Professional Documents
Culture Documents
Different Techniques For Life Estimation
Different Techniques For Life Estimation
Different Techniques For Life Estimation
Transformers are critical and capital intensive assets for utility industry. Although the
transformers are very reliable, many in use today have exceeded their life It is broadly
accepted that the life of a power transformer is the life of the oil/ paper insulating system,
whilst accepting also the fact that most failures in their final form result from an
electro/mechanical base such as a surge or short circuit condition or a mechanical failure.
Paper ageing is a process involving both chemical and physical changes causing a
loss of both mechanical and electrical strength in the cellulose. Deterioration of both the
paper and transformer oil is caused by number of factors including oxidation accelerated by
high temperatures, air and moisture. The oil oxidation will lead to acids and par oxides
production. These compounds are introduced into the system along with additional water
also produced from this reaction.
The ageing of insulation in Transformers is influenced by short term and long term
over loads, Number and intensity of short –circuits, incidence of lightning, and internal
faults. The ageing behavior is likely to be different for different types of transformers. The
life span of the transformer, thus, depends initially on the design, and quality of
manufacture, and later on service conditions and maintenance standard these factors vary
considerably and affect the useful span of service life which therefore needs to be taken
into account for residual life assessment. During the natural ageing of transformers, the
insulation of winding, which is cellulose paper, deteriorates. Such deterioration can be well
assessed by subjecting the cellulose paper to various tests. Cellulose insulation degrades
due to heating or electrical Breakdown, resulting in the production of furfural derivatives,
which dissolve in oil. Hence, the chemical analysis of the Transformer oil gives evidence of
changes that are taking Place in the winding insulation during operating.
1
Estimation from furfural 1 Sludge value 120%
2 Acidity after 25 mg
Oil sample collection oxidation(max)
KOH
Paper sample collection 3 Flash point 2940
F( 146.1
Estimation from degree of
0 C)
polymerization 4 Viscosity at 700 F 37
5 Pour point -250F
6 Specific gravity No limit
OIL SAMPLE COLLECTION 7 Saponification 1.0 mg
value KOH/g
The oil sample is generally taken 8 Electric 40
from the bottom valve of the transformer. strength( 1min)
depending on the oil quality and furfural
content, it can be decided whether REQUIREMENTS OF INSULATING OIL
collection of further oil samples for
The three main functional requirements
ascertaining the status of transformer are of insulating oil are:
required. Approximately five liter of the oil
is to be collected in stainless steel
bottles/glass bottles by following relevant
To meet the insulation function,
standard procedures. Oil sample may be
the oil has high dielectric
required a minimum three times of over a
strength and low dissipation
period of 6-8 months time during the
factor to withstand electric
transformer in service, to ascertain the
stresses imposed in service.
rate of rise of furfural
To meet heat transfer and
cooling function the oil must
S. Characteristics Limit
No.
2
To meet the arc quenching The oil must not contain levels
of Contamination by an
function, the oil requires a
individual Metal.
combination of high dielectric
The Density of oil has to be low
strength, low viscosity and high
enough to ensure that ice
flash point to provide sufficient
cannot float on the oil surfaces
insulation and cooling to ensure
at very low temperatures and
arc is extinguished.
cause internal flashover.
3
Mix Ability: Unused mineral The oil must have low
insulating oil of the same class, Polycyclic Aromatic (PCA)
the same groups are considered carbon content to meet the
to be mixable and compatible requirements of healthy and
with each other. safety legislation.
4
results. samples are as follows-
The oil sample should be
obtained from the bottom drain Chemical tests
valve.Do not attempt to sample if 1. Moisture Content test
the transformer is under negative 2. acidity test
pressure. Electrical tests
The sampling valve must be 1. Breakdown test
cleaned prior to sampling. 2. Resistivity analysis
Flush drain valve with sufficient 3. Particles Analysis test
oil to remove stagnant oil from 4. Flash point and Fire point
the valve and drain pipe(1/2 to 1
gallon of oil).The oil sample must MOISTURE CONTENT ANALYSIS
be representative,ie, oil which is
circulating within the transformer. The effects of moisture on the
Rinse the jar several times with insulation in old transformers have
Fill the 650 ml jar ¾ “from the tap insulation used in transformers is
collected the oil sample Perform the test deterioration in the insulating quality of
The tests that we have performed on oil deterioration, the formation of acids and
5
sludge, is caused by oxidation. Thus, because the dissolved moisture is then
the exclusion of oxygen is of prime changed to an emulsion.
importance. The rate of oxidation also
depends on the temperate of the oil; the NEGATIVE EFFECT OF MOISTURE
higher the temperature, the faster the
oxidative breakdown. This fact points to Deterioration in transformer
the importance of avoiding overloading cellulose decreases both its electrical
of transformers, especially in the and mechanical strength. In general, the
summertime. Oxidation results in greater the water content the more the
mechanical strength reduces.Mineral oil
In the formation of acids in the has a very limited capacity to absorb
insulating oil moisture. Most of the water produced
during ageing remains in the windings,
In the formation of sludge.
reducing the insulation resistance of the
transformer.It also reduces the
transformer’s ability to withstand the
Moisture can be present in oil (a)
mechanical and electrical stresses that
in a dissolved form, (b) as tiny droplets
occur in operation additionally, high
mixed with the oil (emulsion), or (c) in a
levels of moisture can effectively reduce
free state at the bottom of the container
the dielectric strength of the mineral oil.
holding the oil. Demulsification occurs
Over time this will result in outages
when the tiny droplets unite to form larger
and/or the necessary down rating of the
drops which sink to the bottom and form
transformer and ultimately could result in
a pool of free water. Emulsified water or
complete failure.
water in the free state may be readily
removed by filtering or centrifugal While preparing this study we have
treatment; the filtration process can used 831 KF Coulometer manufactured
partially remove dissolved water if the by Metrohm Ltd, Switzerland.
filter papers are thoroughly dried before
filtration and are replaced frequently. PRINCIPLE OF KF COULOMETRIC
DETERMINATIONS
EFFECT OF TEMPERATURE ON The coulometric Karl Fischer
MOISTURE
titration is as version of the classical
The amount of moisture which can water determination method by Carl
be dissolved in oil increases rapidly as Fischer. The traditional method utilizes a
the oil temperature increases. Therefore, methanolic solution of iodine, sulpher
insulating oil purified at too high a dioxide and a base as buffer. Several
temperature may lose a large percentage reactions run in the titration of water –
of its dielectric strength on cooling containing sample and can be
6
summarized by the following overall coulometer Karl Fischer is an absolute
equation: determination no titer need be
H2O+ I2 + [RNH]SO3CH3 + 2 RN ↔ determined. It is necessary only to
[RNH]SO4CH3 + 2 [RNH] ensure that the reaction which generates
According to the above equation, I2 the iodine runs with 100% current
reacts quantitatively with H2O.This efficiency. With the reagents available
chemical relation forms the basis of the today this is always the case.
water determination.
The end point is indicated voltrametrically
In the coulometric Karl Fischer titration, by applying an alternating current of
the iodine needed is generated directly in constant strength to strength to a double
the electrolyte by electrochemical means Pt electrode. This results in a voltage
(“electronic buret”).the rigorously difference between the Pt wires of the
quantitative relationship between the indicator electrodes which is drastically
electric charge and the amount of iodine lowered in the presence of minimal
generated is used for high-precision quantities of free iodine. This fact is used
dispensing of the iodine. As the to determine the end point of the titration.
7
content and thus can be used without The third oil sample of from same
replacement. substation have 78 ppm/cc.
8
general guide for determining when an oil received from other tests. Oil with high
should be replaced or reclaimed, neutralization value affects the winding &
provided suitable rejection limits have paper.
been established and confirmation is
9
assumptions, it has been estimated that
50
different types of transformers would take
years
the following periods of time before
67
sludge would appear:
years
Transformers with free air access 10 correspond to actual field examples due
Transformers with nitrogen over oil years relative periods of serviceability for the
different types of transformers
For this study we have used 702 SM Titrino manufactured by Metrohm Ltd.
10
11
12
ANALYSIS OF SUSPENDED range between 2 and 100 µm can be
PARTICLES AND THEIR EFFECT ON
determined in less than a minute. The
BREAKDOWN VOLTAGE
Spectrex instrument also counts
aggregates as large particles. With care
A Spectrex counter has been used reasonably good agreement has been
to make particle count measurements in obtained between the Royco and
liquid held in transparent containers up to Spectrex counters. The relatively large
a maximum of 200 mm in depth. The liquid volume with which the Spectrex
Spectrex counter uses a helium-neon counter can be used has made it
laser beam which is focused to a small, possible to determine the influence of
defined volume (10 ml) within the liquid. voltage stress and other factors on the
Total particle count over a predetermined particle count.
Fig 4 : PC 2200 Laser Particle Counter
The Spectrex counter permitted for the increased in 5kV steps to 25kV. The
first time a particle count in oil while voltage was then decreased similarly in
voltage stress was simultaneously 5kv steps. No particles were purposely
applied. To stay within the liquid depth added to the "clean" oil but particle
limit of the counter, special test cells motion between the electrodes could be
were built In one cell a ½" dia. clearly seen in the red laser beam of the
hemisphere was spaced from another Spectrex counter (The oil was not stirred
such electrode in horizontal alignment as it is in the ASTM D1816 test so that
The spacing was at least 2 mm to permit particle motion induced by voltage stress
the laser beam to be focused directly could be observed). The particle count
between the electrodes. increased as voltage was increased. The
particle motion back and forth between
Particle count was measured
the electrodes also could be observed to
without voltage and after one minute
increase with voltage. However, as the
intervals as the DC voltage was
voltage was decreased, the particles
13
appeared to stay suspended for some particle concentration started to increase
time. In Fig. 1 the voltage was raised as at 10kV but no partial discharges (above
fast as the counting time would permit In 2pC) were observed below 35kV.
other tests the DC voltage was raised
Progress has been made in
much more slowly without greatly
characterizing the shape of particles
influencing the results. However, with AC
removed from transformer oil and in
voltage the time of voltage application at
recognizing the possibility that small
a fixed voltage does influence the particle
particles may agglomerate to form large
count as shown in Fig. 2. The oscillatory
particles. These large agglomerates may
particle motion observed in the laser
also break up to smaller particles under
beam differs markedly from the back and
both mechanical and electrical stress.
forth motion with DC.
The parameters of these competitive
The visual observations in the laser processes have not been defined.
beam were as instructive as the particle However, the processes may well be
count. Particle chains were not observed responsible for the apparently
with AC voltage even when particles contradictory test results that have been
were purposely added or were produced obtained in some cases.
by voltage breakdowns. With DC, the
With both alternating and direct voltage,
carbonaceous particles after a
particle motion starts at 5% or less of the
breakdown sometimes did line up in a
breakdown voltage. On the other hand,
"chain" so as to almost completely bridge
measurable corona occurs only at
the gap. However, as the DC voltage
voltages above 80% of the breakdown
approached breakdown the particle
voltage. With alternating stress and the
"bridge" between the electrodes became
electrode geometries investigated,
unstable and broke up before voltage
steady corona sometimes does not occur
breakdown occurred.
before voltage breakdown. Particle
It has been possible to combine concentration in high field region tends
Spectrex particle count and partial first to increase as voltage stress
discharge measurements, as illustrated increases; then, at higher stresses or
by the results in Fig. 6. For this purpose, with time, particles tend to be drawn out
a needle to plane gap was used with a 25 of the high stress areas at the center of
mm spacing which could be made corona the electrodes.
free up to about 50kV and still meet the
size limitation for particle counting. For Since these measurements have all
this geometry, no increase in particle been made in oil alone with relatively
count and no corona was observed with small electrode gaps, the pertinence to
14
influence of particles and the lower decreases where as with the decrease in
breakdown strength with direct voltage particle size the BDV increases.
compared with alternating voltage does
suggest that conservative design and PRINCIPLE OF WORKING
care in manufacture may be especially
important with such DC apparatus. The Spectrex provides three
results suggest, also, that corona in oil sealed calibration standards with each
(as distinct from gas-filled voids) may be unit. Each standard contains a precise
more likely to occur under direct than number of NIST traceable polystyrene
alternating voltage. spheres of known size in suspension and
are sealed with inert Argon gas. These
.The larger and conducting particles standards have a proven stability of more
decrease the break down voltage. Also it than 10 years and Provide efficient
is concluded by analysis of different calibration within 10 minutes. The
samples of transformer oil that the specifications of the instrument are as
dissolved particle size increases after follows-
thermal treatment of the good oil as the
suspended particles get combined and Size: 4.75 " x 14 " x 4.5 “(height
form the bigger size particle and hence with Light Tight Cover is 5”)
total count become less. Thus Break
Bottle material: transparent,
down Voltage (BDV) decreases by
scratch free glass
increase of particle size.
15
We had taken two samples from same Bhabhe 40MVA 132/33kv transformer,
transformers and analyzed them with PC- kanchghar, Jabalpur
2200 under various conditions. The
results are given as follow:- Particulars Properties
16
17
Particulars Properties
Total counts 267.00
cc
Specific gravity 1.00
Mean size 9.16
μm
Break down voltage 30 kv
18
Particle size Graph of Oil Sample of
Vinobha Bhabhe 40MVA 132/33kv
transformer, kanchghar, Jabalpur
19
FACTORS CONTROLING & very low power factor varying between
AFFECTING THE BREAKDOWN 10^-4 at 20 degree and 10^-3 at 90
STRENGTH OF THE TRANSFORMER degree at a frequency of 50 Hz.
OIL
20
Breakdown test are normally separation is very critical in
conducted using test cells. For testing measurements with liquids, and also the
pure liquids, the test cells used are small electrode surface smoothness and the
so that less quantity of liquid is used presence of oxide films have a marked
during testing .The electrodes used for influence on the breakdown strength .The
breakdown voltage measurements are test voltages required for these tests are
usually spheres of 0.5 to 1 cm in usually low, of the order of 50-100kV,
diameter with gap spacing of about 100- because of small electrode spacing .The
200mm. The gap is accurately controlled breakdown strengths and d.c.
by using a micrometer. Sometimes conductivities obtained in pure liquids are
parallel plane uniform field electrode very high, of the order of 1MV/cm and
systems are also used. Electrode 10^-18 to 10^-20 mho/cm respectively.
21
independent balancing of the Є and DF
components. The Є-DF tests are carried
out w.r.t. line frequency.
The Resistivity meter is auto
ranging with the reading displayed on 3½
digits DPM. Once the cell Constant is
Fig 7: Restivity test set, DTR –
3K,manufactured by Eltel Industries balanced with the cm dial, the Resistivity
meter reads volume Resistivity directly in
DESCRIPTION
ohm-centimeters. With the cm dial set to
The Dielectric Constant, Tan Delta
1000, the Resistivity meter reads
& Resistivity Test Set has been specially
resistance in ohms multiplied by a factor
designed to determine the Tan Delta,
of 1000. The auto ranging feature
Dielectric Constant and Resistivity of
eliminates the need for selecting the right
transformer oil and other electrical
range manually.
insulating liquids using a guarded three
terminal test cell. This may also be used
for measurement of the above
parameters of solid insulating materials
using a guarded three terminal solid test
cell.
Specifications
There are built-in safety features
which include zero start on voltage
adjustment, auto trip with LED indication
if two grounds are not connected, auto
trip with LED indication if safety interlock
is opened and built-in protection should
the test sample flash over.
The Є (Epsilon) - DF portion of
the instrument operates as a manually
balanced capacitance bridge. Since Є is
ratio of the full cell capacitance to the
empty cell Capacitance (in cm) must be
dialed in or be balanced out by using the
balancing procedure. The cell constant
(in cm) equals 3.6 x∏x1xC, where C is
the cell Capacitance in pF. The bridge
balance is accomplished with the aid of
synchronous and phase sensitive null
detector which allows easy and
22
S.N SPECIFICATIO RANGES 90O C in 15 mins approximately. A knob
O NS and a dial are provided to set the
1. ACCURACY ± 3% of
temperature at required level. A
reading ±
0.2% FS temperature sensing probe is supplied
linear
and this senses the temperature and
2. RESOLUTION 0.01 of
each stops heating the oil once the set
range.
temperature is reached. Two LEDs are
3. CELL 3 digit
CONSTANT adjustmen provided to indicate ‘heating on’ and
t for Tan
‘heating off’. To ensure safety the built-in
Delta zero
and micro switch interlock automatically trips
OIL
Capacitan
out the high voltage when the plexi cover
ce (cm).
Any cell or of the heater is raised.
test fixture
between
Specifications
50-70pF
can be
S.NO SPECIFICATIONS RANGES
used.
1 POWER SUPPLY 230 V AC
4. TEST +500 V
± 10%, 50
VOLTAGE DC-Fixed
Hz OR 110
5. POWER 230 V AC V AC ±
SUPPLY
± 10%, 10%, 60
Hz, 200VA
50Hz, OR 2 TEMPERATURE 20 -110O
110 V AC RANGE C
±10%, 3 ACCURACY OF ±2 Oc
TEMP. CONTROL
60Hz, 150 4 DIMENSION 310 x 190
VA. x 300mm
6. TEMPERATUR 5 WEIGHT Approx 12
-10OC to
E RANGE kgs
90OC
7. HUMIDITY Ambient
to 90%
RH OIL TEST CELL
8. DIMENSION 19”
standard This 3 Terminal Oil Test Cell is
rack
mounts designed for routine and laboratory Tan
chassis. Delta tests on transformer oils and other
9. WEIGHT Approx
electrical insulating liquids. The electrode
17 kgs
of the cell is designed with a spherical
TEST CELL HEATER
bottom which offers more uniform stress
The Oil Test Cell Heater OCH-85 is a on the oil as compared to electrode with
very compact unit and is used to heat the tapered end.
oil in the cell to the required temperature.
This uses high frequency induction
heating which raises the temperature to
23
Fig 10: Restivity
SPACING
v. VOLUME 45ml
vi. DIMENSION 90mm X
185mm
vii. WEIGHT Approx
2.5Kgs
RESISTIVITY CALIBRATOR
FLASH POINT AND FIRE POINT
24
removed. A slightly higher temperature, In open cup devices the sample is
the fire point, is defined as the contained in an open cup (hence the
temperature at which the vapor continues name) which is heated, and at intervals a
to burn after being ignited. Neither of flame is brought over the surface. The
these parameters is related to the measured flash point will actually vary
temperatures of the ignition source or of with the height of the flame above the
the burning liquid, which are much liquid surface, and at sufficient height the
higher. The flash point is often used as measured flash point temperature will
one descriptive characteristic of liquid coincide with the fire point. Examples
fuel, but it is also used to describe liquids include Cleveland Open Cup and
that are not used intentionally as fuels. Pensky-Martens open cup. The main
difference being that the former is heated
MECHANISM
Every flammable liquid has a vapor from below, while the later is heated from
25
flash point test, a brass test cup is filled Gas heated model has a built-in
with a test specimen and fitted with a nickel plated brass natural gas burner, or
cover. The sample is heated and stirred can be supplied with an artificial gas
at specified rates depending on what it is burner or liquid propane burner (specify
that's being tested. An ignition source is when ordering). Both models are
directed into the cup at regular intervals mounted on a sturdy cast iron base.
with simultaneous interruption of stirring
until a flash that spreads throughout the
inside of the cup is seen. The
corresponding temperature is its flash
point.
with cooling vents. Includes line cord begins as soon as the transformer is
receptacle and switch for accessory slow energized. A chemical reaction occurs
26
of heat, oxygen, and core and coil MOISTURE INTRODUCED INTO
components. As the process of oxidation TRANSFORMER OILS
progresses, acids and polar compounds
are formed and in turn become sludge. Through Absorption From The
This sludge will then coat heat transfer Atmosphere Above The Oil Level. Many
surfaces on the core/coil and the transformer tanks are designed to seal
tank/radiators, reducing the heat transfer the transformer from the outside
capacity of the system. The operational atmosphere; however, top side leaks
27
TSI has found that production of water. This process does not significantly
moisture can become a problem if oil is change the acid or polar compound
allowed to deteriorate beyond an acidity levels, or remove dissolved water.
level of .05mg KOH/g oil; therefore, we Oxidation and sludge formation will
recommend treatment of oils that have continue as soon as filtering is stopped.
reached this level. In cases where acidity Very little is gained from this method.
levels do not require treatment, I.F.T.'s of
less than 24 dynes/cm, dielectrics of less A third method is to un-tank a unit,
than 25Kv, and moisture contents above flush the tank, radiators, and core and
30ppm signal the need for hot oil coil with solvents, then refill the unit with
treatment. Units with primary voltages new oil. This method can result in a
above 15Kv should have dielectric successful stabilization of the oil, but
readings of 30Kv or above and moisture there are several major drawbacks. The
28
Vacuum is maintained at a minimum of Oils With Acid Levels From .10
28 inches. This part of the process To .19mg KOH/g oil have an
removes dissolved moisture, air, and exposure time based on ten (10)
dissolved gases from the oil enabling a passes at a flow rate of 600 to
unit to be processed while energized. TSI 900 GPH.
has developed procedures using this
equipment to process transformer oils D-SLUDGING - ENERGIZED
that have oxidized. The thrust of this EQUIPMENT
program is that oil be exposed to
The treatment of oil in the
operational components of the re-refiner
advanced stages of oxidation is called D-
at temperatures above 150°F long
SLUDGING, which is a two step
enough for the purification process to be
treatment process. Oils with acid levels
completed. Pumping speed is of little
greater than .20mg KOH/g oil are
importance. Under normal conditions TSI
exposed to 10 passes for Step 1, and six
recommends flow rates between 400 and
(6) to ten (10) passes for Step 2, at an
900 GPH. Higher flow rates should be
average flow rate of 600 to 900 GPH. A
used with caution on energized
time interval of at least six (6) months
equipment.
occurs between Steps 1 and 2. This time
HOT OIL TREATMENT - ENERGIZED interval is referred to as the D-
EQUIPMENT SLUDGING period. The clean oil from
Step 1 redissolves decay products into
The treatment of oil in the initial stages of
the oil which are removed from the oil in
oxidization is called HOT OIL
Step 2. After treatment the oils will meet
TREATMENT. Within this category there
or exceed the following specifications:
are two exposure time periods.
29