Microcontrolador AKC - 72
Microcontrolador AKC - 72
AKC 72A
Applications include:
• Cold rooms
• Freezing rooms
• Delicatessen appliances
• Refrigeration display cabinets
• Freezing and refrigeration islands
Ordering
Type Description Code no.
AKC 72A Without data communication English, German and French texts 084B1202
English and Hebrew texts 084B1204
Danish, Swedish and Finnish texts 084B1206
Spanish, Italian and Portuguese texts 084B1208
English, Dutch and Polish texts 084B1210
Base For wall mounting 084B1241
For front panel and DIN rail 084B1240
AKV 10
AKV 15 Expansion valve + coils
AKV 20 See data sheet RD.8A.B1.02
AKS 32R Pressure transmitter -1 to 12 bar 1/4 in. flare 060G1036
1/4 in. NPT 060G1037
G3/8 in. 060G1038
Connection plug for AKS 32R with 3.5 m cable 060G1034
AKS 11 Temperature sensor With 3,5 m 12 pcs 084N0003
Pt 1000 ohm cable
With 5,5 m 12 pcs 084N0005
cable
With 8,5 m 12 pcs 084N0008
cable
Configuration
Parameter Description Min. Max Factory
setting
Thermostat
Cutout temp. Thermostat cutout temperature in °C -50 +50 3
Differences Thermostat differential 0,5 10 2
TempSetLimit max Limitation of thermostat upper cut-out temperature -50 +50 50
TempSetLimit min Limitation of thermostat lower cut-out temperature -50 +50 -50
Thermostat mode Thermostat operating mode 1 2 1
1: On/off thermostat. 2: Modulating thermostat
Air on % Weighting of thermostat sensor 0 100 0
Night offset Night setback value in K -25 +25 0
Alarm thermostat
High alarm limit Upper alarm limit in °C -40 +60 10
Pulldown delay Alarm delay after start-up or defrost (in minutes) 0 240 120
High alarm delay Alarm delay on normal regulation (in minutes) 0 120 30
Low alarm limit Lower alarm limit in °C -60 +40 -3
Low alarm delay Alarm delay on too low a temperature (in minutes) 0 120 30
Injection functions
Refrigeration type System refrigerant 0 23 0
Superheat max. K Max. value for superheat (normally not changed) 3 15 12
Superheat min. K Min. value for superheat (normally not changed) 3 10 3
MOP control Selection of MOP function OFF ON OFF
MOP temperature Setting of MOP temperature in °C -50 20 0
Valve selection Installed valve 1: AKV10. 2: AKV15. 3:AKV20. 4:TEV 1 4 1
Defrost functions
Demand defrost Activation of defrost on demand OFF ON OFF
Fan operation Select whether fan to operate during defrost OFF ON OFF
Temp/time stop Selection of how defrost stop is to be made 1 2 1
1: stop on Sdef temperature 2: stop on time
Max. defrost time Setting of defrost time (at stop on temperature, this time is a max. time) 5 180 45
Stop temperature Defrost stop temperature on Sdef 0 60 8
Drain down time Delay after defrost (valve closed during this time) 0 60 5
FanStart Temp / time Selection of fan start method 1 2 1
1: Start on Sdef temperature. 2: Start on time
Max. fan delay Setting of fan time delay (at start on temperature this time is a max. time) 0 60 10
Fan start temp. Fan start temperature (measured on Sdef) -15 0 -3
Configuration
Language Selection of language 0: English 1: German 2: French 0 2 0
Fan pulse period How often does the fan have to carry out an ON/OFF sequence? 6 180 10
Fan on period% How long does the fan have to run during this ON/OFF period? 0 100 100
Fan stop on Sdef Selection of fan stop function (see also next line) OFF ON OFF
Fan stop temp. The fan stops when Sdef registers this temperature during normal operation. (It is -20 +10 -10
overridden by the defrost function)
Air on correction Correction value for sensor “Air on” (set in 1/10 K) -10 +10 0
Air off correction Correction value for sensor “Air off” (set in 1/10 K) -10 +10 0
S2 correction Correction of sensor “S2” (set in 1/10 K) -10 +10 0
Sdef correction Correction value for sensor “Sdef” (set in 1/10 K) -10 +10 0
Fan when DI open Select whether fan to run or stop on DI switch cut out OFF ON ON
DI alarm delay Time delay for a “DI-alarm” 0 180 0
(set in minutes. With setting 0 minutes, there is no alarm)
Main frequency Set main frequency to either 50 or 60 Hz 50 60 50
DO output config. Select use of output DO 1 2 1
1: Compressor. 2: Light control
DANBUSS address Setting of controller address, if applicable 0 124 0
Log interval Set log interval in minutes 15 240 15
Log temperature Select temperature to be logged 1 3 3
1: Air on. 2: Air off 3: Therm. air (weighted value)
ID code Setting of protection code for service menu and manual operation, if applicable 0 255 0
Operation
The graphic display tells Display the historical Manual defrost read-off and
clearly all about the Change the system cutin sequence of a selected setting of defrost program
controller’s settings and the and cutout temperatures. temperature. for a week.
system’s operating
condition
Display
Example
A drawing, e.g. a
Display heading refrigeration appliance
(in this example, a
cold room)
The button and
symbol here belong
Information line
together
Depending on the
picture shown, you
will see a status of a
function or scale with
max. and min. values
Menu survey
This illustration gives an example of how components can be placed for cold room
control.
Dimensions