2. MOUNTING SIZE
INSTRUCTION MANUAL 48mm*48mm 48mm*96mm
Unit:mm 96mm*48mm
44.0
Unit:mm
44.0
Please Carefully read all the instructions in this manual. 50 14.6
Please place this manual in a convenient location for easy reference.
50 14.6
S P E C I F I C AT I O N
90.0
104.0
44.0
58.0
96
50
● Power Supply: 85~265VAC 50/60HZ, 24VDC or 24VAC available on request
● Input: : Thermocouple(K,E,J,N,Wu3_Re25,S,T,R,B,) Pt100( Up to 800 C)
1
Voltage and Current(0-5VDC,0-10VDC,0-50mV,4-20mV,0-20mA 2-10VDC, 1-5VDC, 4-20mA) 1
1 3 .6 80 1
1
● Display: Dual line 4 digits LED display 13 . 6 80
● Output: RELAY/SSR DRIVE/4-20mA/0-5VDC/0-10VDC/1-5VDC(specify when order)
● Power consumption: 5VA maximum 72mm*72mm 96mm*96mm
Unit:mm Unit:mm
● Control method: PID, ON/OFF(P=0), Time proportional control(I=0, D=0)
67.5
90
● Measuring accuracy: 0.2%F.S
● Decimal points for all input signals: 0.1 resolution for thermocouple. 0.1 resolution for RTD.
UP
UP
0.001 for analog input
74 14.6 96 14.6
● Modbus RTU RS-485 communication, SV/PV 4-20mA Re-transmission
● Output bar graphic indication( for analog output such as 4-20mA only)
● Controller can display based on Centigrade or Fahrenheit, switchable between each other.
104.0
80.0
67.5
90.0
74
96
● Alarm Standby function intergrated
● Power up overshoot suppression function intergreated.
● Analog output buffer function 1 1
1
13. 6 1
● ON/OFF Control: Set P=0.0,it will be changed as on/off control. Check 80 13.6 80
manual"6.1 parameter P " . Position difference is HYS. when heating :PV>SV, OUT
stop, when PV<SV-HYS, OUT start, fitting for OUT1. When Cooling:PV>SV+HYS,
output start, when PV<SV,output stop. 3. WIRING
● When anolog signal output, can using output buffer function when in some special
48mm*48mm 48mm*96mm 96mm*48mm 96mm*96mm
control position, which can make output more stable.
Check manual (6.1 level 2 bUFF parameter, and 6.3 level 2 bEr parameter) 1 L AC85-265V N 6 1 L 11
AC85-265V AL2
AL1 A+ 11 VDC,mA
2 RS -485 7 2 N 12
NO B- 12 ANL4/ANL3
RTD
IN
NO
3 8 Voltage mA,V
1. Unique Features OUT For
SSR mA,V
DA - AL2
13
B
3 OUT For SSR Current
NC
13
4 TRS
B
9 NO
Power Up Overshoot Supression NO TC
14 4 14
The overshoot is common when controller just power up, and the PV is getting closer to SV,
5 DA + NO A 10 B-
RS-485
this controller offers a useful features for application where the overshoot should be tolerated AL1
5 A+ 15
72mm*72mm NO
DA -
DA - AL2 6 16
SV
OverShoot
SV
Overshoot suppressed
1 L B- 8 8 TRS
AC85-265V RS -485 TRS VDC/mA
PV PV NO 7 17
2 N A+ 9 DA +
9 ANL4/ANL3 IN
DA+
NC RTD
AL1 8 18
3 10 10 B
NO
Figure 1 Figure 2
VDC/mA 9 B 19
4 11 11 TC
The figure 1 shows significant overshoot after PV reaches to SV, this is harmful to some of ANL4/ANL3 IN
system, MTA offers a feature to suppress the overshoot OUT RTD 10 A 20
5 12 B 12
LED display and indicator built together on one PCB board NO For Alarm output rated:
SSR mA,V B Relay contact output:250V AC, 3A (Resistive load)
6 NC
13 13 Control output rated:
The LED display and LED indicators was built as one panel TC Relay contact output: 250V AC,5A(Resistive load)
,most of controller with their LED display and LED indicator Voltage pulse output: 0/12 V DC or 0/24V DC (Load resistance
installed separately, the chance of the malfunction is high. 7 14 A 14 600 ohm or more)
This controller with all the display and indicator units built Current output: 4 to 20mA DC (Load resistance 500 ohm or less)
together on board, makes it easier to install and easy to test Triac single phase zero crossing: 100A or less
with higher reliability.
3.1 Wiring cautions Twist these leadwires
instrument power
Range 1300°C 600°C 800°C 1300°C 2000°C 1600°C 400°C 1700°C 1800°C
The setting procedures are the same as those of example (2) to (4) in the Band-ra te setti ng 9.6 BAUd=2.4K,4.8K,9.6K,19.2K
above "Setting set value (SV)". Press the SET key after the **ALARM TYPE TABLE (ALd_=00~16)
setting end shifts to the next parameter. When no parameter setting is 10: No alarm output 00: No alarm output
required, return the instrument to the PV/SV display mode. 11: Deviation high alarm 01: Deviation high alarm with hold action
12: Deviation low alarm 02: Deviation low alarm with hold action
6. LEVEL 13: Deviation high/low alarm 03: Deviation high/low alarm with hold action
14: Deviation band alarm 04: Deviation band alarm with hold action
*In any ti me you can pre ss SET key fo r 3 seconds to save value and exit level to PV/S V mode. 15: Process high alarm 05: Process high alarm with hold action
16: Process low alarm 06: Process low alarm with hold action
6.1 Level 1
Press the SET key for 3 seconds to level 1: NOTE: With hol d act ion, When Hod act ion is ON, the alarm act ion is suppressed
at start-up unt il the measured val ue ent ers the non-al arm range.
The following parameter symbols are displayed one by one
every time the SET key is pressed.After the value be
registered ,when no parameter setting is required, Press the SET key for 3 s to return the
7. AUTOTUNING
instrument to the normal display. 1# Factory set value Auto-tuning shall be performed right after the power feed to controller when PV is far away from SV.
Symbol Name Range 1# Description Aut otuning At
NO or YES NO
Press SET key for
Autotuning YES: Autotuning on,NO: Autotuning off SET PV PV
SV SV
SV