TURBINE TRIP PROTECTION

SL ALARM TIME
DESCRIPTION SET VALVE
NO VALVE DELAY
1 Emergency Push Button Trip from UCP and OWS.
2 Fire Protection CH-1 and CH-2 and MBLD 1&2.
3 Condenser Presurre high. 2/3 0.4 kg/cm2 0.2 kg/cm2
4 Lube oil pressur very low. 2/3 1.2 kg/cm2
5 HP Exhaust stem tempreature Very high. 2/3 500 C
6 Axial shift very high. 2/3 1 mm(+-) 0.5 mm
7 HP casing top bottom differential temp .very high 2/3 & >120MW 100 C 90 C
8 IP casing front & rear top bottom differential tempreature
very high 2/3 & >120MW 45 C 30 C
9 Cold gas temp. after H2 cooler very high. 2/3 60 C 55 C
10 Hot Air temp. after exciter very high. 2/3 80 C 75 C
11 Liquid level in main leads. Very high. 2/3
12 Primay water temp. After cooler very high. 2/3 60 C 55 C
13 Turbine bearing metal tempreature very high. 130 C 100 C
14 Main steam temp . Very low . 2/3 460 C 500 C
15 Turbine shaft vibration very high. 320 micron 500 ms
16 Over Speed. 3300 rpm
17 Stator water winding outlet flow very low. 2/3 64 m3/hr 72 m3/hr 60s
18 Main bushing RYB flow very low. 2/3 2 m3/hr 2.15 m3/hr 60s
19 Boiler trip to Turbine Trip. 2/3
20 Generator trip to Turbine trip. 2/3
21 MOT level very low . 1050 mm