fittings supplied at the scanner (scanning
system) or sensor (fixed system).
Air Quality: Clean, instrument grade air only. Air must be oil free and
water free. A 1-5 micron coalescing filter combined with a
drying filter is recommended. Plant utility compressed air
without substantial filtering is not acceptable.
Pressure: 6 – 10 PSI
4.5.3 Shielding
4.5.3.1 Shielding – Scanning Systems
Lead shielding 1/16” (1.6 mm) or greater, mounted to a wood or steel backing, may be
required if obstructions come within 18” (457.2 mm) of the sensor face. The shielding
should cover the length of the scanner, and should not be any closer than 5” (127 mm)
from the sensor face. If the shielding is 5” (127 mm) away from the sensor face, it
should be a minimum of 12” (304.8 mm) wide. If you have any questions, please
contact the Project Management Department.
TDi_Installation_Instructions_080219.doc Page 12 of 20
If the edges of the web are close to the side columns of the machine, the gauge readings
at the edges may include contributions from these columns. To eliminate or minimize
this offset, lead shielding should be placed along the columns.
• The roll must be precision ground, with a roughness height rating of 63 micro inches
or less. There should be no more than 3 mils (76.2 microns) of total runout when the
roll is mounted.
• The sheet should wrap 1" (25.4 mm) around the roll on each side from the
measurement spot of the sensor (see Figure 4 - Sheet wrap around roll).
• The plate width must be 5" (127 mm) or greater with a minimum thickness of
¼" (6.4 mm) and length equal to the mounting distance of the scanner that was
ordered (scanning system) or length spanning the entire web (fixed system).
TDi_Installation_Instructions_080219.doc Page 13 of 20
5 Additional System Features
5.1 Connecting to the TDi Network
The NDC TDI system architecture utilizes Ethernet for inter-device communication.
As such, it is critical to minimize communication interference on the TDI network. The
main reasons to connect to your TDI system are to back up its parameters, remotely
operate it and view its screens, or to extract data for archiving. This document
describes the Best Practices for networking your TDI system.
F1, or Frame Node 1, also known as the Data Server, coordinates all data from gauges
and scanners for same spot measurement. This is the node on which all data extraction,
remote administration or back-ups will take place. For the purposes of backing up node
parameters, the simplest solution is to connect a laptop PC to the TDI Network and run
TDI Backup or NDCback-Java. In this situation, set the IP address of the laptop PC to
any unused IP Address in the 10.0.14.xxx range and subnet mask to 255.255.240.0.
TDi_Installation_Instructions_080219.doc Page 14 of 20
5.1.2 Case 2: Connecting to the TDI Network to Archive Data
or Run RemoteView
If it is determined that a PC needs to be connected to the TDI Network to archive data
or run RemoteView, set it up as shown in Figure 6, below.
Figure 6 shows a Dual-Homed Workstation PC, connected between the TDI Network
and the Company Network. This can be done by simply installing a second NIC
(network interface card) in a PC, and assigning an unused
IP address from the TDI Network (e.g. 10.0.14.198) to one NIC, and an IP address from
the Company Network to the other NIC. As long as the two NICs are not bridged on
the Workstation PC, this creates a firewall between the two networks, and prevents
unnecessary traffic on the TDI Network.
TDi_Installation_Instructions_080219.doc Page 15 of 20
Figure 7: Connecting Company Network to Multiple TDI Networks
Figure 7 shows how to connect to the two TDI Networks, assuming the routers have
been configured properly.
- TDI Network 1
- TDI Network 2
TDi_Installation_Instructions_080219.doc Page 16 of 20
5.2 System Backup (8000 Systems Only)
NDC Model 8000 Systems include a USB Flash Drive (Ref.: NDC P/N 707335).
If the system includes an Embedded Control via the I/O interface, a customer provided
AUTO/MANUAL switch is required.
TDi_Installation_Instructions_080219.doc Page 17 of 20
5.4 Linespeed Tachometer
The linespeed tachometer provides the system with a line speed input. Mount the
tachometer to a driven roll with a minimum diameter of 4" (101.6 mm). The
tachometer includes a 3.8" (96.5 mm) diameter, rubber coated wheel that can be
mounted on the tachometer shaft and then placed against the driven roll. It is
recommended that the encoder be placed on a hinged bracket and mounted so that the
weight of the encoder is used to keep the wheel in contact with the driven roll. If a
decision is made not to use the supplied wheel and to couple the encoder to the driven
roll, a flexible coupler must be employed. Due to the high rpms involved, the shaft
cannot be coupled directly to a motor shaft.
Note: Customer supplied signal is optional. The TTL level signal voltage should not
exceed 5 VDC, with a maximum allowable frequency of 10 kHz. There are also
0-10v or 4-20mA options available; these options should be addressed and
configured with your NDC sales representative at the time of order placement.
5.5 Cables
The NDC field engineer will terminate connections on the rotopulser and control cables
provided by NDC Systems. The interface between components such as the OWS and
the scanner are standard shielded CAT5-E Ethernet cable (Customer provided). After
crimping on Ethernet connectors, leave cables disconnected until the field service
engineer’s inspection. Pull all cables through conduit prior to the field engineer's
arrival. Refer to the Cable Schedule of the Installation Drawing in the Installation
Booklet for cable designations and run restrictions. Under no circumstances should
any NDC cables be run together with cables that are powering equipment on the line,
switching power, running motors, etc.
NDC supplied cables (e.g. tachometer, controls, etc.) are supplied with the cable ends
are already stripped and tinned on one end. Pull these ends through the conduit. Leave
excess cable on the console side. If a cable has a connector at both ends, cut one end
off, at least 6" (152.4 mm) from the connector. The NDC field engineer will reinstall
the connector.
The air input for the Blast Gate should be set up to the following specifications:
Blower: Minimum blower capacity should be 60 CFM per scanner (at the
scanner). NDC recommends blowers capable of >200 CFM to
assure adequate airflow.
TDi_Installation_Instructions_080219.doc Page 18 of 20
Pressure: Pressure within the scanner should be maintained between 0.10”
(2.5mm) and 0.50” (12.7mm) H2O.
5.7 Printer
Both the 8000 and the ProNet systems have printer interface capabilities.
7 Gauge Calibration
All gauges are linearized at the factory, using product samples provided by the
customer. Once the system is installed and operating, this calibration must be fine
tuned and confirmed on line. This process is part of the system start-up and takes
approximately one day. It requires that multiple samples be cut from production runs,
measured by existing in-house methods (scales, micrometers), and compared to the
NDC gauge readings. The NDC field engineer will work with your QC department or
process engineer to accomplish this.
8 Training
While at your facility, the NDC field engineer will conduct operator and maintenance
training. You should make sure that the appropriate personnel are available during the
training sessions.
9 Downtime
9.1 Physical Installation
The line will have to be down for a period of time during the physical installation of the
equipment. The customer should schedule sufficient time prior to the arrival of the
NDC field engineer to assure that all equipment is installed and prepared in accordance
with the customer responsibilities outlined in section 1.2.
TDi_Installation_Instructions_080219.doc Page 19 of 20
10 ProNet (9000 system) Installations
• The ProNet system includes a modem for supporting remote setup and debugging.
Please install an analog phone line (i.e. one suitable for fax and modem), which
connects to the main ProNet enclosure.
• If the ProNet is to be connected on your plant network, please have your system
administrator assign enough IP addresses for the ProNet PC and for each Frame
Node and Sensor Node in the system.
11 Additional Questions
Please contact the Project Management Department or Customer Care Department at
NDC if you have any questions regarding your system configuration, installation, or
operation. NDC contact information should be included in the front section of your
installation package.
TDi_Installation_Instructions_080219.doc Page 20 of 20