Professional Documents
Culture Documents
Goodman Gsc10 CU Manual
Goodman Gsc10 CU Manual
IMPORTANT INFORMATION
Pride and workmanship go into every product to provide our customers with quality products. It is possible, however,
that during its lifetime a product may require service. Products should be serviced only by a qualified service technician
who is familiar with the safety procedures required in the repair and who is equipped with the proper tools, parts, testing
instruments and the appropriate service manual. REVIEW ALL SERVICE INFORMATION IN THE APPROPRIATE
SERVICE MANUAL BEFORE BEGINNING REPAIRS.
WARNING
Only personnel that have been trained to install, To prevent the risk of property damage, personal
adjust, service or repair (hereinafter, “service”) the injury, or death, do not store combustible materials or
equipment specified in this manual should service use gasoline or other flammable liquids or vapors
the equipment. The manufacturer will not be in the vicinity of this appliance.
responsible for any injury or property damage arising
from improper service or service procedures. If you
service this unit, you assume responsibility for any
injury or property damage which may result. In
addition, in jurisdictions that require one or more
licenses to service the equipment specified in this
manual, only licensed personnel should service the
equipment. Improper installation, adjustment,
servicing or repair of the equipment specified in this
manual, or attempting to install, adjust, service or
repair the equipment specified in this manual without
proper training may result in product damage,
property damage, personal injury or death.
To locate an authorized servicer, please consult your telephone book or the dealer from whom you purchased this
product. For further assistance, please contact:
CONSUMER INFORMATION LINE CONSUMER INFORMATION LINE
GOODMAN® BRAND PRODUCTS AMANA® BRAND PRODUCTS
TOLL FREE 1-877-254-4729 (U.S. only) TOLL FREE 1-877-254-4729 (U.S. only)
email us at: customerservice@goodmanmfg.com email us at: customerservice@goodmanmfg.com
fax us at: (713) 856-1821 fax us at: (713) 856-1821
(Not a technical assistance line for dealers.) (Not a technical assistance line for dealers.)
Outside the U.S., call 1-713-861-2500.(Not a technical assistance line for dealers.)
Your telephone company will bill you for the call.
2
IMPORTANT INFORMATION
SAFE REFRIGERANT HANDLING
While these items will not cover every conceivable situation, they should serve as a useful guide.
WARNING
Refrigerants are heavier than air. They can "push out"
the oxygen in your lungs or in any enclosed space.To
avoid possible difficulty in breathing or death:
• Never purge refrigerant into an enclosed room or
space. By law, all refrigerants must be reclaimed.
• If an indoor leak is suspected, thoroughly ventilate
the area before beginning work.
• Liquid refrigerant can be very cold. To avoid possible
frostbite or blindness, avoid contact with refrigerant
and wear gloves and goggles. If liquid refrigerant
does contact your skin or eyes, seek medical help
immediately.
• Always follow EPA regulations. Never burn refrig-
erant, as poisonous gas will be produced.
3
PRODUCT IDENTIFICATION
G S C 14 036 1 AA
1 2 3 4,5 6,7,8 9 10,11
Brand Engineering
G Goodman® brand Major/Minor Revisions
A Amana® brand
Deluxe Voltage
V Value Line 1 - 208/230V Single-Phase 60 Hz
3 - 208/230V Three-Phase 60 Hz
Type 4 - 460V Three-Phase 60 Hz
S Split System
C E 120 5 A
1 2 3,4,5 6 7
Brand Engineering
C Split System Revision Level
Nominal Capacity
018 - 1-1/2 Tons 048 - 4 Tons
024 - 2 Tons 060 - 5 Tons
030 - 2-1/2 Tons 070 - 5 Tons
036 - 3 Tons 090 - 7-1/2 Tons
042 - 3-1/2 Tons 120 - 10 Tons
4
PRODUCT IDENTIFICATION
AWU F 3642 1 6 AA
1 2 3 4 5,6,7,8 9 10 11,12
Brand Engineering*
A Airhandler Major/Minor Revisions
All Airhandlers use DIRECT DRIVE MOTORS. Power supply is AC 208-230v, 60 hz, 1 phase.
5
PRODUCT IDENTIFICATION
C A P F 1824 A 6 AA
1 2 3 4 5,6,7,8 9 10 11,12
Brand Engineering*
C Indoor Coil Major/Minor Revisions
Refrigerant Charge
Unit Application 2 = R-22
A Upflow/Downflow Coil 4 = R-410A
H Horizontal A-Coil 6 = R-410A or R-22
S Horizontal Slab Coil
T Coated Coils Nominal Width for Gas Furnace
A = Fits 14" Furnace Cabinet
B = Fits 17-1/2" Furnace Cabinet
C = Fits 21" Furnace Cabinet
D = Fits 24-1/2" Furnace Cabinet
N = Does Not Apply (Horizontal Slab Coils
MB R 8 00 A A 1
1,2 3 4 5,6 7 8 9
Brand Electrical
MB - Modular Blower 1: 208-230V/60Hz/1 PH
Design Series
Type A: First Series
R- Speed
E- Variable Speed
Circuit Breaker
Airflow A: No Circuit Breaker
8: 800 CFM B: Circuit Breaker
12: 1200 CFM
16: 1500 CFM Factory Heat
20: 2000 CFM 00 No Heat
6
PRODUCT IDENTIFICATION
GSC10
Goodman® BRAND SPLIT CONDENSERS 10 SEER - R22
Model/Rev Description
GSC100903AD New ball valve/brackets, suction tube/assembly and panel w/offset.
Initial release of light commercial models with holding charge only in a double row coil.
GSC100903BA
MODELS DO NOT CONTAIN REFRIGERANT. Units must be evacuated and charged
GSC101203BA
with R-22 per the installation instructions.
Initial release of light commercial 460V models with holding charge only in a double row
GSC100904AC
coil. MODELS DO NOT CONTAIN REFRIGERANT. Units must be evacuated and
GSC101204BA
charged with R-22 per the installation instructions.
7
PRODUCT IDENTIFICATION
GSC13
Goodman® BRAND SPLIT CONDENSERS 13 SEER - R22
Model/Rev Description
GSC130[18-24]1AA Initial release of 26" chassis R-22
GSC130601DA Changed from Copeland ZRK3 series to Copeland ZRK5 series [ZR48K5PFV130 and
GSC130603CA ZR48K5TF130.
8
PRODUCT IDENTIFICATION
GSC13
Goodman® BRAND SPLIT CONDENSERS 13 SEER - R22
Model/Rev Description
GSC130181BB
GSC130241DB
GSC130301DB
Released models holding charge only; MODELS DO NOT CONTAIN REFRIGERANT.
GSC130361FB
Units must be evacuated and charged with R-22 per the installation instructions.
GSC130421BB
GSC130481BB
GSC130601CB
Released models holding charge only; MODELS DO NOT CONTAIN REFRIGERANT.
GSC130421CA
Units must be evacuated and charged with R-22 per the installation instructions.
GSC130481CA
Replacing Copeland ZRK3 series compressor with Copeland ZRK5 series.
GSC130361GB Release models holding charge only; MODELS DO NOT CONTAIN REFRIGERANT.
GSC130421CB Units must be evacuated and charged with R-22 per installation instructions. Changed
GSC130481CB from four-piece louver assembly to a two-piece louver assembly to a two-piece lourver
GSC130601DB assembly.
GSC130181DA
Release models holding charge only; MODELS DO NOT CONTAIN REFRIGERANT.
GSC130241EA
Units must be evacuated and charged with R-22 per the installation instructions.
GSC130301EA
Replaced Copeland compressor with Bristol reciprocating compressor.
GSC130361GA
Release models holding charge only; MODELS DO NOT CONTAIN REFRIGERANT.
GSC130181FA
Units must be evacuated and charged with R-22 per the installation instructions.
GSC130241FA
Reduction of chassis to 23".
Release models holding charge only; MODELS DO NOT CONTAIN REFRIGERANT.
GSC130181GA Units must be evacuated and charged with R-22 per the installation instructions. This is
the reintroduction of the Panasonic compressor.
Release models holding charge only; MODELS DO NOT CONTAIN REFRIGERANT.
GSC130301EC Units must be evacuated and charged with R-22 per the installation instructions.Changed
from four-piece louver assembly to a two-piece louver assembly.
GSC130363BB
Release models holding charge only; MODELS DO NOT CONTAIN REFRIGERANT.
GSC130483BB
Units must be evacuated and charged with R-22 per the installation instructions.
GSC130603BB
Release models holding charge only; MODELS DO NOT CONTAIN REFRIGERANT.
GSC130483CB
Units must be evacuated and charged with R-22 per the installation instructions. Changed
GSC130603CB
from four-piece louver assembly to a two-piece louver assembly.
Release 460v models with holding charge only; MODELS DO NOT CONTAIN
GSC130484BB
REFRIGERANT. Units must be evacuated and charged with R-22 per the installation
GSC130604BB
instructions.
Release 460v models with holding charge only; MODELS DO NOT CONTAIN
GSC130604BC REFRIGERANT. Units must be evacuated and charged with R-22 per the installation
instructions. Changed from four-piece louver assembly to a two-piece louver assembly.
3 ton condensing unit. Release of Goodman 13 SEER Condensers with updated serial
GSC130363BC
plates (MCA and compressor RLA/LRA ratings).
3 ton condensing unit. Changed from four-piece louver assembly to a two-piece louver
GSC130363BD
assembly plus a corner post on Goodman and value series 26" and 29" chassis.
9
PRODUCT IDENTIFICATION
GSC13
Goodman® BRAND SPLIT CONDENSERS 13 SEER - R22
Model/Rev Description
Release 460v models with holding charge only; MODELS DO NOT CONTAIN
REFRIGERANT. Units must be evacuated and charged with R-22 per the installation
GSC130484BC
instructions. Replaced Copeland ZRK3 series compressor with Copeland ZRK5 series
compressor.
Release 460v models with holding charge only; MODELS DO NOT CONTAIN
REFRIGERANT. Units must be evacuated and charged with R-22 per the installation
GSC130484BD
instructions. The current four piece louver assembly has changed to a two piece louver
assembly.
GSC100903AE
GSC100904AD
GSC130241FC
GSC130301ED
GSC130361GC
GSC130363BE Compressors changed from those using mineral oil to those using oil type POE.
GSC130[42-48]1CC
GSC130484BE
GSC130601DC
GSC130603CC
GSC130604BE
GSC130181GB
GSC130241FD
GSC130301EE
GSC130361GD
GSC130363BF
Hairpin removal to improve airflow.
GSC130421CD
GSC13048(1/3)CD
GSD130601DD
GSC130603CD
GSC130604BF
10
PRODUCT IDENTIFICATION
GSC14
Goodman® BRAND SPLIT CONDENSERS 14 SEER - R22
Model/Rev Description
New revisions have screw locations moved in the top panel, base pans, louvers, and
GSC140**1AB
control box covers.
GSC140**1AC Release models containing the Broad Ocean motor 0131M00060 and 0131M00061
GSC140(18-42)1BA Conversion of existing models using 3/8" diameter tube coils to 5 mm coils.
ASC13
Amana® BRAND SPLIT CONDENSERS 13 SEER - R22
Model/Rev Description
ASC130**1AA Initial release new models of Amana® Brand Deluxe 13 Seer AC R-22 conditioners.
VSC13
VALUE SPLIT CONDENSERS 13 SEER - R22
Model/Rev Description
Initial release of Value 13 Seer AC R-22 models.
VSC13018-601AA
2 year part & 5 year compressor warranty in Bahama Beige.
VSC130181BA Converts models from 3/8" to 5mm with new coil slab height & new louver panels.
VSC13030-361BA 2 year part & 5 year compressor warranty in Bahama Beige.
11
PRODUCT IDENTIFICATION
GSH10
Goodman® SPLIT HEAT PUMP 10 SEER - R22
Model/Rev Description
GSH10***AA Initial release.
GSH10***AB Screw locations moved in the top panel, base pans, louvers, and control box covers.
GSH100903AC Heat pump unit without R-22 refrigerant. MODELS DO NOT CONTAIN REFRIGERANT.
GSH101203AC Units must be evacuated and charged with R-22 per the installation instructions.
Heat pump unit without R-22 refrigerant with new ball valve/brackets, suction tube/assembly
GSH101203AD
and panel w/offset.
GSH13042-48*AE
GSH130191AC
Added mufflers.
GSH130484AC,
GSH13060*AC
Initial release of 460v light commercial models without R-22 refrigerant. MODELS DO NOT
GSH100904BA
CONTAIN REFRIGERANT. Units must be evacuated and charged with R-22 per the
GSH101204AC
installation instructions.
GSH100904BB R22 Condenser Models New Compressor with Oil Change from Mineral to POE
GSH100903BC
GSH100904BC Added Export Label "Not for same or use in the United States" to existing domestic GSH
GSH101203AF unit. The new minor revision will say "EXPORT ONLY" in the description.
GSH101204AE
12
PRODUCT IDENTIFICATION
GSH13
Goodman® SPLIT HEAT PUMP 13 SEER - R22
Model/Rev Description
GSH13***AA Initial release of Goodman® Brand Split Heat Pump 13 Seer heat pump units..
Replaced 8-pole fan motors with 6-pole. Screw locations moved in the top panel, base
GSH13**1AB
pans, louvers, and control box covers.
Broad Ocean motors. Screw locations moved in the top panel, base pans, louvers, and
GSH13**1AC
control box covers.
GSH13036-48*AD Broad Ocean motors
GSH13018-301BA Chassis reduction from medium to small.
Release of models with holding charge only; MODELS DO NOT CONTAIN REFRIGERANT.
GSH130421BA Units must be evacuated and charged with R-22 per the installation instructions. Replacing
Copeland ZRK3 series compressors with ZRK5 series compressors.
13
PRODUCT IDENTIFICATION
GSH13
Goodman® SPLIT HEAT PUMP 13 SEER - R22
Model/Rev Description
GSH130181CA
Release models holding charge only; MODELS DO NOT CONTAIN REFRIGERANT. Units
GSH130241CA
must be evacuated and charged with R-22 per the installation instructions. Changing
GSH130301CA
reciprocating compressor to scroll compressor.
GSH130361CA
GSH130[18,24]1CB
Release models with holding charge only; MODELS DO NOT CONTAIN REFRIGERANT.
GSH130[30,36]1CB
Units must be evacuated and charged with R-22 per the installation instructions. Models
GSH130421AG
listed have new 6 pole motor and corresponding new fan blades.
GSH130481AF
Release of models with holding charge only; MODELS DO NOT CONTAIN REFRIGERANT.
GSH130(18,24,30)1CC
Units must be evacuated and charged with R-22 per the installation instructions. The
GSH130361CD
current four-piece louver assembly has changed to a two-pieced louver assembly
Changed to motor (0131M00018P; 1/4 hp, 6 pole), fan blade (B21086750), outdoor piston
GSH130361CC
(0.059) and indoor piston (0.071).
GSH130481BA Release of 4 ton model with Copeland ZR42K5PFV130 compressor.
Release of 4 ton model with Copeland ZR42K5PFV130 compressor. The current four piece
GSH130421BB
louver assembly has changed to a two piece louver plus a corner post on Goodman and
GSH130481BB
value series 26" and 29" chassis.
GSH130363AE
Release models with holding charge only; MODELS DO NOT CONTAIN REFRIGERANT.
GSH130483AE
Units must be evacuated and charged with R-22 per the installation instructions.
GSH130603AC
GSH130363AF Release of models with updated serial plates (MCA and compressor RLA/LRA ratings).
Changed current four piece louver assembly to a two piece louver assembly plus a corner
GSH130363AG
post on Goodman series 26" and 29" chassis.
Release of 460V models with holding charge only; MODELS DO NOT CONTAIN
GSH130484AC
REFRIGERANT. Units must be evacuated and charged with R-22 per the installation
GSH130604AC
instructions.
Release of models with holding charge only; MODELS DO NOT CONTAIN REFRIGERANT.
GSH130483BA
Units must be evacuated and charged with R-22 per the installation instructions. Replacing
GSH130484AD
Copeland ZRK3 series compressors with ZRK5 series.
Release of models with holding charge only; MODELS DO NOT CONTAIN REFRIGERANT.
GSH130483BB Units must be evacuated and charged with R-22 per the installation instructions. The
current four piece louver assembly has changed to a two piece louver plus a corner
Release of models with holding charge only; MODELS DO NOT CONTAIN REFRIGERANT.
GSH130484AE Units must be evacuated and charged with R-22 per the installation instructions. The
current four piece louver assembly has changed to a two piece louver plus a corner
GSH130363AJ
GSH130483BD
Added Export Label "Not for same or use in the United States" to existing domestic GSH
GSH130484AG
unit. The new minor revision will say "EXPORT ONLY" in the description.
GSH130603AE
GSH130604AE
GSH130361CF
Replaced motor 0131M00018P with 0131M00813
GSH130[421,481]BD
14
PRODUCT IDENTIFICATION
GSH14
Goodman® SPLIT HEAT PUMP 14 SEER - R22
Model/Rev Description
GSH140**1AA Initial release of Goodman® Brand Split Heat Pump 14 Seer heat pump units.
GSH140**1AB Screw locations moved in the top panel, base pans, louvers, and control box covers.
GSH140361AF,
GSH140421-48AD Replaced TXV and compensator with flowrator and accumulator.
GSH140601AE
ASH13
Amana® BRAND SPLIT HEAT PUMPS 13 SEER - R22
Model/Rev Description
ASH130**1AA Initial release of Amana® Brand Deluxe 13 Seer R-22 heat pumps.
ASH130**1AB Screw locations moved in the top panel, base pans, louvers, and control box covers.
ASH130**1AC New horizontal style louvers.
VSH13
VALUE SPLIT HEAT PUMP 13 Seer
Model/Rev Description
Initial release of Value Split Heat Pumps 13 Seer R-22 models.
VSH1318-601AA
2 year parts and 5 year compressor warranty in Bahama Beige.
15
PRODUCT IDENTIFICATION AIR HANDLERS
ARUF 13 SEER
A SINGLE PIECE AIR HANDLER R-MULTI-POSITION PSC MOTOR UNPAINTED FLOWRATOR
Model/Rev Description
ARUF****16AA Introduction of new 13 SEER Air Handler Model suitable for use with R-22 and R-410A
ARUF364216AB
Replaced current spot welded blower housing with the same cinched or crimped design
ARUF486016AB
used on the 80% furnace line.
ARUF364216AC
ARUF****16BA Replaced ARUFcoils using wavy fin with louver enhanced fin.
ARPF 13 SEER
A SINGLE PIECE AIR HANDLER R-MULTI-POSITION MOTOR PAINTED FLOWRATOR
Model/Rev Description
ARPF****16AA Introducation of new 13 SEER Air Handler Model suitable for use with R-22 and R-410A
ARPF364216AB Replaced current spot welded blower housing with the same cinched or crimped design
ARPF486016AB used on the 80% furnace line.
ARPF****16BA Replaced ARPF coils using wavy fin with louver enhanced fin.
ADPF 13 SEER
A SINGLE PIECE AIR HANDLER DOWNFLOW PSC MOTOR PAINTED FLOWRATOR
Model/Rev Description
ADPF****16AA Introducation of new 13 SEER Air Handler Model suitable for use with R-22 and R-410A.
ADPF364216AB
Replaced current spot welded blower housing with the same cinched or crimped design
ADPF486016AB
used on the 80% furnace line.
ADPF304216AC
ADPF****1BA Replaced ADPF coils using wavy fin with louver enhanced fin.
ASPF
A SINGLE PIECE AIR HANDLER S-MULTI-POSITION EEM MOTOR PAINTED FLOWRATOR
Model/Rev Description
Control scheme modification that ensures blower operation during and after call for heat
ASPF****16BA on units with heat kits.
Replaced coil wavy fin with louver enhanced fin.
16
PRODUCT IDENTIFICATION AIR HANDLERS
AEPF 13 SEER
A SINGLE PIECE AIR HANDLER E-MULTI-POSITION VARIABLE-SPEED MOTOR PAINTED FLOWRATOR
Model/Rev Description
AEPF****16AA Introduction of new 13 SEER Air Handler Models suitable for use with R-22 and R-410A
AEPF****16BA Introduction of models adding lower kW hit kits on the S&R plate.
Replaced current spot welded blower housing with the same cinched or crimped design
AEPF****16BB
used on the 80% furnace line.
AEPF****16CA Replaced AEPF coils using wavy fin with louver enhanced fin.
AWUF 13 SEER
A SINGLE PIECE AIR HANDLER WALL MOUNT PSC MOTOR UNPAINTED FLOWRATOR
Model/Rev Description
Initial release 13 SEER Dayton wall mount air handlers suitable for use with R-22 and R-
AWUF****16AA
410A refrigerant.
AWUF3005-101AA Introduces 13 SEER Dayton wall mount air handlers using a Burr Oak Louvered Fin coil.
AWUF****1BA Replaced wave fin design with new louvered fin design
AWUF370**16AA Introduction of AWUF37 Air Handlers for use with R-22 and R410A.
AWUF****16BA Revision has louver fins & replaces copper tube hairpins with aluminum hairpins.
17
PRODUCT IDENTIFICATION AIR HANDLERS
ACNF 13 SEER
A SINGLE PIECE AIR HANDLER CEILING MOUNT N-UNCASED FLOWRATOR
Model/Rev Description
Initial release of 13 SEER Dayton uncased air handlers suitable for use with R-22 and R-
ACNF****16AA
410A
ACNF****1BA Replaced wavy fin design with new louvered fin design
MBR
MODULAR BLOWER AIR HANDLER R-MULTI-POSITION PSC MOTOR
Model/Rev Description
MBE
MODULAR BLOWER AIR HANDLER E-MULTI-POSITION VARIABLE-SPEED MOTOR
Model/Rev Description
MBE****AA-1AA Initial release of modular blower with variable speed blower motor.
MBE****AA-1BA Initial release of new models with added lower kW hit kits on the S&R plate.
18
PRODUCT IDENTIFICATION COILS
CAUF
C-INDOOR C OIL A-UPFLOW/DOWNFLOW UNCASED FLOWRATOR
Model/Rev Description
CAUF****6*DA Replaced existing copper coils and other associated parts with aluminum components.
CPTF
C-INDOOR C OIL T-COATED P-PAINTED FLOWRATOR
Model/Rev Description
CTPF1824*6AB
CTPF3030*6AB
CTPF3131*6AB
Drain pan material change to a Decabromodiphenyl Ether free resin.
CTPF3636*6AC
CTPF3642*6AB
CTPF4860*6AB
19
PRODUCT IDENTIFICATION COILS
CSCF 13 SEER
C-INDOOR C OIL HORIZONTAL SLAB COIL C-UNPAINTED FLOWRATOR 13 SEER
Model/Rev Description
Initial release of Burr Oak Louvered Fin. Rows changed by one, (i.e. 4 row to 3 row; 3 row
CSCF*****6BA
to 2 row) where applicable.
CSCF1824N6BB
CSCF3036N6BB
Drain pan material change to a Decabromodiphenyl Ether free resin.
CSCF3642N6CB
CSCF4860N6CB
CHPF
C-INDOOR COIL HORIZONTAL A-COIL PAINTED FLOWRATOR
Model/Rev Description
CHPF*****6AA Intial release of 13 SEER CHPF horizontal A coil.
Released Burr Oak Louvered Fin in place of the Wavy Fin. The rows changed by one, (i.e.
CHPF*****6BA
4 row to 3 row; 3 row to 2 row) where applicable.
CHPF1824A6CA
CHPF2430B6CA
CHPF3636B6CA
CHPF3642C6CA
Louvered fins. Replaced copper tube hairpins with aluminum hairpins.
CHPF3642D6CA
CHPF3743C6BA
CHPF3743D6BA
CHPF4860D6DA
CHPF1824A6CB
CHPF2430B6CB
CHPF3636B6CB
CHPF3642C6CB
Drain pan material change to a Decabromodiphenyl Ether free resin.
CHPF3642D6CB
CHPF3743C6BB
CHPF3743D6BB
CHPF4860D6DB
CHPF1824A6CC
CHPF2430B6CC
CHPF3636B6CC
CHPF3642C6CC
Change to prepainted wrappers
CHPF3642D6CC
CHPF3743C6BC
CHPF3743D6BC
CHPF4860D6DC
20
PRODUCT IDENTIFICATION COILS
CTUF
C-INDOOR C OIL T-COATED U-UNPAINTED FLOWRATOR
Model/Rev Description
CTUF1824*6AA
CTUF3030*6AA
CTUF3131*6AA
Initial release.
CTUF3636*6AA
CTUF3642*6AA
CTUF4860*6AA
CTUF1824*6AB
CTUF3030*6AB
CTUF3131*6AB
Drain pan material change to a Decabromodiphenyl Ether free resin.
CTUF3636*6AC
CTUF3642*6AB
CTUF4860*6AB
CAPT
C-INDOOR C OIL A-UPFLOW/DOWNFLOW PAINTED CASED FLOWRATOR W/TXV
Model/Rev Description
CAPT3131B4BA Initial release of coils with factory-installed, non-adjustable TXV. Single stage AHRI ratings
CAPT3131C4BA for CAPT3131 NTC combinations.
CAPT3743C4AA
Initial release of single stage AHRI ratings for CAPT3743 NTC combinations.
CAPT3743D4AA
CAPT4961C4AA
Initial release of single stage AHRI ratings for CAPT4961C4 NTC combinations.
CAPT4961D4AA
CAPT3131B4AB
CAPT3131C4AB
CAPT3743C4AB
Redesign the wrapper for the CAPT to provide increased ease of installation.
CAPT3743D4AB
CAPT4961C4AB
CAPT4961D4AB
21
PRODUCT IDENTIFICATION COILS
CAPF
C-INDOOR C OIL A-UPFLOW/DOWNFLOW PAINTED CASED FLOWRATOR
Model/Rev Description
CAPF*****6DA Replaced existing copper coils and other associated parts with aluminum components.
CAPF1824A6DC
CAPF1824B6DC
CAPF1824C6DC
CAPF3030A6DC
CAPF3030B6DC
CAPF3030C6DC
CAPF3030D6DC
CAPF3131B6DC
CAPF3131C6DC
CAPF3137B6AB
CAPF3636A6DC
Redesign the wrapper for the CAPF to provide increased ease of installation.
CAPF3636B6DC
CAPF3636C6DC
CAPF3636D6DC
CAPF3642C6DC
CAPF3642D6DC
CAPF3743C6DC
CAPF3743D6DC
CAPF4860C6DC
CAPF4860D6DC
CAPF4961C6DC
CAPF4961D6DC
22
ACCESSORIES
M ode l De s cription ASC13018 ASC13024 ASC13030 ASC13036 ASC13042 ASC13048 ASC13060
OT18-60A Outdoor Thermostat --- --- --- --- --- --- ---
FSK01A* Freeze Protection Kit X X X X X X X
ASC01 A nti Short Cycle Kit X X X X X X X
TX2N2* TXV Kit X --- --- --- --- --- ---
TX3N2* TXV Kit x x x x --- --- ---
TX5N2* TXV Kit --- --- --- --- X X X
CSR-U-1 Hard Start Kit X X X X --- --- ---
CSR-U-2 Hard Start Kit --- --- --- X X X X
CSR-U-3 Hard Start Kit --- --- --- --- --- X X
LSK02A Liquid Solenoid Kit X X X X X X X
M ode l De s cription G/V SC13018 G/V SC13024 G/V SC13030 G/V SC13036
OT18-60A Outdoor Thermostat --- --- --- ---
FSK01A* Freeze Protection Kit X X X X
ASC01 A nti Short Cycle Kit X X X X
TX2N2* TXV Kit X --- --- ---
TX3N2* TXV Kit x x x x
TX5N2* TXV Kit --- --- --- ---
CSR-U-1 Hard Start Kit X X X X
CSR-U-2 Hard Start Kit --- --- --- X
CSR-U-3 Hard Start Kit --- --- --- ---
LSK02A Liquid Solenoid Kit X X X x
23
ACCESSORIES
Model Description G/VSH13018 G/VSH13024 G/VSH13030 G/VSH13036 G/VSH13042 G/VSH13048 G/VSH13060
AFE18-60A All Fuel Kit X X X X X X X
OT18-60A Outdoor Thermostat X X X X X X X
FSK01A* Freeze Protection Kit X X X X X X X
ASC01 Anti Short Cycle Kit X X X X X X X
TX2N2* TXV Kit x --- --- --- --- --- ---
TX3N2* TXV Kit x X X X --- --- ---
TX5N2* TXV Kit --- --- --- --- X X X
OT18-60A Outdoor Lockout Stat X X X X X X X
OT/EHR18-60 Emergency Heat relay kit X X X X X X X
CSR-U-1 Hard Start Kit X X X X --- --- ---
CSR-U-2 Hard Start Kit --- --- --- X X X X
CSR-U-3 Hard Start Kit --- --- --- --- --- X X
LSK02A Liquid Solenoid Kit X X X X X X X
24
ACCESSORIES
Model Description CPKF24 CPKF36 CPKF42 CPKF48 CPKF60 CPKF61
AFE18-60A All Fuel Kit x x x x x x
OT18-60A Outdoor Thermostat x x x x x x
FSK01A* Freeze Protection Kit x x x x x x
ASC01 Anti Short Cycle Kit x x x x x x
TX2N2* TXV Kit --- --- --- --- --- ---
TX3N2* TXV Kit x x --- --- --- ---
TX5N2* TXV Kit --- --- x x x x
OT18-60A Outdoor Lockout Stat x x x x x x
OT/EHR18-60 Emergency Heat relay kit x x x x x x
CSR-U-1 Hard Start Kit x x --- --- --- ---
CSR-U-2 Hard Start Kit --- x x x x x
CSR-U-3 Hard Start Kit --- --- --- x x x
BULB TO BE LOCATED
AT 10 OR 2 O'CLOCK
a field installed access fitting
EVAPORATOR COIL
7/8" NUT
BULB TO BE LOCATED
AT 10 OR 2 O'CLOCK
PISTON TAILPIECE
EXPANSION VALVE
DISTRIBUTOR SEAL
EVAPORATOR COIL
BODY
3/8"-
SWEAT
OT/EHR18-60
OUTDOOR THERMOSTAT &
EMERGENCY HEAT RELAY
OT18-60
Thermostat
Dial
315º
DEAD
DIAL
WARM (Turn Counterclockwise)
45º
Set Point
Adjustment
Screw Set Point
Indicator
Mark
(Shown @ Oº F)
26
ACCESSORIES
FSK01A
FREEZE THERMOSTAT
KIT
Wire Nut
Y
Y
k
ac
Bl
k
ac
Bl
Wire Nut
Install Line
Install Line
Thermostat
Thermostat
Here
Here
Wire Nut
Bla
ck Y
Bla
ck
Y
Wire Nut
ASC01A
ANTI-SHORT -CYCLE CONTROL KIT
SHORT CYCLE
Y1 R1 PROTECTOR
Y2 R2
YELLOW 1
CONTACTOR
T2 T1
BLACK 1 Y
THERMOSTAT
L2 L1 WIRE
C
UNIT
BLACK 1 TERMINAL
BOARD
27
ACCESSORIES
COIL ACCESSORIES
FSK01A FREEZE
COIL MODEL TX2N2 TXV KIT TX3N2 TXV KIT TX5N2 TXV KIT
PROTECTION KIT
CA*F030B4* --- X --- X
CA*F036B4* --- X --- X
CA*F042C4* --- --- X X
CA*F048C4* --- --- X X
CA*F057D4* --- --- X X
CA*F060D4* --- --- X X
CHPF030A4* --- X --- X
CHPF036B4* --- X --- X
CHPF042A4* --- --- X X
CHPF048D4* --- --- X X
CHPF060D4* --- --- X X
CH36FCB --- X --- X
CH48FCB --- --- X X
CH60FCB --- --- X X
CA*F18246* X X --- X
CA*F30306* --- X --- X
CA*F36426* --- X X X
CHPF18246* X --- X X
CHPF30306* --- --- X X
CHPF36426* --- --- X X
CSCF1824N6* X --- --- X
CSCF303N6* --- X --- X
CSCF3642N6* --- X X X
MBR0800AA-1AA - X X X X X
MBR1200AA-1AA - X X X X X X X X X X
MBR1600AA-1AA - X X X X X X X X X X
MBR2000AA-1AA - X X X X X X X X X X
MBE1200AA-1AA - - - - X X X - - - -
MBE1600AA-1AA - - - - - X X - - - -
MBE2000AA-1AA - - - - - X X X - - -
MBE1200AA-1BA - X X X X X X - - - -
MBE1600AA-1BA - X X X X X X - - - -
MBE2000AA-1BA - X X X X X X X - - -
X = Allowable combinations ^ = Circuit 1: Single Phase for Air Handler Motor * = Revision level that my or may not be designated
- = Restricted combinations Circuit 2: 3-Phase for HKR3 Heater Kits C = Circuit Breaker option
28
PRODUCT DESIGN
This section gives a basic description of cooling unit opera-
tion, its various components and their basic operation. En-
sure your system is properly sized for heat gain and loss
according to methods of the Air Conditioning Contractors
Association (ACCA) or equivalent.
CONDENSING UNIT
These units are designed for free air discharge. Condensed
air is pulled through the condenser coil by a direct drive
propeller fan and then discharged from the cabinet top. The
unit requires no additional resistance (i.e. duct work) and
should not be added.
The GSH13, GSH14, ASH13 and VSH13 Heat Pump con-
densing units are designed for 208-230 dual voltage single GSC130361D* and GSC130481AG use Bristol® BENCH-
phase applications. The GSH13 3 ton model is available in MARK™ compressors, the most advanced compressors in
230V, 3 phase applications. The GSH13 4 and 5 ton models the industry today. The BENCHMARK™ reciprocating com-
are available for 230V, 3-phase and 460V, 3-phase applica- pressor can be recognized by a “J” in the fourth character of the
tions. compressor model number. Innovative mechanical design and
The units range in size from 1.5 to 5-ton and have a rating of gas management make the BENCHMARK™ compressor very
13 and 14 SEER. SEER efficiency is dependent upon the unit efficient and remarkably quiet. The sound content (frequency)
and its components. Refer to the "Technical Information" delivers exceptional acoustical characteristics and the virtu-
manual of the unit you are servicing for further details. ally round housing design is compact and also helps to reduce
the overall sound and vibration.
The GSC13, GSC14 and ASC13 and VSC13 Condensing
Units are made in 1.5 through 5 ton sizes. They are designed GSC130181BA and GSC130181CA use Panasonic® rotary
for 208-240 volt single phase applications. The GSC13 3 ton compressors.
model is available in 230V, 3 phase applications. The GSC13
4 and 5 ton models are available for 230V, 3-phase and 460V, COILS AND BLOWER COILS
3-phase applications. MBR/MBE blower cabinets are designed to be used as a two-
Suction and Liquid Line Connections piece blower and coil combination. MBR/MBE blower sections
can be attached to cased evaporator coil. This two-piece
All units come equipped with suction and liquid valves designed arrangement allows for a variety of mix-matching possibilities
for connection to refrigerant-type copper. Front seating valves providing greater flexibility. The MBE blower cabinet uses a
are factory-installed to accept the field-run copper. The total variable speed motor that maintains a constant airflow with a
refrigerant charge needed for a normal operation is also higher duct static.
factory-installed. For additional refrigerant line set information,
refer to the "Technical Information" manual of the unit you are It is approved for applications with cooling coils of up to 0.8
servicing. inches W.C. external static pressure and includes a feature
Compressors that allows airflow to be changed by +15%. The MBR blower
cabinet uses a PSC motor. It is approved for applications with
GSC13, VSC13, GSH13 and VSH13 use a mix of reciprocat- cooling coils of up to 0.5 inches W.C. external static pressure.
ing and scroll compressors, except for the VSC130181AA/BA
which uses a rotary compressor. The ASC13 and ASH13 use
the Copeland Scroll® Compressor. There are a number of
design characteristics which differentiate the scroll com-
pressor from the reciprocating compressor. One is the scroll.
A scroll is an involute spiral which, when matched with a
mating scroll form, generates a series of crescent-shaped gas
pockets between the members (see following illustration).
During compression, one scroll remains stationary while the
other form orbits. This motion causes the resulting gas pocket
to compress and push toward the center of the scrolls. When
the center is reached, the gas is discharged out a port located
at the compressor center.
29
PRODUCT DESIGN
The MBR/MBE blower cabinets with proper coil matches can ARPF*B 2 to 5 ton air handlers are dedicated for downflow
be positioned for upflow, counterflow, horizontal right or operation and are approved for modular homes. Flowrater.
horizontal left operation. All units are constructed with R-4.2 transformer and blower time delay are on all standard ARPF
insulation. In areas of extreme humidity (greater than 80% units. Both the ARUF and ARPF have direct-drive multi-
consistently), insulate the exterior of the blower with insula- speed motors.
tion having a vapor barrier equivalent to ductwork insulation,
AEPF is a multi-position, variable-speed air handler and can
providing local codes permit.
be used with R-410A or R-22 (models ending in 1/16). The
The CAPX/CHPX coils are equipped with a thermostatic unit's blower design includes a variable-speed DC motor and
expansion valve that has a built-in internal check valve for is compatible with heat pumps and variable-capacity cooling
refrigerant metering. The CACF/CAPF/CHPF coils are applications.
equipped with a fixed restrictor orifice.
ASPF is a multi-position air handler that can be used with R-
The coils are designed for upflow, counterflow or horizontal 410A or R-22 and it features a X-13 motor. This motor is a
application, using two-speed direct drive motors on the constant torque motor with very low power consumption and
CACF/CAPF/CHPX models and BPM (Brushless Perma- it is energized by a 24V signal. The X-13 features an
nent Magnet) or ECM motors on the MBE models. integrated control module and is compatible with heat pumps
The ARUF is a multi-position air handler (upflow/horizontal and cooling applications.
or downflow) and is equipped with a flowrator for cooling and
heat pump applications. Because of its seamless copper
tubing and aluminum fins, there are fewer leaks. The steel
cabinet of the ARUF is fully insulated and rust resistant.
Thermal expansion kits for air conditioning and heat pump
applications are available.
30
SYSTEM OPERATION
COOLING HEATING
The refrigerant used in the system is R-22. It is a clear, The heating portion of the refrigeration cycle is similar to the
colorless, non-toxic, non-irritating, and non-explosive liquid. cooling cycle. By energizing the reversing valve solenoid coil,
The chemical formula is CHCLF2. The boiling point, at the flow of the refrigerant is reversed. The indoor coil now
atmospheric pressure is -41.4°F. becomes the condenser coil, and the outdoor coil becomes
A few of the important principles that make the refrigeration the evaporator coil.
cycle possible are: heat always flows from a warmer to a The check valve at the indoor coil will open by the flow of
cooler body, under lower pressure a refrigerant will absorb refrigerant letting the now condensed liquid refrigerant by-
heat and vaporize at a low temperature, the vapors may be pass the indoor expansion device. The check valve at the
drawn off and condensed at a higher pressure and tempera- outdoor coil will be forced closed by the refrigerant flow,
ture to be used again. thereby utilizing the outdoor expansion device.
The indoor evaporator coil functions to cool and dehumidify The restrictor orifice used with the CA*F, CHPF coils and the
the air conditioned spaces through the evaporative process AR*F air handler will be forced onto a seat when running in
taking place within the coil tubes. the cooling cycle, only allowing liquid refrigerant to pass
NOTE: The pressures and temperatures shown in the through the orifice opening. In the heating cycle it will be
refrigerant cycle illustrations on the following pages are for forced off the seat allowing liquid to flow around the restrictor.
demonstration purposes only. Actual temperatures and pres- A check valve is not required in this circuit.
sures are to be obtained from the "Expanded Performance COOLING CYCLE
Chart." When the contacts of the room thermostat close making
Liquid refrigerant at condensing pressure and temperatures, terminals R to Y & G, the low voltage circuit of the transformer
(270 psig and 122°F), leaves the outdoor condensing coil is completed. Current now flows through the magnetic hold-
through the drier and is metered into the indoor coil through ing coils of the compressor contactor (CC) and fan relay
the metering device. As the cool, low pressure, saturated (RFC).
refrigerant enters the tubes of the indoor coil, a portion of the This draws in the normally open contact CC, starting the
liquid immediately vaporizes. It continues to soak up heat and compressor and condenser fan motors. At the same time
vaporizes as it proceeds through the coil, cooling the indoor contacts RFC close starting the indoor fan motor.
coil down to about 48°F.
When the thermostat is satisfied, it opens its contacts,
Heat is continually being transferred to the cool fins and tubes breaking the low voltage circuit, causing the compressor
of the indoor evaporator coil by the warm system air. This contactor and indoor fan relay to open, shutting down the
warming process causes the refrigerant to boil. The heat system.
removed from the air is carried off by the vapor.
If the room thermostat fan selector switch should be set on
As the vapor passes through the last tubes of the coil, it the "on" position, then the indoor blower would run continuous
becomes superheated, that is, it absorbs more heat than is rather than cycling with the compressor.
necessary to vaporize it. This is assurance that only dry gas
will reach the compressor. Liquid reaching the compressor Heat pumps energize the reversing valve thorough the "O"
can weaken or break compressor valves. circuit in the room thermostat. Therefore the reversing valve
remains energized as long as the thermostat subbase is in
The compressor increases the pressure of the gas, thus the cooling position. The only exception to this is during
adding more heat, and discharges hot, high pressure super- defrost.
heated gas into the outdoor condenser coil.
In the condenser coil, the hot refrigerant gas, being warmer
than the outdoor air, first loses its superheat by heat trans-
ferred from the gas through the tubes and fins of the coil. The
refrigerant now becomes saturated, part liquid, part vapor and
then continues to give up heat until it condenses to a liquid
alone. Once the vapor is fully liquefied, it continues to give up
heat which subcools the liquid, and it is ready to repeat the
cycle.
31
SYSTEM OPERATION
DEFROST CYCLE HEATING CYCLE
The defrosting of the outdoor coil is jointly controlled by the The reversing valve on the heat pump models is energized in
defrost timing board, defrost (30/60) control, and compressor the cooling cycle through the "O" terminal on the room
run time. thermostat.
Solid State Defrost Control These models have a 24 volt reversing valve coil. When the
During operation the power to the circuit board is controlled thermostat selector switch is set in the cooling position, the
by a temperature sensor, which is clamped to a return bend "O" terminal on the thermostat is energized all the time.
(3/8" coils) or a feeder tube (5 mm coils) entering the outdoor Care must be taken when selecting a room thermostat. Refer
coil. Defrost timing periods of 30, 60, or 90 minutes may be to the installation instructions shipped with the product for
selected by connecting the circuit board jumper to 30, 60, or approved thermostats.
90 respectively. Accumulation of time for the timing period
selected starts when the sensor closes (approximately 31°
F), and when the room thermostat calls for heat. At the end
of the timing period, the unit’s defrost cycle will be initiated
provided the sensor remains closed. When the sensor opens
(approximately 75° F), the defrost cycle is terminated and the
timing period is reset. If the defrost cycle is not terminated
due to the sensor temperature, a ten minute override inter-
rupts the unit’s defrost period. The new upgraded defrost
control has a 12 minute override interrupt.
DF2
90
DF1
60
30
W2 DFT
32
SYSTEM OPERATION
COOLING CYCLE
Reversing Valve
(Energized)
Indoor Outdoor
Coil Coil
Accumulator
Thermostatic
Expansion
Valve
Bi-Flow
Filter Dryer
Check Valve
HEATING CYCLE
Reversing Valve
(De-Energized)
Indoor Outdoor
Coil Coil
Accumulator
Thermostatic
Expansion
Valve
Bi-Flow
Filter Dryer
Check Valve
33
SYSTEM OPERATION
Most expansion valves used in current Amana® Brand Heat Pump products
use an internally checked expansion valve.
This type of expansion valve does not require an external check valve as shown above.
However, the principle of operation is the same.
In the cooling mode, the orifice is pushed into its In the heating mode, the orifice moves back off its
seat, forcing refrigerant to flow through the metered seat, allowing refrigerant to flow unmetered around
hole in the center of the orifice. the outside of the orifice.
34
SYSTEM OPERATION
COOLING CYCLE - CONDENSING UNIT
Indoor Outdoor
Coil Coil
Thermostatic
Expansion
Valve
35
SYSTEM OPERATION
AFE18-60A CONTROL BOARD during the heating season, it will turn on the furnace during the
cooling season on a “Y” cooling demand. In this situation, the
DESCRIPTION
furnace produces heat and increases the indoor temperature
The AFE18 control is designed for use in heat pump applica- thereby never satisfying the cooling demand. The furnace will
tions where the indoor coil is located above/downstream of a continue to operate and can only be stopped by switching the
gas or fossil fuel furnace. It will operate with single and two thermostat to the off position or removing power to the unit and
stage heat pumps and single and two stage furnaces. The then replacing the outdoor thermostat. When the AFE18
AFE18 control will turn the heat pump unit off when the receives a “Y” and “O” input from the indoor thermo-
furnace is turned on. An anti-short cycle feature is also stat, it recognizes this as a cooling demand in the cooling
incorporated which initiates a 3 minute timed off delay when mode. If the outdoor thermostat is stuck in the closed
the compressor goes off. On initial power up or loss and position switching the “Y” demand to the “W1” furnace input
restoration of power, this 3 minute timed off delay will be during the cooling mode as described above, the AFE18
initiated. The compressor won’t be allowed to restart until the won’t allow the furnace to operate. The outdoor thermostat
3 minute off delay has expired. Also included is a 5 second will have to be replaced to restore the unit to normal operation.
de-bounce feature on the “Y, E, W1 and O” thermostat inputs.
These thermostat inputs must be present for 5 seconds
before the AFE18 control will respond to it.
An optional outdoor thermostat, OT18-60A, can be used with HIGH VOLTAGE!
the AFE18 to switch from heat pump operation to furnace Disconnect ALL power before servicing
or installing. Multiple power sources
operation below a specific ambient temperature setting, i.e.
may be present. Failure to do so may
break even temperature during heating. When used in this cause property damage, personal injury
manner, the “Y” heat demand is switched to the “W1” input or death.
to the furnace by the outdoor thermostat and the furnace is
used to satisfy the first stage “Y” heat demand. On some
controls, if the outdoor thermostat fails closed in this position
36
TROUBLESHOOTING CHART
COOLING/HP ANALYSIS CHART
Sys te m
Uns atis factor y
Com plaint No Cooling Ope r ating
Cooling/He ating
Pr e s s ure s
37
SERVICING
Table of Contents
S-1 CHECKING VOLTAGE ............................................ 36 S-41 AEP* & MBE WITH SINGLE STAGE
S-2 CHECKING WIRING ............................................... 36 CONDENSERS ...................................................... 51
S-3 CHECKING THERMOSTAT, WIRING, S-41A A AEP* & MBE WITH SINGLE STAGE
AND ANTICIPATOR ................................................. 36 HEAT PUMPS .......................................................... 52
S-3A THERMOSTAT AND WIRING .................................. 36 S-60 ELECTRIC HEATER (OPTIONAL ITEM) ................ 53
S-3B COOLING ANTICIPATOR ........................................ 37 S-61A CHECKING HEATER LIMIT CONTROL(S) ............ 54
S-3C HEATING ANTICIPATOR ......................................... 37 S-61B CHECKING HEATER FUSE LINK (OPTIONAL
S-4 CHECKING TRANSFORMER AND ELECTRIC HEATERS) ........................................... 54
CONTROL CIRCUIT ............................................... 37 S-62 CHECKING HEATER ELEMENTS ......................... 54
S-5 CHECKING CYCLE PROTECTOR ........................ 37 S-100 REFRIGERATION REPAIR PRACTICE .................. 55
S-6 CHECKING TIME DELAY RELAY ............................ 38 S-101 LEAK TESTING (NITROGEN OR
S-7 CHECKING CONTACTOR AND/OR RELAYS ........ 38 NITROGEN-TRACED) ............................................ 55
S-8 CHECKING CONTACTOR CONTACTS ................. 38 S-102 EVACUATION .......................................................... 55
S-9 CHECKING FAN RELAY CONTACTS ..................... 38 S-103 CHARGING ............................................................. 56
S-10 COPELAND COMFORT ALERT™ .......................... 39 S-104 CHECKING COMPRESSOR EFFICIENCY ............ 57
S-11 CHECKING LOSS OF CHARGE PROTECTOR .... 41 S-105A PISTON KIT CHART FOR ASC13, GSC13, VSC13,
S-15 CHECKING CAPACITOR ........................................ 41 GSC14, ASH13, GSH13, VSH14, GSH14 UNITS .. 58
S-15A RESISTANCE CHECK ............................................ 41 S-105B THERMOSTATIC EXPANSION VALVE ................... 58
S-15B CAPACITANCE CHECK .......................................... 42 S-106 OVERFEEDING ...................................................... 59
S-16A CHECKING FAN AND BLOWER S-107 UNDERFEEDING ................................................... 59
MOTOR WINDINGS S-108 SUPERHEAT .......................................................... 59
(PSC MOTORS) ...................................................... 42 S-109 CHECKING SUBCOOLING .................................... 60
S-16B CHECKING FAN AND S-110 CHECKING EXPANSION VALVE OPERATION ....... 60
BLOWER MOTOR (ECM MOTORS) ....................... 42 S-111 FIXED ORIFICE RESTRICTOR DEVICES ............. 61
S-16C CHECKING ECM MOTOR WINDINGS ................... 43 S-112 CHECKING RESTRICTED LIQUID LINE .............. 61
S-16D ECM CFM ADJUSTMENTS ..................................... 43 S-113 OVERCHARGE OF REFRIGERANT ...................... 61
S-16E CHECKING GE X13TM MOTORS .......................... 47 S-114 NON-CONDENSABLES ......................................... 61
S-17 CHECKING COMPRESSOR .................................. 47 S-115 COMPRESSOR BURNOUT ................................... 61
S-17A RESISTANCE TEST ................................................ 47 S-120 REFRIGERANT PIPING ......................................... 62
S-17B GROUND TEST ...................................................... 48 S-122 REVERSING VALVE REPLACEMENT .................... 64
S-17D OPERATION TEST .................................................. 48 S-202 DUCT STATIC PRESSURES AND/OR
S-18 TESTING CRANKCASE HEATER STATIC PRESSURE DROP ACROSS COILS ........ 64
(OPTIONAL ITEM) ................................................... 49 S-203 AIR HANDLER EXTERNAL STATIC ........................ 64
S-21 CHECKING REVERSING VALVE AND SOLENOID . 49 S-204 COIL STATIC PRESSURE DROP .......................... 65
S-24 TESTING DEFROST CONTROL ............................ 49
S-25 TESTING DEFROST THERMOSTAT ...................... 49
S-40 AR*F & MBR ELECTRONIC BLOWERS
TIME DELAY RELAY ................................................ 50
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
38
SERVICING
S-1 CHECKING VOLTAGE S-2 CHECKING WIRING
WARNING
Line Voltage now present.
2. Using a voltmeter, measure the voltage across terminals 1. Check wiring visually for signs of overheating, damaged
L1 and L2 of the contactor for the condensing unit or at the insulation and loose connections.
field connections for the air handler or heaters. 2. Use an ohmmeter to check continuity of any suspected
3. No reading - indicates open wiring, open fuse(s) no power open wires.
or etc., from unit to fused disconnect service. Repair as 3. If any wires must be replaced, replace with comparable
needed. gauge and insulation thickness.
4. With ample voltage at line voltage connectors, energize
the unit. S-3 CHECKING THERMOSTAT, WIRING, AND
5. Measure the voltage with the unit starting and operating, ANTICIPATOR
and determine the unit Locked Rotor Voltage. NOTE: If THERMOSTAT WIRE SIZING CHART
checking heaters, be sure all heating elements are
energized. MIN. COPPER WIRE
LENGTH OF RUN
GAUGE (AWG)
Locked Rotor Voltage is the actual voltage available at 25 feet 18
the compressor during starting, locked rotor, or a stalled 50 feet 16
condition. Measured voltage should be above minimum 75 feet 14
listed in chart below.
100 feet 14
To measure Locked Rotor Voltage attach a voltmeter to 125 feet 12
the run "R" and common "C" terminals of the compressor, 150 feet 12
or to the T1 and T2 terminals of the contactor. Start the unit
and allow the compressor to run for several seconds, then S-3A THERMOSTAT AND WIRING
shut down the unit. Immediately attempt to restart the
unit while measuring the Locked Rotor Voltage.
WARNING
6. Lock rotor voltage should read within the voltage tabula-
Line Voltage now present.
tion as shown. If the voltage falls below the minimum
voltage, check the line wire size. Long runs of undersized
wire can cause low voltage. If wire size is adequate, notify With power ON, thermostat calling for cooling
the local power company in regard to either low or high 1. Use a voltmeter to check for 24 volts at thermostat wires
voltage. C and Y in the condensing unit control panel.
2. No voltage indicates trouble in the thermostat, wiring or
REMOTE CONDENSING UNITS external transformer source.
BLOWER COILS
3. Check the continuity of the thermostat and wiring. Repair
VOLTAGE MIN. MAX. or replace as necessary.
Indoor Blower Motor
208/230 198 253
With power ON:
115 104 127
39
SERVICING
3. No voltage indicates the trouble is in the thermostat or A step-down transformer (208/240 volt primary to 24 volt sec-
wiring. ondary) is provided with each indoor unit. This allows ample
4. Check the continuity of the thermostat and wiring. Repair capacity for use with resistance heaters. The outdoor sec-
or replace as necessary. tions do not contain a transformer.
Resistance Heaters
WARNING
1. Set room thermostat setpoint to a higher temperature Disconnect ALL power before servicing.
than room temperature to assure both stages call for
heat. 1. Remove control panel cover, or etc., to gain access to
2. With voltmeter, check for 24 volts at each heater relay. transformer.
Note: BBA/BBC heater relays are DC voltage.
With power ON:
3. No voltage indicates the trouble is in the thermostat or
wiring.
WARNING
4. Check the continuity of the thermostat and wiring. Repair
Line Voltage now present.
or replace as necessary.
NOTE: Consideration must be given to how the heaters are 2. Using a voltmeter, check voltage across secondary volt-
wired (O.D.T. and etc.). Also safety devices must be checked age side of transformer (R to C).
for continuity.
3. No voltage indicates faulty transformer, bad wiring, or bad
splices.
S-3B COOLING ANTICIPATOR
4. Check transformer primary voltage at incoming line volt-
The cooling anticipator is a small heater (resistor) in the age connections and/or splices.
thermostat. During the "off" cycle, it heats the bimetal
element helping the thermostat call for the next cooling cycle. 5 If line voltage available at primary voltage side of trans-
This prevents the room temperature from rising too high former and wiring and splices good, transformer is inop-
before the system is restarted. A properly sized anticipator erative. Replace.
should maintain room temperature within 1 1/2 to 2 degree
range. S-5 CHECKING CYCLE PROTECTOR
The anticipator is supplied in the thermostat and is not to be Some models feature a solid state, delay-on make after break
replaced. If the anticipator should fail for any reason, the time delay relay installed in the low voltage circuit. This
thermostat must be changed. control is used to prevent short cycling of the compressor
under certain operating conditions.
S-3C HEATING ANTICIPATOR The component is normally closed (R1 to Y1). A power
The heating anticipator is a wire wound adjustable heater interruption will break circuit (R1 to Y1) for approximately three
which is energized during the "ON" cycle to help prevent minutes before resetting.
overheating of the conditioned space.
The anticipator is a part of the thermostat and if it should fail 1. Remove wire from Y1 terminal.
for any reason, the thermostat must be replaced. See the 2. Wait for approximately four (4) minutes if machine was
following tables for recommended heater anticipator setting running.
in accordance to the number of electric heaters installed.
With power ON:
problems that may be relayed to the output response of the
B13682-74 VSTM control.
WARNING
S-4 CHECKING TRANSFORMER AND CON- Line Voltage now present.
TROL CIRCUIT
1. Apply 24 VAC to terminals R1 and R2.
2. Should read 24 VAC at terminals Y1 and Y2.
40
SERVICING
3. Remove 24 VAC at terminals R1 and R2. contacts or opens the normally closed contacts. When the
4. Should read 0 VAC at Y1 and Y2. coil is de-energized, springs return the contacts to their
normal position.
5. Reapply 24 VAC to R1 and R2 - within approximately
three (3) to four (4) minutes should read 24 VAC at Y1 and NOTE: Most single phase contactors break only one side of
Y 2. the line (L1), leaving 115 volts to ground present at most
internal components.
If not as above - replace relay.
1. Remove the leads from the holding coil.
S-6 CHECKING TIME DELAY RELAY 2. Using an ohmmeter, test across the coil terminals.
Time delay relays are used in some of the blower cabinets to If the coil does not test continuous, replace the relay or
improve efficiency by delaying the blower off time. Time contactor.
delays are also used in electric heaters to sequence in
multiple electric heaters. S-8 CHECKING CONTACTOR CONTACTS
WARNING
Disconnect ALL power before servicing. WARNING
1. Tag and disconnect all wires from male spade connec- DISCONNECT ELECTRICAL POWER SUPPLY.
tions of relay.
2. Using an ohmmeter, measure the resistance across Disconnect Electrical Power Supply:
terminals H1 and H2. Should read approximately 150 1. Disconnect the wire leads from the terminal (T) side of the
ohms. contactor.
3. Using an ohmmeter, check for continuity across termi- 2. With power ON, energize the contactor.
nals 3 and 1, and 4 and 5.
4. Apply 24 volts to terminals H1 and H2. Check for WARNING
continuity across other terminals - should test continu-
Line Voltage now present.
ous. If not as above - replace.
NOTE: The time delay for the contacts to make will be 3. Using a voltmeter, test across terminals.
approximately 20 to 50 seconds and to open after the coil is
de-energized is approximately 40 to 90 seconds. A. L2 - T1 - No voltage indicates CC1 contacts open.
If a no voltage reading is obtained - replace the contactor.
T2 T1
OHMMETER
CC
VOLT/OHM
METER
TESTING COIL CIRCUIT L2 L1
41
SERVICING
1. Disconnect wires leads from terminals 2 and 4 of Fan
Relay Cooling and 2 and 4, 5 and 6 of Fan Relay Heating.
2. Using an ohmmeter, test between 2 and 4 - should read
open. Test between 5 and 4 - should read continuous.
3. With power ON, energize the relays.
WARNING
Line Voltage now present.
4
3
OHMMETER
2 5 1
DIAGNOSTICS
Applies to ASC13 & ASH13
42
SERVICING
DIAGNOSTICS TABLE
Status LED Status LED Description Status LED Troubleshooting Information
Green “POWER” Module has power Supply voltage is present at module terminals
Red “TRIP” Thermostat demand signal 1. Compressor protector is open
Y1 is present, but the 2. Outdoor unit power disconnect is open
compressor is not 3. Compressor circuit breaker or fuse(s) is open
running 4. Broken wire or connector is not making contact
5. Low pressure switch open if present in system
6. Compressor contactor has failed open
Yellow “ALERT” Long Run Time 1. Low refrigerant charge
Flash Code 1 Compressor is 2. Evaporator blower is not running
running extremely 3. Evaporator coil is frozen
long run cycles 4. Faulty metering device
5. Condenser coil is dirty
6. Liquid line restriction (filter drier blocked if present in system)
7. Thermostat is malfunctioning
Yellow “ALERT” System Pressure Trip 1. High head pressure
Flash Code 2 Discharge or suction 2. Condenser coil poor air circulation (dirty, blocked, damaged)
pressure out of limits or 3. Condenser fan is not running
compressor overloaded 4. Return air duct has substantial leakage
5. If low pressure switch present in system,
check Flash Code 1 information
Yellow “ALERT” Short Cycling 1. Thermostat demand signal is intermittent
Flash Code 3 Compressor is running 2. Time delay relay or control board defective
only briefly 3. If high pressure switch present go to Flash Code 2 information
4. If low pressure switch present go to Flash Code 1 information
Yellow “ALERT” Locked Rotor 1. Run capacitor has failed
Flash Code 4 2. Low line voltage (contact utility if voltage at disconnect is low)
3. Excessive liquid refrigerant in compressor
4. Compressor bearings are seized
Yellow “ALERT” Open Circuit 1. Outdoor unit power disconnect is open
Flash Code 5 2. Compressor circuit breaker or fuse(s) is open
3. Compressor contactor has failed open
4. High pressure switch is open and requires manual reset
5. Open circuit in compressor supply wiring or connections
6. Unusually long compressor protector reset time
due to extreme ambient temperature
7. Compressor windings are damaged
Yellow “ALERT” Open Start Circuit 1. Run capacitor has failed
Flash Code 6 Current only in run circuit 2. Open circuit in compressor start wiring or connections
3. Compressor start winding is damaged
Yellow “ALERT” Open Run Circuit 1. Open circuit in compressor run wiring or connections
Flash Code 7 Current only in start circuit 2. Compressor run winding is damaged
Yellow “ALERT” Welded Contactor 1. Compressor contactor has failed closed
Flash Code 8 Compressor always runs 2. Thermostat demand signal not connected to module
Yellow “ALERT” Low Voltage 1. Control circuit transformer is overloaded
Flash Code 9 Control circuit < 17VAC 2. Low line voltage (contact utility if voltage at disconnect is low)
• Flash Code number corresponds to a number of LED flashes, followed by a pause and then repeated
• TRIP and ALERT LEDs flashing at same time means control circuit voltage is too low for operation.
• Reset ALERT Flash code by removing 24VAC power from module
• Last ALERT Flash code is displayed for 1 minute after module is powered on.
43
SERVICING
reduce light dimming within the home. Only hard start kits
approved by Amana® brand or Copeland should be used.
"Kick Start" and/or "Super Boost" kits are not approved start
assist devices.
The discharge check valve closes off high side pressure to the
compressor after shut down allowing equalization through the
scroll flanks. Equalization requires only about ½ second.
To prevent the compressor from short cycling, a Time Delay
Relay (Cycle Protector) has been added to the low voltage
circuit.
RELAY, START
A potential or voltage type relay is used to take the start
capacitor out of the circuit once the motor comes up to speed.
This type of relay is position sensitive. The normally closed
contacts are wired in series with the start capacitor and the
relay holding coil is wired parallel with the start winding. As
the motor starts and comes up to speed, the increase in
voltage across the start winding will energize the start relay
holding coil and open the contacts to the start capacitor.
Two quick ways to test a capacitor are a resistance and a
capacitance check.
S-11 CHECKING LOSS OF CHARGE PROTECTOR START
CAPACITOR
(Heat Pump Models)
The loss of charge protector senses the pressure in the liquid
line and will open its contacts on a drop in pressure. The low
pressure control will automatically reset itself with a rise in
pressure. RED 10
VIOLET 20
The low pressure control is designed to cut-out (open) at YELLOW 12
approximately 7 PSIG. It will automatically cut-in (close) at START
approximately 25 PSIG. RELAY
Test for continuity using a VOM and if not as above, replace ORANGE 5
the control.
HERM
COM
FAN
T2 T1
S-15 CHECKING CAPACITOR
CAPACITOR, RUN RUN L2 L1
CAPACITOR
A run capacitor is wired across the auxiliary and main
CONTACTOR
windings of a single phase permanent split capacitor motor.
The capacitors primary function is to reduce the line current
while greatly improving the torque characteristics of a motor.
HARD START KIT WIRING
This is accomplished by using the 90° phase relationship
between the capacitor current and voltage in conjunction with
S-15A RESISTANCE CHECK
the motor windings, so that the motor will give two phase
operation when connected to a single phase circuit. The
capacitor also reduces the line current to the motor by
improving the power factor.
The line side of this capacitor is marked with "COM" and is
wired to the line side of the circuit.
CAPACITOR, START
SCROLL COMPRESSOR MODELS
In most cases hard start components are not required on
Scroll compressor equipped units due to a non-replaceable
check valve located in the discharge line of the compressor.
However, in installations that encounter low lock rotor volt-
age, a hard start kit can improve starting characteristics and
44
SERVICING
1. Discharge capacitor and remove wire leads.
WARNING
WARNING Discharge capacitor through a 20 to 30 OHM
Discharge capacitor through a 20 to 30 OHM resistor before handling.
resistor before handling.
Capacitance (MFD) = 2650 X Amperage
Voltage
WARNING
TESTING CAPACITANCE Line Voltage now present.
45
SERVICING
1. Disconnect the 5-pin connector from the motor.
2. Using a volt meter, check for line voltage at terminals #4
& #5 at the power connector. If no voltage is present: OUT - 8 16 OUT +
3. Check the unit for incoming power See section S-1.
ADJUST +/- 7 15 G (FAN)
4. Check the control board, See section S-40.
5. If line voltage is present, reinsert the 5-pin connector and Y1 6 14 Y/Y2
remove the 16-pin connector.
6. Check for signal (24 volts) at the transformer. COOL 5 13 EM Ht/W2
7. Check for signal (24 volts) from the thermostat to the "G"
terminal at the 16-pin connector. DELAY 4 12 24 Vac (R)
3 Gnd
4 AC Line Connection
5 AC Line Connection
1. Disconnect the 5-pin and the 16-pin connectors from the
ECM power head.
2. Remove the 2 screws securing the ECM power head and
separate it from the motor.
3. Disconnect the 3-pin motor connector from the power
head and lay it aside.
4. Using an ohmmeter, check the motor windings for
continuity to ground (pins to motor shell). If the ohmme-
ter indicates continuity to ground, the motor is defective
and must be replaced.
5. Using an ohmmeter, check the windings for continuity
(pin to pin). If no continuity is indicated, the thermal limit
(over load) device may be open. Allow motor to cool and
retest.
46
Troubleshooting Chart for ECM Variable Speed Air Circulator Blower Motors
Symptom Fault Description(s) Possible Causes Corrective Action Cautions and Notes
- Motor rocks
- This is normal start-up for
slightly ---- ---- ----
variable speed motor.
when starting.
- Motor
oscillates up & - It is normal for motor to
down while oscillate with ---- ---- ----
being tested no load on shaft.
off of blower.
- Variation in 230 Vac to motor. - Check line voltage for variation or "sag".
- Unseated pins in wiring harness - Check low voltage connections
connectors. (G, Y, W, R, C) at
- Varies up and down
- Erratic CFM command from motor, unseated pins in motor - Turn power OFF prior to repair.
or intermittent.
"BK" terminal. harness connectors.
- Motor starts, - Improper thermostat connection or setting. - Check-out system controls - Thermostat.
but runs - Moisture present in motor/control module. - Perform Moisture Check.*
erratically.
- Does removing panel or filter
- Incorrect or dirty filter(s). reduce "puffing"?
- "Hunts" or "puffs" at
- Incorrect supply or return ductwork. - Check/replace filter. - Turn power OFF prior to repair.
high CFM (speed).
- Incorrect blower speed setting. - Check/correct duct restrictions.
- Adjust to correct blower speed setting.
*Moisture Check
- Connectors are oriented "down" (or as recommended by equipment manufacturer). - Arrange harnesses with "drip loop" under motor.
- Is condensate drain plugged? - Check for low airflow (too much latent capacity).
- Check for undercharged condition. - Check and plug leaks in return ducts, cabinet.
Note: You must use the correct replacement control/motor module since they are factory programmed for specific operating modes. Even though they look alike, different modules may have completely different
functionality. The ECM variable speed motors are c
Important Note: Using the wrong motor/control module voids all product warranties and may produce unexpected results.
47
48
CHART CONTINUED FROM PREVIOUS PAGE
Troubleshooting Chart for ECM Variable Speed Air Circulator Blower Motors
Symptom Fault Description(s) Possible Causes Corrective Action Cautions and Notes
- Loose blower housing, panels, etc. - Check for loose blower housing,
- High static creating high blower panels, etc.
- Excessive - Noisy blower or cabinet. speed. - Check for air whistling thru seams in - Turn power OFF prior to repair.
noise. - Air leaks in ductwork, cabinets, ducts, cabinets or panels.
or panels. - Check for cabinet/duct deformation.
*Moisture Check
- Connectors are oriented "down" (or as recommended by equipment manufacturer). - Arrange harnesses with "drip loop" under motor.
- Is condensate drain plugged? - Check for low airflow (too much latent capacity).
- Check for undercharged condition. - Check and plug leaks in return ducts, cabinet.
Note: You must use the correct replacement control/motor module since they are factory programmed for specific operating modes. Even though they look alike, different modules may have completely different
functionality. The ECM variable speed motors are c
Important Note: Using the wrong motor/control module voids all product warranties and may produce unexpected results.
SERVICING
CFM DELIVERY
Tables 2, 2A and 3, 3A show the CFM output for dipswitch
3-pin motor
connector combinations 1-2, 5-6 and 7-8.
Table 1
49
SERVICING
HUMIDITY CONTROL
Dipsw itch 1/2 & 7/8
When using a Humidstat (normally closed), cut jumper PJ6
AEPF 1830
on the control board. The Humidstat will only affect cooling
Heating Sw itch Sw itch Heat Pump
Emergency airflow by adjusting the Airflow to 85%.
Element Position Position W ith
Backup
(kw) 1 2 7 8 Backup TWO STAGE HEATING
UP TO 10 O FF O FF O FF O FF 1100 1210 When using staged electric heat, cut jumper PJ4 on the
UP TO 10 ON O FF O FF O FF 890 935 control board.
5 O FF ON O FF O FF 700 770
S-16E CHECKING GE X13TM MOTORS
AEPF3036 / 3137 / 4260 The GE X13TM Motor is a one piece, fully encapsulated, 3
Heating Sw itch Sw itch
Emergency
Heat Pump phase brushless DC (single phase AC input) motor with ball
Element Position Position
Backup
W ith bearing construction. Unlike the ECM 2.3/2.5 motors, the GE
(kw) 1 2 7 8 Backup X13TM features an integral control module.
UP TO 20 O FF O FF O FF O FF 2050 2150
UP TO 20 ON O FF O FF O FF 1750 1835
Note: The GE TECMate will not currently operate the GE
X13TM motor.
UP TO 15 O FF ON O FF O FF 1600 1680
1. Using a voltmeter, check for 230 volts to the motor
UP TO 10 ON ON O FF O FF 1200 1260
connections L and N. If 230 volts is present, proceed to
UP TO 10 ON ON O FF ON 1020 1070
step 2. If 230 volts is not present, check the line voltage
Table 3 circuit to the motor.
Dipsw itch 5/6 & 7/8 2. Using a voltmeter, check for 24 volts from terminal C to
AEPF 1830 either terminal 1, 2, 3, 4, or 5, depending on which tap is
Sw itch Sw itch being used, at the motor. If voltage present, proceed to
Indoor Airflow
Position Position step 3. If no voltage, check 24 volt circuit to motor.
5 6 7 8 Cooling Heat Pump 3. If voltage was present in steps 1 and 2, the motor has
O FF O FF O FF O FF 1100 1100 failed and will need to be replaced.
ON O FF O FF O FF 800 800
O FF ON O FF O FF 600 600
Note: When replacing motor, ensure the belly band is
between the vents on the motor and the wiring has the
proper drip loop to prevent condensate from entering the
AEPF3036 / 3137 / 4260
motor.
Sw itch Sw itch
Indoor Airflow
Position Position
5 6 7 8 Cooling Heat Pump
O FF O FF O FF O FF 1800 1800 High Voltage
ON O FF O FF O FF 1580 1580
Connections
O FF ON O FF O FF 1480 1480
ON ON O FF O FF 1200 1200
3/16"
ON ON O FF ON
Table 3A
1020 1020
C L G N
THERMOSTAT “FAN ONLY” MODE
During Fan Only Operations, the CFM output is 30% of the
cooling setting.
CFM TRIM ADJUST
Minor adjustments can be made through the dip switch
combination of 7-8. Table 4 shows the switch position for
this feature.
NOTE: The airflow will not make the decreasing adjustment
1 2 3 4 5
in Electric Heat mode.
Low Voltage Connections
C FM S w it c h 7 S w it c h 8
1/4”
+10% ON O FF
-1 5 % OFF ON
GE X13TM MOTOR CONNECTIONS
Table 4
50
SERVICING
S-17 CHECKING COMPRESSOR
WARNING
Hermetic compressor electrical terminal venting can
be dangerous. When insulating material which
supports a hermetic compressor or electrical terminal
suddenly disintegrates due to physical abuse or as a
1. Remove the leads from the compressor terminals.
result of an electrical short between the terminal and
the compressor housing, the terminal may be
expelled, venting the vapor and liquid contents of the
compressor housing and system.
See warnings S-17 before removing compressor
terminal cover.
If the compressor terminal PROTECTIVE COVER and gasket
(if required) are not properly in place and secured, there is a 2. Using an ohmmeter, test continuity between terminals S-
remote possibility if a terminal vents, that the vaporous and R, C-R, and C-S, on single phase units or terminals T2,
liquid discharge can be ignited, spouting flames several feet, T2 and T3, on 3 phase units.
causing potentially severe or fatal injury to anyone in its path.
This discharge can be ignited external to the compressor if
the terminal cover is not properly in place and if the discharge
impinges on a sufficient heat source.
C
Ignition of the discharge can also occur at the venting terminal
or inside the compressor, if there is sufficient contaminant air OHMMETER S R
present in the system and an electrical arc occurs as the COMP
terminal vents.
Ignition cannot occur at the venting terminal without the TESTING COMPRESSOR WINDINGS
presence of contaminant air, and cannot occur externally
If either winding does not test continuous, replace the
from the venting terminal without the presence of an external
compressor.
ignition source.
NOTE: If an open compressor is indicated, allow ample time
Therefore, proper evacuation of a hermetic system is essen-
for the internal overload to reset before replacing compressor.
tial at the time of manufacture and during servicing.
To reduce the possibility of external ignition, all open flame, S-17B GROUND TEST
electrical power, and other heat sources should be extin-
guished or turned off prior to servicing a system. If fuse, circuit breaker, ground fault protective device, etc.,
has tripped, this is a strong indication that an electrical
If the following test indicates shorted, grounded or open problem exists and must be found and corrected. The circuit
windings, see procedures S-19 for the next steps to be taken. protective device rating must be checked, and its maximum
rating should coincide with that marked on the equipment
S-17A RESISTANCE TEST nameplate.
Each compressor is equipped with an internal overload. With the terminal protective cover in place, it is acceptable to
The line break internal overload senses both motor amperage replace the fuse or reset the circuit breaker ONE TIME ONLY
and winding temperature. High motor temperature or amper- to see if it was just a nuisance opening. If it opens again, DO
age heats the disc causing it to open, breaking the common NOT continue to reset.
circuit within the compressor on single phase units. Disconnect all power to unit, making sure that all power
Heat generated within the compressor shell, usually due to legs are open.
recycling of the motor, high amperage or insufficient gas to 1. DO NOT remove protective terminal cover. Disconnect
cool the motor, is slow to dissipate. Allow at least three to the three leads going to the compressor terminals at the
four hours for it to cool and reset, then retest. nearest point to the compressor.
Fuse, circuit breaker, ground fault protective device, etc. has 2. Identify the leads and using a Megger, Hi-Potential
not tripped - Ground Tester, or other suitable instrument which puts
out a voltage between 300 and 1500 volts, check for a
ground separately between each of the three leads and
ground (such as an unpainted tube on the compressor).
Do not use a low voltage output instrument such as a volt-
ohmmeter.
51
SERVICING
WARNING
Line Voltage now present.
54
SERVICING
S-41 AEP* & MBE WITH SINGLE STAGE CON- blower motor on low speed on a “W1” only demand. If the
DENSERS first stage heat demand, “W1” cannot be satisfied by the
heat pump, the temperature indoors will continue to drop.
AEP* & MBE ELECTRONIC BLOWER TIME DELAY RELAY The room thermostat will then energize “W2” and 24Vac
SEQUENCE OF OPERATION will be supplied to HR2 on the heater assembly and the
This document covers the basic sequence of operation for a blower motor will change to high speed. When the “W2”
typical application with a mercury bulb thermostat. When a demand is satisfied, the room thermostat will remove the
digital/electronic thermostat is used, the on/off staging of the 24Vac from “W2” and the VSTB will remove the 24Vac
auxiliary heat will vary. Refer to the installation instructions from HR2. The contacts on HR2 will open between 30 to
and wiring diagrams provided with the MBE for specific wiring 70 seconds and heater elements #3 and #4 will be turned
connections, dip switch settings and system configuration. off and the blower motor will change to low speed. On
most digital/electronic thermostats, “W2” will re-
AEP* & MBE WITH SINGLE STAGE CONDENSERS main energized until the first stage demand “W1” is
When used with a single stage condenser, dip switch #4 satisfied and then the “W1” and “W2” demands will
must be set to the on position on the VSTB inside the MBE. be removed.
The “Y” output from the indoor thermostat must be connected 2.3 When the “W1” heat demand is satisfied, the room
to the yellow wire labeled “Y/Y2” inside the wire bundle thermostat will remove the 24Vac from “E/W1” and the
marked “Thermostat” and the yellow wire labeled “Y/Y2” VSTB removes the 24Vac from HR1. The contacts on
inside the wire bundle marked “Outdoor Unit” must be HR1 will open between 30 to 70 seconds and turn off the
connected to “Y” at the condenser. The orange jumper wire heater element(s) and the blower motor ramps down to a
from terminal “Y1” to terminal “O” on the VSTB inside the complete stop.
MBE must remain connected.
1.0 Cooling Operation S-41A AEP* & MBE WITH SINGLE STAGE HEAT
PUMPS
1.1 On a demand for cooling, the room thermostat energizes
“G” and “Y” and 24Vac is supplied to “G” and “Y/Y2” of the When used with a single stage heat pump, dip switch #4 must
MBE unit. The VSTB inside the MBE will turn on the be set to the ON position on the VSTB inside the MBE. The
blower motor and the motor will ramp up to the speed “Y” output from the indoor thermostat must be connected to
programmed in the motor based on the settings for dip the yellow wire labeled “Y/Y2” inside the wire bundle marked
switch 5 and 6. The VSTB will supply 24Vac to “Y” at the “Thermostat” and the yellow wire labeled “Y/Y2” inside the
condenser and the compressor and condenser are turned wire bundle marked “Outdoor Unit” must be connected to “Y”
on. at the heat pump. The orange jumper wire from terminal
1.2 When the cooling demand is satisfied, the room thermo- “Y1” to terminal “O” on the VSTB inside the MBE must
stat removes the 24Vac from “G” and “Y”. The MBEand be removed.
AEP* remove the 24Vac from “Y’ at the condenser and the 3.0 Cooling Operation
compressor and condenser fan are turned off. The blower
motor will ramp down to a complete stop based on the On heat pump units, when the room thermostat is set to the
time and rate programmed in the motor. cooling mode, 24Vac is supplied to terminal “O” of the VSTB
inside the MBE unit. The VSTB will supply 24Vac to “O” at
2.0 Heating Operation
the heat pump to energize the reversing valve. As long as the
2.1 On a demand for heat, the room thermostat energizes thermostat is set for cooling, the reversing valve will be in the
“W1” and 24Vac is supplied to terminal “E/W1” of the energized position for cooling.
VSTB inside the MBEand AEP* units. The VSTB will turn
on the blower motor and the motor will ramp up to the 3.1 On a demand for cooling, the room thermostat energizes
speed programmed in the motor based on the settings for “G” and “Y” and 24Vac is supplied to terminals “G” and “Y/
dip switch 1 and 2. The VSTB will supply 24Vac to heat Y2” of the MBE unit. The VSTB will turn on the blower
sequencer HR1 on the electric heater assembly. motor and the motor will ramp up to the speed pro-
grammed in the motor based on the settings of dip switch
2.2 HR1 contacts M1 and M2 will close within 10 to 20 5 and 6. The VSTB will supply 24Vac to “Y” at the heat
seconds and turn on heater element #1. At the same pump.
time, if the heater assembly contains a second heater
element, HR1 will contain a second set of contacts, M3 3.2 The heat pump is turned on in the cooling mode.
and M4, which will close and turn on heater element #2. 3.3 When the cooling demand is satisfied, the room thermo-
Note: If more than two heater elements are on the heater stat removes the 24Vac from “G” and “Y/Y2” of the MBE
assembly, it will contain a second heat sequencer, HR2, and the VSTB removes the 24Vac from “Y” at the heat
which will control the 3rd and 4th heater elements if pump. The heat pump is turned off and the blower motor
available. For the 3rd and 4th heater elements to will ramp down to a complete stop based on the time and
operate on a second stage heat demand, the PJ4 rate programmed in the motor.
jumper on the VSTB inside the MBE and AEP* must
be cut. With the PJ4 jumper cut, the VSTB will run the
55
SERVICING
4.0 Heating Operation 4.5 When the first stage heat demand “Y” is satisfied, the
On heat pump units, when the room thermostat is set to the room thermostat will remove the 24Vac from “G” and “Y/
Y2” of the MBE and AEP*. The VSTB removes the 24Vac
heating mode, the reversing valve is not energized. As long
from “Y” at the heat pump and the heat pump is turned off.
as the thermostat is set for heating, the reversing valve will be
The blower motor will ramp down to a complete stop
in the de-energized position for heating except during a
based on the time and rate programmed in the motor
defrost cycle. Some installations may use one or more control.
outdoor thermostats to restrict the amount of electric heat
that is available above a preset ambient temperature. Use of 5.0 Defrost Operation
optional controls such as these can change the operation of On heat pump units, when the room thermostat is set to the
the electric heaters during the heating mode. This sequence heating mode, the reversing valve is not energized. As long
of operation does not cover those applications. as the thermostat is set for heating, the reversing valve will be
4.1 On a demand for first stage heat with heat pump units, the in the de-energized position for heating except during a
room thermostat energizes “Y” and “G” and 24Vac is defrost cycle.
supplied to “G” and “Y/Y2” of the MBE. The VSTB will turn 5.1 The heat pump will be on and operating in the heating
on the blower motor and the motor will ramp up to the mode as described the Heating Operation in section 4.
speed programmed in the motor based on the settings of
5.2 The defrost control in the heat pump unit checks to see
dip switch 1 and 2. The VSTB will supply 24Vac to “Y” at
if a defrost is needed every 30, 60 or 90 minutes of heat
the heat pump and the heat pump is turned on in the
pump operation depending on the selectable setting by
heating mode.
monitoring the state of the defrost thermostat attached to
4.2 If the first stage heat demand cannot be satisfied by the the outdoor coil.
heat pump, the temperature indoors will continue to drop.
5.3 If the temperature of the outdoor coil is low enough to
The room thermostat will then energize terminal “W2” for
cause the defrost thermostat to be closed when the
second stage heat and 24Vac will be supplied to “E/W1”
defrost board checks it, the board will initiate a defrost
of the MBE. The VSTB will supply 24Vac to heat
cycle.
sequencer, HR1, on the electric heater assembly.
5.4 When a defrost cycle is initiated, the contacts of the
4.3 HR1 contacts M1 and M2 will close within 10 to 20
HVDR relay on the defrost board open and turns off the
seconds and turn on heater element #1. At the same
outdoor fan. The contacts of the LVDR relay on the
time, if the heater assembly contains a second heater
defrost board closes and supplies 24Vac to “O” and “W2”.
element, HR1 will contain a second set of contacts, M3
The reversing valve is energized and the contacts on HR1
and M4, which will close to turn on heater element #2.
close and turns on the electric heater(s). The unit will
Note: If more than two heater elements are on the heater continue to run in this mode until the defrost cycle is
assembly, it will contain a second heat sequencer, HR2, completed.
which will control the 3rd and 4th heater elements if available. a. For models with defrost control PCBDM133, a 30
For the 3rd and 4th heater elements to operate on a third second compressor delay at defrost initiation/termina-
stage heat demand, the PJ4 jumper on the VSTB inside tion is optional. As shipped from the factory, the
the MBE and AEP* must be cut. If the second stage heat control is set for the delay (“DLY”), which will turn the
demand, “W2”, cannot be satisfied by the heat pump, the compressor off for 30 seconds while the reversing valve
temperature indoors will continue to drop. The room thermo- shifts to/from the cooling mode position. To bypass
stat will then energize “W3” and 24Vac will be supplied to “W/ the delay, which typically reduces sound levels during
W2” of the MBE. The VSTB will supply 24Vac to HR2 on the defrost mode, change the pin settings from “DLY” to
electric heater assembly. When the “W3” demand is satis- “NORM”.
fied, the room thermostat will remove the 24Vac from “W/W2” 5.5 When the temperature of the outdoor coil rises high
of the MBE and AEP*. The contacts on HR2 will open enough to causes the defrost thermostat to open, the
between 30 to 70 seconds and heater elements #3 and #4 will defrost cycle will be terminated. If at the end of the
be turned off. On most digital/electronic thermostats, programmed 10 minute override time the defrost thermo-
“W3” will remain energized until the first stage de- stat is still closed, the defrost board will automatically
mand “Y” is satisfied and then the “G”, “Y”, “W2” and terminate the defrost cycle.
“W3” demands will be removed. 5.6 When the defrost cycle is terminated, the contacts of the
4.4 As the temperature indoors increase, it will reach a point HVDR relay on the defrost board will close to start the
where the second stage heat demand, “W2”, is satisfied. outdoor fan and the contacts of the LVDR relay will open
When this happens, the room thermostat will remove the and turn off the reversing valve and electric heater(s). The
24Vac from “E/W1” of the MBE. The contacts on HR1 will unit will now be back in a normal heating mode with a heat
open between 30 to 70 seconds and turn off both heater pump demand for heating as described in the Heating
element(s). The heat pump remains on along with the Operation in section 4. See section 5.4a.
blower motor because the “Y” demand for first stage heat
will still be present.
56
SERVICING
S-60 ELECTRIC HEATER (OPTIONAL ITEM) TEMPERATURE RISE (F°) @ 240V
Optional electric heaters may be added, in the quantities 3 4.8 7.2 9.6 14.4 19.2 24 28.8
CFM
shown in the specifications section, to provide electric KW KW KW KW KW KW KW KW
resistance heating. Under no condition shall more heaters 600 16 25 38 51 --- --- --- ---
than the quantity shown be installed. 700 14 22 33 43 --- --- --- ---
800 12 19 29 38 57 --- --- ---
The low voltage circuit in the air handler is factory wired and
900 11 17 26 34 51 --- --- ---
terminates at the location provided for the electric heater(s).
A minimum of field wiring is required to complete the instal- 1000 10 15 23 30 46 --- --- ---
lation. 1100 9 14 21 27 41 55 --- ---
1200 8 13 19 25 38 50 --- ---
Other components such as a Heating/Cooling Thermostat
1300 7 12 18 23 35 46 --- ---
and Outdoor Thermostats are available to complete the
installation. 1400 7 11 16 22 32 43 54 65
1500 6 10 15 20 30 40 50 60
The system CFM can be determined by measuring the static
1600 6 9 14 19 28 38 47 57
pressure external to the unit. The installation manual
1700 6 9 14 18 27 36 44 53
supplied with the blower coil, or the blower performance table
in the service manual, shows the CFM for the static mea- 1800 5 8 13 17 25 34 42 50
sured. 1900 5 8 12 16 24 32 40 48
2000 5 8 12 15 23 30 38 45
Alternately, the system CFM can be determined by operating
the electric heaters and indoor blower WITHOUT having the 2100 5 7 11 14 22 29 36 43
compressor in operation. Measure the temperature rise as 2200 4 7 11 14 21 27 34 41
close to the blower inlet and outlet as possible. 2300 4 7 10 13 20 26 33 39
Table 5
BTUH CAPACITY CORRECTION FACTOR
ELECTRIC HEATER CAPACITY BTUH
SUPPLY VOLTAGE 250 230 220 208
HTR 3.0 4.7 6.0 7.0 9.5 14.2 19.5 21.0
MULTIPLICATION FACTOR 1.08 .92 .84 .75 KW KW KW KW KW KW KW KW KW
T = BTUH
CFM x 1.08
57
SERVICING
When repairing the refrigeration system:
WARNING
Disconnect ALL power before servicing.
DANGER WARNING
Always remove the refrigerant charge in a proper To avoid possible explosion, the line from the
manner before applying heat to the system. nitrogen cylinder must include a pressure regulator
and a pressure relief valve. The pressure relief valve
must be set to open at no more than 150 psig.
58
SERVICING
Pressure test the system using dry nitrogen and soapy water R-22
MANIFOLD
to locate leaks. If you wish to use a leak detector, charge the
system to 10 psi using the appropriate refrigerant then use
LOW SIDE HIGH SIDE
nitrogen to finish charging the system to working pressure, GAUGE GAUGE
then apply the detector to suspect areas. If leaks are found, AND VALVE AND VALVE
repair them. After repair, repeat the pressure test. If no leaks
exist, proceed to system evacuation.
800 PSI
RATED
S-102 EVACUATION HOSES
CHARGING
WARNING CYLINDER
AND SCALE
REFRIGERANT UNDER PRESSURE!
{
Failure to follow proper procedures may cause
property damage, personal injury or death. VACUUM PUMP
TO ADAPTER
UNIT SERVICE
VALVE PORTS
This is the most important part of the entire service procedure.
The life and efficiency of the equipment is dependent upon the VACUUM PUMP
thoroughness exercised by the serviceman when evacuating
air (non-condensables) and moisture from the system.
Air in a system causes high condensing temperature and
pressure, resulting in increased power input and reduced
performance.
Moisture chemically reacts with the refrigerant oil to form EVACUATION
corrosive acids. These acids attack motor windings and
parts, causing breakdown. 3. If the vacuum pump is working properly, close the valve to
The equipment required to thoroughly evacuate the system is the vacuum thermocouple gauge and open the high and
a high vacuum pump, capable of producing a vacuum equiva- low side valves to the high vacuum manifold set. With the
lent to 25 microns absolute and a thermocouple vacuum valve on the charging cylinder closed, open the manifold
gauge to give a true reading of the vacuum in the system valve to the cylinder.
NOTE: Never use the system compressor as a vacuum pump 4. Evacuate the system to at least 29 inches gauge before
or run when under a high vacuum. Motor damage could occur. opening valve to thermocouple vacuum gauge.
5. Continue to evacuate to a maximum of 250 microns.
Close valve to vacuum pump and watch rate of rise. If
WARNING vacuum does not rise above 1500 microns in three to five
Do not front seat the service valve(s) with the minutes, system can be considered properly evacuated.
compressor open, with the suction line of the
comprssor closed or severely restricted. 6. If thermocouple vacuum gauge continues to rise and
levels off at about 5000 microns, moisture and non-
1. Connect the vacuum pump, vacuum tight manifold set condensables are still present. If gauge continues to rise
with high vacuum hoses, thermocouple vacuum gauge a leak is present. Repair and re-evacuate.
and charging cylinder as shown. 7. Close valve to thermocouple vacuum gauge and vacuum
2. Start the vacuum pump and open the shut off valve to the pump. Shut off pump and prepare to charge.
high vacuum gauge manifold only. After the compound
gauge (low side) has dropped to approximately 29 inches S-103 CHARGING
of vacuum, open the valve to the vacuum thermocouple
gauge. See that the vacuum pump will blank-off to a
maximum of 25 microns. A high vacuum pump can only
W ARN ING
produce a good vacuum if its oil is non-contaminated. REFRIGERANT UNDER PRESSURE!
* Do not overcharge system with refrigerant.
* Do not operate unit in a vacuum or at negative
pressure.
Failure to follow proper procedures may cause
property damage, personal injury or death.
59
SERVICING
60
SERVICING
Verification of proper rotation of Scroll Compressors is made The TXV internal check valve will hold a pressure differential
as follows. of 100 PSID.
NOTE: The compressor may run backwards (noisy opera- The bulb must be securely fastened with two straps to a clean
tion) for 1 or 2 seconds at shutdown. This is normal and straight section of the suction line. Application of the bulb to
does not harm the compressor. a horizontal run of line is preferred. If a vertical installation
1. Install gauges and verify that the suction pressure drops cannot be avoided, the bulb must be mounted so that the
while the discharge pressure increases. capillary tubing comes out at the top.
2. Listen for normal compressor sound levels. Reverse rota- THE VALVES PROVIDED BY GOODMAN® BRAND ARE
tion results in elevated or unusual sound levels. DESIGNED TO MEET THE SPECIFICATION REQUIRE-
MENTS FOR OPTIMUM PRODUCT OPERATION. DO NOT
3. Reverse rotation will result in substantially reduced amp USE SUBSTITUTES.
draw from tabulated values.
To correct improper rotation, switch any two power supply S-106 OVERFEEDING
leads at the outdoor unit contactor. Overfeeding by the expansion valve results in high suction
The 3 phase Scroll Compressors are direction of rotation sen- pressure, cold suction line, and possible liquid slugging of the
sitive. They will rotate in either direction depending on the compressor.
phasing of the power. There is no negative impact on durabil- If these symptoms are observed:
ity caused by operating 3 phase compressors in reversed
1. Check for an overcharged unit by referring to the cooling
rotation. The compressors internal protector will trip, de-en-
performance charts in the servicing section.
ergizing the compressor. Continued operation of 3 phase scroll
compressors with the rotation reversed will contribute to com- 2. Check the operation of the power element in the valve as
pressor failure. All 3 phase scroll compressors should be explained in S-110 Checking Expansion Valve Operation.
checked for correct phase rotation. 3. Check for restricted or plugged equalizer tube.
62
SERVICING
S-109 CHECKING SUBCOOLING 5. Capture the charge, replace the valve and drier, evacuate
Refrigerant liquid is considered subcooled when its tempera- and recharge.
ture is lower than the saturation temperature corresponding
to its pressure. The degree of subcooling equals the degrees S-111 FIXED ORIFICE RESTRICTOR DEVICES
of temperature decrease below the saturation temperature at The fixed orifice restrictor device (flowrator) used in conjunc-
the existing pressure. tion with the indoor coil is a predetermined bore (I.D.). It is
1. Attach an accurate thermometer or preferably a thermo- designed to control the rate of liquid refrigerant flow into an
couple type temperature tester to the liquid line as it leaves evaporator coil.
the condensing unit. The amount of refrigerant that flows through the fixed orifice
2. Install a high side pressure gauge on the high side (liquid) restrictor device is regulated by the pressure difference
service valve at the front of the unit. between the high and low sides of the system. In the cooling
cycle when the outdoor air temperature rises, the high side
3. Record the gauge pressure and the temperature of the line. condensing pressure rises. At the same time, the cooling
4. Review the technical information manual or specification load on the indoor coil increases, causing the low side
sheet for the model being serviced to obtain the design pressure to rise, but at a slower rate.
subcooling. Since the high side pressure rises faster when the tempera-
5. Obtain the Liquid Line Pressure gauge reading and convert ture increases, more refrigerant flows to the evaporator,
the liquid line pressure gauge reading to temperature by increasing the cooling capacity of the system.
finding the gauge reading in Temperature - Pressure Chart When the outdoor temperature falls, the reverse takes place.
and reading to the left, find the temperature in the °F. Column. The condensing pressure falls, and the cooling loads on the
6. The difference between the thermometer reading and indoor coil decreases, causing less refrigerant flow.
pressure to temperature conversion is the amount of subcool- If a restriction should become evident, proceed as follows:
ing.
1. Recover refrigerant charge.
Add charge to raise subcooling. Recover charge to lower
2. Remove the orifice assembly clean or replace.
subcooling.
3. Replace liquid line drier, evacuate and recharge.
Subcooling Formula = Sat. Liquid Temp. - Liquid Line
Temp.
EXAMPLE:
a. Liquid Line Pressure = 274.5
b. Corresponding Temp. °F. = 120° Capillary Tubes/Orifice Assembly
c. Thermometer on Liquid line = 109°F.
To obtain the amount of subcooling subtract 109°F from CHECKING EQUALIZATION TIME
120°F. During the “OFF” cycle, the high side pressure bleeds to the
The difference is 11° subcooling. See the specification sheet low side through the fixed orifice restriction device. Check
or technical information manual for the design subcooling equalization time as follows:
range for your unit. 1. Attach a gauge manifold to the suction and liquid line dill
valves.
S-110 CHECKING EXPANSION VALVE OPERA- 2. Start the system and allow the pressures to stabilize.
TION
3. Stop the system and check the time it takes for the high
1. Remove the remote bulb of the expansion valve from the and low pressure gauge readings to equalize.
suction line.
If it takes more than seven (7) minutes to equalize, the
2. Start the system and cool the bulb in a container of ice restrictor device is inoperative. Replace, install a liquid line
water, closing the valve. As you cool the bulb, the suction drier, evacuate and recharge.
pressure should fall and the suction temperature will rise.
3. Next warm the bulb in your hand. As you warm the bulb, S-112 CHECKING RESTRICTED LIQUID LINE
the suction pressure should rise and the suction tempera- When the system is operating, the liquid line is warm to the
ture will fall. touch. If the liquid line is restricted, a definite temperature
4. If a temperature or pressure change is noticed, the drop will be noticed at the point of restriction. In severe cases,
expansion valve is operating. If no change is noticed, the frost will form at the restriction and extend down the line in the
valve is restricted, the power element is faulty, or the direction of the flow.
equalizer tube is plugged. Discharge and suction pressures will be low, giving the
63
SERVICING
appearance of an undercharged unit. However, the unit will Now determine if a burn out has actually occurred. Confirm
have normal to high subcooling. by analyzing an oil sample using a Sporlan Acid Test Kit, AK-
3 or its equivalent.
Locate the restriction, replace the restricted part, replace
drier, evacuate and recharge. Remove the compressor and obtain an oil sample from the
suction stub. If the oil is not acidic, either a burnout has not
S-113 OVERCHARGE OF REFRIGERANT occurred or the burnout is so mild that a complete clean-up
is not necessary.
An overcharge of refrigerant is normally indicated by an
excessively high head pressure. If acid level is unacceptable, the system must be cleaned by
using the clean-up drier method.
An evaporator coil, using an expansion valve metering device,
will basically modulate and control a flooded evaporator and
prevent liquid return to the compressor. CAUTION
An evaporator coil, using a capillary tube metering device, Do not allow the sludge or oil to contact the skin.
could allow refrigerant to return to the compressor under Severe burns may result.
extreme overcharge conditions. Also with a capillary tube
metering device, extreme cases of insufficient indoor air can NOTE: The Flushing Method using R-11 refrigerant is no
cause icing of the indoor coil and liquid return to the compres- longer approved by Goodman Company, L.P.
sor, but the head pressure would be lower.
Suction Line Drier Clean-Up Method
There are other causes for high head pressure which may be
Use AMANA® brand part number RF000127 suction line filter
found in the "Service Problem Analysis Guide."
drier kit. This drier should be installed as close to the
If other causes check out normal, an overcharge or a system compressor suction fitting as possible. The filter must be
containing non-condensables would be indicated. accessible and be rechecked for a pressure drop after the
If this system is observed: system has operated for a time. It may be necessary to use
new tubing and form as required.
1. Start the system.
NOTE: At least twelve (12) inches of the suction line
2. Remove and capture small quantities of gas from the immediately out of the compressor stub must be discarded
suction line dill valve until the head pressure is reduced to due to burned residue and contaminates.
normal.
1. Remove compressor discharge line strainer.
3. Observe the system while running a cooling performance
test. If a shortage of refrigerant is indicated, then the 2. Remove the liquid line drier and expansion valve.
system contains non-condensables. 3 Purge all remaining components with dry nitrogen or
carbon dioxide until clean.
S-114 NON-CONDENSABLES 4. Install new components including liquid line drier.
If non-condensables are suspected, shut down the system 5. Braze all joints, leak test, evacuate, and recharge sys-
and allow the pressures to equalize. Wait at least 15 tem.
minutes. Compare the pressure to the temperature of the
coldest coil since this is where most of the refrigerant will be. 6. Start up the unit and record the pressure drop across the
If the pressure indicates a higher temperature than that of the drier.
coil temperature, non-condensables are present. 7. Continue to run the system for a minimum of twelve (12)
Non-condensables are removed from the system by first hours and recheck the pressure drop across the drier.
removing the refrigerant charge, replacing and/or installing Pressure drop should not exceed 6 PSIG.
liquid line drier, evacuating and recharging. 8. Continue to run the system for several days, repeatedly
checking pressure drop across the suction line drier. If
S-115 COMPRESSOR BURNOUT the pressure drop never exceeds the 6 PSIG, the drier has
When a compressor burns out, high temperature develops trapped the contaminants. Remove the suction line drier
causing the refrigerant, oil and motor insulation to decom- from the system.
pose forming acids and sludge. 9. If the pressure drop becomes greater, then it must be
If a compressor is suspected of being burned-out, attach a replaced and steps 5 through 9 repeated until it does not
refrigerant hose to the liquid line dill valve and properly remove exceed 6 PSIG.
and dispose of the refrigerant. NOTICE: Regardless, the cause for burnout must be deter-
mined and corrected before the new compressor is started.
64
SERVICING
S-120 REFRIGERANT PIPING does not exceed 150 feet.
The piping of a refrigeration system is very important in • The distance between the condenser and evaporator in
relation to system capacity, proper oil return to compressor, a completely horizontal installation in which the indoor
pumping rate of compressor and cooling performance of the and outdoor unit do not differ more than 10 feet in
evaporator. vertical distance from each other can approach 150
feet, as long as the equivalent length does not exceed
This long line set application guideline applies to all AHRI 150 feet.
listed R22 air conditioner and heat pump split system
4. Two-Stage Condensing Unit: The maximum length of
matches of nominal capacity 18,000 to 60,000 Btuh. This
tubing must not exceed 75 feet here indoor coil is located
guideline will cover installation requirements and additional above the outdoor unit.
accessories needed for split system installations where the
line set exceeds 50 feet in actual length. NOTE: When the outdoor unit is located above the
indoor coil, the maximum vertical rise must not exceed
Additional Accessories:
25 feet. If the maximum vertical rise exceeds 25 feet,
1. Crankcase Heater- a long line set application can premature compressor failure will occur due to inad-
critically increase the charge level needed for a system. equate oil return.
As a result, the system is very prone to refrigerant
5. Vibration and Noise: In long line applications, refriger-
migration during its off-cycle and a crankcase heater will
ant tubing is highly prone to transmit noise and vibration
help minimize this risk. A crankcase heater is recom-
to the structure it is fastened to. Use adequate vibration-
mended for any long line application (50 watt minimum).
isolating hardware when mounting line set to adjacent
2. TXV Requirement: All line set applications over 50 ft will structure.
require a TXV.
Most refrigerant tubing kits are supplied with 3/8"-thick
3. Hard Start Assist- increased charge level in long line insulation on the vapor line. For long line installations over 50
applications can require extra work from the compressor feet, especially if the line set passes through a high ambient
at start-up. A hard start assist device may be required to temperature, ½”-thick suction line insulation is recommended
overcome this. to reduce loss of capacity. The liquid line should be insulated
4. Liquid Line Solenoid - A long line set application can if passing through an area of 120°F or greater. Do not attach
critically increase the charge level needed for a system. the liquid line to any non-insulated portion of the suction line.
As a result, the system is very prone to refrigerant
migration during its off-cycle and a liquid line solenoid will Table 9 lists multiplier values to recalculate system-cooling
help minimize this. A liquid line solenoid is recommended capacity as a function of a system’s equivalent line length (as
for any long line application on straight cooling units. calculated from the suction line) and the selected suction
tube size. Table 10 lists the equivalent length gained from
Tube Sizing:
adding bends to the suction line. Properly size the suction
1. In long line applications, the “equivalent line length” is the line to minimize capacity loss.
sum of the straight length portions of the suction line plus
losses (in equivalent length) from 45 and 90 degree
bends. Select the proper suction tube size based on REFRIGERANT LINE LENGTH (Ft)
equivalent length of the suction line (see Tables 9 & Cond 0-24 25-49 50-74***
10) and recalculated system capacity. Unit Line Diameter (In. OD)
Tons Suct Liq Suct Liq Suct Liq
Equivalent length = Length horizontal + Length vertical + 1 1/2 5/8 1/4 3/4 3/8 3/4 3/8
Losses from bends (see Table 11) 2 5/8 1/4 3/4 3/8 3/4 3/8
2 1/2 3/4 3/8 3/4* 3/8 7/8 3/8
2. For any residential split system installed with a long 3 3/4 3/8 3/4** 3/8 7/8** 3/8
line set, the liquid line size must never exceed 3/8". 3 1/2 3/4 3/8 7/8** 3/8 1 1/8 3/8
4 7/8 3/8 1 1/8 3/8 1 1/8 3/8
Limiting the liquid line size to 3/8" is critical since an 5 7/8 3/8 1 1/8 3/8 1 1/8 3/8
increased refrigerant charge level from having a larger
liquid line could possibly shorten a compressor’s lifespan.
Table 9
3. Single Stage Condensing Unit: The maximum length
*7/8" required for full ratings
of tubing must not exceed 150 feet.
**1 1/8" required for full ratings
• 50 feet is the maximum recommended vertical differ- ***Lines greater than 74 feet in length or vertical elevation changes more than 50 feet, refer to the long
line set.
ence between the condenser and evaporator when the
evaporator is above the condenser. Equivalent length is
TABLE 10. CAPACITY MULTIPLIERS AS A FUNCTION OF
not to exceed 150 feet. SUCTION LINE SIZE & EQUIVALENT LENGTH
• The vertical difference between the condenser and
evaporator when the evaporator is below the condenser
can approach 150 feet, as long as the equivalent length
65
SERVICING
3. An oil trap is required at the evaporator only if the
Nominal Vapor line EQUIVALENT LINE LENGTH (FT) condenser is above the evaporator. Preformed oil
capacity diameter traps are available at most HVAC supply houses, or oil
Btuh (in.) 50 75 100 125 150
18,000 3/4 .99 .97 .96 .95 .95
traps may be created by brazing tubing elbows together
24,000 3/4 1 .99 .99 .98 .97 (see diagram below). Remember to add the equivalent
30,000 3/4 .98 .97 .96 .95 .94 length from oil traps to the equivalent length calculation of
3/4 .93 .90 .86 .83 .79
36,000
7/8 .98 .96 .94 .92 .90
the suction line. For example, if you construct an oil trap
3/4 .93 .90 .87 .83 .80 using two 45° elbows, one short and one long 90° elbow
42,000 7/8 .97 .96 .94 .93 .92
1-1/8
in a ¾” diameter suction line, the additional equivalent
1 1 .99 .99 .98
3/4 .90 .86 .82 .78 N/R length would be 0.7+ 0.7+1.7+1.5, which equals 4.6 feet
48,000 7/8 .96 .94 .93 .91 .89 (refer to table 9).
1-1/8 1 1 .99 .99 .98
7/8 .93 .91 .89 .86 .84
60,000
1-1/8 .99 .98 .98 .97 .97
Table 11
Installation Requirements
Fig 7. Oil Trap
1. In a completely horizontal installation with a long line set
where the evaporator is at the same altitude as (or slightly 4. Low voltage wiring. Verify low voltage wiring size is
below) the condenser, the line set should be sloped adequate for the length used since it will be increased in
towards the evaporator. This helps reduce refrigerant a long line application.
migration to the condenser during a system’s off-cycle.
System Charging
2. For a system installation where the evaporator is above
the condenser, an inverted vapor line trap should be R22 condensers are factory charged for 15 feet of line set. To
installed on the suction line just before the inlet to the calculate the amount of extra refrigerant (in ounces) needed
evaporator (see Fig 6). The top of the inverted loop must for a line set over 15 feet, multiply the additional length of line
be slightly above the top of the evaporator coil and can be set by 0.6 ounces. Note for the formula below, the linear feet
created simply by brazing two 90° long radius elbows of line set is the actual length of liquid line (or suction line,
together, if a bending tool is unavailable. Properly support since both should be equal) used, not the equivalent length
and secure the inverted loop to the nearest point on the calculated for the suction line.
indoor unit or adjacent structure.
Extra refrigerant needed =
(Linear feet of line set – 15 ft) x X oz/ft.
Where X = 0.6 for 3/8" liquid tubing
66
SERVICING
Follow the charging procedures in the outdoor unit I/O manual
to ensure proper superheat and sub-cooling levels, espe-
cially on a system with a TXV installed in the indoor unit. Heat
pumps should be checked in both heating and cooling mode
for proper charge level. This guideline is meant to provide
installation instructions based on most common long line set
applications. Installation variables may affect system opera-
tion.
NO ADDITIONAL COMPRESSOR OIL IS NEEDED FOR
LONG LINE SET APPLICATIONS TOTAL EXTERNAL STATIC
ON RESIDENTIAL SPLIT SYSTEMS.
NOTE: Both readings may be taken simultaneously and read
S-122 REVERSING VALVE REPLACEMENT directly on the manometer if so desired.
Remove the refrigerant charge from the system. 4. Consult proper table for quantity of air.
When brazing a reversing valve into the system, it is of If external static pressure is being measured on a furnace to
extreme importance that the temperature of the valve does determine airflow, supply static must be taken between the
not exceed 250° F. at any time. "A" coil and the furnace.
Wrap the reversing valve with a large rag saturated with water.
"Re-wet" the rag and thoroughly cool the valve after each
brazing operation of the four joints involved. The wet rag
around the reversing valve will eliminate conducting of heat to
the valve body when brazing the line connection.
The use of a wet rag sometimes can be a nuisance. There are
commercial grades of heat absorbing paste that may be
substituted.
After the valve has been installed leak test, evacuate and
recharge.
Air Flow
67
SERVICING
S-204 COIL STATIC PRESSURE DROP
1. Using a draft gauge (inclined manometer), connect the
positive probe underneath the coil and the negative probe
above the coil.
2. A direct reading can be taken of the static pressure drop
across the coil.
3. Consult proper table for quantity of air.
68
ACCESSORIES WIRING DIAGRAMS
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
24VAC
F1 3A
POWER SUPPLY P1-8 +VD C
INPUT R POWER +5VDC
FURNACE DEMAND P1-7
SUPPLY W1-FURN
OUTPUT F W1 W2-HP
BLOWER FAN DEMAND P1-4 +VD C
OUTPUT U G 24VAC
POWER SUPPLY INPUT R P1-6 C G-STAT
(COMMON) C
SECOND STAGE FURNACE
N P1-5
K1
69
ACCESSORIES WIRING DIAGRAMS
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
E
E
ED
EE
IT
U
H
BL
R
W
G
C G W2 R
C
BLUE
G
3
WHITE
Indoor Thermostat
BROWN
W2
1
BLACK
RED
THERMOSTAT
EMERGENCY E
HEAT
RELAY
OT/EHR18-60 O
C R W2 O
O
Y
YE
W
R
R
BL
ED
L
AN
HI
LO
UE
TE
W
E
E
E
ED
EE
IT
U
BR
H
BL
R
W
G
C G W2 W3 R
C
BLUE
G
2
2
3
WHITE
Indoor Thermostat
BROWN
W2
1
BLACK
RED
THERMOSTAT
EMERGENCY E
HEAT
RELAY
R
OT/EHR18-60 O
C R W2 O Y
O
YE
Note:
W
R
R
BL
LL
ED
AN
U
IT
O
E
G
E
stage for electric heat (W2), tie white and From Outdoor Unit
brown wires from air handler together.
Typical Wiring Schematics for OT/EHR18-60 (Outdoor Thermostat & Emergency Heat Relay).
This wiring diagram is for reference only. Not all wiring is as shown above.
Refer to the appropriate wiring diagram for the unit being serviced.
70
ACCESSORIES WIRING DIAGRAMS
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
15kw and Above with Two OT/EHR18-60's, Two Stage Electric Heat and Two Stage Thermostat
From Air Handler
OT/EHR18-60 #1
N
W
EN
E
E
ED
IT
U
BR
RE
H
BL
R
W
G
C G W2 W3 R
C
BLUE
G
3
WHITE
Indoor Thermostat
BROWN
W2
1
BLACK
RED W3
THERMOSTAT
EMERGENCY E
HEAT
RELAY
R
OT/EHR18-60 #2 O
Y
BLUE
3
WHITE
BROWN
1
BLACK
RED
THERMOSTAT
EMERGENCY
HEAT
RELAY
C R W2 O Y
O
YE
W
RE
R
BL
LL
H
AN
D
UE
IT
O
G
E
W
E
Typical Wiring Schematics for OT/EHR18-60 (Outdoor Thermostat & Emergency Heat Relay).
This wiring diagram is for reference only. Not all wiring is as shown above.
Refer to the appropriate wiring diagram for the unit being serviced.
71
ACCESSORIES WIRING DIAGRAMS
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
FL FL
FL FL
HTR1 TL BK
HTR2 TL FL
HTR1 TL FL HTR1 TL
FL BK
HTR2 TL RD
HTR1 TL FL
RD HTR2 TL RD
FL HTR3 TL
BK BK YL
1 FL
HTR3 TL
BK BK 1 HTR4 TL
2 BK 1 BL
RD BK 1
2 2
PU 3 RD YL
RD 2
BK BL YL BK PU PU
PU 3 BL 3 BL BK RD
4 BK
M1 BL RD BL 3
M1 M3 M1
BL
R RD
M1 M3 4
RD M2 M4 M2
4
M1 M3 M5 M7
RD
5 YL BL 4
M2 R2 RD
R R1 BR 5
M2 M4 M6 M8
5
WH 6 M2 M4 BK R1 R2 BR 5
BK
RD WH 6 BK
BK
BK WH 6 RD WH 6
7
BK RD 7
BK 7 7
RD YL
8 BK 8
YL
RD 8
BK BL 8
9 RD 9 BK
RD 9
9
L1 L2
L1 L2 L1 L2 L1 L2
ONE (1) ELEMENT ROWS TWO (2) ELEMENT ROWS THREE (3) ELEMENT ROWS L1 L2 L1 L2
FOUR (4) ELEMENT ROWS
NOTE: WHEN INSTALLING HEATER KIT, ENSURE SPEED TAP DOES NOT EXCEED MINIMUM BLOWER SPEED (MBS) SPECIFIED FOR THE AIRHANDLER/HEATER
KIT COMBINATION ON THIS UNIT'S S&R PLATE. AFTER INSTALLING OPTIONAL HEAT KIT, MARK AN "X" IN THE PROVIDED ABOVE.
MARK ACCORDING TO NUMBER OF HEATER ELEMENT ROWS INSTALLED. NO MARK INDICATES NO HEAT KIT INSTALLED.
1 PLF
PLF 1 2 3 4 5 6 7 8 9 3 PLF 2
RC EM
BK RD PU BL BR WH NO
NC
M1
SEE LO
SEE NOTE 4 EBTDR
NOTE
2 BR M2 COM
HI
WH
1 2 3 SEE NOTE 1
TR
EBTDR R C EBTDR G
4 24V 5
GR BK
SEE NOTE 5 RD
RD
6 5 4 PLF
PU SEE NOTE 1
G EBTDR
NO RD
R K1 C 1 2 3 240 RD WH BR BL GR
BL XFMR-R BK
RD XFMR-C COM TR COLOR CODE WIRING CODE
K1 PU
C
5 24V 4
BK BLACK GR GREEN FACTORY WIRING
NC RD RED PU PURPLE HIGH VOLTAGE
BL SPEEDUP BL YL YELLOW BR BROWN LOW VOLTAGE
M1 M2 BL BL BLUE WH WHITE FIELD WIRING
RD HIGH VOLTAGE
COMPONENT CODE LOW VOLTAGE NOTE 2
72
ACCESSORIES WIRING DIAGRAMS
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
R TR R
1 4
208/240 24V
HTR2
2
BK
3 5
Y BL BL
FL HTR3 TL
PU
BK
PC
BL
FL HTR4 TL
BK 1
BL EBTDR
2 R R
G
R
BL 3 PU BL R K1
NO
R XFMR-R
M5 M7
Y BL 4 BL XFMR-C COM
RS2 K1
M6 M8
C
BR 5 BR NC
SPEEDUP M1
W 6 W
Y
BL 8
BK
R 9
W BR G PK BL
L1 L2 L1 L2
SR
EQUIPMENT GROUND
EQUIPMENT GROUND
USE COPPER OR ALUMINUM WIRE
USE COPPER WIRE
73
ACCESSORIES WIRING DIAGRAMS
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
FL FL
FL FL
HTR1 TL
HTR2 TL FL BK
FL
HTR1 TL HTR1 TL BK
FL HTR2 TL R
FL
HTR1 TL
R HTR2 TL R
FL
BK BK 1 HTR3 TL Y
FL
HTR3 TL
BK BK 1
2 BK 1 HTR4 TL BL
R BK 1
2 2
PU 3 R Y
R 2
BK BL Y BK PU PU
PU 3 BL 3 BL BK R
4 BK
M1 BL M1 M3 M1
R BL 3
BL R
R R
M1 M3 4
R
4
M1 M3 M5 M7
5 M2 M4 M2 Y BL 4
M2 R2 R
R R1 BR 5
M2 M4 M6 M8
5
W 6 M2 M4 BK R1 R2 BR 5
BK
R W 6 BK
BK
BK W 6 R W 6
7
BK R 7
BK 7 7
R Y
8 BK 8
Y
R 8
BK BL 8
9 R 9 BK
R 9
9
L1 L2
L1 L2 L1 L2 L1 L2
ONE (1) ELEMENT ROWS TWO (2) ELEMENT ROWS THREE (3) ELEMENT ROWS L1 L2 L1 L2
FOUR (4) ELEMENT ROWS
AFTER INSTALLING OPTIONAL HEAT KIT, MARK AN "X" IN THE PROVIDED ABOVE.
MARK ACCORDING TO NUMBER OF HEATER ELEMENT ROWS INSTALLED
NO MARK INDICATES NO HEAT KIT INSTALLED
TO TO
* SEE NOTE 7 C ONDEN SER TH ERM OSTAT
LOW VOLTAGE 208/240 VOLTS
YCO N O W 1 C Y1 Y/Y2
FIEL D CON NEC TION
R C W2 W2 R G O
BOX
PL 1 2 1 PL 1
R PL 2 2 1 PL 2
SEE N OTE 8 EM TO L OW VOLTAGE
BK TER MINAL BOARD
Y O W BL PU Y
R BL BR BR R G O PL1 1 2 3 4 5 67 8 9
1 2 3
PL 2 1 2 3 4 5 6 7 8 9
TR
BL
BK TR 4 2 4 VOLT 5
240
R 1 4 5 PL 2 6 PL2 4 PL 2
Y BL
PN. B1368270 REV. A
J1
BL 208 R SEE
SEE N OTE 5
R YCON COM O
2 2 4V N OTE 4
CONDENSERHEATPUMP
HUM
W
OT2
OT1
E\W1
W2 W1 YCO N
W/W2
BR
W1
3 5 PJ2
IN4005
N O TE DIO D E
O C OM PJ4 DIODE
O OTC
PJ6 O N VSTB
BR
W2
W2
OU TD O OR
R
PJ6
PJ2
PJ4
OT OT OT Y1 Y Y2 G
OT1 OT2
ED
R HUM O W W2 E W1 C
THERMOSTATS
2 1 C
BL
HEATER
W1
BR W *SEE N OTE 7
BL
C
W2
BL PU
Y1
R
R G
Y1
C OLO R C ODE
Y/Y2
Y W IRIN G COD E
HUMIDISTAT
R R W W HITE G G R EEN
HUM
DS 1
J2 J3 BL FAC TORY W IRIN G
BR BK BL AC K PU PUR PL E HIGH VO LTAGE
W R R ED BR BROW N LO W VO LTAGE
G Y YEL LOW 0 O RANGE FIEL D W IRIN G
BL BL UE PK PIN K HIGH VO LTAGE
LO W VO LTAGE
C OMPON ENT C ODE
EM EVAPORATO R M OTOR TL TH ERM AL LIMIT
PL PLUG H TR H EAT EL EMEN T
PJ2 ,PJ 4,PJ6 PRO GRAM JU MPER R R EL AY
VSTB VAR IABLE SPEED TR TR ANSF ORMER
TER MINAL BOARD
FL FU SE LI NK
EM
74
ACCESSORIES WIRING DIAGRAMS
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
BL
L1 L2
BL
24V
G
4
5
TR
9
9
COM
1
3
208
2
240
8
8
R
BK
R
7
BL
BK
7
R
W
6
6
BK
EM
4 2 BR
R
5
5
W
8 6
1
R
R
4
BK
BL
BR
BK
PU
3
3
2
2
BK
1
BK
1
PL 1
PL2
R
HTR2 TL
O
O
Y1 Y/Y2
PK
THERMOSTAT
HTR1 TL
G
G
Y
W
TO
BR
BL
BL
C
R
W2
BR
W1
BR
CONDENSER
O
YCON O
BL
TO
PK
BR
Y
G
Y
W
BL
R
BR
BL
R
O
Y
THERMOSTATS HUMIDISTAT
E\W1 O OTC OT1 OT2 C R Y1 G HUM
R YCON COM O W2 ED W1 W2 C R
R
BL
W1 W2
BR
OT1 PJ4
J2 J3
W
OT2 PJ2
DS1
HUM PJ6
VSTB
J1
Blower Section
75
ACCESSORIES WIRING DIAGRAMS
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
FL FL
FL FL HTR1 TL BK
HTR2 TL FL
HTR1 TL FL HTR1 TL
FL BK
HTR2 TL RD
HTR1 TL FL
RD HTR2 TL RD
FL HTR3 TL
BK BK 1 FL YL
HTR3 TL
BK BK 1 HTR4 TL
2 BK 1 BL
RD BK 1
2 2
PU 3 RD YL
RD 2
BK BL YL BK PU PU
PU 3 BL 3 BL BK RD
4 BK BL 3
M1 BL RD
M1 M3 M1
BL RD
R RD
M1 M3 4
RD M2 M4 M2
4
YL
M1 M3 M5 M7
BL
5 4
M2 R2 RD M2 M4 M6 M8
R R1 BR 5
5 R1 R2
WH 6 M2 M4 BK BR 5
BK BK
RD WH 6
BK
BK WH 6 RD WH 6
7
BK RD 7
BK 7 7
RD YL
8 BK 8
YL
RD BK BL 8
8
9 RD 9 BK
RD 9
9
L1 L2
L1 L2 L1 L2 L1 L2
ONE (1) ELEMENT ROWS TWO (2) ELEMENT ROWS THREE (3) ELEMENT ROWS FOUR (4) ELEMENT ROWS
L1 L2 L1 L2
NOTE: WHEN INSTALLING HEATER KIT, ENSURE SPEED TAP DOES NOT EXCEED MINIMUM BLOWER SPEED (MBS) SPECIFIED FOR THE AIRHANDLER/HEAT ER
KIT COMBINATION ON THIS UNIT'S S&R PLATE. AFTER INSTALLING OPTIONAL HEAT KIT, MARK AN "X" IN THE PROVIDED ABOVE.
MARK ACCORDING TO NUMBER OF HEATER ELEMENT ROWS INSTALLED. NO MARK INDICATES NO HEAT KIT INSTALLED.
XFMR-R
PLM 1 2 3 4 5 6 7 8 9 1 PLM PLM 2 XFMR-C K1 COM
EM C
RD 1 PLF
NC
CLGN SPEED
PLF 1 2 3 4 5 6 7 89 PLF 2
UP M1 M2
RD BK RD BL BR WH
SEE
BR NOTE 4
1 2 3 SEE NOTE 1
WH
BL CR
TR
B A 7 4
4 24V 5
BL
GR 6 4 PLF
RD 5 1
RD 2
CR EM
BK 3
RD 4
G EBTDR C
R K1
NO RD 4 BK SEE NOTE 1 5
XFMR-R
XFMR-C COM RD 2 R C G W1 W2 Y1 Y2 O DH 1 2 3 4 5
C 1 3 240
C
K1
7 1 SEE
RD
NC RD NOTE 3 TR COLOR CODE WIRING CODE
SPEED M1 M2 BL
UP GR A B 5 24V 4
BK BLACK GR GREEN FACTORY WIRING
RD RED PU PURPLE HIGH VOLTAGE
BL YL YELLOW BR BROWN LOW VOLTAGE
BL BL BL BLUE WH WHITE
BL FIELD WIRING
BL RD WH PU HIGH VOLTAGE
COMPONENT CODE LOW VOLTAGE
RD
OR BR YL
EM EVAPORATOR MOTOR TR TRANSFORMER
TB TERMINAL BOARD PLF FEMALE PLUG CONNECTOR
R RELAY PLM MALE PLUG CONNECTOR
1 2345 CR CONTROL RELAY FL FUSE LINK
EBTDR ELECTRONIC BLOWER TIME TL THERMAL LIMIT
COPPER EM DELAY RELAY HTR HEAT ELEMENTS
POWER SUPPLY Notes:
(SEE RATING PLATE) CLGN 1) Red wires to be on transformer terminal "3" for 240 volts and on terminal "2" for 208 volts.
USE MIN. 75°C FIELD WIRE BL 2) See composite wiring diagrams in installation instructions
RD BK for proper low voltage wiring connections.
3) Confirm speed tap selected is appropriate for application. If speed tap needs
to be changed, connect red wire from terminal 4 of CR relay to appropriate tap
at TB
4) Brown and white wires are used with Heat Kits only.
IF REPLACEMENT OF THE ORIGINAL WIRES
SUPPLIED WITH THIS ASSEMBLY IS NECESSARY,
USE WIRE THAT CONFORMS TO THE
NATIONAL ELECTRIC CODE.
0140A00034-C
76
ACCESSORIES WIRING DIAGRAMS
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
EQUIPMENT GROUND
USE COPPER WIRE
77
ACCESSORIES WIRING DIAGRAMS
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
FL
TL
FL
FL HTR1 BK
FL
TL TL
HTR1 TL
FL FL HTR1 BK HTR2
FL FL RD
TL TL TL TL
HTR1 HTR2 HTR2 RD HTR3
FL YL
BK FL
PLM PLM
TL PLM TL
HTR3 PLM
HTR4 BL
BK BK 1 RD BK 1 BK 1 BK 1
2
2 2 RD YL 2
PU PU
RD RD YL BK BL BK RD
BL 3
PU 3 PU 3 BL 3
RD
BK RD M1 M3 M1 RD
BL BL BL 4 YL
M1 M3 M5 M7
BL 4
BK RD M2 M4 M2
4 M1 M3 4 RD M2 M4 M6 M8
M1 R1 R2
BR 5
R R R1 R2 BR 5
5 5 BK
M2 M4 BK BK
M2 RD WH 6 BK
RD WH 6
WH 6 WH 6
7
7
BK
BK RD YL
7 7 8 YL
BK BK BL 8
BK
RD RD BK
8 8 RD 9
RD 9
9 9
L1 L2 L1 L2
L1 L2 L1 L2 L1 L2 L1 L2
ONE (1) ELEMENT ROWS TWO (2) ELEMENT ROWS THREE (3) ELEMENT ROWS FOUR (4) ELEMENT ROWS
NOTE: WHEN INSTALLING HEATER KIT, ENSURE SPEED TAP DOES NOT EXCEED MINIMUM BLOWER SPEED (MBS) SPECIFIED FOR THE AIRHANDLER/HEATER
KIT COMBINATION ON THIS UNIT'S S&R PLATE. AFTER INSTALLING OPTIONAL HEAT KIT, MARK A "X" IN THE PROVIDED ABOVE.
MARK ACCORDING TO NUMBER OF HEATER ELEMENT ROWS INSTALLED. NO MARK INDICATES NO HEAT KIT INSTALLED.
208/240 VOLTS
RD
PLF 1 2 3 4 5 6 7 8 9
SEE NOTE 1
GR BK RD BL BR WH 1 2 3 5
SEE
BR NOTE 4
TR
WH
3 1 2 4
BL
4 24V 5 CR
HOLDER
FUSE
RD 6 5 4 PLF 1
WH 2 EM
PU 3
4 C
5
CR BK
RD
SEE SEE R C G W1 W2 Y1 Y2 O DH 1 2 3 4 5
4 NOTE 3 BK NOTE 1
WH
C 1 2 3 240
RD 2 5 RD
TR COLOR CODE WIRING CODE
GR 1 3 5 24V 4
1) RED WIRES TO BE ON TRANSFORMER TERMINAL "3" FOR 240 VOLTS AND ON TERMINAL
"2" FOR 280 VOLTS.
IF REPLACEMENT OF THE ORIGINAL WIRES 2) SEE COMPLETE WIRING DIAGRAMS IN INSTALLATION INSTRUCTIONS FOR PROPER LOW
VOLTAGE WIRING CONNECTIONS.
SUPPLIED WITH THIS ASSEMBLY IS NECESSARY, 3) CONFIRM SPEED TAP SELECTION IS APPROPRIATE FOR APPLICATION. IF SPEED TAP
USE WIRE THAT CONFORMS TO THE NATIONAL NEEDS TO BE CHANGED, CONNECT PURPLE WIRE FROM TERMINAL 4 OF CR RELAY TO
APPROPRIATE TAP AT TB
ELECTRIC CODE. 4) BROWN AND WHITE WIRES ARE USED FOR HEAT KITS ONLY. 0140A00040-D
78
AIRHANDLERS
79
80
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
WIRING DIAGRAMS
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
ACNF
WIRING DIAGRAMS ADPF, ARPF, ARUF, ATUF
FL FL
FL FL
HTR1 TL BK
HTR2 TL FL
HTR1 TL FL HTR1 TL
FL BK
HTR2 TL RD
HTR1 TL FL
RD HTR2 TL RD
FL HTR3 TL
BK BK YL
1 FL
HTR3 TL
BK BK 1 HTR4 TL
2 BK 1 BL
RD BK 1
2 2
PU 3 RD YL
RD 2
BK BL YL BK PU PU
PU 3 BL 3 BL BK RD
4 BK
M1 BL RD BL 3
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
M1 M3 M1
BL RD
R RD M1 M3 4 RD
4
M1 M3 M5 M7
5 M2 M4 M2 YL BL 4
M2 R1 R2 RD
R BR 5
M2 M4 M6 M8
5
M2 M4 BK R1 R2
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
5
WH 6
BK
BR
RD WH 6 BK
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
BK
BK WH 6 RD WH 6
7
BK RD 7
RD BK 7 7
YL
8 BK 8
YL
RD 8
BK BL 8
9 RD 9 BK
RD 9
9
L1 L2
L1 L2 L1 L2 L1 L2
ONE (1) ELEMENT ROWS TWO (2) ELEMENT ROWS THREE (3) ELEMENT ROWS L1 L2 L1 L2
FOUR (4) ELEMENT ROWS
NOTE: WHEN INSTALLING HEATER KIT, ENSURE SPEED TAP DOES NOT EXCEED MINIMUM BLOWER SPEED (MBS) SPECIFIED FOR THE AIRHANDLER/HEAT ER
KIT COMBINATION ON THIS UNIT'S S&R PLATE. AFTER INSTALLING OPTIONAL HEAT KIT, MARK AN "X" IN THE PROVIDED ABOVE.
MARK ACCORDING TO NUMBER OF HEATER ELEMENT ROWS INSTALLED. NO MARK INDICATES NO HEAT KIT INSTALLED.
RC EM
BK RD PU BL BR WH NO
NC
M1
SEE LO
SEE NOTE 4 EBTDR
NOTE
2 BR M2 COM
HI
HIGH VOLTAGE!
WH
1 2 3 SEE NOTE 1
TR
EBTDR R C EBTDR G
4 24V 5
GR BK
SEE NOTE 5 RD
RD
PU SEE NOTE 1 6 5 4 PLF
G EBTDR
NO RD
R K1 C 1 2 3 240 RD WH BR BL GR
BL XFMR-R BK
RD XFMR-C COM TR COLOR CODE WIRING CODE
K1 PU 4
C
5 24V BK BLACK GR GREEN FACTORY WIRING
NC RD RED PU PURPLE HIGH VOLTAGE
BL BL YL YELLOW BR BROWN LOW VOLTAGE
SPEEDUP M1 M2 BL BL BLUE WH WHITE FIELD WIRING
RD HIGH VOLTAGE
COMPONENT CODE LOW VOLTAGE NOTE 2
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
81
WIRING DIAGRAMS ADPF, ARPF, ARUF, ATUF
FL FL
FL FL
HTR1 TL BK
HTR2 TL FL
FL
HTR1 TL HTR1 TL BK
FL HTR2 TL RD
FL
HTR1 TL
RD HTR2 TL RD
FL
BK BK 1 HTR3 TL YL
FL
HTR3 TL
BK BK 1
2 BK 1 HTR4 TL BL
RD BK 1
2 2
PU 3 RD YL
RD 2
BK BL YL BK PU PU
PU 3 BL 3
BL B K RD
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
4 BK
M1 BL RD BL 3
M1 M3 M1
BL RD
R RD
M1 M3 4
RD
4
M1 M3 M5 M7
5 M2 M4 M2 YL BL 4
M2 R2 RD
R R1 M2 M4 M6 M8
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
BR 5
5
WH M2 M4 BK R1 R2 BR 5
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
6
BK
RD WH 6 BK
BK
BK WH 6 RD WH 6
7
BK RD 7
BK 7 7
RD YL
8 BK 8
YL
RD 8
BK BL 8
9 RD 9 BK
RD 9
9
L1 L2
L1 L2 L1 L2 L1 L2
ONE (1) ELEMENT ROWS TWO (2) ELEMENT ROWS THREE (3) ELEMENT ROWS FOUR (4) ELEMENT ROWS
L1 L2 L1 L2
NOTE: WHEN INSTALLING HEATER KIT, ENSURE SPEED TAP DOES NOT EXCEED MINIMUM BLOWER SPEED (MBS) SPECIFIED FOR THE AIRHANDLER/HEATER
KIT COMBINATION ON THIS UNIT'S S&R PLATE. AFTER INSTALLING OPTIONAL HEAT KIT, MARK A "X" IN THE PROVIDED ABOVE.
MARK ACCORDING TO NUMBER OF HEATER ELEMENT ROWS INSTALLED. NO MARK INDICATES NO HEAT KIT INSTALLED.
1 PLF
PLF 1 2 3 4 5 6 7 8 9 3 PLF 2
RC EM
BK RD PU BL BR WH NO
SEE NC
M1
NOTE 4 HI
EBTDR
BR M2 COM
LO
HIGH VOLTAGE!
WH
1 2 3 SEE NOTE 1
TR
EBTDR R C EBTDR G
4 24V 5
GR BK
SEE NOTE 5 RD
RD
SEE NOTE 1 6 5 4 PLF
PU
G EBTDR
NO RD
R K1 C 1 2 3 240 RD WH BR BL GR
BL XFMR-R RD
RD XFMR-C COM TR COLOR CODE WIRING CODE
K1 PU
C
5 24V 4
BK BLACK GR GREEN FACTORY WIRING
NC RD RED PU PURPLE HIGH VOLTAGE
BL BL YL YELLOW BR BROWN LOW VOLTAGE
SPEEDUP M1 M2 BL BL BLUE WH WHITE FIELD WIRING
RD HIGH VOLTAGE
COMPONENT CODE LOW VOLTAGE
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
82
WIRING DIAGRAMS AEPF
FL FL
FL FL
HTR1 TL BK
HTR2 TL FL
FL
HTR1 TL HTR1 TL BK
FL HTR2 TL R
FL
HTR1 TL
R HTR2 TL R
FL
BK BK 1 HTR3 TL Y
FL
HTR3 TL
BK BK 1
2 BK 1 HTR4 TL BL
R BK 1
2 2
PU 3 R Y
R 2
BK BL Y BK PU PU
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
PU 3 BL 3 BL BK R
4 BK
M1 BL R BL 3
M1 M3 M1
BL R
R R
M1 M3 4
R
4
M1 M3 M5 M7
5 M2 M4 M2 Y BL 4
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
M2 R2 R
R R1 BR 5
M2 M4 M6 M8
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
5
W 6 M2 M4 BK R1 R2 BR 5
BK
R W 6 BK
BK
BK W 6 R W 6
7
BK R 7
BK 7 7
R Y
8 BK 8
Y
R 8
BK BL 8
9 R 9 BK
R 9
9
L1 L2
L1 L2 L1 L2 L1 L2
ONE (1) ELEMENT ROWS TWO (2) ELEMENT ROWS THREE (3) ELEMENT ROWS L1 L2 L1 L2
FOUR (4) ELEMENT ROWS
AFTER INSTALLING OPTIONAL HEAT KIT, MARK AN "X" IN THE PROVIDED ABOVE.
MARK ACCORDING TO NUMBER OF HEATER ELEMENT ROWS INSTALLED
NO MARK INDICATES NO HEAT KIT INSTALLED
TO
* SEE NOTE 7 TO
C O NDEN SER TH ERM O STAT
LOW VOLTAGE 208/240 VOLTS
YCO N O W 1 C Y1 Y/Y2
FIELD CO N NEC TION
R C W2 W2 R G O
BOX
PL1 2 1 PL1
R PL2 2 1 PL2
SEE N OTE 8 EM TO LOW VOLTAGE
BK TER MINAL BOARD
Y O W BL PU Y
R BL BR BR R G O PL1 1 2 3 4 5 67 8 9
1 2 3
PL2 1 2 3 4 5 6 7 8 9
TR
BL
BK TR 4 24 VOLT 5
240
R 1 4 5 PL2 6 PL2 4 PL2
Y
P N. B1368270 REV.A
J1
BL
BL 208 SEE
HIGH VOLTAGE!
R
R YCON COM O
2 24V SEE N O TE 5 N O TE 4
CONDENSERHEATPUMP
HUM
W
OT2
OT1
E\W1
W2 W1 YCO N
W/W2
BR
W1
3 5 PJ2
IN4005
N O TE DIOD E
O C OM PJ4 DIODE
O OTC
PJ6 O N VSTB
BR
W2
W2
O U TD O O R
R
PJ6
PJ2
PJ4
OT OT OT Y1 Y2 G
OT1 OT2
Y
ED
R HUM O W W2 E W1 C
THERMOSTATS
2 1 C
BL
HEATE R
W1
BR W *SEE N O TE 7
BL
C
W2
PU
BL
Y1
R
R G
Y1
C O LO R C O DE
Y/Y2
Y W IRIN G COD E
HUM IDIS TAT
R R
HUM
DS1
J2 J3 BL W W HITE G GR EEN FAC TO RY W IRIN G
BR BK BLAC K PU PUR PLE HIGH VOLTAG E
W R R ED BR BROW N
LO W VO LTAG E
G Y YELLO W 0 ORANGE FIELD W IRIN G
BL BLUE PK PIN K HIGH VOLTAG E
LO W VO LTAG E
C O MPON ENT C O DE
EM EVAPORATOR M O TO R TL TH ERM AL LIMIT
PL PLUG H TR H EAT ELEMEN T
PJ2,PJ 4,PJ6 PRO GRAM JU MPER R R ELAY
VSTB VAR IABLE SPEED TR TR ANSF O RMER
TER MINAL BOARD
FL FU SE LI NK
EM
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
83
WIRING DIAGRAMS AEPF******CA
FL FL FL
FL
HTR 1 TL BK
HTR1 TL HTR1 TL BK FL
HTR1 TL FL FL
HTR 2 TL RD
PL1 HTR2
TL RD FL
HTR2 TL BK FL
BK BK 1 PL1
TL
PL1 HTR 3 TL YL
RD BK 1 HTR3 FL PL1
2 BK 1
HTR 4 TL BL BK 1
RD
2 2
PU 3 RD YL
BK RD YL PU 2
BL BK PU
PU
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
3 3
BL BL
4 RD BK RD
M1 BL M1 M3 M1
RD BL 3
R BK BL 4 RD
M1 M3 4 RD M1 M3 M5 M7
5 M2 M4 M2 YL BL 4
M2 R2 RD
R1
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
R BR 5
M2 M4 M6 M8
5
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
WH 6 M2 M4 BK R1 R2 BR 5
BK
RD WH 6 BK
BK
BK WH 6 RD WH 6
7
BK BK 7
RD RD 7 7
8
YL
BK 8
YL
RD BK BL 8
8
9 RD 9 BK
RD 9
9
L1 L2
L1 L2 L1 L2 L1 L2
ONE(1)ELEMENTROWS TWO(2) ELEMENTROWS THREE(3)ELEMENTROWS FOUR(4)ELEMENTROWS
L1 L2 L1 L2
RD PL2 2 1 PL2
SEENOTE8 EM TOLOWVOLTAGE
BK TERMINALBOARD
FORHEAT YL OR WH BL PU YL
PUMPS ONLY RD BL BR BR RD GR PL1 1 2 3 4 5 6 7 8 9
EQUIPMENTGROUND
USECOPPER WIRE 1 2 3
PL2 1 2 3 4 5 6 7 8 9
TR
BL
RD TR 4 24VOLT 5
BK 240
RD 1 4 5 PL2 6 PL2 4 PL2
YL
PN. B1368270R EV.A
J1
BL
BL 208 RD SEE
HIGH VOLTAGE!
SEENOTE5
R YCON COM O
2 24V NOTE4
HUM
WH
OT2
OT 1
E\W1
W2 W1 YCON
W/W 2
BR
W1
OR 3 5 PJ2
IN4005
COM PJ4 NOTEDIODE
O
PJ6 DIODE
ON VSTB
BR
OTC OT 1 OT2
W2
W2
TH ERMOSTATS
O U TDO OR
RD
PJ6
PJ2
PJ4
OT OT OT Y1 Y Y2 G C
ED
R HUM O W W2 E W1
2 1 C
BL
HEATER
W1
BR WH EQUIPMENTGROUND *SEENOTE7
BL USECOPPER WIRE
C
W2
WH O SEENOTE3 SEENOTE2
RD BK SEENOTE1
24 VAC
VSTB
BR
C
PU
BL
Y1
R
RD GR
Y1
COLORCODE
Y/Y2
YL WIRINGCODE
HUMID ISTAT
RD RD
H UM
DS1
J2 J3 BL WH WHITE GR GREEN FACTORYWIRING
BR BK BLACK PU PURPLE HIGHVOLTAGE
WH RD RED BR BROWN LOWVOLTAGE
GR YL YELLOW 0R ORANGE FIELDWIRING
BL BLUE PK PINK HIGHVOLTAGE
LOWVOLTAGE
EQUIPMENTGROUND
USECOPPER WIRE COMPONENTCODE
EM EVAPORATOR MOTOR TL THERMALLIMIT
PL PLUG HTR HEATELEMENT
PJ2,PJ4,PJ6 PROGRAMJUMPER R RELAY
VSTB VARIABLE SPEED TR TRANSFORMER
TERMINALBOARD
FL FUSELINK
EM
COPPER NOTES:
POWER SUPPLY
(SEERATINGPLATE) 1.FORHEATPUMPAPPLICATIONSREMOVEORANGEJUMPERWIREBETWEENO&Y1.
2.FORTWOSTAGEELECTRICHEATAPPLICATIONSCUT PJ4.(USEONLYON15&20KWMODELS).
3.FOROUTDOORTHERMOSTATOPERATIONOFSECONDSTAGEHEAT,CUTPJ2&ADDOT18-60TOOTC&OT2.
4.FORSINGLESTAGECOOLINGAPPLICATIONSCONNECTTHERMOSTATTOY/Y2ONLY,
TAPEORREMOVEY1CONNECTION. CONNECTCONDENSINGUNITTOYCON&C.
5.WHENHUMIDSTATISPROVIDEDCUTPJ6.THERMOSTATOPENSONHUMIDITYRISE.
6.REDWIRESTOBEONTRANSFORMERTERMINAL3 FOR240 VOLTSANDONTERMINAL2FOR208VOLTS.
7.SEECOMPOSITEWIRINGDIAGRAMSININSTALLATIONINSTRUCTIONSFORPROPERLOWVOLTAGE
CONNECTIONSANDDETAILSONCOMPATIBLETHERMOSTATSANDTHEIRCONNECTIONS.
8.DISCARDORIGINAL"PL1"PLUGCONNECTORWHENINSTALLINGOPTIONALHEATKIT.
CONTROLSSHOWNWITHUTILITIESIN"ON"POSITIONANDTHERMOSTATIN"OFF"POSITION.
0140A00041-B
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
84
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
FL FL
FL FL
HTR1 TL BK
HTR2 TL FL
HTR1 TL FL HTR1 TL
FL BK
HTR2 TL RD
HTR1 TL FL
HTR2 TL RD
RD FL HTR3 TL YL
BK BK 1 FL
HTR3 TL
BK BK 1 HTR4 TL
2 BK 1 BL
RD BK 1
2 2
PU 3 RD YL
RD 2
BK BL YL BK PU PU
PU 3 BL 3
BL BK RD
4 3
M1 BK BL RD BL
M1 M3 M1
BL 4 RD
R RD 4 M1 M3 M5 M7
5 M1 M3 RD M2 M4 M2 YL BL 4
M2 R1 R2 RD M2 M4 M6 M8
R BR 5
5
6 M2 M4 BK R1 R2 BR 5
WH BK
RD WH 6 BK
6
BK
BK WH RD WH 6
7
BK RD 7
BK 7 7
RD 8 YL
BK 8
YL
WIRING DIAGRAMS
RD BK BL 8
8
9 RD 9 BK
RD 9
9
L1 L2
L1 L2 L1 L2 L1 L2
ONE (1) ELEMENT ROWS TWO (2) ELEMENT ROWS THREE (3) ELEMENT ROWS FOUR (4) ELEMENT ROWS
L1 L2 L1 L2
NOTE: WHEN INSTALLING HEATER KIT, ENSURE SPEED TAP DOES NOT EXCEED MINIMUM BLOWER SPEED (MBS) SPECIFIED FOR THE AIRHANDLER/HEAT ER
KIT COMBINATION ON THIS UNIT'S S&R PLATE. AFTER INSTALLING OPTIONAL HEAT KIT, MARK AN "X" IN THE PROVIDED ABOVE.
MARK ACCORDING TO NUMBER OF HEATER ELEMENT ROWS INSTALLED. NO MARK INDICATES NO HEAT KIT INSTALLED.
RD BK RD BL BR WH
SEE
BR NOTE 4
1 2 3 SEE NOTE 1
WH
BL CR
TR
B A 7 4
4 24V 5
BL
GR 6
RD 5 4 PLF 1
RD 2
CR EM
BK 3
XFMR-R RD 4
COM C
R 4 BK SEE NOTE 1 5
RD
RD
EBTDR RD C 1 2 3 R C G W1 W2 Y1 Y2 O DH 1 2 3 4 5
XFMR-C 7 1 RD 240
SEE
C NOTE 3 TR COLOR CODE WIRING CODE
NO NC BL 4
GR 5 24V
G GR A B BK BLACK GR GREEN FACTORY WIRING
RD RED PU PURPLE HIGH VOLTAGE
BL YL YELLOW BR BROWN LOW VOLTAGE
BL BL BL BLUE WH WHITE
BL FIELD WIRING
BL RD HIGH VOLTAGE
COMPONENT CODE LOW VOLTAGE
RD
EM EVAPORATOR MOTOR TR TRANSFORMER
COPPER OR
COPPER ALUMINUM
POWER SUPPLY TB TERMINAL BOARD PLF FEMALE PLUG CONNECTOR
POWER SUPPLY R RELAY PLM MALE PLUG CONNECTOR
(SEE RATING
(SEE RATING PLATE)
PLATE) 1 234 5 CR CONTROL RELAY FL FUSE LINK
USE MIN.
USE MIN.75°C FIELD
75°C FIELD
WIRE WIRE EBTDR ELECTRONIC BLOWER TIME TL THERMAL LIMIT
EM DELAY RELAY HTR HEAT ELEMENTS
Notes:
C L GN 1) Red wires to be on transformer terminal "3" for 240 volts and on terminal "2" for 208 volts.
BL 2) See composite wiring diagrams in installation instructions
RD BK for proper low voltage wiring connections.
3) Confirm speed tap selected is appropriate for application. If speed tap needs
to be changed, connect red wire from terminal 4 of CR relay to appropriate tap
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
at TB
4) Brown and white wires are used with Heat Kits only.
IF REPLACEMENT OF THE ORIGINAL WIRES
SUPPLIED WITH THIS ASSEMBLY IS NEC ESSARY,
USE WIRE THAT CONFORMS TO THE
NATIONAL ELECTRIC CODE.
0140A00034
ASPF******AA
85
86
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
WIRING DIAGRAMS
EQUIPMENT GROUND
USE COPPER WIRE
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
ASPF******BA
WIRING DIAGRAMS ASPF******CA
FL
TL
FL HTR1
FL BK
FL
TL TL TL
HTR1 HTR1
FL FL FL BK HTR2 RD
FL
TL TL TL TL
HTR1 HTR2 HTR2 RD HTR3
BK FL FL YL
TL TL
HTR3 HTR4 BL
BK BK 1 RD BK 1 BK 1 BK 1
2
2 2 RD YL 2
PU PU
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
RD RD YL BK BL BK RD
BL 3
PU 3 PU 3 BL 3
RD
BK RD M1 M3 M1 RD
BL BL BL 4 YL
M1 M3 M5 M7
BL 4
RD
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
4 BK 4
M2 M4 M2
RD M4
M1 M1 M3 M2 M6 M8
R1 R2
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
BR 5
R R R1 R2 BR 5
5 5 BK BK
M2 M2 M4 BK
BK
RD WH 6
RD WH 6
WH 6 WH 6
7
7
BK
BK RD YL
7 7 8 YL
BK BK BL 8
BK
RD RD BK
8 8 RD 9
RD 9
9 9
L1 L2 L1 L2
L1 L2 L1 L2 L1 L2 L1 L2
ONE (1) ELEMENT ROWS TWO (2) ELEMENT ROWS THREE (3) ELEMENT ROWS FOUR (4) ELEMENT ROWS
NOTE:WHEN INSTALLING HEATER KIT, ENSURE SPEED TAP DOES NOT EXCEED MINIMUM BLOWER SPEED (MBS) SPECIFIED FOR THE AIRHANDLER/HEATER
KIT COMBINATION ON THIS UNIT'S S&R PLATE. AFTER INSTALLING OPTIONAL HEAT KIT, MARK A "X" IN THE PROVIDED ABOVE.
MARK ACCORDING TO NUMBER OF HEATER ELEMENT ROWS INSTALLED. NO MARK INDICATES NO HEAT KIT INSTALLED.
208/240VOLTS
RD
PLF 1 2 3 4 5 6 7 8 9
SEE NOTE 1
BK RD BL BR WH 5
HIGH VOLTAGE!
GR 1 2 3
SEE
BR NOTE 4
TR
WH
3 1 2 4
BL
4 24V 5 CR
HOLDER
FUSE
RD 6 5 4 PLF 1
WH
2 EM
PU 3
4 C
5
CR BK
RD
SEE SEE R C G W1 W2 Y1 Y2 O DH 1 2 3 4 5
4 NOTE3 BK NOTE 1
WH
C 1 2 3 240
RD 2 5 RD
TR COLOR CODE WIRING CODE
GR 1 3 5 24V 4
FACTORY WIRING
BK BLACK GR GREEN
BL BL RD RED PU PURPLE HIGH VOLTAGE
BL YL YELLOW BR BROWN LOWVOLTAGE
BL WH PU BL BLUE WH WHITE FIELD WIRING
BL FUSE
HOLDER HIGH VOLTAGE
RD RD
OR BR YL COMPONENTCODE LOWVOLTAGE
1) RED WIRES TO BE ON TRANSFORMER TERMINAL "3" FOR 240 VOLTS AND ON TERMINAL
"2" FOR 280 VOLTS.
IF REPLACEMENT OF THE ORIGINAL WIRES 2) SEE COMPLETE WIRING DIAGRAMS ININSTALLATION INSTRUCTIONS FOR PROPER LOW
VOLTAGE WIRING CONNECTIONS.
SUPPLIED WITH THIS ASSEMBLY IS NECESSARY, 3) CONFIRM SPEED TAP SELECTION IS APPROPRIATE FOR APPLICATION. IF SPEED TAP
USE WIRE THAT CONFORMS TO THE NATIONAL NEEDS TO BE CHANGED, CONNECT PURPLE WIRE FROM TERMINAL 4 OF CR RELAY TO
APPROPRIATE TAP AT TB
ELECTRIC CODE. 4) BROWN AND WHITE WIRES ARE USED FOR HEAT KITS ONLY. 0140A00040-D
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
87
88
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
FL FL FL
FL
TL TL TL TL
HTR1 HTR1 BK HTR1
HTR 1 FL BK
FL FL
TL TL
TL HTR2 HTR2
HTR2 RD RD
FL FL
BK BK TL TL
BK 1
HTR3 HTR3 YL
FL
BK 1
2 RD BK 1 TL
HTR4 BL
RD
RD YL 2 BK 1
2
PU 3 PU
BK RD YL BK
BL BL 3 2
PU
PU 3
4 RD BL
M1 RD BL M1 M3 M1 BK RD
BL 4 3
WIRING DIAGRAMS
BL
R BK 4 RD M2 M4 M2
5 M1 M3 RD
R2 M1 M3 M5 M7
M2 R1 BR 5 YL BL 4
R RD M2 M4 M6 M8
5 BK
WH 6
M2 M4 BK
RD 6 R1 R2 BR 5
WH
6
BK
WH BK
BK 7 RD WH 6
BK 7
BK
RD 7 YL
RD BK 8 7
8
RD 8
BK YL
RD BL 8
9
9
BK
9 RD 9
L1 L2 L1 L2 L1 L2 L1 L2
L1 L2 L1 L2
ONE (1) ELEMENT ROWS TWO (2) ELEMENT ROWS THREE (3) ELEMENT ROWS FOUR (4) ELEMENT ROWS
NOTE: WHEN INSTALLING HEATER KIT, ENSURE SPEED TAP DOES NOT EXCEED MINIMUM BLOWER SPEED (MBS) SPECIFIED FOR THE AIRHANDLER/HEAT ER KIT COMBINATION ON THIS
UNIT'S S&R PLATE. AFTER INSTALLING OPTIONAL HEAT KIT, MARK A "X" IN THE BOX PROVIDED ABOVE. MARK ACCORDING TO NUMBER OF HEATER ELEMENT ROWS INSTALLED. NO MARK
INDICATES NO HEAT KIT INSTALLED.
BR WH SEE
BK RD BL
GR NOTE 4 SEE NOTE 1 COLOR CODE
BR ALTERNATE HEAT RELAY
WH 1 2 3 1 BK BLACK GR GREEN
BL RD RED PU PURPLE
TR YL YELLOW BR BROWN
BL BLUE WH WHITE
RD or BK 4 7
WH B A
4 24V 5 CR
PU
COMPONENT CODE
CR
FUSE
BK 6 5 4 PLM 1 CR CONTROL RELAY
RD HOLDER
SEE 2 EM EVAPORATOR MOTOR
7 BK NOTE 1 (OPTIONAL) EM
WH 3 FL FUSE LINK
C 1 2 3
4 C
RD 240 5 HTR HEAT ELEMENTS
RD 4 1
TR PLF FEMALE PLUG CONNECTOR
5 24V 4
GR A B R C G W 1 W2 Y1 Y2 O DH 1 2 3 4 5 PLM MALE PLUG CONNECTOR
BL
R RELAY
BL
BL
WH PU
TB TERMINAL BOARD
BL FUSE
BL TR TRANSFORMER
HOLDER
RD or BK RD or BK (OPTIONAL) OR BR YL NOTES: TL THERMAL LIMIT
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
ELECTRIC CODE. BL 0140A00063-B
BL
ALTERNATE HEAT RELAY
ASPF******C*
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
208/230 VOLTS
EQUIPMENT GROUND
* *
XFMR-R M2 M1 SEE TL1 TL1 HTR 2 TL2 * R1 * *
*
NO NOTE 5
R
TL2 M4 M3
TL1 HTR 1 TL2
XFMR-C HTR1
COM
BK TL1 RD
C M2 M1
NC TL2*
G SU
HTR2* RD
EBTDR
WIRING DIAGRAMS
*
FC EM
BK
* NC NO
BL
HI
DISC DISC
M2
COM
LO
SEE NOTE 1 EBTDR
1 2 3
BK
PU BK BK EBTDR TR EBTDR
RD RD RD
R
SEE C G
NOTE 4 24 VOLT 5
3 R1
BR RD BL
RD * RD BK
3 2 1
M2 M4 TR
R1 RD GR
M1 BL WH BR
M3 5
RD RD COLOR CODE WIRING CODE
4
WH
RD RD * WH WHITE GR GREEN FACTORY WIRING
BR RD BK BLACK PU PURPLE HIGH VOLTAGE
RD RED BR BROWN LOW VOLTAGE
YL YELLOW FIELD WIRING
GR BL BLUE HIGH VOLTAGE
RD LOW VOLTAGE NOTE 3
WH COMPONENT CODE
BR BL
DISC DISCONNECT SWITCH R RELAY
EM EVAPORATOR MOTOR FC FAN CAPACITOR
EBTDR ELECTRONIC BLOWER TL THERMAL LIMIT
TIME DELAY RELAY TR TRANSFORMER
RD PU BK HTR HEATER ELEMENT
EVAPORATOR MOTOR LEADS NOTES:
PU COMMON 1) RED WI RE TO B E ON TRANSFORMER TERMINAL 3 FOR 230 VOLTS AND ON
BK HIGH TERMINAL 2 F OR 208 VOLTS.
RD LOW 2) TO PLACE AIRHANDLER IN HIGH SPEED, REMOVE RED MOTOR LEAD FROM E LECTRONIC
EM BLOW ER TIME DELAY RELAY (EBTDR) COM TERMINAL AND REPLACE WI TH BLACK
MOTOR LEAD. ALL UNITS WI LL BE FACTORY CONNECTED AT LOW SPEED.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
FC
CONTROLS SHOWN WITH UTILITIES IN "ON" POSITION AND THERMOSTAT IN "OFF" POSITION.
AWUF [18, 24, 30, 36]**
IF REPLACEMENT OF THE ORIGINAL WIRES SUPPLIED WITH THIS ASSEMBLY IS NECESSARY, USE 105°C. WIRE. SIZE TO CONFORM TO THE NATIONA L ELECTRIC CODE. BT14933447 REV B
89
90
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
WIRING DIAGRAMS
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
AWUF[31-32]**
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
BK
WIRING DIAGRAMS
TL2
BK HTR1
BK RD
BK
BK BK * TL2*
HTR2*
WH
GR YL
OR BR RD
BR
RD
PULL TO
DISCONNECT
BL
RD
RD
RD
RD
WH
PU
RD 4 NOTES:
6. W IRING CODE:
1 2 3 FACTORY WIRING
12345 240 HIGH VOLTAGE
EM TR LOW VOLTAGE
FIELD W IRING
C L GN 5 24V 4 HIGH VOLTAGE
BL BL LOW VOLTAGE NOTE 3
RD BK
GR/YL
RD 7. COMPONENT CODE:
DISC -- DISCONNECT SWITCH R -- RELAY
BL EM -- EVAPORATOR MOTOR FC -- FAN CAPACITOR
EBTDR -- ELECTRIC BLOW ER TL -- THERMAL LIMIT
TIME DELAY RELAY TR -- TRANSFORMER
HTR -- HEATER ELEMENT
0140A00036 REV. A
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
AWUF37
91
BLOWERS
92
WIRING DIAGRAMS MBE
IF NEEDED
CONDENSING HUMIDISTAT
UNIT (OPTIONAL)
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
THERMOSTATS HUMIDISTAT
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
3.) OT1 PJ4 MUST BE CUT FOR THIS CONFIGURATION CONDENSER HEATPUMP
R YCON COM O W2 ED Y1
SWITCH
5.) DIP SWITCH #4 MUST BE IN THE "ON" POSITION OT1
W1 W2
OT2
HUM
DIP
PLEASE REFER
TO MANUAL
OFF
ON
FOR PROPER
DIP SWITCH(CFM)
CONFIGURATION.
OUTDOOR ROOM
THERMOSTAT THERMOSTAT
W C R G Y
IF NEEDED
CONDENSING HUMIDISTAT
UNIT (OPTIONAL)
W1 W2
5.) DIP SWITCH #4 MUST BE IN THE "ON" POSITION OT1
OT2
HUM
DIP
PLEASE REFER
TO MANUAL
OFF
ON
FOR PROPER
DIP SWITCH(CFM)
CONFIGURATION.
COOLING ONLY - 2 STAGE HEAT (1st ROOM T'STAT & 2nd OT)
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
93
WIRING DIAGRAMS MBE
OUTDOOR ROOM
THERMOSTAT THERMOSTAT
W1 W2 C R G Y
IF NEEDED
CONDENSING HUMIDISTAT
UNIT (OPTIONAL)
OUTDOOR
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
3.) OT1 PJ4 MUST BE CUT FOR THIS CONFIGURATION CONDENSER HEATPUMP
R YCON COM O W2 ED Y1
OT2 PJ2 MUST BE CUT FOR THIS CONFIGURATION
SWITCH
W1 W2
5.) DIP SWITCH #4 MUST BE IN THE "ON" POSITION OT1
OT2
HUM
DIP
PLEASE REFER
TO MANUAL
OFF
ON
FOR PROPER
DIP SWITCH(CFM)
CONFIGURATION.
ROOM
HEATPUMP THERMOSTAT
R Y C O W2 E W2 O C R G Y
IF NEEDED
HEATPUMP
HUMIDISTAT
R
CONDENSER
YCON COM O W2 ED
(OPTIONAL)
SEE NOTE 4
THERMOSTATS HUMIDISTAT
E\W1 W/W2 O OTC OT1 OT2 C R Y1 G Y/Y2 HUM
NOTES: REMOVE
1.) Y ENABLES HI SPD FAN COOLING OUTDOOR PRODUCTION
CONDENSER HEATPUMP
WIRE Y1 - O
2.) E AND W2 ENABLE HI SPD FAN HEATING R YCON COM O W2 ED Y1
W1 W2
OT1
4.) CUT HUM PJ6 JUMPER IF USING HUMIDISTAT
STAT OPENS ON HUMIDITY RISE OT2
HUM
5.) DIP SWITCH #4 MUST BE IN THE "ON" POSITION
DIP
PLEASE REFER
TO MANUAL
OFF
ON
FOR PROPER
DIP SWITCH(CFM)
CONFIGURATION.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
94
WIRING DIAGRAMS MBE
ROOM
HEATPUMP THERMOSTAT
R Y C O W2 E W2 O C R G Y
IF NEEDED
HUMIDISTAT
HEATPUMP
R
CONDENSER
YCON COM O W2 ED
(OPTIONAL)
SEE NOTE 4
THERMOSTATS HUMIDISTAT
E\W1 W/W2 O OTC OT1 OT2 C R Y1 G Y/Y2 HUM
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
NOTES: REMOVE
1.) Y ENABLES HI SPD FAN COOLING OUTDOOR PRODUCTION
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
HEATPUMP
WIRE Y1 - O
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
CONDENSER
2.) E ENABLES LO SPD FAN HEATING R YCON COM O W2 ED Y1
W2 ENABLES HI SPD FAN HEATING
W1 W2 C R
3.) OT1 PJ4 MUST BE CUT FOR THIS CONFIGURATION HEATER 24 VAC
SWITCH
W1 W2
OT1
4.) CUT HUM PJ6 JUMPER IF USING HUMIDISTAT OT2
STAT OPENS ON HUMIDITY RISE
HUM
DIP
PLEASE REFER
5.) DIP SWITCH #4 MUST BE IN THE "ON" POSITION TO MANUAL
OFF
ON
FOR PROPER
DIP SWITCH(CFM)
CONFIGURATION.
OUTDOOR
THERMOSTAT ROOM
HEATPUMP THERMOSTAT
R Y C O W2 E W2 O C R G Y
IF NEEDED
HUMIDISTAT
HEATPUMP
R
CONDENSER
YCON COM O W2 ED
(OPTIONAL)
SEE NOTE 4
THERMOSTATS HUMIDISTAT
E\W1 W/W2 O OTC OT1 OT2 C R Y1 G Y/Y2 HUM
NOTES: REMOVE
1.) Y ENABLES HI SPD FAN COOLING OUTDOOR PRODUCTION
CONDENSER HEATPUMP
WIRE Y1 - O
2.) E ENABLES LO SPD FAN HEATING R YCON COM O W2 ED Y1
W2 ENABLES LO SPD FAN HEATING
W2 AND OT2 CLOSED ENABLES HI SPD FAN HEATING W1 W2 C R
HEATER 24 VAC
3.) 0T2 PJ2 MUST BE CUT FOR THIS CONFIGURATION
SWITCH
W1 W2
OT1
OT2
4.) CUT HUM PJ6 JUMPER IF USING HUMIDISTAT
HUM
STAT OPENS ON HUMIDITY RISE
DIP
PLEASE REFER
TO MANUAL
OFF
FOR PROPER
DIP SWITCH(CFM)
CONFIGURATION.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
95
WIRING DIAGRAMS MBE
IF NEEDED
HUMIDISTAT
HEATPUMP
R
CONDENSER
YCON COM O W2 ED OTC OT1 OT2
(OPTIONAL)
OUTDOOR
SEE NOTE 4
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
THERMOSTATS HUMIDISTAT
E\W1 W/W2 O OTC OT1 OT2 C R Y1 G Y/Y2 HUM
REMOVE
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
SWITCH
W1 W2
OT1
3.) OT1 PJ4 AND 0T2 PJ2 MUST BE CUT
OT2
FOR THIS CONFIGURATION
HUM
DIP
4.) CUT HUM PJ6 JUMPER IF USING HUMIDISTAT PLEASE REFER
TO MANUAL
OFF
STAT OPENS ON HUMIDITY RISE
ON
FOR PROPER
DIP SWITCH(CFM)
CONFIGURATION.
5.) DIP SWITCH #4 MUST BE IN THE "ON" POSITION
2nd STAGE HEATER
1st STAGE HEATER
OUTDOOR
HIGH VOLTAGE!
THERMOSTAT ROOM
HEATPUMP THERMOSTAT
R Y C O W2 E W2 O C R G Y
IF NEEDED
HUMIDISTAT
HEATPUMP
R
CONDENSER
YCON COM O W2 ED
(OPTIONAL)
SEE NOTE 4
THERMOSTATS HUMIDISTAT
E\W1 W/W2 O OTC OT1 OT2 C R Y1 G Y/Y2 HUM
NOTES: REMOVE
1.) Y ENABLES HI SPD FAN COOLING OUTDOOR PRODUCTION
CONDENSER HEATPUMP
WIRE Y1 - O
2.) E ENABLES LO SPD FAN HEATING R YCON COM O W2 ED Y1
W2 ENABLES LO SPD FAN HEATING
W2 AND OT2 CLOSED ENABLES HI SPD FAN HEATING W1 W2 C R
HEATER 24 VAC
3.) 0T2 PJ2 MUST BE CUT FOR THIS CONFIGURATION
SWITCH
W1 W2
OT1
OT2
4.) CUT HUM PJ6 JUMPER IF USING HUMIDISTAT
STAT OPENS ON HUMIDITY RISE HUM
DIP
PLEASE REFER
TO MANUAL
OFF
FOR PROPER
DIP SWITCH(CFM)
CONFIGURATION.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
96
WIRING DIAGRAMS MBE
IF
N
RSG - 2 SPD E
CONDENSING E
D
HUMIDISTAT
UNIT (OPTIONAL)
C E
D
X
Y2
NOTES: Y1 SEE NOTE 4
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
ROOM
THERMOSTAT
HIGH VOLTAGE!
W W2 C R Y1 G Y2
IF
N
RSG - 2 SPD E
CONDENSING E
D
HUMIDISTAT
UNIT (OPTIONAL)
C E
D
X
Y2
NOTES: Y1 SEE NOTE 4
1.) Y1 ENABLES LO SPD FAN COOLING THERMOSTATS HUMIDISTAT
Y/Y2 ENABLES HI SPD FAN COOLING E\W1 W/W2 O OTC OT1 OT2 C R Y1 G Y/Y2 HUM
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
97
WIRING DIAGRAMS MBE
Two-Stage Cooling with Conventional Two-Stage Thermostat
OUTDOOR ROOM
THERMOSTAT THERMOSTAT
W C R Y1 G Y2
IF NEEDED
RSG - 2 SPD
CONDENSING HUMIDISTAT
C UNIT (OPTIONAL)
X
Y2
NOTES: Y1 SEE NOTE 4
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
SWITCH
W1 W2
OT1
5.) DIP SWITCH #4 MUST BE IN THE "OFF" POSITION OT2
HUM
DIP
PLEASE REFER
TO MANUAL
OFF
ON
FOR PROPER
DIP SWITCH(CFM)
CONFIGURATION.
OUTDOOR ROOM
THERMOSTAT THERMOSTAT
W1 W2 C R Y1 G Y2
IF NEEDED
RSG - 2 SPD
CONDENSING HUMIDISTAT
C UNIT (OPTIONAL)
X
Y2
NOTES: Y1 SEE NOTE 4
1.) Y1 ENABLES LO SPD FAN COOLING THERMOSTATS HUMIDISTAT
Y/Y2 ENABLES HI SPD FAN COOLING E\W1 W/W2 O OTC OT1 OT2 C R Y1 G Y/Y2 HUM
CONDENSER HEATPUMP
R YCON COM O W2 ED Y1
3.) OT1 PJ4 MUST BE CUT FOR THIS CONFIGURATION
OT2 PJ2 MUST BE CUT FOR THIS CONFIGURATION
W1 W2 C R
HEATER 24 VAC
4.) CUT HUM PJ6 JUMPER IF USING HUMIDISTAT
SWITCH
HUM
DIP
PLEASE REFER
TO MANUAL
OFF
ON
FOR PROPER
DIP SWITCH(CFM)
CONFIGURATION.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
98
WIRING DIAGRAMS MBE
Heat Pump with Single or Two-Stage Heating (Options for Emergency Heat)
with Conventional Thermostat
ROOM
HEATPUMP THERMOSTAT
R Y C O W2 E W2 O C R G Y
IF NEEDED
HUMIDISTAT
HEATPUMP
R
CONDENSER
YCON COM O W2 ED
(OPTIONAL)
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
SEE NOTE 4
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
THERMOSTATS HUMIDISTAT
E\W1 W/W2 O OTC OT1 OT2 C R Y1 G Y/Y2 HUM
NOTES: REMOVE
1.) Y ENABLES HI SPD FAN COOLING OUTDOOR PRODUCTION
CONDENSER HEATPUMP
WIRE Y1 - O
2.) E AND W2 ENABLE HI SPD FAN HEATING R YCON COM O W2 ED Y1
SWITCH
W1 W2
4.) CUT HUM PJ6 JUMPER IF USING HUMIDISTAT OT1
STAT OPENS ON HUMIDITY RISE OT2
HUM
5.) DIP SWITCH #4 MUST BE IN THE "ON" POSITION
DIP
PLEASE REFER
TO MANUAL
OFF
ON
FOR PROPER
DIP SWITCH(CFM)
CONFIGURATION.
ROOM
HEATPUMP THERMOSTAT
R Y C O W2 E W2 O C R G Y
IF NEEDED
SEE NOTE 4
THERMOSTATS HUMIDISTAT
E\W1 W/W2 OTC OT1 OT2 C R Y1 G Y/Y2 HUM
NOTES: REMOVE
1.) Y ENABLES HI SPD FAN COOLING OUTDOOR PRODUCTION
CO NDENS ER
HEATPUMP WIRE Y1-O
2.) E ENABLES LO SPD FAN HEATING R YCON COM O W2 ED Y1
W2 ENABLES HI SPD FAN HEATING
5
1
CR11
CR9 W1 W2 C R
3.) OT1 PJ4 MUST BE CUT FOR THIS CONFIGURATION 24 VAC
S
CR3
R2
W1 W2
1 2 3 4 5 67 8
WI
CR8
4.) CUT HUM PJ6 JUMPER IF USING HUMIDISTAT CR10 OT1 PJ4 TC
CR7
H
STAT OPENS ON HUMIDITY RISE
CR6
OT2 PJ2
J3
R1 CR5
HUM
CR2
PJ6 C2
J2
DI
5.) DIP SWITCH #4 MUST BE
4
CR1
DS1
PLEASE REFER P
1
O O
IN THE "ON" POSITION TO MANUAL
N FF
FOR PROPER R3
DIP SWITCH
J1
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
99
WIRING DIAGRAMS MBE
OUTDOOR
THERMOSTAT ROOM
HEATPUMP THERMOSTAT
R Y C O W2 E W2 O C R G Y
IF NEEDED
CO N DEN S ER
HEATPUMP HUMIDISTAT
R YCON COM O W2 ED (OPTIONAL)
SEE NOTE 4
THERMOSTATS HUMIDISTAT
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
NOTES: REMOVE
1.) Y ENABLES HI SPD FAN COOLING
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
OUTDOOR PRODUCTION
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
CO N DEN S ER
HEATPUMP
WIRE Y1-O
2.) E ENABLES LO SPD FAN HEATING R YCON COM O W2 ED Y1
W2 ENABLES LO SPD FAN HEATING
W2 AND OT2 CLOSED ENABLES HI SPD
5
1
W1 W2 R
CR11
C
FAN HEATING
CR9
24 VAC
S
CR3
1 2 3 4 5 67 8
WI
CR8
CR10 OT1 PJ4 TC
CR7
H
4.) CUT HUM PJ6 JUMPER IF USING HUMIDISTAT
CR6
OT2 PJ2
J3
R1 CR5
J2
DI
4
CR1
DS1
PLEASE REFER P
1
O O
5.) DIP SWITCH #4 MUST BE TO MANUAL
N FF
FOR PROPER
IN THE "ON" POSITION
R3
DIP SWITCH
J1
CONFIGURATION. GOODMAN MFG. CO. L.P.
2nd STAGE HEATER
1ST STAGE HEATER
ROOM
HIGH VOLTAGE!
HEATPUMP THERMOSTAT
R Y C O W2 E W2 O C R G Y
IF
N
E
E
D HUMIDISTAT
HEATPUMP
CO NDENS ER
OUTDOOR
SEE NOTE 4
THERMOSTATS HUMIDISTAT
E\W1 W/W2 OTC OT1 OT2 C R Y1 G Y/Y2 HUM
REMOVE
OUTDOOR PRODUCTION
NOTES:
1.) Y ENABLES HI SPD FAN COOLING
CO NDENS ER HEATPUMP WIRE Y1-O
R YCON COM O W2 ED Y1
W1 R
CR11
W2 C
W2 AND OT1 CLOSED ENABLES LO SPD FAN HEATING CR9
24 VAC
W2 AND OT2 CLOSED ENABLES HI SPD FAN HEATING S
CR3
R2
W1 W2
1 2 3 4 5 67 8
WI
CR8
CR10 OT1 PJ4 TC
CR7
3.) OT1 PJ4 AND OT2 PJ2 MUST BE CUT FOR THIS PJ2
H CR6
OT2
CONFIGURATION
J3
R1 CR5
HUM
CR2
PJ6 C2
J2
DI
4
PLEASE REFER P
1
O O
STAT OPENS ON HUMIDITY RISE TO MANUAL
N FF
FOR PROPER R3
DIP SWITCH
J1
5.) DIP SWITCH #4 MUST BE IN THE "ON" POSITION CONFIGURATION. GOODMAN MFG. CO. L.P.
2nd STAGE HEATER
1ST STAGE HEATER
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
100
WIRING DIAGRAMS MBE
OUTDOOR
THERMOSTAT ROOM
HEATPUMP THERMOSTAT
R Y C O W2 E W2 O C R G Y
IF NEEDED
CO NDENS ER
HEATPUMP HUMIDISTAT
R YCON COM O W2 ED (OPTIONAL)
SEE NOTE 4
THERMOSTATS HUMIDISTAT
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
NOTES: REMOVE
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
CO NDENS ER
HEATPUMP WIRE Y1-O
2.) E ENABLES LO SPD FAN HEATING R YCON COM O W2 ED Y1
W2 AND OT2 CLOSED ENABLES HI SPD FAN HEATING
5
1
W1 R
CR11
W2 C
3.) OT1 PJ4 AND OT2 PJ2 MUST BE CUT
CR9
24 VAC
S
CR3
1 2 3 4 5 67 8
W1 W2 WI
CR8
CR10 OT1 PJ4 TC
CR7
H
4.) CUT HUM PJ6 JUMPER IF USING HUMIDISTAT
CR6
OT2 PJ2
J3
R1 CR5
J2
DI
4
CR1
DS1
PLEASE REFER P
1
O O
5.) DIP SWITCH #4 MUST BE IN THE "ON" POSITION TO MANUAL
FOR PROPER N FF
R3
DIP SWITCH
J1
CONFIGURATION. GOODMAN MFG. CO. L.P.
2nd STAGE HEATER
1ST STAGE HEATER
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
101
WIRING DIAGRAMS MBE
Two Speed Heat Pump with Single or Two-Stage Heating
(Options for Emergency Heat) with Conventional Two-Stage Thermostat
RTG ROOM
HEATPUMP THERMOSTAT
R Y2 C O W2 Y1 E W2 O C R G Y2 Y1
IF NEEDED
CO NDENS ER
HEATPUMP HUMIDISTAT
R YCON COM O W2 ED (OPTIONAL)
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
SEE NOTE 4
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
THERMOSTATS HUMIDISTAT
E\W1 W/W2 OTC OT1 OT2 C R Y1 G Y/Y2 HUM REMOVE
NOTES: PRODUCTION
1.) Y ENABLES HI SPD FAN COOLING OUTDOOR WIRE Y1-O
CO NDENS ER HEATPUMP
2.) E AND W2 ENABLE HI SPD FAN HEATING R YCON COM O W2 ED Y1
5
3.) IF OT2 PJ2 JUMPER IS CUT, E AND W2 ENABLE LO
1
W1 R
CR11
CR9 W2 C
SPD FAN HEATING 24 VAC
S
CR3
R2
W1 W2
1 2 3 4 5 67 8
WI
CR8
OT1
4.) CUT HUM PJ6 JUMPER IF USING HUMIDISTAT PJ4 TC
CR10 CR7
H CR6
STAT OPENS ON HUMIDITY RISE OT2 PJ2
J3
R1 CR5
HUM
CR2
PJ6 C2
J2
DI
4
5.) DIP SWITCH #4 MUST BE IN THE "OFF" POSITION
CR1
DS1
PLEASE REFER P
1
TO MANUAL O O
FOR PROPER N FF
R3
DIP SWITCH
J1
RTG ROOM
HEATPUMP THERMOSTAT
R Y2 C O W2 Y1 E W2 O C R G Y2 Y1
IF NEEDED
CO NDENS ER
HEATPUMP HUMIDISTAT
R YCON COM O W2 ED (OPTIONAL)
SEE NOTE 4
THERMOSTATS HUMIDISTAT
E\W1 W/W2 OTC OT1 OT2 C R Y1 G Y/Y2 HUM REMOVE
NOTES: PRODUCTION
1.) Y ENABLES HI SPD FAN COOLING OUTDOOR WIRE Y1-O
CO NDENS ER HEATPUMP
2.) E ENABLES LO SPD FAN HEATING R YCON COM O W2 ED Y1
W2 ENABLES HI SPD FAN HEATING
5
1
W1 R
CR11
W2 C
3.) OT1 PJ4 MUST BE CUT FOR THIS
CR9
24 VAC
CONFIGURATION S
CR3
R2
1 2 3 4 5 67 8
W1 W2 WI
CR8
CR10 OT1 PJ4 TC
CR7
R1 CR5
STAT OPENS ON HUMIDITY RISE HUM PJ6
CR2
C2
J2
DI
4
CR1
DS1
PLEASE REFER P
1
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
102
WIRING DIAGRAMS MBE
OUTDOOR
RTG ROOM
THERMOSTAT
HEATPUMP THERMOSTAT
R Y2 C O W2 Y1 E W2 O C R G Y2 Y1
IF NEEDED
CO NDENS ER
HEATPUMP HUMIDISTAT
R YCON COM O W2 ED (OPTIONAL)
SEE NOTE 4
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
THERMOSTATS HUMIDISTAT
E\W1 W/W2 OTC OT1 OT2 C R Y1 G Y/Y2 HUM REMOVE
PRODUCTION
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
NOTES:
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
5
1
CR11
W1 W2 C R
FAN HEATING
CR9
24 VAC
S
CR3
R2
W1 W2
1 2 3 4 5 67 8
WI
3.) OT2 PJ2 MUST BE CUT FOR THIS
CR8
CR10 OT1 PJ4 TC
CR7
J3
R1 CR5
HUM
CR2
PJ6
4.) CUT HUM PJ6 JUMPER IF USING HUMIDISTAT
C2
J2
DI
4
CR1
DS1
PLEASE REFER P
1
STAT OPENS ON HUMIDITY RISE TO MANUAL O O
FOR PROPER R3
N FF
DIP SWITCH
J1
5.) DIP SWITCH #4 MUST BE IN THE "OFF" POSITION CONFIGURATION. GOODMAN MFG. CO. L.P.
2ND STAGE HEATER
1ST STAGE HEATER
CO NDENS ER
HEATPUMP HUMIDISTAT
R YCON COM O W2 ED (OPTIONAL)
OTC OT1 OT2
CR11
CR9 W1 W2 C R
24 VAC
S
CR3
R2
W1 W2
1 2 3 4 5 67 8
WI
3.) OT1 PJ4 AND OT2 PJ2 MUST BE CUT FOR THIS
CR8
CR10 OT1 PJ4 TC
CR7
R1 CR5
HUM
CR2
PJ6
4.) CUT HUM PJ6 JUMPER IF USING HUMIDISTAT
C2
J2
DI
4
CR1
DS1
PLEASE REFER P
1
5.) DIP SWITCH #4 MUST BE IN THE "OFF" POSITION CONFIGURATION. GOODMAN MFG. CO. L.P.
2ND STAGE HEATER
1ST STAGE HEATER
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
103
WIRING DIAGRAMS MBE
OUTDOOR
RTG ROOM
THERMOSTAT
HEATPUMP THERMOSTAT
R Y2 C O W2 Y1 E W2 O C R G Y2 Y1
IF NEEDED
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
SEE NOTE 4
THERMOSTATS HUMIDISTAT
E\W1 W/W2 OTC OT1 OT2 C R Y1 G Y/Y2 HUM REMOVE
NOTES: PRODUCTION
1.) Y ENABLES HI SPD FAN COOLING OUTDOOR WIRE Y1-O
CO NDENS ER HEATPUMP
2.) E ENABLES LO SPD FAN HEATING R YCON COM O W2 ED Y1
W2 AND OT2 CLOSED ENABLES HI SPD
FAN HEATING
5
1
CR11
CR9 W1 W2 C R
24 VAC
3.) OT1 PJ4 AND OT2 PJ2 MUST BE CUT FOR THIS S
CR3
R2
W1 W2
1 2 3 4 5 67 8
WI
CR8
CONFIGURATION CR10 OT1 PJ4 TC
CR7
H CR6
OT2 PJ2
J3
4.) CUT HUM PJ6 JUMPER IF USING HUMIDISTAT
R1 CR5
HUM
CR2
PJ6 C2
STAT OPENS ON HUMIDITY RISE
J2
DI
4
CR1
DS1
PLEASE REFER
1
P
TO MANUAL O O
N FF
5.) DIP SWITCH #4 MUST BE IN THE "OFF" POSITION FOR PROPER R3
DIP SWITCH
J1
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
104
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
TO Y ON
TSTWK01 BOARD
4 1N4005
DIODES
RSG 2 5 Y1 R1
Y2 R2
WIRING DIAGRAMS
1 3 Y1 Y2 W1 W2 G C R
REMOTE
CONDENSING HUMIDISTAT
C Y (OPTIONAL)
IF NEEDED
UNIT TO COMMON ON
TSTWK01 BOARD
SEE NOTE 1
ENCODED THERMOSTAT HUMIDISTAT
THERMOSTATS
S1 S2 S3 G Com R E\W1 W/W2 OTC OT1 OT2 C R Y1 G Y/Y2 HUM
TSTWK01 TEST
CR5 OUTDOOR
BOARD CR11 CR4 R3 CO NDENSER HEATPUMP
C H F
R2
R6 LED2 R YCON COM O W2 ED Y1
PWR Y2 Y1 CR9 CR2
5
ZD3 ZD1
1
ZD2
P1
CR8 R8 CR11
CR14 Q1 CR9 W1 W2 C R
24 VAC CR3
R5 CR7 R2 S
K1
CR8
R7 CR6 W1 W2 WI
C1
T2 T1 CR13 R4 CR10 OT1 PJ4 TC
CR7
K2
CR12 C4
PJ2
H CR6
OT2
J3
R1 CR5
K3 Q2
CR2
HUM PJ6 C2
J2
4
DI CR1
1
1 2 3 4 5 67 8
C2
DS1
C5 R1 PLEASE REFER P
C3
TO MANUAL O O
CR1
FOR PROPER N FF
CR3 R3
J1
DIP SWITCH
L2 L1 CONFIGURATION. GOODMAN MFG. CO. L.P.
GOODMAN MFG. CO. L.P.
24 V Y/Y2
2ND STAGE HEATER
YLO/Y1 NOTES: 1ST STAGE HEATER
1.) STAT OPENS ON HUMIDITY RISE CUT OT1 PJ4 FOR 2 STAGE HEAT OPERATION
C/X 2.) DIP SWITCH #4 MUST BE IN THE ON POSITION
230 V
CUT HUM PJ6 FOR HUMIDISTAT OPERATION
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
(Encoded with add on 1N006 Diodes)
(TSTWK01 Kit Required)
MBE
105
106
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
TO Y ON
TSTWK01 BOARD
OUTDOOR
THERMOSTAT
4 1N4005
DIODES
RSG 2 5 Y1 R1
Y2 R2
1 3 Y1 Y2 W1 W2 G C R
REMOTE
WIRING DIAGRAMS
CONDENSING HUMIDISTAT
C Y (OPTIONAL)
IF NEEDED
UNIT TO COMMON ON
TSTWK01 BOARD
SEE NOTE 2
ENCODED THERMOSTAT THERMOSTATS HUMIDISTAT
S1 S2 S3 G Com R E\W1 W/W2 OTC OT1 OT2 C R Y1 G Y/Y2 HUM
TSTWK01 TEST
CR5 OUTDOOR
BOARD CR11
R2
CR4 R3 CONDENSER HEATPUMP
C H F LED2 R YCON COM O W2 ED Y1
R6
PWR Y2 Y1 CR9 CR2
5
ZD3 ZD1
1
ZD2
P1
R8 CR11
W1 W2 R
CR8
CR14 Q1
CR9 C
24 VAC CR3
R5 CR7 R2 S
K1
R7 CR6 W1 W2 WI
CR8
C1
T2 T1 CR13 R4 CR10 OT1 PJ4 TC
CR7
K2
CR12 C4
PJ2
H CR6
OT2
J3
R1 CR5
K3 Q2
CR2
HUM PJ6 C2
J2
4
DI CR1
1
1 2 3 4 5 67 8
C2
DS1
C5 R1 PLEASE REFER P
C3
TO MANUAL O O
FF
CR1
CR3 FOR PROPER R3
N
J1
DIP SWITCH
L2 L1 CONFIGURATION. GOODMAN MFG. CO. L.P.
GOODMAN MFG. CO. L.P.
24 V Y/Y2
2ND STAGE HEATER
YLO/Y1 NOTES: 1ST STAGE HEATER
1.) OT2 CLOSED AND W2 DEMAND ENABLES
CUT OT2 PJ2 FOR THIS CONFIGURATION
C/X 2ND STG HEAT AND HI FAN
230 V 2.) STAT OPENS ON HUMIDITY RISE
CUT HUM PJ6 FOR HUMIDISTAT OPERATION
3.) DIP SWITCH #4 MUST BE IN THE ON POSITION
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
MBE
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
TO Y ON
TSTWK01 BOARD
CHET 18-60
ENCODED
THERMOSTAT
WIRING DIAGRAMS
4
RSG 2 5 Y1 R1
Y2 R2
1 3 S1 S2 S3 R
REMOTE
CONDENSING HUMIDISTAT
C Y (OPTIONAL)
UNIT TO COMMON ON
TSTWK01 BOARD
SEE NOTE 1
ENCODED THERMOSTAT THERMOSTATS HUMIDISTAT
S1 S2 S3 G Com R E\W1 W/W2 OTC OT1 OT2 C R Y1 G Y/Y2 HUM
TSTWK01 TEST
CR5 OUTDOOR
BOARD CR11
R2
CR4 R3 C O N D E N S ER HEATPUMP
C H F LED2 R YCON COM O W2 ED Y1
R6
PWR Y2 Y1 CR9 CR2
5
ZD3 ZD1
1
P1
ZD2 R8 CR11
W1 W2 R
CR8
CR14 Q1
CR9 C
24 VAC CR3
R5 CR7 R2 S
K1
R7 CR6 C1 W1 W2 WI
CR8
T2 T1 CR13 R4 CR10 OT1 PJ4 TC
CR7
K2
CR12 C4 H CR6
OT2 PJ2
J3
R1 CR5
K3 Q2
CR2
HUM PJ6 C2
J2
4
DI CR1
1
1 2 3 4 5 67 8
C2
DS1
C5 R1 PLEASE REFER P
C3
TO MANUAL O O
FF
CR1
CR3 FOR PROPER R3
N
J1
DIP SWITCH
L2 L1
CONFIGURATION. GOODMAN MFG. CO. L.P.
GOODMAN MFG. CO. L.P.
24 V Y/Y2
2ND STAGE HEATER
YLO/Y1 NOTES: 1ST STAGE HEATER
1.) STAT OPENS ON HUMIDITY RISE CUT OT2 PJ2 FOR THIS CONFIGURATION
C/X 2.) DIP SWITCH #4 MUST BE IN THE ON POSITION
230 V
CUT HUM PJ6 FOR HUMIDISTAT OPERATION
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
(TSTWK01 Kit Required)
MBE
107
108
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
TO Y ON
TSTWK01 BOARD
CHET 18-60
OUTDOOR
ENCODED THERMOSTAT
4
THERMOSTAT
RSG 2 5 Y1 R1
Y2 R2
1 3 S1 S2 S3 R
WIRING DIAGRAMS
REMOTE
CONDENSING HUMIDISTAT
C Y (OPTIONAL)
UNIT TO COMMON ON
TSTWK01 BOARD
SEE NOTE 2
ENCODED THERMOSTAT
THERMOSTATS HUMIDISTAT
S1 S2 S3 G Com R E\W1 W/W2 OTC OT1 OT2 C R Y1 G Y/Y2 HUM
TSTWK01 TEST
CR5 OUTDOOR
BOARD CR11
R2
CR4 R3 C O N D EN S ER HEATPUMP
C H F LED2 R YCON COM O W2 ED Y1
R6
PWR Y2 Y1 CR9 CR2
5
ZD3 ZD1
1
P1
ZD2 R8 CR11
CR8
CR14 Q1
CR9 W1 W2 C R
24 VAC CR3
R5 CR7 R2 S
K1
R7 CR6 W1 W2 WI
CR8
C1
T2 T1 CR13 R4 CR10 OT1 PJ4 TC
CR7
K2
CR12 C4
PJ2
H CR6
OT2
J3
R1 CR5
K3 Q2
CR2
HUM PJ6 C2
J2
4
DI CR1
1
1 2 3 4 5 67 8
C2
DS1
C5 R1 PLEASE REFER P
C3
TO MANUAL O O
FF
CR1
CR3 FOR PROPER R3
N
J1
DIP SWITCH
L2 L1
CONFIGURATION. GOODMAN MFG. CO. L.P.
GOODMAN MFG. CO. L.P.
24 V Y/Y2
2ND STAGE HEATER
YLO/Y1 NOTES: 1ST STAGE HEATER
1.) OT2 CLOSED AND W2 DEMAND ENABLES
CUT OT2 PJ2 FOR THIS CONFIGURATION
C/X 2ND STG HEAT AND HI FAN
230 V 2.) STAT OPENS ON HUMIDITY RISE
CUT HUM PJ6 FOR HUMIDISTAT OPERATION
3.) DIP SWITCH #4 MUST BE IN THE ON POSITION
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
MBE
REMOTE/SPLITS
109
110
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
RD R
YL Y NOTE 1
T1 T2
BL C L1 L2
5 SR 2 1
C SC C
BK IO CADM
H C
LVJB X S
2 C AU
C RCCF
A COMP
D MA F
RD BK COLOR CODE M IN
R
1
WIRING DIAGRAMS
3 BK --------------- BLACK
LAT BL --------------- BLUE C
NOTE 3 A SA
BR --------------- BROWN D
OR --------------- ORANGE (IF USED)
M
PU --------------- PURPLE
ALTERNATE DOUBLE
RD --------------- RED
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
ASC130[18-60]1**
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
BL OR WH RD HVDR SA
BL --------------- BLUE D
BL YL OR BK RD RD DF2 (IF USED)
BR --------------- BROWN M
RD 2 5
BL OR --------------- ORANGE ALTERNATE DOUBLE
POLE CONTACTOR ONLY
1 3
OR PU --------------- PURPLE IO
CMR (HIGH)
RD --------------- RED X
) AU
WH -------------- WHITE W
O CM
YL --------------- YELLOW (L
SC M
3 2 AI
N
WIRING CODE
BK BK 2 1 4 5
BL BK BK RD RD BL FACTORY WIRING CMR
LAT
HIGH VOLTAGE
NOTE 4
BL T2 RD LOW VOLTAGE CH
T1
BL OPTIONAL HIGH VOLTAGE
BK SR RD
L1 (IF USED)
YL L2
NOTE 3
5 YL C FIELD WIRING
YL BK BK DFT
1 HIGH VOLTAGE CADM R
2 BL DC
LOW VOLTAGE Y DFT C
C R Y
YL RD
VDR
L
R CMR
W2
YL
PU COMPONENT CODE (IF USED)
C HERM YL NOTE 3 RVC
C --------------- CONTACTOR O
RD F YL
YL CADM -------- COMFORT ALERT DIAGNOSTIC MODULE
BR RCCF
CH ------------- CRANKCASE HEATER O S
LP C
T1 T2 RD YL BK
CM ------------ OUTDOOR FAN MOTOR
RD BL RD YL SA CMR ---------- CONDENSER MOTOR RELAY
L1 L2 (IF USED)
R C Y R C S COMP -------- COMPRESSOR
NOTE 2
CADM RD DC ------------- DEFROST CONTROL
RD YL
BK DFT ----------- DEFROST THERMOSTAT
R C
HVDR -------- HIGH VOLTAGE DEFROST RELAY
O W2 Y
BK BK IO -------------- INTERNAL OVERLOAD
RVC INDOOR POWER
LAT ------------ LOW AMBIENT THERMOSTAT
COMP LPS ------------ LOW PRESSURE SWITCH SUPPLY
MAIN LVDR --------- LOW VOLTAGE DEFROST RELAY
RD EQUIPMENT GROUND
BK
LVJB ---------- LOW VOLTAGE JUNCTION BOX NOTES:
AUX RD USE COPPER
DFT RCCF --------- RUN CAPACITOR FOR COMPRESSOR & FAN 1) TO INDOOR UNIT LOW VOLTAGE
RD
CONDUCTORS ONLY TERMINAL BLOCK & INDOOR
RVC ----------- REVERSING VALVE COIL
YL THERMOSTAT.
MAIN SA ------------- START ASSIST 2) START ASSIST FACTORY
PU
C S SC ------------- START CAPACITOR FOR COMPRESSOR (OPTIONAL) EQUIPPED WHEN REQUIRED.
AUX 3) CRANKCASE HEATER MAY BE
BR
SR ------------- START RELAY FOR COMPRESSOR (OPTIONAL)
R FACTORY OR FIELD INSTALLED.
IO YL LP
S YL 4) LAT POSITION SHOWN .FOR HIGH
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
BK CONTROLS SHOWN WITH THERMOSTAT IN 'OFF' POSITION.
BK
AMBIENT TEMPERATURE
(HIGH) BK
CH USE N.E.C. CLASS 2 WIRE
RD
(IF USED) NOTE 3
CM (LOW)
VENDOR : GOODMAN PRINT SHOP 08/05 0140R00021P
ASH130[18-60]1A*
111
112
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
LVJB
OUTDOOR POWER SUPPLY
CONTROL BOX
SEE RATING PLATE
YL Y NOTE 1
BL C
T1 T3
L1 T2 L3
L2
C C C
WIRING DIAGRAMS
COLOR CODE L2
BK --------------- BLACK
BL --------------- BLUE
COMP
BR --------------- BROWN
L1
OR --------------- ORANGE FC
L3
PU --------------- PURPLE
RD --------------- RED
WH -------------- WHITE
YL --------------- YELLOW
X
YL WIRING CODE IO AU
BL BK PU
BK YL FACTORY WIRING
M
HIGH VOLTAGE CM
AI
N
T2 T3 RD CH
T1 LOW VOLTAGE
OPTIONAL HIGH VOLTAGE
YL/BK L1 L2 L3
SEE NOTE3
C PU FIELD WIRING
HIGH VOLTAGE
PU LOW VOLTAGE C
BK
BK
FC
BK
LPS
BR
YL/BK
BK HPS
YL/BK
BK
Y C
NOTES:
1) TO INDOOR UNIT LOW VOLTAGE
EQUIPMENT GROUND COMPONENT C ODE TERMINAL BLOCK & INDOOR
LPS
SEE NOTE 2 C --------------- CONTACTOR THERMOSTAT.
BK RD YL
CM ------------ OUTDOOR FAN MOTOR 2) USE COPPER CONDUCTOR ONLY.
COMP -------- COMPRESSOR 3) CRANKCASE HEATER FACTORY
YL INSTALLED OPTION
FC-------------- FAN CAPACITOR
L1 L3
MAIN LVJB ---------- LOW VOLTAGE JUNCTION BOX USE N.E.C. CLASS 2 WIRE
BK BK
PU CH-------------- CRANKCASE HEATER
AUX CH
BR CONTROLS SHOWN WITH THERMOSTAT IN 'OFF' POSITION.
HPS
IO
BK LPS------------- LOW PRESSURE SWITCH
L2
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
HPS------------ HIGH PRESSURE SWITCH
BK
CM COMP
0140R00092-D
GSC10***[3/4]**
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
LVJB
T1 T2
L1 5 SR 2 1 L2
C SC C
COLOR CODE IO H C
BK --------------- BLACK
BL --------------- BLUE X S
C AU
WIRING DIAGRAMS
IO AU (IF USED)
POLE CONTACTOR ONLY
T2 RD WIRING CODE
T1
FACTORY WIRING M
BK SR RD AI
N
HIGH VOLTAGE CM
YL L1 L2
5 LOW VOLTAGE
C OPTIONAL HIGH VOLTAGE
1
2 BL FIELD WIRING
HIGH VOLTAGE
RD
YL PU RD
SEE NOTE 1
NOTES:
COMP
1) TO INDOOR UNIT LOW VOLTAGE TERMINAL BLOCK &
MAIN
EQUIPMENT GROUND INDOOR THERMOSTAT.
RD 2) START ASSIST FACTORY EQUIPPED WHEN REQUIRED.
BK SEE NOTE 3 3) USE COPPER CONDUCTORS ONLY.
AUX
MAIN
PU
AUX YL
BR
IO C S
BK USE N.E.C. CLASS 2 WIRE
R
CM
0140R00015P-C
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
GSC130[18-60]1**, GSC140[18-42]CA
113
114
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
YL Y SEE NOTE 1
BL C
T1 T3
L1 T2 L3
L2
C C C
T2
COLOR CODE
BK --------------- BLACK
BL --------------- BLUE COMP
BR --------------- BROWN T1
WIRING DIAGRAMS
OR --------------- ORANGE
T3 FC
PU --------------- PURPLE
RD --------------- RED
WH -------------- WHITE
YL --------------- YELLOW
WIRING CODE X
FACTORY WIRING IO AU
BL BK RD HIGH VOLTAGE
BK YL LOW VOLTAGE M
AI
CM N
T2 T3 RD FIELD WIRING
T1
HIGH VOLTAGE
YL L1 L2 L3
C
C
RD
COMPONENT CODE
C --------------- CONTACTOR
PU CM ------------ OUTDOOR FAN MOTOR
COMP -------- COMPRESSOR
FC ------------- FAN CAPACITOR
FC BR
IO -------------- INTERNAL OVERLOAD
LVJB ---------- LOW VOLTAGE JUNCTION BOX
Y C
SEE NOTE 1
NOTES:
1) TO INDOOR UNIT LOW VOLTAGE TERMINAL BLOCK &
INDOOR THERMOSTAT.
2) USE COPPER CONDUCTOR ONLY
EQUIPMENT GROUND
BK RD SEE NOTE 2
COMP 0140R00016P-D
CM
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
VSZ130[18-60]1** & GSZ140[18-60]1A*/B*
GSC130[36-60]3** & GSC130[48-60]4**
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
YL Y
NOTE 1
BL C T1 T2
L1 L2
5 SR 2 1
C SC C
IO H C
X S
C AU RCCF
COMP
M F
WIRING DIAGRAMS
COLOR CODE AI
N R
BK --------------- BLACK
BL --------------- BLUE
SC BR --------------- BROWN X SA
IO AU (IF USED)
OR --------------- ORANGE ALTERNATE DOUBLE
PU --------------- PURPLE M
BL BK A
POLE CONTACTOR ONLY
RD RD BL RD --------------- RED CM IN
BK BK
WH -------------- WHITE
T2 RD YL --------------- YELLOW
T1
BK SR RD
YL L1 L2
5
C
WIRING CODE
1
2 BL FACTORY WIRING
HIGH VOLTAGE
YL LOW VOLTAGE
OPTIONAL HIGH VOLTAGE
RD
FIELD WIRING
YL HIGH VOLTAGE
PU
C HERM LOW VOLTAGE
YL
RD F YL C
YL
BR RCCF
SA
(IF USED)
T1 T2 NOTE 2
RD
L1 L2
ALTERNATE DOUBLE
POLE CONTACTOR Y C
COMPONENT CODE
C --------------- CONTACTOR
CM ------------ OUTDOOR FAN MOTOR
EQUIPMENT GROUND
COMP -------- COMPRESSOR
COMP USE COPPER NOTES:
IO -------------- INTERNAL OVERLOAD
MAIN CONDUCTORS ONLY 1) TO INDOOR UNIT LOW VOLTAGE
LVJB ---------- LOW VOLTAGE JUNCTION BOX
RD TERMINAL BLOCK & INDOOR
RCCF --------- RUN CAPACITOR FOR COMPRESSOR & FAN THERMOSTAT.
BK AUX
MAIN SA ------------- START ASSIST 2) START ASSIST FACTORY
PU EQUIPPED WHEN REQUIRED.
SC ------------- START CAPACITOR FOR COMPRESSOR (OPTIONAL)
AUX YL
BR S R ------------- START RELAY FOR COMPRESSOR (OPTIONAL) USE N.E.C. CLASS 2 WIRE
IO C S
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
BK CONTROLS SHOWN WITH THERMOSTAT IN 'OFF' POSITION.
R
0140R00015P
GSC130[18-60]1**
CM
115
116
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
WIRING DIAGRAMS
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
GSH10*****A*
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
BK --------------- BLACK
BL OR WH RD BL --------------- BLUE
SA
YL BK RD RD BR --------------- BROWN
(IF USED)
ALTERNATE DOUBLE
OR --------------- ORANGE POLE CONTACTOR ONLY
PU --------------- PURPLE
RD --------------- RED
X
WH -------------- WHITE DF1 DF2 AU
IO
SC YL --------------- YELLOW
HVDR M
AI
CM N
BK BK CHS
BL BK BK RD RD BL WIRING CODE
CH
FACTORY WIRING
BL T2 RD HIGH VOLTAGE (IF USED)
T1
BK SR RD LOW VOLTAGE NOTE 3
YL L1 L2 DFT
5
OPTIONAL HIGH VOLTAGE
C R
DC
YL BK RD DFT C
1 FIELD WIRING Y
2 BL
HIGH VOLTAGE
LVDR
YL RD R W2
PU
YL RCCF RVC
PU O
H C F
O LPS C
YL
BR
T1 T2
RD YL
SA COMPONENT CODE
R C
L1 L2 (IF USED) C --------------- CONTACTOR
NOTE 2 O W2 Y
ALTERNATE CH ------------- CRANKCASE HEATER
DOUBLE POLE RD INDOOR POWER
CHS ------------- CRANKCASE HEATER SWITCH
CONTACTOR CM ------------ OUTDOOR FAN MOTOR SUPPLY
COMP -------- COMPRESSOR SEE NOTE 1
BK BK BK DC ------------- DEFROST CONTROL
RVC NOTES:
COMP DFT ----------- DEFROST THERMOSTAT 1. TO INDOOR UNIT LOW VOLTAGE TERMINAL BLOCK & INDOOR
EQUIPMENT GROUND
MAIN SEE NOTE 4 HVDR -------- HIGH VOLTAGE DEFROST RELAY THERMOSTAT.
RD 2. START ASSIST FACTORY EQUIPPED WHEN REQUIRED.
BK
IO -------------- INTERNAL OVERLOAD
AUX 3. CRANKCASE HEATER & CRANKCASE HEATER SWITCH ARE
RD DFT LPS ------------ LOW PRESSURE SWITCH
FACTORY INSTALLED OPTION.
RD LVDR --------- LOW VOLTAGE DEFROST RELAY
YL RD BK 4. USE COPPER CONDUCTOR ONLY.
MAIN BK LVJB ---------- LOW VOLTAGE JUNCTION BOX
PU C RD RCCF --------- RUN CAPACITOR FOR COMPRESSOR & FAN USE N.E.C. CLASS 2 WIRE
S
AUX RVC ----------- REVERSING VALVE COIL
BR R SA ------------- START ASSIST
IO LPS CHS
YL YL SC ------------- START CAPACITOR FOR COMPRESSOR (OPTIONAL)
BK
SR ------------- START RELAY FOR COMPRESSOR (OPTIONAL)
CH
(IF USED) GR
CONTROLS SHOWN WITH THERMOSTAT IN ’OFF’ POSITION.
CM SEE NOTE 3
0140R00019P-C
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
GSH130[18/24/36]1B*/C*, GSH130301CD
GSH130[42AF/AG/B*, 48AE/AF, 60AC]
117
118
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
W2 COLOR CODE T1
O O R R DFT
C Y BK --------------- BLACK COMP
BL --------------- BLUE
WIRING DIAGRAMS
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
GSH130363AH
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
X
AU
M
WIRING DIAGRAMS
COLOR CODE AI
N
BK --------------- BLACK
BL --------------- BLUE
BR --------------- BROWN SA
(IF USED)
OR --------------- ORANGE
PU --------------- PURPLE
ALTERNATE DOUBLE
POLE CONTACTOR ONLY
RD --------------- RED
WH -------------- WHITE X
AU
YL --------------- YELLOW
M
AI
N
WIRING CODE
CHS
FACTORY WIRING
HIGH VOLTAGE NOTE 3
LOW VOLTAGE NOTE 3
OPTIONAL HIGH VOLTAGE
FIELD WIRING
HIGH VOLTAGE
LOW VOLTAGE
COMPONENT CODE
C --------------- CONTACTOR
L1 L2 (IF USED) CH ------------- CRANKCASE HEATER
RD NOTE 2
ALTERNATE DOUBLE CHS ----------- CRANKCASE HEATER SWITCH
BK RD R C
POLE CONTACTOR CM ------------ OUTDOOR FAN MOTOR
COMP -------- COMPRESSOR
DC ------------- DEFROST CONTROL
DFT ----------- DEFROST THERMOSTAT
INDOOR POWER
HVDR -------- HIGH VOLTAGE DEFROST RELAY SUPPLY
EQUIPMENT GROUND IO -------------- INTERNAL OVERLOAD
USE COPPER LPS ------------ LOW PRESSURE SWITCH NOTES:
CONDUCTORS ONLY LVDR --------- LOW VOLTAGE DEFROST RELAY 1) TO INDOOR UNIT LOW VOLTAGE
TERMINAL BLOCK & INDOOR
LVJB ---------- LOW VOLTAGE JUNCTION BOX
THERMOSTAT.
CHS RD RCCF --------- RUN CAPACITOR FOR COMPRESSOR & FAN
BK 2) START ASSIST FACTORY
RVC ----------- REVERSING VALVE COIL EQUIPPED WHEN REQUIRED.
CH
SA ------------- START ASSIST 3) CRANKCASE HEATER AND
SC ------------- START CAPACITOR FOR COMPRESSOR (OPTIONAL) CRANKCASE HEATER SWITCH
S R ------------- START RELAY FOR COMPRESSOR (OPTIONAL)
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
ARE FACTORY INSTALLED.
GR
CONTROLS SHOWN WITH THERMOSTAT IN 'OFF' POSITION.
VENDOR: GOODMAN PRINT SHOP 07/05 0140R00235-A
GSH130301BB/C*
119
120
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
YL Y
NOTE 1
BL C T1 T2
L1 L2
5 SR 2 1
C SC C
IO H C
X S
C AU RCCF
COMP
M F
COLOR CODE AI
N R
WIRING DIAGRAMS
BK --------------- BLACK
BL --------------- BLUE
SC BR --------------- BROWN X SA
IO AU (IF USED)
OR --------------- ORANGE
ALTERNATE DOUBLE
PU --------------- PURPLE M
BL BK A
BK BK
RD RD BL RD --------------- RED POLE CONTACTOR ONLY CM IN
WH -------------- WHITE
T2 RD YL --------------- YELLOW
T1
BK SR RD
YL L1 L2
5
C
WIRING CODE
1
2 BL FACTORY WIRING
HIGH VOLTAGE
YL LOW VOLTAGE
OPTIONAL HIGH VOLTAGE
RD
FIELD WIRING
YL HIGH VOLTAGE
PU
C HERM LOW VOLTAGE
YL
RD F YL C
YL
BR RCCF
SA
(IF USED)
T1 T2 NOTE 2
RD
L1 L2
ALTERNATE DOUBLE
POLE CONTACTOR Y C
COMPONENT CODE
C --------------- CONTACTOR
CM ------------ OUTDOOR FAN MOTOR
EQUIPMENT GROUND
COMP -------- COMPRESSOR
COMP USE COPPER NOTES:
IO -------------- INTERNAL OVERLOAD
MAIN CONDUCTORS ONLY 1) TO INDOOR UNIT LOW VOLTAGE
LVJB ---------- LOW VOLTAGE JUNCTION BOX
RD TERMINAL BLOCK & INDOOR
RCCF --------- RUN CAPACITOR FOR COMPRESSOR & FAN THERMOSTAT.
BK AUX
MAIN SA ------------- START ASSIST 2) START ASSIST FACTORY
PU EQUIPPED WHEN REQUIRED.
SC ------------- START CAPACITOR FOR COMPRESSOR (OPTIONAL)
AUX YL
BR S R ------------- START RELAY FOR COMPRESSOR (OPTIONAL) USE N.E.C. CLASS 2 WIRE
IO C S
BK CONTROLS SHOWN WITH THERMOSTAT IN 'OFF' POSITION.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
R
CM 0140R00015P
VSC130[18-60]1**