Business-Critical ContinuityTM
Liebert.PEX
New generation cooling solution for IDC room
Trust Over 40 Years Of Experience In Precision Cooling
Liebert.PEX unit is a new generation precision air conditioning unit based on Emerson global
development and design platforms. Emerson Liebert precision cooling business started back in 1965 in
the United States, and, and has the operating experiences of thousands of units used in computer room,
IDC and communication room.
Liebert.PEX has integrated more than 40 years of Emerson R&D experiences and excellent engineering
design philosophies.
Energy-saving, space-saving, environment-
friendly, long service life and low cost
Nowadays, there are more and more various kinds of network-related businesses,
and the loss due to one business interruption is more and more heavier. Therefore,
we need to put more efforts and supports in basic infrastructure construction. The
environmental basis for safe operation of equipment has raised more attention for us.
Temperature (°C)
1
High energy- Your Environmental Cooling System Consumes From
35% to 45% of Data Center Energy
efficient Your data center is composed of many different types of equipment, which gener-
ate substantial sensible heat.
Do you know that your precision air conditioning consumes over 35% of its total energy?
Each Component That Cooling system consumes a significant amount of power in your data center, the
Goes Into The Liebert. energy efficiency of your environmental control system becomes a priority. Make
sure you’ve got the right cooling solution.
PEX Is Designed,
Manufactured and Electricity
Transformer
Tested To Ensure That and UPS
10%
It Will Contribute To Its 12%
ent
Overall Efficiency. mo
vem
Air
IT equipment 50%
Cooling 25%
Lighting, etc. 3%
2
Energy-saving, space-saving, environment-
friendly, long service life and low cost
requirements.
se
r fa
n1
3%
3 Infrared Humidifier
Evaporator fan 16%
Compressor 70%
The Infrared Humidifier has been a feature on
Liebert environmental control systems for over
25 years. Its high efficiency, rapid response and
cleanliness has made it an industry standard in
applications that demand precise, particle-free
humidity control.
5 EC fan option
The optional EC fan can be lowered into the floor
stand for increased efficiency from reduced air
resistance when the units are operated.
3
Intelligent Ensures the optimized performance of precision air
conditioning unit
control The Liebert iCOM-control system featured on the Liebert.PEX brings high-level
supervision to multiple units allowing them to work together as a single system to
optimize the performance of precision air conditioning units.
High-Level
Supervision To
Multiple Units With
The Liebert iCom
Control System
Compressor is on
Compressor is on Compressor is on
Compressor is on
When the IDC room needs cooling, iCOM controller will automatically shut
down some units with heating demand to avoid the competitive operating
status of synchronous heating and cooling.
Unit Diary List - Free field area within the Spare Parts List - Critical spare part numbers
unit memory where unit maintenance are saved in unit memory and may be displayed
shares history with any authorized users o n t h e L a r g e G r a p h i c D i s p l a y, s p e e d i n g
or loggedin service contacts, including identification of parts.
record of what others have done.
5
Save useful Best return on investment in IDC room space
space of IDC Having the minimum unit size and required service access area, the Liebert.PEX
offers the best return on the investment you make on your data center space.
room All major components of the Liebert.PEX are accessible from the front for easy
serviceability.
Units can also be easily dismantled and re-assembled for difficult access and site jobs
(e.g. small lifts, stairways and doors).
Liebert.PEX system
structure design is
compact and space-
efficient.
Considering both the unit size and the required service access area, the Liebert.PEX
offers the best return on the investment you make on your data center space.
6
Energy-saving, space-saving, environment-
friendly, long service life and low cost
Emerson Liebert insists Control system with functions of expert self-diagnosis and fault pre-alarm
on high reliability Frame is riveted through rivets made of carbon steel, which is strong and easy-to-
dismantle
design.
Internal/external double-side panel with fire-proof and heat-insulation materials
inside
Multi-protection mechanisms such as compressor high/low pressure protection,
high temperature of discharged gas, air flow loss and fan over load protection
7
Liebert.PEX Unit Upflow unit
Designed for in-room or duct applications
has many kinds
of air supply and
cooling methods
Liebert.PEX meets your
specific needs
Downflow unit
Designed for raised floor applications
8
Energy-saving, space-saving, environment-
friendly, long service life and low cost
Liebert.PEX
offers you high efficient and high reliable space-saving design
High reliability
High quality components that have been strictly certified
Advanced controller automatically balances the operation and wearing of
components to prolong the system life
Control system with functions of expert self-diagnosis and fault pre-alarm
Space saving
Compared to the average level in cooling industry, offers 15% more cooling capacity
per square meter
All major components of the Liebert.PEX are accessible from the front
Units can also be easily dismantled and re-assembled for difficult access and site jobs
Intelligent control
Teamwork mode can intelligently control the units to work in IDC room with
unbalanced loads coordinately
Spare Parts List supports the fast identification of parts
Unit records all kinds of data and provides shareable history data
Variety of configurations
Many kinds of configurations of upflow and downflow unit
Dual-chilled water circuit design
Green design, compatible with R22 and R407C cooling systems
Can be configured according to special needs
Energy-saving, space-saving, environment-
friendly, long service life and low cost
Liebert.PEX Specifications
Down Flow Unit (Single Cooling Cycle)
Model (P*****A/W/G)
Type
P1020F P1025F P1030F P1035F P2045F P2055F
Total (kW) 20 23.1 30.1 33.1 45 53.2
Cooling Capacity (kW)
Sensible (kW) 18.9 21.5 26.6 29.4 41.7 47.3
Standard flow volume (m3/h) 5670 6660 8280 8190 12240 13680
Fan
Fan number 1 1 1 1 2 2
Electric heater Power (kW) 6 6 6 6 9 9
Infrared humidifier Capacity (kg/h) 4.5 4.5 4.5 4.5 10 10
Dimensions W×D×H (mm) 853×874×1970 1704×874×1970
Net weight kg 320 330 340 350 560 570
Quantity of water intake
1.15 1.32 1.73 1.9 2.58 3.05
(32°C)l/s
Condenser water supply
Pressure drop (kPa) 45.5 60.9 54.4 50 92.1 101.3
requirement (32/37°C)
Plate exchanger water
28 28 35 35 35 35
in/out line (mm)
FLA (A) 23.1 25.2 30.4 32.3 48.5 53.5
Electrical
Breaker (A) 32 32 40 40 63 63
Remark:
1. Test conditions: 380V/50Hz 3P, 24°C room temperature, and 50%RH.
2. The standard flow valve of water/glycol unit is two-way valve, and triple-way valve can also be selected.
3. When the water pressure of water cooled unit is higher than 1034 kPa, please contact Emerson Network Power Co., Ltd.
4. If the required data is not listed in the table, please contact Emerson Network Power Co., Ltd.
5.Electronic expansion valve(EEV) can be selected.
6.EC fan can be selected.
Upflow Unit (Single Cooling Cycle)
Model (P*****A/W/G)
Type
P1020U/D P1025U/D P1030U/D P1035U/D P2045U/D P2055U/D
Total (kW) 19.4 22.1 29.2 32.4 44.4 52
Cooling Capacity (kW)
Sensible (kW) 18.3 20.7 25.9 28 40.7 46.1
Standard flow volume (m3/h) 5400 6300 7866 7920 11610 13032
Fan
Fan number 1 1 1 1 2 2
Electric heater Power (kW) 6 6 6 6 9 9
Infrared humidifier Capacity (kg/h) 4.5 4.5 4.5 4.5 10 10
Dimensions W×D×H (mm) 853×874×1970 1704×874×1970
Net weight kg 320 330 340 350 560 570
Quantity of water intake
1.15 1.32 1.73 1.9 2.58 3.05
(32°C)l/s
Condenser water supply
Pressure drop (kPa) 45.5 60.9 54.4 50 92.1 101.3
requirement (32/37°C)
Plate exchanger water in/out
28 28 35 35 35 35
line (mm)
FLA (A) 23.1 25.2 30.4 32.3 48.5 53.5
Electrical
Breaker (A) 32 32 40 40 63 63
Cooling Capacity Total (kW) 39.5 45.7 57.9 65.9 79.4 87.2 97.9
(kW) Sensible (kW) 37.2 42 51.6 56.3 69.2 77.5 83.9
Standard flow volume (m3/h) 10440 12240 15390 15480 19188 22770 22860
Fan
Fan number 2 2 2 2 3 3 3
Electric heater Power (kW) 9 9 9 9 12 12 12
Infrared humidifier Capacity (kg/h) 10 10 10 10 10 10 10
Dimensions W×D×H (mm) 1704×874×1970 2553×874×1970
Net weight kg 590 610 640 650 910 930 950
Quantity of water intake
2.35 2.66 3.47 3.83 4.67 5.12 5.73
Condenser (32°C)l/s
water supply
Pressure drop (kPa) 46.9 61.1 45.4 50.1 54.9 89.4 94.5
requirement
(32/37°C) Plate exchanger water in/out
28 28 35 35 35 35 35
line (mm)
FLA (A) 42.9 47.1 57.5 61.3 71.9 77.7 87.7
Electrical
Breaker (A) 63 63 80 80 100 100 100
Remark:
1. Test conditions: 380V/50Hz 3P, 24°C room temperature, and 50%RH.
2. The standard flow valve of water/glycol unit is two-way valve, and triple-way valve can also be selected.
3. When the water pressure of water cooled unit is higher than 1034 kPa, please contact Emerson Network Power Co., Ltd.
4. If the required data is not listed in the table, please contact Emerson Network Power Co., Ltd.
5.Electronic expansion valve(EEV) can be selected.
6.EC fan can be selected.
Energy-saving, space-saving, environment-
friendly, long service life and low cost
Upflow Unit
Model(P****C)
Type
P1030U/D P1040U/D P2050U/D P2070U/D P2090U/D P3110U/D P3140U/D
Cooling Capac- Total(kW) 36.8 41.4 61.1 78.1 88.1 118.2 131.9
ity Sensible(kW) 30.2 32.8 49.2 62.2 70.1 94 101.9
Standard Flow Volume(m3/h) 8100 8280 11070 16020 16740 23940 23940
Fan
Fan Number 1 1 2 2 2 3 3
Electric Heater Power(kW) 6 6 9 9 9 12 12
Infraed Humidi-
fier
Capacity(kg/h) 4.5 4.5 10 10 10 10 10
Dimensions WġDġH(mm) 853ġ874ġ1970 1704ġ874ġ1970 2553ġ874ġ1970
Weight Net Weight(kg) 260 270 480 480 480 730 760
Quantity of Water Intake(l/s) 1.8 2.0 2.9 3.7 4.2 5.6 6.3
chilled water Pressure Drop(kPa) 121 84 78 124 86 127 103
parameters
Dimensions of Water
Pipe(mm)
32 32 42 42 42 54 54
FLA(A) 11 11 23.5 23.5 24 28.2 28.2
Electrical
Breaker(A) 16 16 25 25 25 32 32
Remark:
1. The testing working condition: 380V/50Hzċ3P, supply/return water temperature is 7/12ņ, the return air is at 24ņLj50%RH.
2. The standard flow valve of water/glycol unit is two-way valve, and triple-way valve can also be selected.
3. When the water pressure of water cooled unit is higher than 1034 kPa, please contact Emerson Network Power Co., Ltd.
4. If the required data is not listed in the table, please contact Emerson Network Power Co., Ltd.
5.EC fan can be selected.
13
Liebert.PEX Dual Cooling Source
Downflow Unit(Single Cooling Cycle)
Model(P***DD*)
Type
P1020D P1025D P1030D P1035D P2045D P2055D
Total(kW) 20 23.1 30.1 33.1 45 53.2
Air Cooled
Sensible(kW) 18.9 21.5 26.6 29.4 41.7 47.3
Total(kW) 23.2 25.4 28.5 28.5 53.2 56.8
Chilled Water
Sensible(kW) 19.6 21.9 25.5 25.5 43.7 47.3
Standard Flow Volume(m3/h) 5670 6660 8280 8190 12240 13680
Fan
Fan Number 1 1 1 1 2 2
Electric Heater Power(kW) 6 6 6 6 9 9
Infraed Humidifier Capacity(kg/h) 4.5 4.5 4.5 4.5 10 10
Dimensions WġDġH(mm) 853ġ874ġ1970 1704ġ874ġ1970
Weight Net Weight(kg) 320 330 340 350 560 570
Quantity of Water Intake(l/s) 1.1 1.2 1.4 1.4 2.5 2.7
chilled water
Pressure Drop(kPa) 29.9 37.8 50.7 50.7 40.2 47.0
parameters
Dimensions of Water Pipe(mm) 25 25 25 25 32 32
FLA(A) 23.1 25.2 30.4 32.3 48.5 53.5
Electrical
Breaker(A) 32 32 40 40 63 63
Remark:
1. The testing working condition: 380V/50Hzċ3P, supply/return water temperature is 7/12ņ, the return air is at 24ņLj50%RH.
2. The standard flow valve of water/glycol unit is two-way valve, and triple-way valve can also be selected.
3. When the water pressure of water cooled unit is higher than 1034 kPa, please contact Emerson Network Power Co., Ltd.
4. If the required data is not listed in the table, please contact Emerson Network Power Co., Ltd.
5.Electronic expansion valve(EEV) can be selected.
6.EC fan can be selected.
Energy-saving, space-saving, environment-
friendly, long service life and low cost
Remark:
1. The testing working condition: 380V/50Hzċ3P, supply/return water temperature is 7/12ņ, the return air is at 24ņLj50%RH.
2. The standard flow valve of water/glycol unit is two-way valve, and triple-way valve can also be selected.
3. When the water pressure of water cooled unit is higher than 1034 kPa, please contact Emerson Network Power Co., Ltd.
4. If the required data is not listed in the table, please contact Emerson Network Power Co., Ltd.
5.Electronic expansion valve(EEV) can be selected.
6.EC fan can be selected.
15
St. Louis-based US Emerson Electric Co., was established Ltd. uses its industry-leading network power technologies,
in 1890 and has been one of the renowned international R&D, manufacturing, global marketing and service platforms,
companies. Emerson’s expertise covers 5 areas: Process to supply the world with the most comprehensive End-to-End
Control; Electronics and Telecommunications; Industrial Network Power Total Solution. We bring together technology &
Automation; Heating, Ventilation and Air Conditioning; and engineering to create solutions for the benefit of our customers.
Appliance and Tools. Its innovative solutions have been applied The core products include telecom power systems, board
in more than 150 countries. Emerson has 60-plus divisions and mounted power supplies, custom power supplies, UPS, precision
110,000 employees worldwide. Emerson was ranked one of air conditionings, outdoor shelter solutions, automatic transfer
Global Top 500 and realized USD$17.3 billion sales in FY2005. systems, network power protection products, VRLA batteries,
Emerson has been recognized as “World’s Most Admired LV & precision distribution cabinets, centralized power and
Companies” by Fortune, and ranked second in the electronics environment monitoring systems, DC power systems and AC
industry category. motor drive inverters used in electric utility power systems.
Emerson Network Power Co., Ltd. is a subsidiary company Emerson Network Power Co., Ltd. is the trusted supplier of
of American Emerson Electric Co.. It has 28 sales offices and network power products and solutions for global IT industry and
29 service centers all over China. Emerson Network Power Co., telecom market.
Critical business continuity, Emerson Network Power and Emerson Network Power logo are all the trademarks and service marks of
Emerson Electric, all rights reserved by Emerson Electric, 2008.
E-X6210604-0310