Professional Documents
Culture Documents
Chapter III D
Chapter III D
Chapter III D
accordance with the National Structural Code of the Philippines 2015. For concrete, the
following parameters and constants shall be used in analyzing the proposed structures of
the project:
1. Load Calculation
Dead loads consist of all construction materials incorporated into the structure
including walls, floors, roofs, ceilings, stairways, built-in partitions, finishes, cladding
and other similarly incorporated architectural and structural items. For design purposes,
minimum values of dead loads are provided on Tables 204-1 and 204-2 of NSCP 2015.
Live loads are the maximum load expected by the intended use and occupancy of
the structure. For design purposes, the minimum values of uniform and concentrated live
loads are provided on Table 205-1 of NSCP 2015 while the minimum values of special
Buildings and other vertical structures shall be designed and constructed to resist these
loads as specified and presented on sections 207A through 207 F of NSCP 2015.
For the first step in wind load analysis, the occupancy category of the building or
structure shall be determined through Table 103-1. On this table, structures are
categorized into 5, namely: (1) Essential Facilities, (2) Hazardous Facilities, (3) Special
Knowing the applicable occupancy category, the second step is to determine the
The third step is to determine certain wind load parameters that should be
considered in the calculation of wind loads. First is the wind directionality factor (K d). It
shall be determined from Table 207A.6.1 which defines the directionality factor for
different structure types. For each wind direction, the exposure category of the structure
shall be determined in accordance with Section 207A.7. The wind speed-up effect shall
also be included in the calculation of design wind loads using the topographic factor
(Kzt). If site conditions and locations meet all the conditions stated on Section 207A.8.1,
where K1, K2, and K3 are given in Figure 207.8.1 of NSCP 2015
If site conditions and locations do not meet all the conditions stated on Section
It shall be determined in accordance with Section 207A.91. This section states that for a
In this section, buildings are classified into three, namely: (1) enclosed. (2) partially
enclosed, and (3) open. Based on enclosure classification, internal pressure coefficient
After determining the wind parameters, the fourth step is to determine the velocity
pressure exposure coefficient (Kh or Kz) in accordance with Table 207B.3-1. Shown in
this table are the velocity factor coefficients on elevations from the ground level of the
The fifth step is to determine the velocity pressure (qz) evaluated at a certain
height. In accordance with Section 207B.3.2, it can be determined using the equation,
where V is in m/s
The sixth step is to determine the external pressure coefficient (Cp or Cn) in
For the last step of wind load analysis, the design wind load (p) shall be calculated
earthquake load. According to Section 208 of NSCP 205, structures should be able to
Like in the wind load analysis, the first step in the earthquake load analysis is the
determination of the occupancy category of the structure in accordance with Table 103-1.
Knowing the applicable occupancy category, the second step is to determine the
seismic importance factors (I, Ip) which shall be determined from Table 208-1. This table
The third step is to determine the soil profile type of the site. Table 208-2
provides the different soil profile types and their respective soil profile names and
fourth step. The section states that the Philippine archipelago is divided into two seismic
zones only, Zone 2 and Zone 4. Knowing the seismic zone, determines the seismic zone
The fifth step is the determination of seismic source type from Table 208-4.
Indicated on this table are the seismic source description and seismic source definition of
each seismic source types. Three seismic source types are present on the table.
For the sixth step, the proponents considered the condition on Section 208.4.4.3,
which is the determination of near source factor for sites under seismic zone 4. From
Tables 208-5 and 208-6, the near source factors, Na and Nv, shall be determined with
With respect to soil profile type and seismic zone factor, the seventh step is to
determine the seismic response coefficients, Ca and Cv in accordance with Tables 208-7
The eighth step is to determine the seismic force amplification factor (ꭥ o) and
numerical coefficient (R) from Table 208-11A. Determine also the total seismic dead
load (W) and the structure period (T) in accordance with Sections 208.6.1 and 208.5.2.2.
The ninth step is to compute for the total design base shear (V) using equations
208-8, 208-9, 208-10, 208-11 or 208-15, as applicable. The equations are as follows:
Furthermore, for seismic zone, the total base shear shall also not be less than:
Then, calculate the design storey shear (Vx) in accordance with Section
should be evaluated to determine the most critical conditions for design. The following
where:
D = dead load
E = earthquake load
L = live load except roof live load, including any permitted live load reduction
combination,
f1 = 1.0 for floors in places of public assembly, for live loads in excess of 4.8kpa
classified into two types; one-way and two-way slabs. If the ratio of short span and the
long span slab is less than 0.5, the slab is considered a one-way slab. On the other hand, if
the ratio is greater than 0.5 then the slab is a two-way slab. After determining the type of
For the design of one-way slab, the first step is to determine the minimum slab
thickness (h) in accordance with Table 407.3.1.1. The table discusses the minimum slab
Then, for the second step, calculate the total factored load coming from the slab-
For slabs built integrally with supports, the third step is the calculation of factored
1
d2 = h – cc - (reinforcement bar diameter) - 2(reinforcement bar diameter)
where d1 is the distance of the reinforcement from the extreme compression fiber
to the centroid of the reinforcement of short span and d2 is the distance of the
reinforcement from the extreme compression fiber to the centroid of the reinforcement of
long span.
Then, for the fifth step, solve the value of Rn using the formula of the nominal or
design moment,
Mu = ØRnbd2
Ø represents the strength reduction factor which shall be determined from Table 421.2.1
Having the needed values, the sixth step is to solve for the required steel ratio ρ
0.85𝑓’𝑐 2𝑅𝑛
ρ= [1 − √1 − ]
𝑓𝑦 0.85𝑓′𝑐
The resulting value of ρ must be less than the maximum steel percentage, ρmax,
1.4 √𝑓′𝑐
ρmin = or[ ]
𝑓𝑦 4𝑓𝑦
The seventh step is to determine the required steel area, As, using the formula:
As = ρbd
Having the required steel area, determine on the eight step the required spacing of
S = 𝐴𝑑 𝑏/𝐴𝑠
where Ad is the actual reinforcing bar area and b is the 1-meter strip. Spacing of
main bars (S) should not be greater than doubled slab thickness or 450 mm. For the
spacing of the reinforcement to be used, select the smallest value among S, 3h or 450
mm.
Like in the design of one-way slabs, the first step in the design of two-way slabs
is the determination of the minimum slab thickness (h). This shall be determined by
dividing the perimeter of the panel by 180. In accordance with Section 408, the minimum
slab thickness for slabs without drop panel is 125 mm and for slabs with drop panel is
100mm.
The second step is to calculate the total factored load coming from the slab-
For the third step, compute the slab moments using the moment coefficient table
which shows the relationship of span ratio to the moment coefficient depending on the
The fourth step is to determine the effective depth (d1 and d2) can be acquired
1
d2 = h – cc - (reinforcement bar diameter) - 2(reinforcement bar diameter)
where d1 is the distance of the reinforcement from the extreme compression fiber
to the centroid of the reinforcement of short span and d2 is the distance of the
reinforcement from the extreme compression fiber to the centroid of the reinforcement of
long span.
Then, for the fifth step, solve for the value of Rn using the formula of the nominal
or design moment,
Mu = ØRnbd2
Ø is the strength reduction factor which shall be determined from Table 421.2.1 and b is
Having the needed values, the sixth step is to solve for the required steel ratio ρ
0.85𝑓’𝑐 2𝑅𝑛
ρ= [1 − √1 − ]
𝑓𝑦 0.85𝑓′𝑐
The resulting value of ρ must be less than the maximum steel percentage, ρ max, which can
and must be greater than the maximum steel percentage, ρmin, which can be
1.4 √𝑓′𝑐
ρmin = or[ ]
𝑓𝑦 4𝑓𝑦
The seventh step is to determine the required steel area, As, using the equation,
As = ρbd
Having the required steel area, determine on the eight step the required spacing of
S = 𝐴𝑑 𝑏/𝐴𝑠
where Ad is the actual reinforcing bar area and b is the 1-meter strip. Spacing of
main bars (S) should not be greater than doubled slab thickness or 450 mm. For the
spacing of the reinforcement to be used, select the smallest value among S, 3h or 450
mm.
For the design of beams, determine first the design moments (Mu) of the critical
beam at end 1, at midspan and at end 2. Factor this moments using the load combinations
presented in Section 3.3 of NSCP 2015. Adapt the maximum design moment.
The second step is determining the effective depth (d) which can be acquired
1
d = h – cc - (Ø rebar) - (Ø stirrups) - (reinforcement bar spacing)
2
For the third step, determine if the section is singly or doubly reinforced. The type
Ø for beam is equal to 0.90. Mn(max) is the ultimate nominal moment than can be acquired
1 𝜌𝑚𝑎𝑥 𝑓𝑦
Mn(max) = ρmaxfybd2[1 − 𝑥 ]
1.7 𝑓′𝑐
where b is the width of the beam and ρmax can be computed using,
reinforced, determine the number of reinforcement by first calculating the design strength
Mu = ØRnbd2
0.85𝑓’𝑐 2𝑅𝑛
ρ= [1 − √1 − ]
𝑓𝑦 0.85𝑓′𝑐
The resulting value of ρ must be less than the maximum steel percentage, ρ max,
and must be greater than the maximum steel percentage, ρmin, which can be
1.4 √𝑓′𝑐
ρmin = or[ ]
𝑓𝑦 4𝑓𝑦
As = ρbd
Then, determine the required number of reinforcement (N). This can be calculated
𝐴
N = 𝐴𝑠
𝑑
moment of the beam due to the resistance of the compression concrete and the balancing
tensile reinforcing (Mn1) and (b) the resisting moment of the beam due to the nominal
moment capacity of the compression steel and the balancing amount of the additional
tensile steel (Mn2). Shown in Figure 15 is doubly reinforced beam broken into parts.
To calculate the resisting moments, determine first the value of As1 using the
equation,
As1 = ρmaxbd
Then, determine the resisting moment Mn1 by substituting the resulting As1 to the
equation,
𝑎 𝜌𝑓𝑦𝑑
Mn1 = As1fy[𝑑 − 2] wherein a = [0.85𝑓′𝑐]
The next step is to determine the resisting moment Mn2 by subtracting Mn1 to Mn
𝑀𝑢
which is equal to
∅
.Then, the area As2 is to be determined by the equation,
Ey < E’s
𝑓𝑦 0.003(𝑐−𝑑′ ) 𝑎
wherein Ey = 𝐸 and E’s = where c = ß
𝑠 𝑐
Determine the area of the compression steel (As’) and the area of the tension steel
𝑀 𝑛2 𝐸′𝑠
As’ = 𝑓′𝑠(𝑑−𝑑 ′ ) wherein f’s =
(fy)
𝐸𝑦
As = As1 + As2
Then, determine the required number of reinforcement (N). This can be calculated
The fifth step is to determine the stirrups spacing. Stirrups are required when
1
maximum factored shear (Vu) is greater than Ø𝑉𝑐 . The design shear strength of
2
Vc = 0.17λ√𝑓′𝑐𝑏d
To determine the stirrups spacing (S), calculate first the nominal shear strength of
𝑉𝑢 +Ø𝑉𝑐
Vs =
Ø
The resulting Vs is substituted to the equation,
𝐴𝑣 𝐹𝑦
S=
𝑉𝑠
structure from being subjected to becoming a soft-storey structure. The first step in the
design analysis is to determine the maximum axial load (Pu) from the dead loads, live
loads and seismic loads. Factor the load through the load combination presented in
The second step is to determine the required gross area (Ag) that can carry the
For the third step, determine the required number of reinforcement (N). This can
N = 𝐴𝑠 /𝐴𝑑
following:
a. 16 (rebar diameter)
designed enough to support the load coming from the column. For the design analysis of
column footing, the first step is to determine the allowable bearing capacity of the soil
The second step is to determine the nominal moment capacity (Mn) and the
𝑀𝑢
Mn = ∅
𝑃𝑢
Pn = ∅
where Ø = 0.90. While, Mu and Pu is the maximum factored moment and load.
For the third step, calculate the effective soil bearing capacity (qe) given by the
equation,
wherein γc is the concrete unit weight and γs is the soil unit weight. The unit
−𝑃𝑛 6𝑀𝑛
qe = -
𝑏2 𝑏3
The fifth step is determining the shear strength (Vu). This is determined by the
equation,
1
Vu = 2 (qu) (x) (B) - for wide beam shear
wherein bearing pressure for strength design (qu) is determined by dividing the
factored load (Pu) to the footing area (Afg) and load F is calculated by multiplying qu to
1 1
x = (footing dimension) - (column dimension)
2 2
Then, for the sixth step, compare the maximum shear strength (Vu) to the shear
Depth of footing is adequate for wide beam shear and punching shear if shear
strength of concrete (Vc) is greater than the maximum shear strength (Vu).
The seventh step is to determine required area of steel. First, determine the
Mu = ØRnbd2
0.85𝑓’𝑐 2𝑅𝑛
ρ= [1 − √1 − ]
𝑓𝑦 0.85𝑓′𝑐
The resulting value of ρ must be less than the maximum steel percentage, ρmax,
and must be greater than the maximum steel percentage, ρmin, which can be
1.4 √𝑓′𝑐
ρmin = or[ ]
𝑓𝑦 4𝑓𝑦
As = ρbd
N = 𝐴𝑠 /𝐴𝑑
where Ad is the actual reinforcing bar area.
order to find the dimension and height of the facility, the volume of recyclable and
To be able to find out the volume generated per day, the projected waste must be
determined first wherein the total capacity of the proposed project is multiplied by the
waste generation rates. The waste generation rates estimate the amount of waste created
Recovery Facility Toolkit (2013), the estimated per capita waste generation rates
observed in rural and urban areas in the Philippines are 0.3 kg/capita/day and
0.7kg/capita/day, respectively.
composition of the municipality to ascertain the mass generated for recyclable and
biodegradable wastes per day. This waste composition is influenced by factors such as
Lastly, volume will now be determined through the ratio of the mass generated
The elevated water tank is designed for the purpose of providing storage of water
for drinking and cleaning purposes as well as for fire suppression purposes.
For the design of the elevated water tank, the required volume capacity of the
tank (V) should be determine. This is computed by multiplying the total number of
consumers to the total water consumption daily. According to Batas Pambansa 220,
twenty percent (20%) of average daily demand and an additional 20% for fire