Professional Documents
Culture Documents
0 Wiring
0 Wiring
pmaher 31/05/01
15-1
Domestic Wiring
Consumer Earthing
3-pin socket
There is no need for a consumer earth to be for metal-cased
provided unless metal-cased appliances are likely devices
to be used.
Consumer loads that have metal cases such as
cookers, must have an earth connection. Then, if
Figure 15-6 An earth connection must be provided if
a wiring fault develops making the metal case metal cased loads are likely to be connected.
pmaher 31/05/01
15-2
Domestic Wiring
pmaher 31/05/01
15-3
Domestic Wiring
pmaher 31/05/01
15-4
Lightning Protection
pmaher 31/05/01
16-1
Lightning Protection
result from a direct strike, they are still becomes an excellent conductor above the
dangerous, particularly for electronic equipment. threshold. They are faster acting and usually
Voltages are induced both between live and clamp to lower voltages than spark-gap
neutral and neutral and earth. The “line-to- arrestors, therefore providing better protection
neutral” voltage surge can be reduced by twisting for electronic equipment such as TVs, CFLs with
the cables together if insulated conductors are electronic ballasts, and generator controllers.
used. For low current ratings, they are very cheap
(about $1) as they are mass-produced for use in
domestic appliances. However, for the higher
16.3 Lightning Arrestor Types current ratings designed for use on overhead
Spark-gap lines, they are expensive ($50 to $100)
especially when compared to spark-gap devices.
The conventional lightning arrestor consists of a
spark gap for the lightning to arc across and a Powerhouse Distribution Consumer
series resistance to limit the flow of current Ballast
System Loads
after the voltage surge. They are generally Induction
Load Lightning
isolation Arrestor Lightning Mains switch
switch on 1st pole Arrestor at consumer
slower acting than more modern arrestors and do Generator
RCD
L IGC L L
connection
pmaher 31/05/01
16-2
Lightning Protection
current handling to reduce the voltage across that do not contain electronics are reasonably
the sensitive electronic components in the IGC. well protected by spark-gap arrestors. However,
loads that contain electronics, such as TV’s,
The additional varistors should have a voltage radios and CFL’s are much more sensitive and
rating at least 25% above the rated voltage of require varistors for protection. The best
the distribution system. This will avoid them protection is provided by pole mountable
being damaged under normal operating varistors with current rating of more than
conditions. However, their voltage rating should 50,000 Amps as these can withstand very high-
be less than the voltage rating of the soldered energy discharges.
varistor. If they are damaged then they can
easily be replaced on site as they are not A cheaper alternative that works particularly
soldered. For example, if a varistor with an AC well with PTC themistor load-limiters (see Figure
voltage rating of 420V (usually the case) is 15-7) is to fit a disk-type varistor between line
already fitted to the IGC then additional and neutral on the load side of the limiter and
lightning protection can be achieved by have a pole mounted spark-gap arrestor. In the
connecting devices with 320V rating. event of lightning induced surge, the varistor will
clamp the voltage in the house, with the
16.5 Protection of Consumer Loads additional voltage being dropped across the PTC.
It is difficult to specify the number of lightning Once the voltage is high enough, the spark-gap
arrestors required for a scheme as it depends on arrestor will operate and conduct most of the
many factors, including the frequency of current. Note that this puts extra stresses on
lightning, expense of replacing damaged the PTC. However, these are cheaper to replace
appliances and the cost of the arrestors. than most domestic appliances.
Electrical guidelines for micro hydro in Nepal
state that the maximum distance of a consumer During stormy weather, consumers should be
from an arrestor is 500m and less in areas where encouraged to disconnect their supply via the
the risk of lightning strikes is high. When mains switch at the entrance to their house.
selecting the precise location to protect a Note the use of a double pole switch at the
number of consumers, preference should be consumer service entrance to isolate the live and
given to points in the system which are near to the neutral (Section 14.4). This is the most
areas where lightning is more likely to strike. secure method to prevent damage to delicate
loads such as CFL’s. Where the consumer
When fitting arrestors, the neutral is normally premises require an earth, it is important that
earthed at the lightning arrestor to minimise the the consumer earth is separate from the earth
neutral to ground voltage surge, as this can cause to which the lightning arrestor is connected and
the insulation to break down. This is not preferably 10m or more away. This is because
achievable when an RCD is fitted in the high currents to earth can result in dangerous
powerhouse, as earthing the neutral will cause voltage potentials close to the earth connection.
the RCD to trip. However, the neutral can be Earthed
earthed through an additional lightning arrestor, Consumer
as shown in Figure 16-3. Load
pmaher 31/05/01
16-3
Lightning Protection
pmaher 31/05/01
16-4
Testing, Commissioning and Operation
17 TESTING, •
same voltage as the generator.
Check the ballast meter to ensure that the
pmaher 31/05/01
17-1
Testing, Commissioning and Operation
pmaher 31/05/01
17-2
Fault-finding
18 FAULT-FINDING
Problem Possible Causes Solution
No voltage/low power Insufficient turbine power • Check water supply, nozzle and generator
output speed.
Wiring fault • Check wiring and MCB and RCD are switched
on.
Capacitor values incorrect • Check capacitors are connected as shown in
the wiring diagram.
• Check capacitor values are correct for
generator.
Generator has lost residual • Disconnect consumer load. When generator is
magnetism stationary, connect a battery of 6V or more
across any two generator terminals for one or
two seconds. Re-start with no user load
connected.
Ballast loads not connected • Check for loose or missing connections
Over-voltage trip properly (ballast meter reads • Check that any switches in the ballast circuit
operates 100%) are on.
• Check that all ballast loads become hot. If
not, measure resistance and replace if
necessary.
Generator output higher than IGC • Operate turbine at reduced power output or
rating replace IGC with one of higher rating
Controller damaged and fails to • Check whether fault is due to incorrect wiring
deliver power to ballast (ballast of IGC. If not, then replace circuit board.
meter does not operate or only
over a limited range),
Ballast trip lamp lit Ballast short circuited • Check resistance between ballast leads and
between each ballast lead and earth to test
for short circuits. Repair or replace faulty
wiring / ballast loads.
Ballast load too large • Check that the power rating of ballast is less
than or equal to the power rating of the IGC.
Light bulbs flicker Response speed of controller • Alter setting of response speed
incorrect. potentiometer on circuit board.
Ballast load much greater than • Reduce capacity of ballast load.
generator rating.
Uneven turbine output • Check turbine for misalignment, damage or
blockage.
• Check for badly worn bearings.
Motor protection switch Generator connection incorrect • Check generator connections.
operates
Too much excitation current • Reduce the amount of capacitance connected.
(motor protection switch operates
even when turbine operating at
reduced power output)
Too much load current (motor • Increase rating of motor protection switch
protection switch operates with and generator if necessary.
turbine operating at full power • Operate turbine at reduce power output
output) • Avoid overloading the generator
Short circuit in distribution • Isolate sections of the distribution system
system until the fault is found. Alternatively measure
the resistance at different sections to
identify the fault.
pmaher 31/05/01
18-1
Fault-finding
RCD operates Current leaking to ground either • Disconnect consumer loads and restart to
in powerhouse or elsewhere establish if the fault is in the powerhouse. If
in powerhouse check wiring of earthed
devices (e.g. controller casing) to locate
earth fault.
• If fault is elsewhere in the system,
disconnect all earthed consumer loads
• Check lightning arrestors for short to ground
by temporarily disconnecting.
Individual house Load limiter tripped • disconnect all domestic loads and wait for 5
without power minutes. Reconnect less loads than before
load limiter fuse blown • check fuse.
Wiring fault • check service wire connection
• check domestic wiring
Group of houses Wiring fault • check distribution cable connected to the
without power houses for a fault
All houses without Wiring fault • check wiring of main consumer switch in
power (generator, powerhouse
controller and ballast • check first section of distribution cable for
breaks .
working normally)
•
Further notes on fault finding:
pmaher 31/05/01
18-2
Appendices
19 APPENDICIES
Appendix A Basic Electricity
pmaher 31/05/01
19-1
Appendices
V oltage
Pow er
I = P/V
= 200/12
0
π
= 16.7 Amps
High current means high losses in electric cables φ = − 90°
V oltage
Real and Apparent Power
The basic formula for power is current times
Pow er voltage:
0
Current
π
The reason for this difference is that there are
φ = 90°
two types of electrical loads; resistive loads and
reactive loads. With resistive loads the current
is in phase with the voltage as shown in Figure
Figure 19-3 If the load is a pure capacitor, then the
current leads the voltage by 90° and the average power
19-2 and in this case the power factor=1 and the
consumed = 0 Watts real power equals the apparent power. Reactive
pmaher 31/05/01
19-2
Appendices
When the power factor equals 1.0, then the net and
requirement for reactive power is zero and only
resistive power is supplied. Power factor
S = P2 × Q2
correction means to bring the power factor Figure 19-6 Power triangle showing relationship between
closer to one and reduce the reactive power real and apparent power.
consumption. In practice this usually means
connecting capacitors in parallel with an inductive
Power Factor Correction
load to raise the power factor.
Circuits which have a lagging power factor
Since the reactive power does not show up on an caused by inductive loads (see Figure 19-4) such
electricity meter, domestic consumers are not as electric motors or fluorescent lamps, require
normally charged for reactive power. However a supply of reactive power. For small loads
this extra reactive power must still be provided connected to the electricity grid, this does not
by the generator. So to prevent a pico hydro present a problem as the reactive power can
system from becoming overloaded, power factor easily be supplied. However, this may not be the
correction is often an important consideration case with small stand-alone induction generators.
for the developer. Power factor correction is sometimes necessary
in these situations to allow the most efficient
A power factor of 1.0 means that a load is purely use to be made out of the power available.
resistive. No reactive power is used and real and
apparent power have the same value. If the The term “power factor correction” means to
power factor is less than one, then the load is increase a lagging power factor towards 1 so that
partly inductive. Power factors of some typical the amount of reactive power required by a
loads are given in the following table: circuit is reduced (see Figure 19-5.). This can be
achieved by connecting capacitors across the
load. Capacitance causes the current to lead the
Load Power factor
voltage rather than lag behind. This can be
Incandescent lamp 1.0 understood by comparing Figure 19-3 and Figure
Fluorescent lamps 0.5 - 0.7 19-4. The net effect of this is that the total
Motors 0.2 - 0.95 reactive power requirement of the circuit is
Table 19-1 Variation of power factors for common loads reduced. Additional considerations are the
availability and cost of suitable capacitors and
how much capacitance to connect. These may
Power Triangle
determine to what extent the power factor can
The relationship between real and apparent
be corrected. However, it is important to avoid
power and power factor can be summarised in a
over-correction of the power factor. Selection
“power triangle.”
of capacitors for power factor correction is
explained in Section 13.1.
pmaher 31/05/01
19-3
Appendices
Appendix C Turbine Operating Speeds for A useful guideline is to use the synchronous
Mechanical Loads speed of the motor. This will be slightly less than
the operating speed when the generator is being
A Operating speed under driven (synchronous speed + 3% slip) This will
mean that under normal conditions of operating
heavy mechanical load
Power (kW)
pmaher 31/05/01
19-4
Appendices
pmaher 31/05/01
19-5
20 USEFUL REFERENCES AND ADDRESSES
References:
1. Harvey, A. et al. ‘Micro Hydro Design Manual,’ Intermediate Technology Publications, 1993.
Editorial Address
Micro Hydro Research Group
Department of Electrical and Electronic Engineering
The Nottingham Trent University
Burton Street
Nottingham
NG7 4BU
ESMAP
C/o Energy, Mining and Telecommunications Department
The World Bank
1818H Street, NW
Washington, DC 20433
U.S.A.
pmaher 31/05/01
20-1
21 GLOSSARY
Abney level a device used for measuring the incline of a slope; can be used to calculate the head
ac alternating current; electric current which changes direction at frequent intervals .e.g. at 50Hz or
50 times per second
Altimeter a device which uses air pressure to calculate difference in vertical height between two points
Ballast load usually an electrical heating element which consumes any unused power produced by the generator
Battery used for storing dc electricity; re-chargeable batteries (e.g. lead-acid, Nickel Cadmium) can be used
to light houses which are too far from the generator to have a connection
Belt drive system for transferring rotating mechanical power from one shaft to another using pulley wheels and
belts
Bucket method method of flow measurement using a bucket of known volume and a stopwatch
Canal can be a practical and low cost method in some rural areas of transporting water to the forebay and
reducing the length of penstock required
Capacitor electronic device used to allow induction motors to work as generators; also used for power factor
correction; capacitance is measured in micro Farads (μF)
CFL Compact Fluorescent Lamp; energy efficient light bulb requiring less power than other varieties
Demand survey Assessment of the power requirements and ability to pay of a community
Efficiency the word used to describe how ell the power is converted from one form to another; it is the ratio of
the output power to the input power expressed as a percentage; the efficiency of a pico hydro
system is usually about 45%.
Emergency lighting tube light with rechargeable battery which can be switched on when the electricity supply fails
Energy storage energy storage may be required if the flow of water cannot be guaranteed to be high enough
throughout the year; batteries and reservoirs are examples of how energy can be stored
Flow measurement of the quantity of water flowing past a point in one second; measured in metres per
second or litres per second and used to calculate the hydraulic power
Forebay structure which is sometimes used for pico hydro at the start of the penstock ensuring that the
water is sufficiently deep
Frequency the switching backwards and forwards of alternating current; measured in Hertz (cycles per second)
Fuse electrical safety device which prevents damage to circuits or appliances caused by short circuits or
overloading
pmaher 31/05/01
21-1
Head the vertical drop of a water in a stream or in the penstock; measured in metres
IGC Induction Generator Controller – and electronic device used to keep the voltage and frequency steady
Induction motor electrical machine which can be used to drive mechanical loads
Lighting package an electricity supply suitable for one lamp and possibly a radio
Lightning arrestor a device which allows current surges caused by lighting strikes to be conducted away to ground
Load control a system to keep the amount of load on the generator constant
Load limiter a device which prevents too much current being taken by a consumer
Low-pressure pipe can be used as a cost-effective alternative to a canal to bring water to the mouth of the penstock
MCB Miniature Circuit Breaker; alternative safety device to the fuse with the advantage that it can be
reset after tripping due to a short circuit or overloading
Meter device which displays the level of generator voltage or ballast power
Motor Protection Safety device which disconnects if too much current is drawn. Unlike an MCB, which operates at only
one current level, the tripping current can be selected from a range, e.g. 6 to 10 amps.
Switch
Over-voltage trip protection circuit built into the IGC which automatically disconnects the supply to protect the
consumer loads if the voltage rises too high
Pelton turbine rotating wheel with buckets around the outside which absorb the power of a water jet and convert it
into rotating mechanical power; most Pelton designs require a head of 20 metres or more to work
efficiently
Penstock pipe containing water under pressure: brings water from forebay to powerhouse
p.c.d. pitch circle diameter; diameter line around a Pelton turbine at the centre of jet interaction
PTC Positive Temperature Coefficient Thermistor; electronic device which can be used as a low-cost form
of load limiting
Power measurement of energy supply and demand; given in Watts(W) or Kilowatts(kW); may be hydraulic
power, mechanical power or electrical power.
Power factor reducing the reactive power requirements of loads such as induction motors and fluorescent lighting
by connecting capacitors of certain value across the supply.
correction
Powerhouse building which contains the turbine, generator and any directly driven mechanical loads
RCD Residual Current Device; used to disconnect the supply in the event of an earth
fault
Reservoir small scale energy storage; sometimes used during the dry season if flows are insufficient; water
pmaher 31/05/01
21-2
collected during the day so that the turbine can be run in the evening for lighting
Resistance property of materials related to how well they conduct electric current e.g. plastic has a high
resistance and is called and insulator, copper has a low resistance and is called a conductor;
resistance is measured in ohms (Ω)
Salt Gulp method of flow measurement by adding salt to the water and measuring the conductivity change
Stand-alone system Electricity system which is not connected to the National Grid
Transformer A device with allows the voltage of an ac circuit to be changed up or down by a fixed amount
(e.g. 240v to 12v) Sometimes the distribution voltage is raised so that houses further than 1km from
the generator can be connected. Higher voltage reduces losses in the cables.
Turbine nozzle restricts the flow of water at the end of the penstock to produce a high velocity jet
Valve device used to regulate the flow of water in the penstock. A gate valve is preferred
Voltage measurement of “electrical pressure” which is required in order for current to flow around a circuit;
measured in volts (v)
Voltage drop loss of voltage across the distribution system because of the cable resistance. A voltage drop of up
to ±6% is acceptable
pmaher 31/05/01
21-3
22 INDEX
Abney Level (Clinometer), 7-1, 7-3 mechanical, 2-3, 9-9, 12-3, 13-1, 13-7, 13-8, 13-
Ballast Heaters, 9-5 12
Battery charging, 5-4, 9-3 Meters
Canals, 6-3, 10-1, 10-2, 10-4 ballast meter, 9-6
Capacitance voltmeter, 9-6
excitation, 9-3 Miniature Circuit Breaker (MCB), 9-8, 9-9, 13-6,
power factor correction, 13-2, 13-3, 13-4 14-3, 14-7, 14-13, 15-3, 17-1, 18-1
Current, 8-2, 9-1, 9-8, 13-3, 14-8, 14-9, 14-10, Over-voltage trip, 9-6, 18-1
15-3, 18-2 Pelton turbine, 1-1
Distribution Peltric Set, 8-1, 8-2
cable, 14-1, 14-3 Penstock
layout, 14-2 diameter, 11-1
poles, 14-1, 14-4 materials, 11-2
service connections, 14-7 pressure rating, 11-1
Distribution System, 2-3, 14-1 Penstock Filters, 10-2
Domestic Wiring, 15-1 Pico hydro, 1-1, 2-1, 2-2, 4-1, 5-4, 8-1, 8-2, 9-3
Earth-fault protection, 9-1 Pipe
Efficiency, 2-2 drainage, 6-3, 10-4, 10-5
Energy storage, 6-3, 10-6, 13-4 flushing, 10-6, 11-2
Flow measurement, 7-1, 7-4, 7-9 Pitch circle diameter (p.c.d.), 8-3
Forebay tanks, 2-1, 6-2, 7-1, 7-2, 10-5, 11-2 Positive temperature coefficient thermistor
Frequency, 9-5, 9-7, 17-2 (PTC), 15-3
Fuses, 15-3, 15-4 Power
Head measurement, 7-1, 7-2 electrical, 2-2, 2-3, 4-1, 9-8, 9-9, 14-11
IGC hydraulic, 2-2, 2-3, 8-3, 9-8
installation of, 9-11 mechanical, 2-2, 2-3, 4-1, 8-2, 8-3, 10-7, 13-7,
Induction Generator Controller (IGC), 9-5 13-8, 14-11
Induction generators, 1-1, 9-3, 9-5, 9-7, 14-12 Power factor correction, 13-2, 13-3, 13-4
Induction motors, 1-1, 8-1, 9-3, 9-8, 9-9, 13-6, Powerhouse, 12-1
13-7, 13-9, 14-12 Reservoirs, 2-1, 6-3, 10-1, 10-2, 10-6, 10-7, 12-3
Intake design, 10-1 Residual current device (RCD), 9-1, 9-2, 9-9, 9-
Lighting 10, 15-1, 15-2, 17-1, 18-1, 18-2
compact fluorescent, 13-2, 13-4 Safety, 9-1
emergency, 13-5 Salt Gulp Method, 7-4, 7-7
incandescent, 13-1, 13-4 Scheme
packages, 5-2 layout, 6-1
tube, 7-2, 13-1 Scheme layout, 6-1
Lightning Arrestors, 9-9, 12-3, 18-2 Survey
Load Control, 9-1, 9-5 demand, 5-1
Load limiters, 15-3 site, 7-1
Loads Turbine nozzle, 2-1, 2-2, 8-2, 8-3, 9-5, 10-2, 11-1,
consumer, 2-3, 14-10 11-2, 11-3, 17-1, 18-1
electrical, 2-2, 2-3, 9-1, 9-2, 13-1, 13-4, 13-7, Voltage, 9-5, 13-3, 14-3, 14-9, 14-10, 14-12
14-8 Voltage drop, 14-8, 14-11
Water source, 2-1, 5-3, 6-2, 11-1, 14-1
pmaher 31/05/01
22-1