Professional Documents
Culture Documents
SAUPEC 2017 Paper 76 PDF
SAUPEC 2017 Paper 76 PDF
net/publication/313536517
CITATIONS READS
2 4,028
3 authors:
Ganesh K. Venayagamoorthy
Clemson University
491 PUBLICATIONS 12,852 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by Inno Davidson on 10 February 2017.
Abstract: Lightning strikes tend to terminate on the earthwire and/or tower. Depending on factors
such as the conductor, tower, soil impedance and magnitude of the strike, it will result in flashover
across an insulator and the resultant fault surge will propagate along the line until it is extinguished or
the breaker operates. This movement of the surge currents
of associated equipment such as circuit breakers and transformers and impacts network performance
adversely. The paper investigates the concept of tower footing resistances and the factors that
influence the earthing resistances. Tower footing resistance needs to be kept uniform and as low as
possible to prevent back flashovers across the insulator under lightning conditions. Theoretical
simulations were conducted on the different methods that are available to improve the tower footing
resistance values. A case study was undertaken to ascertain the tower footing resistance of an 88kV
Eskom line. The crows earthing configuration was then utilized to reduce the footing resistance to a
value less than 30 ohms. Results obtained are presented and discussed.
Where: 90 ohm-meter
R = Tower footing resistance h = 0.5 meters
= soil resistivity d = 10 mm
L = length of conductor (meters) L = 10 meter and increased to 60 meters
a = radius of conductor (meters)
D = distance between rods (meters)
Rods = number of electrodes
Table 1 shows the relationship between the number of Various instruments can be used to measure tower
radials and resistance. The following unit parameter footing resistance. These meters should inject a high
values were used: = 90, L = 50, d = 0.01, h = 0.5 frequency lightning-like pulse into the base of the tower
and measures the voltage response as a function of the
Table 1: Number of radials and resistance injected current to give one an impedance value. This is
N* 2 3 4 6 8 12 often referred to as the fall of potential method.
N(n) 0.7 1.53 2.45 4.42 6.5 11
Rg-ohms 2.19 1.61 1.34 1.09 0.96 0.85 Meters, such as the Zed Meter varies from conventional
three/four terminal low frequency earth testers. These
* Number of radial conductors
testers use a low frequency generator that measures the
power system resistance of a tower and adjacent parallel
towers. Due to the high frequency nature of lightning, the
From figure 4 shows once again that
affected tower is treated as isolated and ignores the
reached, in terms of the amount of electrode used against
parallel effect of adjacent towers. To simulate the high Figure 6: Tower footing resistance values along a terrain
frequency response of the single affected tower, a high
frequency pulse generator is required to calculate the The earthing on the towers with high resistance value
towers impedance. were improved. This was done by including copper in the
It should be noted that a low frequency generator will not on selected towers where the resistance value was greater
give one the same high frequency response and as a result than 30 ohms. Figure 6 illustrates the additional earthing
will under read the impedance value since the shield-wire installed to improve the resistance on selected towers on
and adjacent towers dampen the frequency response of an 88kV line.
the injected current pulse.
The new tower footing resistance values superimposed on
the old values are shown in the figure 7.
4. RESULTS AND DISCUSSIONS Figure 7: Old and new tower footing resistances
6. REFERENCES
2005.
[6] I E Davidson. orithm for
Proceedings of the 6 th
Southern African Universities Power Engineering
Conference (SAUPEC), University of the
Witwatersrand, South Africa, January 1996, Vol. 6,
pp. 279-282, 1996.
[7] G.A, Adegboyega and K.O. Odeyemi
of Soil Resistivity on Grounding of Electrical
Systems: A case study of North-
Journal of Academic and Applied Studies; Vol 1(3)
September 2011, Pages 28-38.
[8]
Technologies: Available at:
www.lightningman.com.au
[9] G.B. Lo Piparo, T. Kisielewicz, C. Mazzetti and F.
Fiamingo Protection of apparatus against lightning
surge in an extended earthing arrangement
Proceedings of the 16th IEEE International
Conference on Environment and Electrical
Engineering, Florence, Italy, 7-10 June 2016, pages
148-151.
[10] T.G. Pires, J.W.L. Nerys, C.L.B. Silva, N. Diogo,
W.P. Calixto, A.J. Alves Computation of
Resistance and Potential of Grounding Grids in any
Geometry Proceedings Of the 16th IEEE
International Conference on Environment and
Electrical Engineering, Florence, Italy, 7-10 June
2016, pages 142-147.