Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Three Phase Thyristor Controlled Rectifier/Charger

Type : 400V125-xxxA-REC
Power Electronics & Controls • Design • Engineering • Manufacturing

Features :
 Ideal for industrials, sub-stations etc.
 Reliable full wave thyristor control technology
 Input Voltage : Three Phase 400 Vac
 Input Frequency : 50/60 Hz
 Output : 125 Vdc, positive or negative grounded
 Automatic 3-stages microprocessor battery charging control
with adjustable FLOAT / EQUALIZE / BOOST setting
 Internal adjustable battery charging current limit
 I/O galvanic isolation with Lightning arrester and transient
absorber
 Protection : short circuit / overload / over voltage / over
temperature and Ground Fault Alarms
 Low Voltage Disconnect (LVD) for battery over-discharge
protection
 ON-OFF controlled fan cooling
 LED panel indicators including battery status monitoring
 Input / battery / output Volt & Ampere meters
 Audible fault alarms
 Alarm & lamp test push & reset button
 Automatic & manual operation selector
 High ambient temperature capability up to 55 deg.C
 Standard floor mounted cubicle

Specifications Single DC Output 125Vdc Up To 300A


Control Type Full Wave Thyristor Controlled Rectifier
 Three Phase, 400 Vac (nominal), 4-wires
Input Voltage
 Input Voltage Variation : -20% + 10%
Input Frequency  50/60 Hz (nominal)
Output Voltage 125 Vdc (nominal)
Output Ripple Voltage ± 1% Vpp (max) at 125 Vdc, without battery
 FLOAT Adjustment: 80% ~ 130% VN
 EQUALIZE Adjustment: 80% ~ 130% VN
Output Voltage Adjustment  BOOST Adjustment: 80% ~ 130% VN
 Mode Selector : AUTO / FLOAT / EQUALIZE / BOOST
 BOOST only for Manual Mode
Output Current Capacity Up to 300 Adc (max) at 125 Vdc
 Rectifier Current Limit : 50% ~ 100% IN
Output Current Limit Adjustment
 Battery Charging Current Limit : 30% ~ 100% IN
Input Protections  Lightning Arrester
 Magnetic Circuit Breaker (MCB)
 Over Current Limit
 Rectifier Output MCB
Output Protections
 Load MCB
 Output Over Voltage
 Positive & Negative Ground Fault

1/2
Three Phase Thyristor Controlled Rectifier/Charger
Type : 400V125-xxxA-REC
Power Electronics & Controls • Design • Engineering • Manufacturing

 Automatic 3-Stage Charging Control (EQUALIZE / ABSORPTION /


Battery Charging Control Method FLOAT)
 Microprocessor Control
 Charging Current Limit
Battery Protections  Battery MCB
 Battery Low Voltage Disconnect (LVD)
 Input AC-Voltmeter & Ampere meter with R-S-T Phase Selector
Switch
Panel Metering  DC Output Voltmeter
 Battery Current Ampere meter
 Load Current Ampere meter
 AC-INPUT
 DC-OUTPUT
 INPUT TOO LOW / TOO HIGH
Status Indicators  BATTERY EMPTY / LOW / HIGH / FULL
 GROUND FAULT
 OVER LOAD
 OVER TEMPERATURE

 AUTO
 FLOAT Mode
Rectifier Mode Indicators
 EQUALIZE Mode
 BOOST Mode
 Mode Selector AUTO / FLOAT / EQUALIZE / BOOST
Selector & Push Buttons  Indicator lamps & Alarm Reset Push Button
 Indicator lamps & Alarm Test Push Button
 Steel construction for indoor service
 Front side mounting for all Switches, Meters and Indicator Lamps
Enclosures
 Front side installation wiring terminals & maintenance accessibility
 Powder Coating Painting
Ambient Temperature Up to 55 deg.C (max)
Humidity 95% (max), non-condense
Altitude 1000 Meters
Grounding Ground Connector
Dimension According to power capacity requirement
Weight According to power capacity requirement

Due to continuous innovation, research and product improvement, the specifications, pictures and dimensions in this product
information sheet are subject to change without prior notice

2/2