DEHUMIDIFIER

INSTALLATION AND OPERATING INSTRUCTIONS

MODELS : DS-045
DS-060
DS-080

Please read this instruction manual before using the heat pump
CONTENTS
Safety Instruction 3
Attention during Usage 4-5
Principle of dehumiditifier 6

Specification 6
Descriptions of Parts 7

Panel Controll 8

Exploded Views 9

I nstallation note 10

Remote Controller 11-12


Operation Guide 13
AUTO Operation Mode 14
Air Direction Adjustment 15
Timer Operations 16
Defrost system 17

Assistant heater 17

Water drainage system 17


Error codes 18
Wiring diagram 18

Maintenance 19-21
Trouble Shooting 22

2
Safety Instruction

Please read the following Safety Instructions carefully prior to use.

The instructions are classified into two levels, WARNING and CAUTION according to
the seriousness of possible risks and damages as follows. Compliance to the
instructions are strictly required for safety use.

Installation

WARNING
Please call Sales/Service Shop for the Installation.
Do not attempt to install the air conditioner by yourself because improper works
may cause electric shock, fire, water leakage.

lnstallation in a inadequate place may cause accidents. Do not install in the following place.

CAUTION
Connect the earth Do not install in the Do not get the unit
cable. place where there is exposed to vapor
any possibility of or oil steam.
inflammable gas
leakage around the
unit.

earthing

PROHIBITION PROHIBITION

WARNING
When abnormality such as burnt-small found, Use an exclusive power source with a
immediately stop the operation button and circuit breaker
contact sales shop.

OFF STRICT
ENFORCEMENT

3
Attention during Usage
WARNING
Ensure the power plug is secure Never pull out the power plug Never use damaged electric
If the plug is not secure, it may during operation. wires or unspecified electric
cause a electric shock, over-heat- otherwise, it may cause a elec- wires.
ing or a fire. tric shock or a fire due to over - otherwise it may cause a elec-
heating. tric shock or a fire.

Do not use the same socket Do not operate when the hands Do not insert a rod or other ob-
with other electric appliances or are wet. jects into the inlet or outlet
use an extension cord. due to danger of a electric shock. vents.
otherwise it may cause a elec- otherwise, it may cause a elec-
tric shock or a fire due to over- tric shock or a fire.
heating.

Do not expose yourself to a In case of abnormal condition Do not attempt to carry out a
single directional airflow for a (burning smell etc.),pull out the repair.
long period to avoid harming to power plug to stop the dehu- Improper repairs may cause a
your health. midifier from running, or dis- electric shock or a fire. You should
connect the power supply by contact the dealer of service cen-
means of a electric current tre to arrange for a repair.
protector.
If the abnormal condition persists,
it may cause a electric shock or a
fire due to over-heating. Please
consult the dealer of service cen-
tre as soon as possible to
arrange for a repair.

OFF

4
Attention during Usage

Do not hold the electric wire to If the air-conditioner is not in Switch off the power supply
pull out the power plug. use for a long time, it is neces- while cleaning the de-
Pulling of the electric wire may sary to pull out the power plug. humidifier.
cause over-heating of the electric Excessive dust on the power plug Please take care not to damage
wire of a fire. may also cause over-heating or the internal fan which is rotating
a fire. at a high speed.

OFF

PROHIBITION

Do not use the dehumidifier Do not place a heater in front of Do not pour water onto the
for other purposes. the dehumidifier. dehumidifier for cleaning.
Do not use it for keeping precision If internal combustion of the heater Due to danger of electric shocks.
instruments, food, plants and ar- is not complete, it may give out
tistic items. This may affect the poisonous carbon monoxide.
quality of the food.

PROHIBITION PROHIBITION PROHIBITION

5
Principle of dehumidifier

CONDENSER EVAPORATOR
COMPRESSOR

WARM
DRY COLD COLD AMBIENT
AIR DRY DRY AIR
OUTLET AIR AIR INLET

FAN

CONDENSE WATER

CAPILLARY WATER TANK


WATER
DRAIN
OUT
WATER PUMP

The dehumidifier use the refrigeration circuit to change the damp air warm dry air.
When the damp air passes the condenser, the air water will be condensed and the air
will become dry.
The Specification Of Dehumidifier (R410a)
Model DS-045 DS-060 DS-080
Capacity(L/hr) 4.5 6 8
Heating capacity(W) 2300 3200 4300
Power consumption(W) 1300 1650 2300
Air flow(m3/hr) 850 850 1150
Refrigerant(g) 1350 1750 2030
Power supply 230V/50Hz/1Ph 230V/50Hz/1Ph 230V/50Hz/1Ph
Current(A) 5.8 7.0 10.5
Aux electric heater(W)(option) 2000 2000 2000
Compressor type Rotary Rotary Rotary
Compressor(brand name) Daikin or sanyo Daikin or sanyo Daikin or sanyo
Water pump Yes Yes Yes
Applicable area(㎡) 100-150 150-200 200-250
Noise(dB(A)) 47 48 53
Drain pipe(mm) 500 500 500
Packing dimension(mm)(WxHxD) 535x1790x470 535x1790x470 535x1790x520
Unit dimension(mm)(WxHxD) 485x1725x320 485x1725x320 485x1725x370
Weight(net/gross)(kg) 72/82 77/87 84/94
Test condition: Dry ball temperature 30℃. Relative humidity of 80RH%.

6
Descriptions of Parts
1 Air Outlet
2 Control Panel
1
3 Air filter(inside)
4 Air Inlet
5 Humidity sensor
ON/OFF MODE

2
“ ” UP FAN

“ ” L-R
DOWN SWING

HEATER TIMER

U-D
SWING

6 Indoor temperature sensor


7 Water drainage system
8 Four way valve
9 Compressor
 Electrical control Box
10

9 8

7 5
6

7
Exploded Views
9

10

8
11
7
6
5 12

33
4

15
13
16

1 35 14
36
24
22
17
21
23
20 18

19
25
31 26 37
2 27
28 38
3 34 32 30 29

19 Plastic-base 38 Power Cord


18 Water pan 2 37 Defrost temperature sensor
17 Water pan 1 36 Humidity sensor
16 Evaporator 35 Filling gas valve
15 Plastic foam air duct 34 Stepper motor
14 Fan motor fixer 33 Flow detector
13 Fan motor 32 Electrical Box
12 Cover 31 Transformer
11 Cross flow fan 30 Circuit Board
10 Right panel 29 Motor Capacitor
9 Auxiliary electric heater 28 Public Terminal
8 Upper fixing board 27 Compressor Capacitor
7 Condenser 26 Terminal
6 Top cover 25 Truckle
5 Left panel 24 Drain pipe
4 Back board 23 Auto water drainage system
3 Control panel 22 Four Way Valve /Copper Pipe
2 Front Panel 2 21 Compressor
1 Front Panel 1 20 Chassis

8
Installation note
To ensure dehumidifier is steady during running, it prepared top dead plate and
root support foot, the installation and use as following fig. 1 and 2.

fig. 1

Please note that root support foot can draw out or draw back, it is convenient for
user moving dehumidifier to other place by root wheel.

fig. 2

Function of the needle valve


When the heat pump need to measure the pressure of the current system or to
filling refrigerant, the operator can use this low-pressure needle and make the
appropriate maintenance work!

needle valve

9
Panel Control

Button
Press the button to start operation,
ON / OFF press the button again to stop operation.
Display
Mode is selected in a sequence:
MODE Automatic ; Dehumidifying ; Fan ;
Heating.
ON/OFF MODE Select the fan speed. Each time press the
FAN SPEED button; fan speed is selected in a sequence:
LOW , MID , HIGH.
“ ” UP FAN

+/
_ One press of the “ + “ button to raise
the temperature by 1 oC; One press of
the “ - ” button to lower the temperature
“ ” L-R
DOWN SWING by 1 oC.

Set the swing or stop of Left-Right Airflow


SWING
vane.
HEATER TIMER

Set the swing or stop of Up-Down Airflow


U-D
SWING vane.
SWING

Press once to switch on assistant heater;


HEATER Press again to switch off assistant heater.

Buttons
Press the "L-R Swing" and "U-D Swing"
TIMER
together to enter timer setting

Display
4 2
3
1

6
5

10 8

9 7

1 A Auto operation mode 6 Displays when turns to CLOCK status


2 Fan operation mode 7 C Displays when turns to TEMPERATURE status
3 Heating operation mode 8 % Displays when turns to HUMIDITY status
4 Dehumidifying operation mode 9 CLOCK or TEMPERATURE or HUMIDITY display
5 Assistant heater display
10
Remote Controller

Signal Emitter :
Sending out remote control signal
to the air-conditioner Temperature Adjustment Button :
Adjust temperature settings
Press once to set temperature 1
degree higher.
Remote Controller Display Panel : Press once to set temperature 1
Display settings degree lower.

DRY
TEMP
On/Off Button :
Mode Button : Press once to start Air-conditioner
O
Select Automatic, Heating, C running; Press again to stop
De-humidifying, Fan modes running.

AUTO FAN

SW ING
ON / OFF Timer Off Button :
FAN Button :
Set Timer-off hour.
Air flow setting

MODE OFF ON
Timer On Button : Set Timer-on
hour.
Timer Cancel Button : TIM ER
Cancel Timer-On and Timer-Off FAN
settings
CANCEL CONFIRM Timer Confirm Button :
Send Timer-on or Timer-off data to
the air-conditioner
SWIN G HEATER

Manual Assistant Heater Button :


Air Direction Button :
Press once to switch on assistant
Set air louver swinging or stationary
heater; Press again to switch off
assistant heater.( option )

11
Remote Controller

Emission Indicator :
This symbol flashes once when the
Remote Controller emits signals to
the Dehumidifier.
Mode Display :
Press "Mode" button to display the
DRY current working mode. Automatic,
Temperature Display : Heating, Dehumidifying, Fan modes
It displays the current set tempera-
ture which may be adjusted by Tem-
perature Adjustment Button or
o
within the range of 18 ~30 C. In Au-
tomatic Mode, temperature is not dis- O
played but " Standard " (standard)
temperature + 2oC) or " Standard "
C Timer Display :
(standard temperature -2 C) is
o HR
It displays the time setting for Timer-
displayed.
On or Timer-Off in the range of 1~12
hours.
AUTO FAN
FAN Display :
It displays the current amount of air
flow. SWING
FAN Display on
Remote Controller
Air Direction Display :
When "Swing" is in display, the up-
Automatic AUTO FAN
down louver of the air-conditioner is
swinging. When the display
Low FAN disappears, the up-down louver
stops swinging.
Mid FAN

High FAN

NOTE:
All Displays on the diagram are listed out for demonstration. During operation, only the
relevant Display will appear on the Remote Controller.

12
Operation Guide

Proper settings of Heating, Dehumidifying and Fan modes


Mode Selection ( 1 )

Press "Mode" button to select the required working mode, which is


changed in the following sequence when pressed once:

Automatic Dehumidifying Fan Heating


DRY
TEMP

NOTE:
Heating mode is available only on cooling-heating type air conditioner.
O
C 3
Automatic operation will be explained in detail on next page.
AUTO FAN

Air Flow Selection ( 2 ) SWING


ON / OFF
4
Press "FAN" button to select the required amount of air flow,
which is changed in the following sequence when pressed once : MODE OFF ON

Automatic Low Mid High 1 TIMER


FAN

NOTE: 2 CANCEL CONFIRM


When Automatic FAN is selected, the air-conditioner will automatically select the suit-
able amount of air flow according to room temperature.
When Dehumidifying is selected, the amount of air flow is set by the machine and fan SWING SLEEP HEATER
setting is not functional.

Temperature Setting Selection ( 3 )

Press "Temperature Adjustment Button " to set temperature 1


degree higher.
Press "Temperature Adjustment Button " to set temperature 1
degree lower.
Hold down the Button to increase of decrease the temperature
settings progressively.

NOTE:
Range of adjustable temperature settings : 18oC ~ 31oC.

Starting Operation ( 4 )

Press "On/Off" button, and when the unit receives the signal, it gives
out two "beep" tones, the operation light is on and the dehumidi-
fier starts operation.

NOTE:
If it is desired to run the machine at the same settings for mode, air flow and temperature
as the last operation, skip Steps 1~3 and start the machine directly.
If the interval is shorter than 3 minutes from last shut down to the present switch-on, the
compressor only re-starts after 3 minutes to protect the system.
After switching on and if the mode is changed, the system may delay for 3 minutes before
starting operation.
When heating mode is selected, the internal fan will delay operation for a while when the
machine is switched on to prevent cool air circulation at the beginning.
After switching on, air flow amount and temperature may be separately adjusted as desired.

13
AUTO Operation Mode
Automatic operation Mode
Mode Selection (1)
Press "Mode" button to select Automatic Operation mode.
To set the temperature (heating) by button '+' and '- ', 5 seconds later
will be confirm; then to set the dehumidify by button '+' and '- ', 5 AUTO

seconds later will be confirm. TEMP

Fan Selection (2)

Press "FAN" button to select the required amount of air flow, AUTO FAN
which is changed in the following sequence when pressed once :
SWING
ON / OFF
3
Automatic Low Mid High

MODE OFF ON

NOTE:
When Automatic FAN is selected, the unit will automatically select the suitable amount of
1 TIMER
FAN
air flow according to room temperature.

Starting Operation (3)


2 CANCEL CONFIRM

Press " On/Off " button, and when the unit receives the signal, it SWING HEATER
gives out two " beep " tones, the operation light is on and the de-
humidifier starts operation is automatic mode.

NOTE:
In automatic mode, user can select the room temperature and humidity
separately:

Heating 18~31°C adjustable Factory setting is 25 °C

Dehumidify 1%~99% adjustable Factory setting is 60%

Adjustment in Automatic Mode

Feeling Button Operation

Press once to change the air flow pro-


Unsuitable fan speed
FAN gressively until the suitable air flow is
selected.

14
Air Direction Adjustment

Up-Down Air Direction Adjustment


ON/OFF MODE

“ ” UP FAN

“ ” L-R
DOWN SWING

HEATER TIMER

U-D
SWING

Airflow horizontally Airflow upward Airflow downward


NOTE:

To stop the up-down air louver in a desired position, set the louver to automatic swinging and
when it reaches the desired position, stop the louver from swinging. It is necessary to adjust
the louver angle by means of the remote controller, Setting of the louver with the hand may
affect its normal operation, in which event, switch off the unit temporarily and re-start operation.
To get the best effect, the up-down air flow is usually set in the following manner :
Dehumidifying - Horizontal air direction or upward air direction. Heating -
Downward air direction.

Changing Left-Right Air Direction

ON/OFF MODE

COOL
TEMP
“ ” UP FAN
O
C

“ ” L-R
DOWN SWING AUTO FAN

SWING
ON / OFF

HEATER TIMER OR

MODE OFF ON
U-D
SWING

FAN TIMER

CANCEL CONFIRM

SWING SLEEP HEATER

NOTE:
Don’t move the Left-Right vane directly.
15
Timer Operations

Timer Switch On
1. Press "Timer On" button to set time for timer-on switching. Press
the button once to change the time interval of 1 hour in a cyclic
manner of 6, 7, 8 ...12 ..1, 2..5, 6 (The display is showing the
previous time as the starting time of the present setting)
If the button is held down, the time interval will increase progres- DRY
sively by 1 hour unit. TEMP

2. Point the remote controller towards the receiver on the unit, press
O
C
HR AFT
"Timer Confirm" button to send the timer setting to the de- ON
humidifier. Then the timer light on the unit lights up, indicating AUTO FAN
that the unit is in the timer mode. When it reaches the switch-on
SWING
time, the dehumidifier will operate in the pre-set modes. ON / OFF

NOTE:
MODE OFF ON
Before timer operation, please set the operation mode, temperature, air flow etc. on the
remote controller, With timer being set to switch-on mode. the Dehumidifier will operate
according to the last setting.
TIMER
1
Usually, timer-on setting is made while the dehumidifier is not in operation. If timer-on is FAN
set while the dehumidifier is running, then the unit will shut down immediately and re-start
at the pre-set time.
If the "On-Off" button is pressed while the unit is under timer-on setting, then the unit will start
CANCEL CONFIRM 2
immediately, the timer setting is cancelled and the timer light will be off.

SWING SLEEP HEATER


Timer Switch Off
1. Press "Timer Off" button to set time for timer-off switching. Press
the button once to change the time interval of 1 hour in a cyclic
manner of 6, 7, 8 ...12 ..1, 2..5, 6 (The display is showing the
previous time as the starting time of the present setting)
If the button is held down, the time interval will increase progres-
sively by 1 hour unit.

2. Press "Timer Confirm" button to send the timer setting to the De-
humidifier. Then the timer light on the unit lights up, indicating
that the unit is in the timer mode. When it reaches the switch-off
time, the air-conditioner will automatically shut down.

NOTE:
Timer-Off can only be set when the Dehumidifier is running.
Timer-On and Timer-Off cannot be set at the same time.
Timer display on the remote controller : While time passes, the display shows the remaining
time.
If the "On-Off" button is pressed while the unit is under timer-off setting, then the unit will
shut down immediately, the timer setting is cancelled and the timer light will be off.

Timer Cancellation

Press "Timer-Cancel" button to cancel the timer-on or timer-off


settings.

16
Defrost system
Sequences of the defrosting:
1- Start
The defrosting is engaged if the following conditions are at the same time fulfiled:
- the compressor and the fan motor run without stopping;
o
- the defrosting sensor temperature lower than 3 C , and the duration of time more
than 45 minutes;
o
- the defrosting sensor temperature goes down to -7 C.
2- After 15 seconds, the 4 way valve shifts.
3- Five seconds after its stop, the compressor starts alone ; And the accumulated freeze
on the gills becomes melting, what is generally with a steam cloud .
4- Stop:
The defrosting stops if one of the following conditions is fulfiled:
- the defrosting operates 20 seconds and the detected temperature by the defrost
o
sensor goes up to 12 C;
- the compressor had run totally 8 minutes.
5- The compressor runs.
6- After 15 seconds the 4 way valve shifts
7- Five seconds after its stop the compressor and the fan start for restarting in
heating mode.
8- The running light is blinking during defrosting.

Assistant heater ( Option )

1〉Electrical heater does work only if in heating temperature or dehumidify mode;


2〉when compressor is running, press button ‘heater’, the display board’s ‘ ’ lights, electrical
heater starts; press button‘heater’ again, the display board’s ‘ ’turn off, electrical heater stops.
When get to desire temperature, both compressor and electrical heater stop at the same time;
3〉When compressor is not running, press button ‘heater’, the display board’s ‘ ’ flashes, the
heater is standby at the moment, it works after compressor starts.

Water drainage system


During the dehumidify mode, the condenser water will be drained into the internal water tank .When the
water reaches the certain level, the water drain pump will work. If the water can be drained out in 8 mins,
the dehumidifier will keep working. If not, the compressor and the motor will stop working. Mean while an
error message “ E4 “ will appear in the control panel to inform you to empty the water.
In this instance, you should cut the power off, and then restart the dehumidifier ,and the operation
will continue .

17
Error Codes

ON/OFF MODE

E1 : Room temperature sensor error;


E2 : Defrost temperature sensor error; “ ” UP FAN

E3 : Humidity sensor error;


“ ” L-R
DOWN SWING

E4 : Drain error;
P1 : Electrical heater error; HEATER TIMER

U-D
SWING

Wiring diagram
With electrical assistant heater
WIRING DIAGRAM
FAN Synchronization STEP
COMPRESSOR MOTOR MOTOR MOTOR
RED PUMP
S FM C2 MS MS
4WV

WHITE C1 Y/G
CM R G
BLUE

BROWN
BLUE

Y/G C 5 5
G
AC-N2
BLACK

RY1 RY2 HF MF LF AC-N RY6 RY9 LEFT


AC-N TEMPERATURE
P1

CONTROLLER
NO
PCB
WATER
COM

WATER LEVEL SWITCH


CONNECT 230V / 50HZ

BLACK
L BLACK ROOM
RT

WHITE BLACK TEMPERATURE SENSOR


N DEFROST
OPT H-SENS

Y/G TEMPERATURE SENSOR


G 3 HUMIDITY
WHITE CNA CNB
TERMINAL TEMPERATURE SENSOR
WHITE

11
ASSISTANT HEATER DISPLAY
WHITE RED COM RECEIVE
NO TRANSFORMER CN-DISP BOARD
PUBLIC TERMINAL

Without electrical assistant heater

WIRING DIAGRAM
Synchronization STEP
FAN MOTOR
COMPRESSOR MOTOR
PUMP MOTOR
RED MS MS
S FM
4WV

C1 C2
WHITE Y/G
CM R
BLUE

G
BROWN
BLUE

Y/G C 5 5
G
BLACK

AC-N2
RY1 RY2 HF MF LF AC-N
RY6 LEFT
AC-N
WATER

WATER LEVEL SWITCH


NO
CONNECT 230V / 50HZ

BLACK ROOM
COM

L
PCB
RT

TEMPERATURE SENSOR
WHITE
N DEFROST
OPT

Y/G TEMPERATURE SENSOR


G CNA CNB 3 HUMIDITY
H-SENS

TERMINAL TEMPERATURE SENSOR

11
DISPLAY
RECEIVE
TRANSFORMER CN-DISP BOARD

18
Maintenance

For smart use of the Dehumidifier:

Setting of proper room Do not block the air inlet


temperature or outlet

Proper
temperature

Close doors and windows Use the timer effectively


during operation

If the unit is not to be used Use the louvers effectively


for a long time, turn off the
power supply main switch. TIM ER HEATER
A

SWING SWING
+
C
%

_ FAN
SPEED MODE ON/OF F

OFF

19
Maintenance

For smart use of the Dehumidifier:

WARNING
Before maintenance,be sure to turn off the system and the circuit breaker.

Remote Controller Body

Wipe the air conditioner by using a soft and


Do not use water, wipe the controller with a dry cloth.For serious stains,use a neutral
dry cloth.Do not use glass cleaner or chemical detergent diluted with water.Wring the water
cloth. out of the cloth before wiping.then wipe off
the detergent completely.

Do not use the following for cleaning

o o
Gasoline,benzine, thinner or cleanser may Hot water over 40 C (104 C ) may cause
damage the coating of the unit. discoloring or deformation.

Air Filter cleaning


Press the clasp on the top of the grill and pull the grill out,
and then the filter will be taken out along a gradient way.

Clean the filter. Once every


Use a vacuum cleaner to remove dust, or wash the filter with two weeks
water.After washing, dry the filter completely in the shade.
Then, reinstall it onto the unit.

20
Maintenance

To keep your Dehumidifier in good condition after season:

1. Operate in FAN mode for about half a day.

On a fine day, unit shall be started and operate in


FAN mode for about half a day until the inside of
the unit becomes thoroughly dry.

2. Turn off the power supply main switch.

OFF

3. Cleaning the body.

4. Take out the batteries from the


wireless remote controller.

21
Trouble shooting

Before asking for service, check the following first.

Phenomenon Cause or check points

The system does not restart When unit is stopped, it won't restart
immediately. immediately until 3 minutes have elapsed
to protect the system.
When the electric plug is pulled out and
reinserted, the protection circuit will work
for 3 minutes to protect the dehumidifier.

Noise is heard: During unit operation or at stop, a swishing


or gurgling noise may be heard. At first 2-3
minutes after unit start, this noise is more
noticeable. (This noise is generated by
Normal refrigerant flowing in the system.)
Performance During unit operation, a cracking noise may
inspection be heard. This noise is generated by the
casing expanding or shrinking because of
temperature changes.
Should there be a big noise from air flow in
unit operation, air filter may be too dirty.

Smells are generated. This is because the system circulates smells


from the interior air such as the smell of
furniture, cigarettes.

Multiple Does not work at all. Is power plug inserted?


check Is there a power failure?
Is fuse blown out?

Is the air filter dirty? Normally it should be


cleaned every 15 days.
Inefficient
Are there any obstacles before inlet and outlet?
Is temperature set correctly?
Are there some doors or windows left open?

22