Download as pdf or txt
Download as pdf or txt
You are on page 1of 15

Heat Mass Transfer

DOI 10.1007/s00231-016-1838-x

ORIGINAL

Heat transfer augmentation in double pipe heat exchanger using


mechanical turbulators
Kushal Kamboj1 · Gurjeet Singh2 · Rohit Sharma1 · Dilbagh Panchal1 · Jaspreet Hira1 

Received: 20 August 2015 / Accepted: 13 May 2016


© Springer-Verlag Berlin Heidelberg 2016

Abstract  The work presented here focuses on heat transfer of circular cross-section 15, 10, and 5 cm at Reynolds’s
augmentation by means of divergent-convergent spring tur- number ranging between 9000 < Re < 40,000 is done
bulator (the enhancement device). Aim of the present work graphically.
is to find such an optimum pitch at which the augmenta-
tion in heat transfer is maximum and the amount of power List of symbols
consumption is minimum, so that an economic design can D Pipe diameter
be created with maximum thermal efficiency. So, the con- g Acceleration due to gravity
cept of pitch variation is introduced, which is defined as the h Heat transfer coefficient
horizontal distance between two consecutive turbulators. It hf Head loss
describes that, the lesser is the pitch the more number of K Thermal conductivity of fluid
turbulators that can be inserted in inner pipe of double pipe L Characteristics length of pipe
heat exchanger, hence more will be the friction factor. This ln Natural logarithm
physics increases convective ability of the heat transfer ṁ Mass flow rate of fluid
process from the surface of inner pipe. There is a certain Nu Local Nusselt number based on bulk tempera-
limit to which a pitch can be decreased, lesser the pitch the ture of the fluid
more the pressure drop and friction factor and hence the Nut Convective heat transfer coefficient of tube
more will be the pumping power requirement to maintain Nup  Convective heat transfer coefficient of plain
a desired mass flow rate of hot water. Analysis of thermal tube
factors such as Nusselts number, friction factor, with dif- p Pitch length/spacing
ferent pitches of divergent convergent spring turbulators P Static pressure
Pr Prandtl number
ΔP Pressure drop over length L of pipe
* Kushal Kamboj
r Pipe radius
kushhalkamboj@gmail.com
Re Reynolds number
Gurjeet Singh
Ts Surface temperature
gurjeetsingh0009@gmail.com
T∞ Bulk temperature
Rohit Sharma
T Temperature
r25sharma@gmail.com
Cp Specific heat capacity
Dilbagh Panchal
dilbagh129@gmail.com
Subscripts
Jaspreet Hira L Characteristic length of pipe
jhira@amity.edu
m Mean
1
Amity University Uttar Pradesh, Noida, India max Maximum
2
Mechanical Engineering Department, PEC University min Minimum
of Technology, Chandigarh 160012, India PT Plain tube

13
Heat Mass Transfer

t Turbulator the surface, of course, also increases the friction factor and
Theo Theoretical thus the power requirement for the pump or the fan.
Exp. Experimental Designing a heat exchanger, which suits majority of
o Outlet, outer applications, is very difficult as well as important, as it
i Inlet, inner always has the limitation of size and fluid flow rate, result-
a Air ing in a low heat transfer rate. The augmentation of heat
w Pipe wall transfer is the ability to achieve high performance heat
exchangers, leads to its size reduction and high initial
Greek symbols investment.
λ Darcy friction factor So, the passive heat enhancement techniques can be
η Thermal performance applied by installing the turbulence generators or turbula-
μ Fluid viscosity tors, e.g. the insertion of twisted stripes and tapes [2–13],
ν Kinematic viscosity the insertion of coil wire [14–16] and helical wire coil in
ρ Fluid density the heat exchangers. The results of those studies show that
Δ Net change in quantity although heat transfer efficiencies were improved, the fric-
τ Shear stress tion factor of pipes was considerably increased.
β Coefficient of thermal expansion In recent years, thousands of numerical and experimen-
tal studies have been performed on heat transfer enhance-
Abbreviations ment techniques of different configuration. Mainly heat
DCST-C Divergent convergent spring turbulator-circular transfer and frictional characteristics have been studied in
DPHE Double pipe heat exchanger detail with respect to different geometrical parameters in
LPH Liter per hour various ranges of Reynolds number. Further these studies
LPM Liter per minute have been cross-verified with researches already performed
RTD Resistance temperature detectors in this field.
It is investigated by studying various research papers
that there is a scope of design modification in heat transfer
1 Introduction enhancement device which can significantly affect the rate
of heat transfer and friction factor. As it is clear, twisted
A heat exchanger is a device that is used to transfer ther- tape gives better results which encourage new researchers
mal energy (enthalpy) between two or more fluids, between to further improve the design. So, in this research a new
a solid surface and a fluid, or between solid particulates concept inspired by the literature which is divergent con-
and a fluid, at different temperatures and in thermal con- vergent spring turbulators of circular cross section (DCST-
tact. In heat exchangers, there are usually no external heat C). The spring type design of DCST is influenced from
and work interactions. Typical applications involve heat- experiments performed by Kumbhar et al. [17] as heat
ing or cooling of a fluid stream of concern and evapora- transfer behavior in a tube with conical wire coil inserts.
tion or condensation of single or multi-component fluid The conical shape and divergent-convergent section is
streams. Temperature gradient is the factor facilitating influenced from experiments performed by Eiamsa-ard
the heat transfer including a certitude that heat exchange et al. [18] as enhancement of turbulent flow heat trans-
occurs in the direction of decreasing temperature. Heat fer in a tube by using nozzle turbulators. Sufficient pitch
transfer theory explains itself by three distinctive modes of (as zero pitch increased the friction factor and hence the
heat transmission; radiation, conduction and convection. In pumping power requirements) is provided in DCST which
Heat exchangers radiation phenomenon does take place, is analogous to experimental investigation of heat transfer
but its role is rather insignificant vis-à-vis conduction and and turbulent flow friction in a tube fitted with perforated
convection. conical-rings by Kongkaitpaiboo et al. [19].
Tubes with rough surfaces have much higher heat trans- So far no work is reported on the study of spring turbu-
fer coefficients than tubes with smooth surfaces. Therefore, lators of varying cross section, so it is a new design which
tube surfaces are often intentionally roughened, corrugated, is influenced by twisted tapes and wire coil inserts. This
or finned in order to enhance the convection heat transfer research work is focused upon overcoming the limitations
coefficient and thus the convection heat transfer rate. Heat imposed previouslySo, the DCST-C design advantage is
transfer in turbulent flow in a tube has been increased by as that it uses less material and also expected to have higher
much as 400 % by roughening the surface [1]. Roughening heat transfer rate at the cost of lesser pressure drop.

13
Heat Mass Transfer

Fig. 1  Block diagram of double pipe heat exchanger

2 Methodology and experimental set up 2.2 Assumptions

2.1 Objectives 1. Flow is assumed to be steady.


2. Flow is non-uniform.
The focus here is on the experimental, graphical analysis & 3. Flow is incompressible.
study of the effect of divergent-convergent springs having cir- 4. Isothermal conditions are maintained, though minor
cular cross-sections, on the following factors & parameters: heat losses are neglected.
5. Coefficient of thermal expansion on inner side and coef-
1. Heat gain and heat drop ficient of thermal contraction on outer side of inner pipe
2. Friction factor, negates each other, of concentric tube heat exchanger.
3. Nusselt number 6. Inner pipe’s inner surface is assumed to be smooth.
4. Convective heat transfer coefficient 7. Sieder-tate equation takes into account the change in
5. Overall heat transfer coefficient viscosity (µ and µs) due to temperature change between
6. Nusselt number versus reynolds number for verification the bulk fluid average temperature and the heat transfer
of Nusselt number of plain tube surface temperature, respectively. The viscosity factor
7. Ratio of friction factors of DCST and that of plain tube will change as the Nusselt number changes. Though
versus Reynolds number. viscosity factor varies very nearly to unity, hence is
8. Friction factor verification of plain tube. assumed to be constant.
9. Ratio of Nusselt number of DCST and that of plain tube
versus Reynolds number. 2.3 Experimental setup
10. Mass flow rate of hot water versus heat gain and heat
drop. The experimental set up used in the present work is shown
11. Thermal performance factor versus Reynolds number in Figs. 1 and 2 and is discussed as follows:

13
Heat Mass Transfer

Fig. 2  Photograph of double pipe heat exchanger

The setup includes a hot water tank consisting of four 2.4 Augmetation technique used in current work
heaters of capacity 2 KW each that can maintain a maxi-
mum constant temperature of 75 °C. The setup includes Aim of the work was to employ divergent-convergent
two motors of capacity 1 HP for hot water and 0.5 HP turbulators (DCST) of circular (DCST-C) cross-section
for cold water. This is so because hot water is required as shown in Fig. 3, inside of copper tube of double pipe
to supply higher LPHs than cold water at certain specific heat Exchanger. DCST-C s made of high carbon spring
stages. steel with 10 cm of free length and an external diameter of
Test section includes two pipes; Inner pipe (smooth) of 2.1 cm. It was only sufficiently large so that it could make
copper, 4 m length and its U-bend is of 0.232 m length, an interference fit with inner tube of DPHE. These were
and outer pipe is made up of G.I. which is insulated and mounted at regular intervals on two thin cylindrical rods
is approximately equal in length to that of inner pipe. with rod diameter equals to the minimum diameter or mid-
Two well calibrated rotameters of range 0–2000 and section of DCST-C. Three rods mounted with DCST-C are
0–1500 LPH are used for hot water and cold water respec- inserted in the inner tube prior to attaching U-bend section
tively. Two pressure gauges are used of range 0–5 kg/cm2 to outer tube as shown in Fig. 4a–c.
with ±0.01 error. Inner tube contained hot water flow with flow rate rang-
To measure inlet and outlet temperatures of hot water ing from 700 to 2000 LPH and outer tube contained cold
and cold water four pt-100 RTDs are used and to meas- water with flow rate varying between 500 and 1500 LPH.
ure outside wall temperature of inner copper tube four Rotameters were installed to measure the flow rate, and
chip sensors are used and all the experimental work taken was controlled by flow regulating valves. As described ear-
under insulated environment. Readings of temperature lier this work utilized passive technique for heat transfer
are noted down from multi-point digital temperature enhancement, which is primarily aimed to generate a swirl/
indicators. turbulent flow.

13
Heat Mass Transfer

Fig. 3  Conceptual design
of DCST with flow path of
turbulator

Fig.  4  a DCST mounted on rod with Pitch = 15 cm. b DCST mounted on rod with Pitch = 10 cm. c DCST mounted on rod with Pitch = 5 cm

A number of DCST-C were mounted on a brass rod of As it can be observed from Fig. 4a–c that lower the pitch
8 mm diameter and 200 cm of length, by brazing to elimi- results in more number of springs that can be mounted on
nate any undue movement of DCST-C, inserted in inner a single rod. The term “pitch” used throughout the paper
pipe of copper and flow was initiated. Three variations in refers to the distance between two consecutive DCST-C
pitch ratios were provided viz. 5, 10 and 15 cm as shown in when mounted on brass rod. The concept behind varying
Fig. 4a–c. The spring pitch was kept constant in all of the the pitch was that lower is the pitch the more are the DCST-
DCST-C. C that can be mounted on a single rod and more will be the

13
Heat Mass Transfer

Fig. 5  Validation of Nusselt 160.000


number for plain tube with
literature 140.000

120.000

100.000

Nu
80.000

60.000

40.000
NuExp.

20.000
NuDittus-Boelter
Equation
0.000
9000 14000 19000 24000 29000 34000 39000 44000
Re

obstruction they will cause to hot water when inserted in was obtained in 15 min. LPH of hot water was main-
inner copper pipe and more will be the friction factor pro- tained constant for six variations in LPH of cold water
duced leading to more fluid mixing, breaking of boundary and this procedure was obtained for a range of 500–
layer, swirl production and consequently higher will be the 1500 LPH of cold water and 700–2000 LPH range of
heat transfer. hot water. The cold water and hot water followed coun-
ter flow directions at their respective flow rates. When
2.5 Experimental procedure constant and stable values at temperature display panel
were obtained, then the inlet–outlet and inner wall tem-
2.5.1 Step 1: Rotameter and RTDs calibration peratures were measured. After obtaining the results
for plain tube the Nusselt number verification for plain
Two buckets of 25 L were used to collect water for 3 min tube is done by comparing with results obtained from
which flows through cold water and hot water side rotam- Eq. (14).
eter (shown in Tables 1, 2). Further, four RTDs were cali-
brated by dipping in water troughs one after another and 2.5.4 Step 4: Preparing dcst for inner tube insertion
observed readings were compared with the referenced set
by premeasured RTD value (shown in Table 3). DCST of length 18 cm were mounted and brazed on 2 m
brass rods at a pitch of 15, 10 and 5 cm after wards. A pair
2.5.2 Step 2: Standardization and verification for each pitch set was made as shown in Fig. 4a–c. The
U-bend of pipes were given a detachable flange coupling
Plain tube readings were obtained for pressure drop and joint due to which it became fairly convenient to insert
hence friction factor characteristics at normal temperature DCSTs in and out. The same procedure to initiate the
of water. The main motive behind this study was to insert experiment was followed as mentioned for plain tube. The
DCST of varying pitches in inner plain tube which could steady state was achieved within 20 min after insertion of
make its surface rough, and hence could alter its readings. DCSTs. Friction factor and pressure drop results were col-
After obtaining sufficient amount of readings, the collected lected and compared with plain tube results. Same proce-
data was compared with calculated theoretical value. dure was followed for all DCSTs with varying pitches.

2.5.3 Step 3: Initiating and executing plain tube 2.5.5 Step 5: Thermal performance results


experimetation and repeatability

After obtaining the readings as mentioned in step-II, The procedure was re-initiated for thermal performance
260 L of water was heated to 75 °C which took approxi- and repeatability check (shown in Tables 4, 5). For a con-
mately 1.5 h to reach this stage. Then the hot and cold stant pumping power equivalent Reynolds number was cal-
water motors were started at same LPH and steady flow culated and water was kept at 75 °C.

13
Heat Mass Transfer

Fig.  6  a Effect of pitch on HTE (a) 180.000


for DCST with plain tube, Pitch
P = 15, 10, 5 cm. b Effect of 160.000
pitch on HTE for DCST with
P = 5, 10 and 15 cm NuT/NuPT 140.000
versus Re
120.000

100.000

Nu
80.000

60.000
Nu Exp.
40.000
Nu Exp. p=5cm
20.000 Nu Exp. p=10cm
Nu Exp. p =15cm
0.000
9000 14000 19000 24000 29000 34000 39000 44000
Re

(b) 1.220
Nu5cm/NupT
1.200
Nu10cm/NupT

1.180 Nu15cm/NupT

1.160
NuT/NuPT

1.140

1.120

1.100

1.080

1.060

1.040
9000 14000 19000 24000 29000 34000 39000 44000
Re

2.5.6 Step 6: For heat transfer coefficient calculation parametric study of effects of Reynolds number varying from
9000 to 40,000. Aspiration behind the variation of pitch ratios
Hot water at 75 °C is allowed to pass through the inner was basically to enhance the friction factor which varies in an
pipe of heat exchanger at 1000 LPH (mh  = 0.2715 kg/s). inverse proportion with all these parameters. But, increasing
Cold water is now allowed to pass through the outer pipe friction factor i.e. decrease in pitch ratio or an increase in the
of heat exchanger in counter current direction at 1000 LPH number of turbulators employed, puts a direct impact on pres-
(mc = 0.2715 kg/s). The inlet and outlet temperatures for both sure drop and hence on the required pumping power. But, to
hot water and cold water (T1–T4) are recorded only after maintain higher levels of Reynolds number or high LPMs,
temperature of both the fluids attains a constant value. The a high and constant pumping power is desired. Hence, it is
procedure was repeated for different cold water flow rates. required to maintain optimum conditions such that a balance
can be created between pitch ratio, friction factor, pressure loss
2.6 Data reduction and hence pumping power. Equations which form the basis of
such experimental investigation can be summed as follows.
Heat exchangers with working fluid water was taken in Since Reynolds number represents the ratio of momen-
all of the experiments mentioned in previous section, with tum to viscous forces the relative magnitudes of Gr and Re

13
Heat Mass Transfer

Fig. 7  Verification of friction 40.000


factor for plain tube
35.000

30.000

25.000

20.000

λ
15.000

10.000
λDarcy-Weisbach Friction Factor*1000
5.000
λBlasius Equation*1000
0.000
5000 10000 15000 20000 25000
Re

are an indication of the relative importance of natural and inner tube. The average heat flux from the tube wall to the
forced convection in determining heat transfer. Forced con- fluid is defined in terms of surface area.
vection effects are usually insignificant when Gr/Re2 >> 1  
and conversely natural convection effects may be neglected Q = hA(Tw − Tb ) + σ A Tw4 − Tb4 (7)
when Gr/Re2 << 1. When the ratio is of the order of one,
combined effects of natural and forced convection have to The convective heat flux is assumed to be uniformly dis-
be taken into account. tributed over the heated wall tube and can be evaluated
Grashof number [21, 22] as
gβ(Ts − T∞ )D3 Q = hA(Tw − Tb ) (8)
GrD = (1)
ν2 The averaged heat transfer coefficient, h and the mean Nus-
The steady state of the heat transfer rate is assumed to be selts number, Nu are estimated as follows Cp,a
equal to the heat loss from the test section which can be
Cp,a (To − Ti )
expressed as h= (9)
A(Tw = Tb )
Qair = Qconv (2)
hD
where, Nu = (10)
k
Qair = ṁCp,a (T0 − Ti ) (3) 2.7 Standard equations
Qconv = hA(Tw − Tb ) (4) 2.7.1 Friction factor calculations
where,  ∆P 
∗D
Darcy − Weisbach Friction Factor :  = L 2 
 
To − T i ρV
Tb = (5) 2 (11)
2

 Tw 0.316
Tw = (6) Blasius Equation:  = (12)
N Re0.25
where, N—total number of thermocouples or resistance
0.046
temperature detectors between inlet and exit of the test sec- Colburn’s Equation:  = (13)
tion and evaluation is done at the outer wall surface of the Re0.2

13
Heat Mass Transfer

Fig.  8  a Friction factor com- (a) 70.000


parison of DCST and plain tube;
(λ vs. Re). b Friction factor
comparison of DCST and plain 60.000
tube; λP/λT versus Re

50.000

40.000

λ
30.000

20.000
λDarcy-Weisbach Fricon Factor*1000
λ5cm*1000
10.000
λ10cm*1000
λ15cm*1000
0.000
5000 10000 15000 20000 25000
Re

(b) 2.000

1.800

1.600

1.400

1.200
Nu

1.000

0.800

0.600
λpT/λ5cm
0.400
λpT/λ10cm
0.200
λpT/λ15cm
0.000
5000 10000 15000 20000 25000
Re

2.7.2 Heat transfer calculations readings obtained for plain tube tends to bend greater
towards deviations of more than 90 % for which the simul-
Dittus–Boelter Equation [20]: taneous action of natural and forced convection are held
accountable. It is worthy to note that natural convection
NuPT,Theo = 0.023 ∗ Re0.8 ∗ Pr0.4 ; for Re > 104 (14) phenomena is more pronounced and dominating at lower
Sieder-Tate Equation [21]: values of Reynolds number whereas forced convection
ruled the upper limits of Reynolds number.
µ 0.14
 
NuPT,Theo = 0.023 ∗ Re0.8 ∗ Pr0.4 ∗
µs
; for Re > 104 (15) 2.7.3 Thermal performance calculations
 0.14
µ
µs is known as viscosity correction factor and falls At constant pumping power
very close to 1, hence was taken unity for all calculations.    
When the ratio was measured for wide range of Reynolds  ∗ Re3 =  ∗ Re3
PT T (16)
number (especially at lower values), the experimental

13
Heat Mass Transfer


T
1
3 well within the agreement depicted by the graphical trends
RePT = ReEquivalent = ReT (17) formed by Eq. (14).
PT

NuT
 3.1.2 Dcst of different pitches
NuPT
η=  (18) When DCST with different pitches (P  = 5, 10 and 15)
0.333
T
PT were inserted in internal copper tube of double pipe
heat exchanger, it exhibited different trends when the
3 Results and discussion graph between the obtained experimental values of Nus-
selt number and Reynolds number was plotted, which
3.1 Heat transfer analysis is depicted in Fig. 6a, b. While analyzing the graph, it
is clear that the rate of heat transfer is significantly
3.1.1 Plain tube enhanced when the plain tube and tube with DCST-C
with various pitches are compared for a given fixed value
The first step before starting the experiments that had any of Reynolds number.
inclusions of varying pitch turbulators was to measure plain Hence, obstruction, or resistance to flow, caused by
tube readings keeping several parameters in mind to be cal- DCST-C is the phenomenon which is accountable for
culated. Nusselt number is one of such parameters which, such enhancement, which significantly increases with
sequentially is thought to be measured under an unvary- decreasing pitch. This obstruction intrigues the thermal
ing or constant condition of heat flux. Then compared the boundary layer destruction adjacent to the inner tube wall
obtained results for convective heat transfer coefficient and leading to swirl flow and local turbulent zones thereby
Nusselt number vis-à-vis the results that were obtained augmenting the heat transfer and heat transfer ratio with
from the fundamental equations given by Dittus–Boelter, as increase in Reynolds number. This, on the other side,
mentioned in Eq. (14). The main motive behind conduct- agitates the entirety of thermal boundary layer thereby
ing the plain tube experiments was the experimental vali- increasing the value of heat transfer coefficient.
dation of plain tube. From Fig. 5, it can be concluded that While contemplating the quantitative analysis the results
the results obtained from plain tube experiments, for heat concluded that the heat transfer rate of the tube having
transfer i.e., the trend followed by the graph representing DCST-C at different pitches is found within the range of 1.1–
the variation of Nusselt number with Reynolds number lies 1.6 times higher vis-à-vis the heat transfer rate for plain tube.

Fig. 9  Thermal performance 1.06


factor versus Reynolds number η, p=5 cm
1.04 η, p=10 cm

η, p=15 cm
1.02

0.98
η

0.96

0.94

0.92

0.9
9000 14000 19000 24000 29000 34000 39000
Re

13
Heat Mass Transfer

3.2 Friction factor analysis behind this phenomenon was that the less is the distance
between two consecutive DCST-C the more are the DCST-
3.2.1 Plain tube C that can be mounted on the cylindrical rod and hence
inserted in inner copper tube, consequently causing more
Friction Factor is the first parameter that is measured before obstruction to the hot water stream, and hence more is the
commencing any experiments related to DCST-C, i.e., turbulence induced resulting in larger pressure drop and
when the apparatus is freshly fabricated, so as to validate hence increase in friction factor.
and verify the plain inner copper tube for pressure drop
and friction factor by comparing to the standard data under 3.3 Thermal performance factor
optimal experimenting conditions. The obtained results
of friction factor were then compared vis-à-vis the results At this stage, experimentation involved DCST with vary-
obtained from the fundamental equations given by Blasius ing pitches, which includes an augmentation of heat trans-
and Colburn as mentioned in Eqs. (12) and (13). fer rate, though with a simultaneous increment in friction
From Fig. 7, it can be concluded that the results obtained factor with decrease in pitch. The criteria of decreas-
from plain tube experiments, for friction factor i.e., the ing pitches comes at a price, that is, every extra turbula-
trend followed by the graph representing the variation of tors inserted cause an extra resistance to flowing water
friction factor with Reynolds number lies well within i.e., and hence leading to an increment in friction factor. The
±10 to ±13 % agreement depicted by the graphical trends more is the obstruction caused the more will be the effort
formed by Eqs. (11) and (12). Darcy–Weisbach equation required by pump to sustain a constant mass flow rate and
was used for calculating experimental values of friction hence more will be the pumping power required which at
factor. a certain level proves to be uneconomical. Consequently,
a mutual agreement or an optimum state has to be con-
3.2.2 Dcst of different pitches cluded between the effectiveness of DCST in heat transfer
augmentation and the increase in friction factor it causes.
Experiments were performed under unvarying or constant This problem is to be judged from performance evaluation
conditions of heat flux for measuring the effect of inserting criteria.
DCST-C of different pitches viz. 5, 10 and 15 cm. To obtain As depicted in Fig. 9, when graph is plotted between
the friction factor and to plot the trend followed, calcula- thermal performance factor and Reynolds number that at
tions were made when friction factor varied with the vary- constant pumping power, with an increase in Reynolds num-
ing Reynolds number. The results hence obtained were com- ber there is a decrease in thermal performance factor. Also,
pared with that obtained while using plain inner copper tube. it can be seen that, for same pumping power DCST with
In Fig. 8a, b, the trend indicates an increment in fric- P = 15 cm proved to be most efficient, the reason being the
tion factor with a decrease in DCST-C pitches. The reason least friction offered by this pitch of DCST springs.

13
Heat Mass Transfer

3.4 Comparision of performance parameters


of different mechanical turbulators

S.No. Authors Configuration name Configuration design Reynolds no. Heat transfer Friction factor
range

1 Promvonge et al. [14] Twisted tape 2000–12,000 140 % < Nu < 228 % 200–386 %

2 Kumbhar and Sane [17] Conical wire coil inserts 2000–10,000 5 % < Nu < 12 % 40–66.7 %

3 Eiamsa-ard et al. [18] Nozzle Turbulators 8000–18,000 212 % < Nu < 300 % Pressure drop


increased
250–800 Pa/m

4 Kongkaitpaiboon et al. Perforated conical rings 4000–20,000 200 % < Nu < 350 % Increased by 6


[19] times

5 Present work Divergent convergent 5000–40,000 11.46 % < Nu < 26.76 % 20.79–66.87 %


spring turbulators

13
Heat Mass Transfer

In present work, Nusselt number (Nu) is increased by only and their effect, not sharply but gradually decreases
15.3 % at the expense of 66.21 % increase in friction factor with increment in Reynolds number.
for Reynolds no. range (5000–40,000), whereas maximum (b) The Nusselt number is found to be enhanced by 11.46,
increase in Nusselt number is claimed by Kongkaitpaiboon 17.88 and 26.76 % with DCST-C pitches P  = 15, 10
et al. [19]. which is 150 % but at the expense of 6 times and 5 cm, vis-à-vis plain tube.
increase in friction factor for Reynolds no. range (4000– (c) Friction factor and pressure drop characteristics were
20,000) and it is well known that by increasing the Reyn- also studied and evaluated. It reveals that, with an
olds number friction factor increases and hence, increase increment in DCST-C pitch, friction factor and pres-
the required pumping power which makes the process sure drop increases. DCST-C offers a maximum of
uneconomical. 20.79, 48.59 and 66.87 % friction factor with 15, 10
So, in present work a wide range of Reynolds number and 5 cm respectively, vis-à-vis friction factor gener-
is used and at higher Reynolds number increase in friction ated by plain tube.
factor is in well acceptable range which is much lower as (d) Thermal performance factor offered by DCST-C with
compared with the previous studies. varying pitches is also studied and it is found that the
DCST-C with high pitch generates least amount of
friction factor vis-à-vis DCST-C with P = 10 cm and
4 Conclusion P  = 15 cm, which leads to a maximum thermal per-
formance factor of 1.0525. Thermal performance fac-
The objectives mentioned are successfully performed in the tor for P  = 15 cm was 6 % more than DCST with
range of cold water varying from 500 to 1500 LPH and hot P = 10 cm and 8 % more than DCST-C with P = 5 cm
water ranging from 500 to 2000 LPH, thereby obtaining a and that too at same pumping power.
wide range of Reynolds number from as low as 9000 to as
high as 40,000. The effects of DCST-C with varying pitch The experiment for augmentation of heat transfer is suc-
ratios when inserted in inner plain tube of double pipe heat cessfully performed with DCST-C arrangement in dou-
exchanger are studied including their role in heat transfer ble pipe heat exchanger and heat transfer (Nusselt no) is
augmentation. The most significant conclusions that are enhanced by 26.76 %, Friction factor is increased maxi-
drawn after performing this experiment are as: mum of 66.87 % for DCST-C pitch 5 cm vis-à-vis plain
tube. However, thermal performance factor gives maximum
(a) Keeping the experimentation conditions approximately value 1.0525 for DCST-C pitch 15 cm.
identical, Heat transfer augmentation, is best provided
by using DCST-C with P = 5 cm. It depicts an inverse
Compliance with ethical standards 
trend where Nusselt number ratio (thermal efficiency)
decreases with increase in Reynolds number. It can be Conflict of interest  The authors declare no conflict of interest.
comprehended as the relative effect of plain tube and
tubes with DCST-C installed, on heat transfer augmen-
tation. Hence, it can be concluded that DCST-C (best Appendix
results given by DCST-C with P  = 5 cm) performs
great at relatively lower values of Reynolds number See Tables 1, 2, 3, 4 and 5.

Table 1  .
For large rotameter
LPH m (kg/s) T (s) Observation I (kg) m1 (kg/s) Observation II (kg) m2 (kg/s) Observation III (kg) m3 (kg/s) Mavg % Error

800 0.22666 180 39.9 0.22166 40.3 0.22388 40.1 0.22277 0.22277 1.71568
900 0.255 180 44.8 0.24888 44.7 0.24833 44.9 0.24888 0.24888 2.39651
1000 0.28333 180 49.6 0.27555 49.9 0.27722 49.8 0.27648 0.27648 2.4183
1100 0.31166 180 54.5 0.30277 54.7 0.30388 54.7 0.30351 0.30351 2.61437
1200 0.34 180 60.1 0.33388 59.8 0.33222 59.7 0.33259 0.33259 2.19864

13
Heat Mass Transfer

Table 2  .
For small rotameter
LPH m T Observation I (kg) m1 (kg/s) Observation II (kg) m2 (kg/s) Observation III (kg) m3 (kg/s) Mavg % Error
(kg/s) (s)

300 0.08333 180 14.9 0.08277 14.6 0.08111 14.75 0.08194 0.08194 1.66273
400 0.11333 180 20.1 0.11166 20.1 0.11166 20.2 0.11222 0.11185 1.30719
500 0.14166 180 25.2 0.14 25.1 0.13944 25 0.13888 0.13944 1.56862
600 0.17 180 30.3 0.16833 30.1 0.16722 30 0.16666 0.1674 1.52505
700 0.19833 180 35.1 0.195 35 0.19444 35.1 0.195 0.19481 1.77404

Table 3  . RTD calibration


T1 T4 T5 T8

Obs. I 34.1 34.1 35 34.1


Obs. II 35.1 33.9 34 33.9
Obs. III 34.1 35.1 34.1 35.1
Obs. IV 34.1 34.9 33.9 33.9
Obs. V 35.1 35.1 35.1 33.9
Obs .VI 34.1 34.1 33.9 35.1
Obs. VII 33.9 34 34.1 34.1
Obs. VIII 34 33.9 34 34
Calibration ±1 ±1 ±1 ±1

Table 4  . Experimental data for repeatability


Heat transfer versus Re for DCST having pitch 15 cm
mcw, mhw T1 T2 T3 T4 Rehw Trial 1 Trial 2 %diff
Nu Exp Nu Exp

0.113 35.9 57 75.8 57.1 9712.452 59.067 63.044 −6.732


0.141 35.8 56.2 75.8 57.9 12043.41 73.314 74.622 −1.783
0.17 35.8 55.8 75.9 58.6 14457.88 88.222 87.217 1.138
0.198 35.9 55.7 75.9 59.6 17115.7 97.27 98.551 −1.317

Table 5  . Experimental data for repeatability


Heat transfer versus Re for DCST having pitch 10 cm
mcw, mhw T1 T2 T3 T4 Rehw Trial 1 Trial 2 %diff
Nu Exp Nu Exp

0.113 36.2 58.1 76.3 57.1 9643.4 62.77 64.32 −2.482


0.141 36.2 57.7 76.2 57.6 12043.41 77.715 78.9 −1.534
0.17 36.3 56.9 76.2 58.6 14457.88 92.489 91.31 1.269
0.198 36.3 56.7 76.1 59.6 17115.7 103.88 107.66 −3.642

13
Heat Mass Transfer

References 12. Watanable K, Taira T, Mori Y (1983) Heat transfer augmentation


in turbulent flow by twisted tapes at high temperatures and opti-
mum performance. Heat Transf Japn Res 12:1–31
1. Yakut K, Sahin B (2004) Flow-induced vibration analysis of con-
13. Zozulya NV, Shkuratov IY (1974) Effect of length of twisted
ical rings used of heat transfer enhancement in heat exchanger.
tape turbulence promoter and its initial twisting pitch on aug-
Appl Energy 78:273–288
mentation of heat transfer inside a tube. Heat Transf Sov Res
2. Date AW (1974) Prediction of fully developed flow in a tube
6:98–100
containing a twisted tape. Int J Heat Mass Transf 17:845–859
14. Promvonge P (2008) Heat transfer behaviors in round tube with
3. Date AW, Saha SK (1990) Numerical prediction of laminar flow
conical ring inserts. Energy Convers Manag 49:8–15
and heat transfer in a tube fitted with regularly spaced twisted-
15. Rahai H, Shojaeefard MH (2001) Mixing enhancement using a
tape elements. Int J Heat Fluid Flow 11:346–354
coil insert. Appl Therm Eng 21:303–309
4. Duplessis JP, Kroeger DG (1983) Numerical prediction of lami-
16. Arici ME, Asan H (1994) Enhancement of turbulent flow heat
nar flow with heat transfer in tube with a twisted tape insert. In:
transfer in tubes by means of wire coil inserts. ASME PD Adv
Proceedings of the international conference on numerical meth-
Heat Transf 64:113–117
ods in laminar and turbulent flow, 775–785
17. Kumbhar DG, Sane NK (2000) Heat transfer behavior in a tube
5. Manglik RM, Bergles AE (1992) Heat transfer enhancement and
with conical wire coil inserts. The 3rd international conference
pressure drop in viscous liquid flows in isothermal tubes with
on advances in mechanical engineering, NIT, Surat, Gujarat,
twisted-tape inserts. Int J Heat Mass Transf 27(4):249–257
India
6. Manglik RM, Bergles AE (1992) Heat transfer and pressure drop
18. Eiamsa-ard S, Somravysin P, Sripattanapipat S, Pethkool S,

correlations for twisted-tape inserts in isothermal tubes: Part II-
Promvonge P (2005) Enhancement of turbulent flow heat trans-
transition and turbulent flows, enhanced heat transfer. ASME
fer in a tube by using nozzle turbulators. The 19th conference of
HTD 202:99–106
mechanical engineering network of Thailand, Phuket, Thailand
7. Sarada SN, Raju ASR, Radha KK, Sunder LS (2010) Enhance-
19. Kongkaitpaiboon V, Nanan K, Eiamsa-ard S (2010) Experimen-
ment of heat transfer using varying width twisted tape inserts. Int
tal investigation of heat transfer and turbulent flow friction in
J Eng Sci Technol 2(6):107–111
a tube fitted with perforated conical–rings. Int Commun Heat
8. Patil AG (2000) Laminar flow heat transfer and pressure drop
Mass Transf 37:560–567
characteristics of power-law inside tubes with varying width
20. Dittus FW, Boelter LMK (1930) University of California Publi-
twisted tape inserts. ASME Trans 122:143–149
cations on Engineering 2, p 433
9. Saha SK, Dutta A (2001) Thermo-hydraulic study of laminar
21. Incropera Frank P, DeWitt David P (2000) Fundamentals of heat
swirl flow through a circular tube fitted with twisted tapes. Trans
and mass transfer, 4th edn. Wiley, New York, p 493
ASME J Heat Transf 123:417–421
22. Incropera FP, DeWitt DP, Bergman TL, Lavine AS (2007) Fun-
10. Saha SK, Gaitonde UN, Date AW (1990) Heat transfer and pres-
damentals of heat and mass transfer, 6th edn. Wiley, Hoboken,
sure drop characteristics of turbulent flow in circular tube fitted
NJ
with regularly spaced twisted tape elements. Exp Therm Fluid
Sci 3:632–640
11. Sharma PK, Subramanyam T, Kishore PS, Rao Dharma, Kakac S
(2003) Laminar convective heat transfer with twisted tape inserts
in a tube. Int J Therm Sci 42:821–828

13

You might also like