circuit-breakers for motor protection
April '99
SACE Isomax S
Annex to SACE Isomax S technical catalogue 649240 690 V • 3-1000 A • 35-200 kA (380/415 V)
Introduction
pag. 2
ion
duct
Intro
Main characteristics
ics
erist
pag. 4
ract
Cha
Characteristic curves
pag. 8
es
Curv
Applications of the circuit-breaker
ions
and coordination tables
licat
App
Ordering codes
es
Cod
ion
The S2X 80 current-limiting motor protection circuit-breaker
duct
Intro
IS809001
2
Integration with the SACE Isomax S family
duct
Intro
The outside dimensions of the SACE S2X 80 circuit-
breaker, which are exactly the same as the S2 B/N/S
circuit-breakers in the Isomax S series, bring users sig-
nificant benefits in terms of standardising their support
and installation structures, offering the possibility of fit-
ting connection terminals of the same type and using
exactly the same mounting system both for installation
on sheet metal and on a DIN channel using a mounting
bracket.
The circuit-breaker can be converted into the moving
part of a plug-in circuit-breaker using the same conver-
sion kit as S2 B/N/S circuit-breakers.
The S2X 80 circuit-breaker also uses the same acces-
sories as the corresponding S2 circuit-breakers. These
accessories naturally retain the same electrical charac-
teristics.
This therefore ensures optimal stock management.
It is worth noting that these circuit-breakers can also
be used with:
- the solenoid operator for horizontal installation or on
the front of the circuit-breaker;
IS809002
- the adjustable-depth rotary handle operating mecha-
nism in the version that can also be used for ma-
chine tool emergency stops.
3
ics
erist
Electrical and general characteristics
ract
Cha
IS809004
S2X 80
Rated uninterrupted current, Iu [A] 80
Rated service current, In [A] 1 ... 80
Isolation behaviour
Reference standards IEC 947-2 / EN 60947-2
Terminals (1)
fixed version (F) EF - FC Cu - FC CuAl - R
Mechanical life No. operations / Operations per hour No. 25000 / 240
Depth [mm] 70
Notes
(1) See page 7 for information on the types of terminals.
4
Overcurrent releases
e
ract
Cha
The overcurrent releases are magnetic-only models with
Magnetic only a fixed tripping threshold Im = 13 x In, available in the
overcurrent releases service currents shown in the table.
SACE Isomax S2X 80 circuit-breaker The S2X 80 circuit-breaker equipped with this high-
tripping-threshold magnetic release provides short-cir-
Phases L1 - L2 - L3 cuit protection while at the same time allowing the mo-
tor’s inrush current to stabilise. Used in conjunction with
Service current Magnetic trip
a thermal relay and contactor, it provides traditional
current
switching and protection for the motor.
In [A] Im = 13 x In [A] The thermal relay provides protection against overloads
and phase failures or unbalances, while the contactor
1 13 performs the function of starting and stopping the
motor.
1.6 21
2 26
2.5 32
3.2 42
4 52
5 65 Circuit-breaker with
magnetic release
6.5 84
8.5 110
11 145
12.5 163
Contactor
16 210
20 260
Thermal relay
25 325
32 415
42 545
52 680
63 820
Motor
GSSC0424a
80 1040
5
ics
erist
Main characteristics and construction features
ract
Cha
SACE S2X80
6
e
ract
Cha
Versions and connections The S2X 80 circuit-breaker is supplied in a basic ver-
The SACE S2X 80 circuit-breaker is available in a fixed sion with front terminals for copper cables up to
and plug-in version, with a similar range of terminals to 90 mm2. Terminal covers (high or low) can be supplied
that provided for the S2 B/N/S circuit-breakers. as shown in the following table.
EF FC Cu FC CuAl R
IS809007
7
Current-limiting curves
es
Curv
The current-limiting and specific let-through energy cal short-circuit current Is [kA eff.]
curves at 440 V AC and 690 V AC are shown below. – the value of the specific let-through energy I2t [A2s] let
The two curves show the following respectively: through by the circuit-breaker in relation to the pro-
– the peak value Ip [kA] of the current limited by the spective symmetrical short-circuit current Is [kA eff.].
circuit-breaker in relation to the prospective symmetri-
GS800001
8
es
Curv
Current-limiting curves at 440 V~ for SACE Isomax S2X 80 circuit-breakers
GS800002
9
Current-limiting curves
es
Curv
GS800003
10
Specific let-through energy curves
es
Curv
Specific let-through energy curves at 400 V~ for SACE Isomax S2X 80 circuit-breakers
GS800004
11
Specific let-through energy curves
es
Curv
Specific let-through energy curves at 440 V~ for SACE Isomax S2X 80 circuit-breakers
GS800005
12
es
Curv
Specific let-through energy curves at 500 V~ for SACE Isomax S2X 80 circuit-breakers
GS800006
13
ions
Applications of the circuit-breaker
licat
App
Overload
protection Thermal relay
Installations in which there are a Installations in which there are a Special applications, such as
large number of operations for large number of operations for large motors with a limited
low powers low and medium powers number of operations for high
powers
14
io
licat
App
A number of different factors need to be taken into ac- ABB’s extensive experience in the field of starting,
count when choosing these devices, such as: switching and protecting motors allows you to use par-
• the power of the motor ticularly reliable devices such as:
• the type of starting: direct line, reverse motion, star- • the circuit-breakers in the Isomax S series and, in
delta, with reactance, with static power supply this particular case, the SACE S2X 80 current-limit-
• the type of motor: with cage rotor or wound rotor ing circuit-breaker, which has a rated service current
• the fault current at the point in the network where the from 1 to 80 A and magnetic-only protection with a
motor is installed. fixed tripping threshold of 13 x In, completing the
The type of starter and the devices forming it must be already vast SACE Isomax S range
chosen to obtain: • the A-line series of three-pole contactors, model A9
• optimum protection of the installation to A300, and the EH series of three-pole contactors,
• low costs, including low running and maintenance from EH 370 to EH 700
costs • the TA and T series of three-pole thermal relays, for
• easy and safe installation currents from 1 to 650 A.
• simple design.
A B C
Contactor Contactor
Thermal relay
GSSC0291
GSSC0291
15
ions
Coordination tables according to IEC 947-4-1 Standards
licat
App
16
400 V - 50 Hz - 35 kA
io
licat
Normal direct-line starting, type 2
MOTOR MCCB SACE Isomax S CONTACTOR THERMAL RELAY GROUP
App
Power, Pe Current, Ie Type In I3 setting I3 Type Type setting [A] Imax
[kW] [A] [A] [A] [A] min max [A]
0.37 1.1 S2X 80 1.6 21 21 A9 TA25DU1.4 1 1.4 1.4
0.55 1.5 S2X 80 2 26 26 A9 TA25DU1.8 1.3 1.8 1.8
0.75 1.9 S2X 80 2.5 33 33 A9 TA25DU2.4 1.7 2.4 2.4
1.1 2.8 S2X 80 4 52 52 A9 TA25DU3.1 2.2 3.1 3.1
1.5 3.5 S2X 80 5 65 65 A16 TA25DU4.0 2.8 4 4
2.2 5 S2X 80 6.5 84 84 A26 TA25DU6.5 4.5 6.5 6.5
3 6.6 S2X 80 8.5 110 110 A26 TA25DU8.5 6 8.5 8.5
4 8.6 S2X 80 11 145 145 A30 TA25DU11 7.5 11 11
5.5 11.5 S2X 80 16 210 210 A30 TA25DU14 10 14 14
7.5 15.2 S2X 80 20 260 260 A30 TA25DU19 13 19 19
11 22 S2X 80 32 415 415 A30 TA42DU25 18 25 25
15 28.5 S2X 80 32 415 415 A50 TA75DU32 22 32 32
18.5 36 S2X 80 42 540 540 A50 TA75DU42 29 42 42
22 42 S2X 80 52 680 680 A50 TA75DU52 36 52 50
30 56 S2X 80 63 820 820 A63 TA75DU63 45 63 63
37 68 S2X 80 80 1040 1040 A75 TA75DU80 60 80 75
45 83 S3N160 (1) 160 1250 640-1500 A95 TA110DU90 66 90 90
55 98 S3N160 (1) 160 1500 640-1500 A110 TA110DU110 80 110 110
75 135 S3N250 (1) 200 2150 800-2400 A145 TA200DU150 110 150 145
90 158 S3N250 (1) 200 2400 800-2400 A185 TA200DU175 130 175 175
110 193 S4N250 PR211/I 250 3000 375-3000 A210 TA450DU235 165 235 210
132 232 S5N400 PR211/I 320 3840 480-3840 A260 TA450DU310 220 310 260
160 282 S5N400 PR211/I 400 4800 600-4800 A300 TA450DU310 220 310 300
200 349 S6N630 PR211/I 630 6300 945-7560 EH370 T450DU400 285 400 400
250 430 S6N630 PR211/I 630 7560 945-7560 EH550 T900DU500 355 500 500
290 520 S6N800 PR211/I 800 8000 1200-9600 EH550 T900DU650 465 650 550
315 545 S6N800 PR211/I 800 9600 1200-9600 EH700 T900DU650 465 650 650
355 610 S6N800 PR211/I 800 9600 1200-9600 EH700 T900DU650 465 650 650
(1) with adjustable magnetic-only release
400 V - 50 Hz - 35 kA
Heavy direct-line starting, type 2
MOTOR MCCB SACE Isomax S CONTACTOR THERMAL RELAY GROUP
Power, Pe Current, Ie Type In I3 setting I3 Type Type N° primary setting [A] Imax
[kW] [A] [A] [A] [A] windings min max [A]
0.37 1.1 S2X 80 1.6 21 21 A9 TA25DU1.4 (2) 0 1 1.4 1.4
0.55 1.5 S2X 80 2 26 26 A9 TA25DU1.8 (2) 0 1.3 1.8 1.8
0.75 1.9 S2X 80 2.5 33 33 A9 TA25DU2.4 (2) 0 1.7 2.4 2.4
1.1 2.8 S2X 80 4 52 52 A9 TA25DU3.1 (2) 0 2.2 3.1 3.1
1.5 3.5 S2X 80 5 65 65 A16 TA25DU4.0 (2) 0 2.8 4 4
2.2 5 S2X 80 6.5 84 84 A26 TA25DU6.5 (2) 0 4.5 6.5 6.5
3 6.6 S2X 80 8.5 110 110 A26 TA25DU8.5 (2) 0 6 8.5 8.5
4 8.6 S2X 80 11 145 145 A30 TA25DU11 (2) 0 7.5 11 11
5.5 11.5 S2X 80 16 210 210 A30 TA450SU60 4 10 15 15
7.5 15.2 S2X 80 20 260 260 A30 TA450SU60 3 13 20 20
11 22 S2X 80 32 415 415 A30 TA450SU60 2 20 30 30
15 28.5 S2X 80 32 415 415 A50 TA450SU80 2 23 40 40
18.5 36 S2X 80 42 540 540 A50 TA450SU80 2 23 40 40
22 42 S2X 80 52 680 680 A50 TA450SU60 1 40 60 50
30 56 S2X 80 63 820 820 A63 TA450SU80 1 55 80 63
37 68 S2X 80 80 1040 1040 A95 TA450SU80 1 55 80 80
45 83 S3N160 (1) 160 1250 640-1500 A110 TA450SU105 1 70 105 105
55 98 S3N160 (1) 160 1500 640-1500 A145 TA450SU140 1 95 140 140
75 135 S3N250 (1) 200 2150 800-2400 A145 TA450SU185 1 130 185 145
90 158 S3N250 (1) 200 2400 800-2400 A185 TA450SU185 1 130 185 185
110 193 S4N250 PR211/I 250 3000 375-3000 A210 TA450SU235 1 165 235 210
132 232 S5N400 PR211/I 320 3840 480-3840 A260 TA450SU310 1 220 310 260
160 282 S5N400 PR211/I 400 4800 600-4800 EH370 T450SU310 1 220 310 310
200 349 S6N630 PR211/I 630 6300 945-7560 EH370 T450SU400 1 285 400 400
250 430 S6N630 PR211/I 630 7560 945-7560 EH550 T900SU500 1 355 500 500
290 520 S6N800 PR211/I 800 8000 1200-9600 EH550 T900SU650 1 465 650 550
315 545 S6N800 PR211/I 800 9600 1200-9600 EH700 T900SU650 1 465 650 650
355 610 S6N800 PR211/I 800 9600 1200-9600 EH700 T900SU650 1 465 650 650
(1) with adjustable magnetic-only release - (2) provide bypass contactor during starting
17
ions
400 V - 50 Hz - 50 kA
licat
400 V - 50 Hz - 50 kA
Heavy direct-line starting, type 2
MOTOR MCCB SACE Isomax S CONTACTOR THERMAL RELAY GROUP
Power, Pe Current, Ie Type In I3 setting I3 Type Type N° primary setting [A] Imax
[kW] [A] [A] [A] [A] windings min max [A]
0.37 1.1 S2X 80 1.6 21 21 A9 TA25DU1.4 (2) 1 1.4 1.4
0.55 1.5 S2X 80 2 26 26 A9 TA25DU1.8 (2) 0 1.3 1.8 1.8
0.75 1.9 S2X 80 2.5 33 33 A9 TA25DU2.4 (2) 0 1.7 2.4 2.4
1.1 2.8 S2X 80 4 52 52 A9 TA25DU3.1 (2) 0 2.2 3.1 3.1
1.5 3.5 S2X 80 5 65 65 A16 TA25DU4.0 (2) 0 2.8 4 4
2.2 5 S2X 80 6.5 84 84 A26 TA25DU6.5 (2) 0 4.5 6.5 6.5
3 6.6 S2X 80 8.5 110 110 A26 TA25DU8.5 (2) 0 6 8.5 8.5
4 8.6 S2X 80 11 145 145 A30 TA25DU11 (2) 0 7.5 11 11
5.5 11.5 S2X 80 16 210 210 A30 TA450SU60 4 10 15 15
7.5 15.2 S2X 80 20 260 260 A30 TA450SU60 3 13 20 20
11 22 S2X 80 32 415 415 A30 TA450SU60 2 20 30 30
15 28.5 S2X 80 32 415 415 A50 TA450SU80 2 23 40 32
18.5 36 S2X 80 42 540 540 A50 TA450SU80 2 23 40 40
22 42 S2X 80 52 680 680 A50 TA450SU60 1 40 60 50
30 56 S2X 80 63 820 820 A63 TA450SU80 1 55 80 63
37 68 S2X 80 80 1040 1040 A95 TA450SU80 1 55 80 80
45 83 S3H160 (1) 160 1250 640-1500 A110 TA450SU105 1 70 105 105
55 98 S3H160 (1) 160 1500 640-1500 A145 TA450SU140 1 95 140 140
75 135 S3H250 (1) 200 2150 800-2400 A145 TA450SU185 1 130 185 145
90 158 S3H250 (1) 200 2400 800-2400 A185 TA450SU185 1 130 185 185
110 193 S4H250 PR211/I 250 3000 375-3000 A210 TA450SU235 1 165 235 210
132 232 S5H400 PR211/I 320 3840 480-3840 A260 TA450SU310 1 220 310 260
160 282 S5H400 PR211/I 400 4800 600-4800 EH370 T450SU310 1 220 310 310
200 349 S6S630 PR211/I 630 6300 945-7560 EH370 T450SU400 1 285 400 400
250 430 S6S630 PR211/I 630 7560 945-7560 EH550 T900SU500 1 355 500 500
290 520 S6S800 PR211/I 800 8000 1200-9600 EH550 T900SU650 1 465 650 550
315 545 S6S800 PR211/I 800 9600 1200-9600 EH700 T900SU650 1 465 650 650
355 610 S6S800 PR211/I 800 9600 1200-9600 EH700 T900SU650 1 465 650 650
(1) with adjustable magnetic-only release - (2) provide bypass contactor during starting
18
440 V - 50 Hz - 50 kA
io
licat
Normal direct-line starting, type 2
MOTOR MCCB SACE Isomax S CONTACTOR THERMAL RELAY GROUP
App
Power, Pe Current, Ie Type In I3 setting I3 Type Type setting [A] Imax
[kW] [A] [A] [A] [A] min max [A]
0.37 1 S2X 80 1.6 21 21 A9 TA25DU1.4 1 1.4 1.4
0.55 1.4 S2X 80 2 26 26 A9 TA25DU1.8 1.3 1.8 1.80
0.75 1.7 S2X 80 2.5 33 33 A9 TA25DU2.4 1.7 2.4 2.4
1.1 2.2 S2X 80 3.2 42 42 A9 TA25DU3.1 2.2 3.1 3.1
1.5 3 S2X 80 4 52 52 A16 TA25DU4 2.8 4 4
2.2 4.4 S2X 80 5 65 65 A26 TA25DU5 3.5 5 5
3 5.7 S2X 80 6.5 84 84 A26 TA25DU6.5 4.5 6.5 6.5
4 7.8 S2X 80 11 145 145 A30 TA25DU11 7.5 11 11
5.5 10.5 S2X 80 16 210 210 A30 TA25DU14 10 14 14
7.5 13.5 S2X 80 16 210 210 A30 TA25DU14 10 14 14
11 19 S2X 80 25 325 325 A30 TA42DU25 18 25 25
15 26 S2X 80 32 415 415 A50 TA75DU32 22 32 32
18.5 32 S2X 80 42 540 540 A50 TA75DU42 29 42 42
22 38 S2X 80 52 680 680 A50 TA75DU52 36 52 45
30 52 S2X 80 63 820 820 A63 TA75DU63 45 63 63
37 63 S2X 80 80 1040 1040 A75 TA75DU80 60 80 70
45 75 S3H160 (1) 100 1150 500-1500 A95 TA110DU90 65 90 90
55 90 S3H160 (1) 125 1400 500-1500 A110 TA110DU110 80 110 100
75 120 S3H250 (1) 160 1920 800-2400 A145 TA200DU135 100 135 135
90 147 S3H250 (1) 200 2300 800-2400 A185 TA200DU175 130 175 175
110 177 S4H250 PR211/I 250 3000 375-3000 A210 TA450DU235 165 235 210
132 212 S5H400 PR211/I 320 3200 480-3840 A260 TA450DU235 165 235 235
160 260 S5H400 PR211/I 400 4000 600-4800 A300 TA450DU310 220 310 300
200 320 S5H400 PR211/I 400 4800 600-4800 EH370 T450DU400 285 400 370
250 410 S6H630 PR211/I 630 6300 945-7560 EH550 T900DU500 355 500 500
290 448 S6H630 PR211/I 630 7560 945-7560 EH550 T900DU500 355 500 500
315 500 S6H800 PR211/I 800 8000 1200-9600 EH550 T900DU650 465 650 550
355 549 S6H800 PR211/I 800 9600 1200-9600 EH700 T900DU650 465 650 650
(1) with adjustable magnetic-only release
440 V - 50 Hz - 50 kA
Heavy direct-line starting, type 2
MOTOR MCCB SACE Isomax S CONTACTOR THERMAL RELAY GROUP
Power, Pe Current, Ie Type In I3 setting I3 Type Type N° primary setting [A] Imax
[kW] [A] [A] [A] [A] windings min max [A]
0.37 1 S2X 80 1.6 21 21 A9 TA25DU1.4 (2) 0 1 1.4 1.4
0.55 1.4 S2X 80 2 26 26 A9 TA25DU1.8 (2) 0 1.3 1.8 1.8
0.75 1.7 S2X 80 2.5 33 33 A9 TA25DU2.4 (2) 0 1.7 2.4 2.4
1.1 2.2 S2X 80 3.2 42 42 A9 TA25DU3.1 (2) 0 2.2 3.1 3.1
1.5 3 S2X 80 4 52 52 A16 TA25DU4 (2) 0 2.8 4 4
2.2 4.4 S2X 80 6.5 84 84 A26 TA25DU5 (2) 0 3.5 5 5
3 5.7 S2X 80 8.5 110 110 A26 TA25DU6.5 (2) 0 4.5 6.5 6.5
4 7.8 S2X 80 11 145 145 A30 TA25DU11 (2) 0 7.5 11 11
5.5 10.5 S2X 80 16 210 210 A30 TA25DU14 (2) 0 10 14 14
7.5 13.5 S2X 80 16 210 210 A30 TA450SU60 4 10 15 15
11 19 S2X 80 25 325 325 A30 TA450SU80 3 18 27 25
15 26 S2X 80 32 415 415 A50 TA450SU60 2 20 30 30
18.5 32 S2X 80 42 540 540 A50 TA450SU80 2 28 40 40
22 38 S2X 80 52 680 680 A50 TA450SU80 2 28 40 40
30 52 S2X 80 63 820 820 A63 TA450SU60 1 40 60 60
37 63 S2X 80 80 1040 1040 A95 TA450SU80 1 55 80 80
45 75 S3H160 (1) 100 1150 500-1500 A110 TA450SU105 1 70 105 100
55 90 S3H160 (1) 125 1400 500-1500 A145 TA450SU105 1 70 105 105
75 120 S3H250 (1) 160 1920 800-2400 A145 TA450SU140 1 95 140 140
90 147 S3H250 (1) 200 2300 800-2400 A185 TA450SU185 1 130 185 185
110 177 S4H250-PR211/I 250 3000 375-3000 A210 TA450SU235 1 165 235 210
132 212 S5H400-PR211/I 320 3200 480-3840 A260 TA450SU235 1 165 235 235
160 260 S5H400-PR211/I 400 4000 600-4800 EH370 T450SU310 1 220 310 310
200 320 S5H400-PR211/I 400 4800 600-4800 EH370 T450SU400 1 285 400 370
250 410 S6H630-PR211/I 630 6300 945-7560 EH550 T900SU500 1 355 500 500
290 448 S6H630-PR211/I 630 7560 945-7560 EH550 T900SU500 1 355 500 500
315 500 S6H800-PR211/I 800 8000 1200-9600 EH550 T900SU650 1 465 650 550
355 549 S6H800-PR211/I 800 9600 1200-9600 EH700 T900SU650 1 465 650 650
(1) with adjustable magnetic-only release - (2) provide bypass contactor during starting
19
ions
500 V - 50 Hz - 50 kA
Normal direct-line starting, type 2
licat
20
Ordering codes
es
SACE Isomax S2X 80
Cod
circuit-breaker
F = FIXED
S2X 80 Iu (40 °C) = 80 A • Icu (415 V) = 70 kA
21
Ordering codes
es
circuit-breaker
Fixed parts
code 1SDA0 R1
3 pole
FC = Front terminals
for copper cables
S2P FP FC 13298
R = Rear terminals
S2P FP R 13299
PSIS9606
22
Ordering codes
es
Cod
SACE Isomax S2X 80 accessories
Duty releases
Shunt opening releases
Type code 1SDA0 R1
24 ... 30 V AC 13311
48 V AC - 60 V DC 13306
110 ... 130 V AC 13312
220 ... 250 V AC 13313
380 ... 440 V AC 13314
24 V DC 13304
48 V DC 13305
IS809010
110 V DC 13307
220 V DC 13309
250 V DC 13310
Undervoltage releases
Type code 1SDA0 R1
24 V AC 50 Hz 23401
48 V AC 23402
110 V AC 50 Hz 13319
110 V AC 60 Hz 45046
220 V AC 50 Hz 13320
380 V AC 50 Hz - 380 ... 440 V AC 60 Hz 13321
24 V DC 13315
IS809011
48 V DC 13316
60 V DC 45045
110 V DC 13317
220 V DC 13318
Electrical signalling
IS809013
Auxiliary contacts
Type code 1SDA0 R1
23
Ordering codes
es
Cod
Motor operator
Solenoid operator
Type code 1SDA0 R1
48 V DC 48015
60 V DC / 110 V DC 48016
110 V DC / 220 ... 230 V AC 48017
220 V DC 48018
version for horizontal installation alongside the circuit-breaker
48 V DC 48025
60 V DC / 110 V DC 48026
110 V DC / 220 ... 230 V AC 48027
220 V DC 48028
Locks
IS809017
24
Ordering codes
es
Cod
SACE Isomax S2X 80 accessories
Connection terminals
Type code 1SDA0 R1
6 pieces
EF = Extended front terminals 25797
FC CuAl = Front terminals for copper/aluminium cables
(2.5 - 50 mm2) 36194
(35 - 95 mm2) 25801
R = Threaded rear terminals 13294
IS809018
Converting versions
Conversion kit
Type code 1SDA0 R1
3 pole
for converting from fixed to moving part of plug-in 13296
Installation accessories
IS809019
IP54 protection
Type code 1SDA0 R1
IS809020
25
ITSLV 649284/011 en 04/'99
http://www.abb.it/sace-lv