CICPY Viet Nam

Location Phu Yen


Building owner
Program user TuanDo
Company Novas
Comments

By Trane
Dataset name C:\Users\dell\Desktop\Phu Yen 2.trc

Calculation time 10:55 AM on 11/22/2019


TRACE® 700 version 6.2.4
Location Da nang, Viet Nam
Latitude 16.1 deg
Longitude -108.3 deg
Time Zone -7
Elevation 0 m
Barometric pressure 101.9 kPa
Air density 1.2257 kg/cu m
Air specific heat 1.0234 kJ/kg·°C
Density-specific heat product 1.2536 kJ/cu m·°C
Latent heat factor 3,067.7 kJ/cu m
Enthalpy factor 1,226 J·kg/cu m·kJ
Summer design dry bulb 36 °C
Summer design wet bulb 29 °C
Winter design dry bulb 17 °C
Summer clearness number 1.00
Winter clearness number 1.00
Summer ground reflectance 0.20
Winter ground reflectance 0.20
Carbon Dioxide Level 400 ppm
Design simulation period January - December
Cooling load methodology TETD-TA1
Heating load methodology UATD
System Checksums
By Trane
Tang 1 Single Zone
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 7 / 16 Mo/Hr: Sum of Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 35 / 30 / 25 OADB: Peaks OADB: 17 SADB 12.8 20.1
Ra Plenum 31.0 19.3
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 24.0 20.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 24.4 19.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 15.48 0.00 15.48 1.41 25.19 2.70 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 6.69 0.00 6.69 0.61 5.54 0.59 Glass/Door Cond -2.47 -2.47 12.08 Cooling Heating
Wall Cond 26.97 19.08 46.05 4.20 23.77 2.55 Wall Cond -3.81 -6.79 33.22
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 66,179 66,179
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 66,179 66,179
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0 Main Fan 66,179 66,179
Infiltration 35.20 35.20 3.21 7.50 0.81 Infiltration -2.33 -2.33 11.40 Sec Fan 0 0
Sub Total ==> 84.34 19.08 103.42 9.42 62.00 6.66 Sub Total ==> -8.61 -11.59 56.70 Nom Vent 2,117 2,117
AHU Vent 2,117 2,117
Internal Loads Internal Loads Infil 558 558
Lights 35.71 8.93 44.64 4.07 35.71 3.83 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 16.11 0 16 1.47 8.06 0.87 People 0.00 0 0.00 Return 66,738 66,738
Misc 800.01 0.00 800.01 72.88 800.01 85.90 Misc 0.00 0.00 0.00 Exhaust 2,675 2,675
Sub Total ==> 851.83 8.93 860.76 78.42 843.78 90.60 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 28.01 -28.01 0.00 0.00 25.52 2.74 Ceiling Load -2.98 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 133.49 12.16 0.00 0.00 Ventilation Load 0.00 -8.85 43.30 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.01 0.01 0.00 0.01 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 3.2 3.2
Duct Heat Pkup 0.00 0.00 0.00 Lps/m² 29.65 29.65
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 60.27
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 2.03
W/m² 491.58 -9.16
Grand Total ==> 964.19 0.00 1,097.68 100.00 931.31 100.00 Grand Total ==> -11.59 -20.44 100.00 No. People 100

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass CapacityCoil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1,097.67 958.91 66,179 24.4 16.6 8.6 12.8 11.5 7.9 Floor 2,232 Main Htg -20.5 66,179 19.9 20.1
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1,097.67 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 1,058 120 11 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -20.5

Project Name: CICPY Viet Nam TRACE® 700 v6.2.4 calculated at 10:55 AM on 11/22/2019
Dataset Name: Phu Yen 2.trc Alternative - 1 System Checksums Report Page 1 of 1