Professional Documents
Culture Documents
DSF Secondary Power Supply Uninterruptible Power Supplies
DSF Secondary Power Supply Uninterruptible Power Supplies
UPS systems shall be provided for all critical loads that cannot tolerate power interruptions. These shall be further backed by the
standby generator system.
Each uninterruptible power supplies (UPS) system shall be hot-swappable, comprising of a fully controlled recti er charger, battery
bank, inverter, static bypass, and manual bypass capable of providing safe and secure power supply.
N+1 Hot Swappable Critical Care Nursing Units, Surgical Theaters 60 minutes
Dedicated N+1 Hot Swappable CCTV and Security Systems 120 minutes
UPS modules,
batteries,
battery monitoring,
DC disconnects, and
maintenance bypass.
The UPS system shall be single or multi-module or redundant con guration as described above.
The UPS system shall be sized to maintain the load and be equipped with a battery able to supply this load for speci ed minutes, at a
temperature of 25°C. The battery is to provide 100 percent of the speci ed capacity at initial startup.
Apart from rack mounted UPS, the main outgoing cables from UPS supplies shall be provided with 4-pole circuit breakers to facilitate
mitigation of oating neutrals.
System components
System includes:
System operation
Utility power available: recti er/charger supplies load through primary inverter and maintains battery in fully charged “ oat”
condition. Load is served from the recti er/chargers-inverter assembly or assemblies depending on the system con guration.
Utility power failure: load supplied from battery through static inverter if utility power drops below preset limits, or fails. There is no
output disturbance transmitted to load.
Utility power returns: recti er/charger supplies power to load through inverter while it recharges battery. There is no output
disturbance transmitted to load.
Failure of both recti er/charger assemblies or battery: static switch transfers load to synchronized utility power, without disturbance,
when inverter output deviates beyond speci ed quality limits. When inverter output returns to acceptable operation, it is
synchronized to utility power, and after preset timing interval, static switch returns load to inverter without disturbance.
Single recti er failure: static switch of failed module removes module from system output and transfers load to utility power bus.
Overload or short circuit: static switch transfers load to utility power during load inrush and clearing of faulted branch circuits; load
automatically transfers back to inverter without disturbance.
Inverter failure: static switch shall transfer to utility power without disturbance and remain until manually returned.
Maintenance operation: load shall be transferred manually to utility power using bypass switch. During bypass mode, operation of
system or static switch shall not affect power to load.
Adjustable to maximum of 125 percent of that required to operate at full load with battery bank on oat charge.
Current Walk In: 25 to 100 percent in 15 seconds.
Environmental range
The UPS shall be able to withstand any combination of the environmental conditions encountered in Qatar, and maintain operation
without mechanical or electrical damage or degradation of function when the UPS is mounted inside a shelter with access doors
closed:
UPS power factor over full range of loads and input voltages
80 percent, lagging or better.
Total harmonic distortion (THD) of input power supply current and voltage wave forms
Provide input harmonic lters to limit re ected current THD of input power supply to ve percent, maximum at full load, according to
IEEE Standard 519. Input power supply has a short-circuit rating of 65 kA symmetrical.
Maximum three percent RMS THD and maximum one percent any single harmonic, at rated frequency and voltage, from 10 percent
load to full load and over battery voltage range, measured into a non-linear load. Excessive ltering shall not be required to reduce
harmonics.
UPS system shall be capable of handling non-linear load currents typical of that of a K20-rated transformer.
Audible noise
Noise generated by the UPS under any condition of normal operation shall not exceed the allowable sound pressure level of 75 dB
measured at 62 m from the nearest surface of the cabinet.
Charging units
Each recti er/charger unit shall be solid state and shall provide direct current to the inverter unit and for battery charging utilizing
6-pole Silicon Controlled Recti er (SCR) bridge or Insulated Gate Bipolar Transistors (IGBTs). IGBTs are preferred.
Each recti er/charger unit shall be provided with an input circuit breaker. In addition to supplying power for the load, the
recti er/charger shall be capable of recharging the batteries. The charging rate shall be suf cient to restore the battery from
discharge to 95 percent of full charge within ten times the discharge time. After the battery is recharged, the recti er/charger shall
maintain the battery at full charge until the next emergency operation (Note: the recti er/charger shall be thermally compensated to
prevent battery overcharging and thermal runaway).
The input AC current limit shall be designed so that demands in excess of the DC output current needed to operate the inverter at
rated load and simultaneously recharge a discharged battery to 95 percent of its original capacity shall not cause a corresponding
decrease in the output DC voltage from the recti er/battery charger.
Each recti er/charger unit shall provide for input current limiting and battery recharge current limiting. Both are to be independently
adjustable. The input current limit shall be adjustable from 100 to 125 percent full load. The battery recharge current limit shall be
adjustable from two to 25 percent of the maximum discharge current.
The recti er/charger unit shall provide features whereby when the AC power is returned to the AC input bus, after the UPS has been
operating on battery power or has been de-energized, the total initial power requirement at the input terminals will not exceed
20 percent of rated load, and the power will gradually increase to 100 percent of full rating over the 15-second time interval.
The recti er/charger unit shall have an output lter to minimize ripple current into the battery. Under no conditions shall ripple
current into the battery exceed three percent RMS.
Electronic controls shall be incorporated to provide individual phase voltage compensation to obtain phase voltage balance under
all conditions, including up to a 50 percent current unbalance.
Each inverter unit in the system shall have fault sensing and static isolation, as well as an output circuit breaker, for removal of a
faulted module from the system without affecting the critical load bus.
The inverter shall be constructed of solid-state devices capable of providing the speci ed rated volt-amperes (VA) within the
operating range of the battery while connected to a 1.0 to 0.8 leading or lagging power factor load. The inverter shall current-limit
for loads in excess of 150 percent of its full load rating. Maximum effective current at the output of the inverter (when bypass AC
input is not available) shall be 150 percent. The inverter shall be capable of at least 300 percent current for short circuit conditions.
If the short circuit is sustained, the inverter shall shutdown and disconnect automatically from the critical load bus.