Professional Documents
Culture Documents
ONYX FirstVision Installation and Operation Manual PDF
ONYX FirstVision Installation and Operation Manual PDF
ONYX FirstVision Installation and Operation Manual PDF
Document 53034
9/22/10
P/N: 53034:B
Rev: B
ECN: 10-424
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of smoke detec- Heat detectors do not sense particles of combustion and alarm only
tors, heat detectors, manual pull stations, audible warning devices, when heat on their sensors increases at a predetermined rate or
and a fire alarm control panel with remote notification capability—can reaches a predetermined level. Rate-of-rise heat detectors may be
provide early warning of a developing fire. Such a system, however, subject to reduced sensitivity over time. For this reason, the rate-of-
does not assure protection against property damage or loss of life rise feature of each detector should be tested at least once per year
resulting from a fire. by a qualified fire protection specialist. Heat detectors are designed
The Manufacturer recommends that smoke and/or heat detectors be to protect property, not life.
located throughout a protected premise following the recommenda- IMPORTANT! Smoke detectors must be installed in the same room
tions of the current edition of the National Fire Protection Association as the control panel and in rooms used by the system for the connec-
Standard 72 (NFPA 72), manufacturer's recommendations, State and tion of alarm transmission wiring, communications, signaling, and/or
local codes, and the recommendations contained in the Guide for power. If detectors are not so located, a developing fire may damage
Proper Use of System Smoke Detectors, which is made available at the alarm system, crippling its ability to report a fire.
no charge to all installing dealers. A study by the Federal Emergency Audible warning devices such as bells may not alert people if these
Management Agency (an agency of the United States government) devices are located on the other side of closed or partly open doors or
indicated that smoke detectors may not go off in as many as 35% of are located on another floor of a building. Any warning device may
all fires. While fire alarm systems are designed to provide early warn- fail to alert people with a disability or those who have recently con-
ing against fire, they do not guarantee warning or protection against sumed drugs, alcohol or medication. Please note that:
fire. A fire alarm system may not provide timely or adequate warning,
or simply may not function, for a variety of reasons: • Strobes can, under certain circumstances, cause seizures in people
with conditions such as epilepsy.
Smoke detectors may not sense fire where smoke cannot reach the
• Studies have shown that certain people, even when they hear a fire
detectors such as in chimneys, in or behind walls, on roofs, or on the
alarm signal, do not respond or comprehend the meaning of the signal.
other side of closed doors. Smoke detectors also may not sense a
It is the property owner's responsibility to conduct fire drills and other
fire on another level or floor of a building. A second-floor detector, for training exercise to make people aware of fire alarm signals and
example, may not sense a first-floor or basement fire. instruct them on the proper reaction to alarm signals.
Particles of combustion or “smoke” from a developing fire may not • In rare instances, the sounding of a warning device can cause tempo-
reach the sensing chambers of smoke detectors because: rary or permanent hearing loss.
• Barriers such as closed or partially closed doors, walls, or chimneys A fire alarm system will not operate without any electrical power. If
may inhibit particle or smoke flow. AC power fails, the system will operate from standby batteries only for
• Smoke particles may become “cold,” stratify, and not reach the ceiling a specified time and only if the batteries have been properly main-
or upper walls where detectors are located. tained and replaced regularly.
• Smoke particles may be blown away from detectors by air outlets. Equipment used in the system may not be technically compatible
• Smoke particles may be drawn into air returns before reaching the with the control panel. It is essential to use only equipment listed for
detector. service with your control panel.
The amount of “smoke” present may be insufficient to alarm smoke Telephone lines needed to transmit alarm signals from a premise to
detectors. Smoke detectors are designed to alarm at various levels of a central monitoring station may be out of service or temporarily dis-
smoke density. If such density levels are not created by a developing abled. For added protection against telephone line failure, backup
fire at the location of detectors, the detectors will not go into alarm. radio transmission systems are recommended.
Smoke detectors, even when working properly, have sensing limita- The most common cause of fire alarm malfunction is inadequate
tions. Detectors that have photoelectronic sensing chambers tend to maintenance. To keep the entire fire alarm system in excellent work-
detect smoldering fires better than flaming fires, which have little visi- ing order, ongoing maintenance is required per the manufacturer's
ble smoke. Detectors that have ionizing-type sensing chambers tend recommendations, and UL and NFPA standards. At a minimum, the
to detect fast-flaming fires better than smoldering fires. Because fires requirements of NFPA 72 shall be followed. Environments with large
develop in different ways and are often unpredictable in their growth, amounts of dust, dirt or high air velocity require more frequent mainte-
neither type of detector is necessarily best and a given type of detec- nance. A maintenance agreement should be arranged through the
tor may not provide adequate warning of a fire. local manufacturer's representative. Maintenance should be sched-
Smoke detectors cannot be expected to provide adequate warning of uled monthly or as required by National and/or local fire codes and
fires caused by arson, children playing with matches (especially in should be performed by authorized professional fire alarm installers
bedrooms), smoking in bed, and violent explosions (caused by escap- only. Adequate written records of all inspections should be kept.
ing gas, improper storage of flammable materials, etc.).
FCC Warning
WARNING: This equipment generates, uses, and can radi- Canadian Requirements: This digital apparatus does not
ate radio frequency energy and if not installed and used in exceed the Class A limits for radiation noise emissions from
accordance with the instruction manual, may cause interfer- digital apparatus set out in the Radio Interference Regula-
ence to radio communications. It has been tested and tions of the Canadian Department of Communications.
found to comply with the limits for class A computing device Le present appareil numerique n'emet pas de bruits radio-
pursuant to Subpart B of Part 15 of FCC Rules, which is electriques depassant les limites applicables aux appareils
designed to provide reasonable protection against such numeriques de la classe A prescrites dans le Reglement sur
interference when operated in a commercial environment. le brouillage radioelectrique edicte par le ministere des
Operation of this equipment in a residential area is likely to Communications du Canada.
cause interference, in which case the user will be required
to correct the interference at his own expense.
Acclimate Plus™, HARSH™, NOTI•FIRE•NET™, VeriFire™, NION™ and NOTIFER Intergrated Systems™ are trademarks, and ONYX®, ONYXWorks®, FlashScan®,
UniNet®, VIEW® and NOTIFIER® are registered trademarks of Honeywell. Windows® is a registered trademark of the Microsoft Corporation.
©2010 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
General:
Material Aluminum
Enclosure:
Door Finish Black epoxy powder coat finish, fine texture – Door only
Conduit punch outs (2) ½" and (2) ¾" on the top and bottom of the enclosure (8) total
Display:
Size 19"
CPU:
Slots NONE
Video Integral
USB ports 8
System RAM 2 GB
Peripherals:
Other:
Motherboard Lithium Battery Battery is not field replaceable. Contact Technical Services for information.
DC to DC Converter Fuse Fuse is only replaceable by authorized personnel. Contact Technical Services for
information.
Fuse:10A, 250V, SLO BLO, 5x20mm.
Table 1.3
Number of buildings supported per See comment Limited by number of floors (above).
campus
Total number of events supported 3000 3000 events supported across entire
campus.
Pixel size for bitmap icon graphics 68 x 68 This is a recommended average size.
Individual icons may be bigger or
smaller as needed.
Table 1.3
Rapid EyeTM CCTV Gateway supports these Digital Video Recorders (DVRs):
V5 • 4.5.0
• 7.0
V6 • 4.5.0 Build 58
• 7.0
LT • 4.5.0 Build 58
• 7.0
V7 • 7.0
• 8.0
V8 • 8.0
• 8.1
NOTE: Check the software version under the System tab of the Maintenance section in Rapid
Eye Multi Media View software.
Before it can be used by an event responder, FIRSTVISION must be configured with information
about the building into which it is installed. Those configuration tasks are performed with the
ONYX® FIRSTVISION™ Configuration Tool (refer to 53035ONYX® FIRSTVISION™
Configuration Tool manual). The Configuration Tool tasks include entering meaningful
information about the layout of all floors in the buildings (drawing background), the locations of all
sensing devices that communicate with FIRSTVISION, building features (such as water supplies),
and hazards (such as flammable or reactive chemicals).
FIRSTVISION should be installed in the authorized event responder’s preferred building entry
location.
Refer to “The Development of FIRSTVISION” on page 65 for more information about this product.
Events that FIRSTVISION Processes and Annunciates
FIRSTVISION only supports SLC loop modules and devices. Only device or module events that use
formats of LxxDyyy and LxxMyyy (respectively) that are reported by the types of devices listed
below; are processed and annunciated by FIRSTVISION:
• Fire Alarms
• Supervisory
• Medical
• Security
• Critical Process
Compatibility
AFP-200 NAM
AFP-300/400 NAM
AFP-1010 SIB-NET
AM2020 SIB-NET
NFS-320 NCM-W/F
NFS-640 NCM-W/F
NFS2-640 NCM-W/F
NFS-3030 NCM-W/F
NFS2-3030 NCM-W/F
The ONYX® FIRSTVISION™ Configuration Tool can import VeriFire® databases into FIRSTVISION
campuses. Refer to the ONYX®FIRSTVISION™ Configuration Tool Programming Manual (PN:
53035) for more information.
1.2.2 Networking
The following figure illustrates a very simple possible NOTI•FIRE•NET™ network that includes
FIRSTVISION. For more information, refer to “Multiple Connections” on page 15 and “Make
Connections to FIRSTVISION” on page 29.
Ethernet (TCP/IP)
Network
NFN Gateway PC
NFN Gateway
OR
NFN Network
NOTE: If you have multiple NFN gateways in the network, then all the gateways should be set in
the same mode (Canadian mode, Supervising Station mode, etc.).
NOTE: If you are connecting FIRSTVISION to an NFN Gateway PC and plan on running the
ONYX® software application also, the Workstation must be set to Supervising Station Mode (refer
to the ONYX® Workstation manual).
Multiple Connections
A single FIRSTVISION unit can monitor many NOTI•FIRE•NET™ networks, each connected
through at least one NFN gateway.
Ethernet (TCP/IP)
Network
NFN Gateway
NFN Gateway
NFN Network
NFN Gateway
NFN Network
Ethernet (TCP/IP)
Network FIRSTVISION with CCTV Gateway
NFN Gateway
NFN Network
Ethernet (TCP/IP)
Network
NFN Gateway
NFN Network
NOTE: If you are connecting FIRSTVISION to an NFN Gateway PC and plan on running the
ONYX® software application also, the Workstation must be set to Supervising Station Mode (refer
to the ONYX® Workstation manual).
FIRSTVISION-ENC Enclosure
NOTE:
UL 864, 9th Edition—ONYX® systems work with products that have been UL 864, 9th Edition
listed as well as products that have not received UL 864, 9th Edition certification. Operation of
systems that are comprised of equipment that is UL 864, 9th Edition listed together with products
that are not UL 864, 9th Edition listed requires the approval of the local Authority Having
Jurisdiction (AHJ).
CAN/ULC-S559-04, 1st Edition—ONYX® systems work with products that have been CAN/ULC-
S559-04, 1st Edition listed as well as products that have not received CAN/ULC-S559-04, 1st
Edition certification. Operation of systems that are comprised of equipment that is CAN/ULC-
S559-04, 1st Edition listed together with products that are not CAN/ULC-S559-04, 1st Edition
listed requires the approval of the local Authority Having Jurisdiction (AHJ).
1.3.1 Compliance
This product has been investigated to, and found to be in compliance with the following standards.
National Fire Protection Association
• NFPA 72—National Fire Alarm Code
Underwriters Laboratories
• UL-864—Control Units for Fire Alarm Systems, Ninth Edition
• UL-1076—Proprietary Burglar Alarm Units and Systems, Fifth Edition
• UL-2017—General-Purpose Signaling Devices and Systems, First Edition
Underwriters Laboratories Canada
• CAN/ULC-S527-99—Standard for Control Units for Fire Alarm Systems, Second Edition
• CAN/ULC-S559-04—Equipment for Fire Signal Receiving Centres and Systems, First
Edition
1.3.2 Installation
This product is intended to be installed in accordance with the following regulatory agencies.
Local
• AHJ—Authority Having Jurisdiction
WARNING: Installation
! Improper installation, maintenance, and lack of routine testing could result in system malfunction.
1.5.2 Procedures
Supported Hardware
The FIRSTVISION application version 2.x and later runs only on the FIRSTVISION version 2.x
hardware, which includes the 19” diagonal LCD screen. Older hardware models of FIRSTVISION
cannot be upgraded to run the FIRSTVISION version 2.x application.
Step 3. Reboot the FIRSTVISION machine. The FIRSTVISION application automatically starts when
the system boots up.
NOTE: You must reboot the FIRSTVISION machine any time you update Site.xml, in order for the
FIRSTVISION application to use the updated site information.
NOTE: Rapid EyeTM CCTV Gateway attempts to start (if installed) when the FIRSTVISION unit
boots up even if you don't have any DVRs configured through the FIRSTVISION Configuration Tool.
If no configured DVRs are detected, CCTV Gateway shuts down. This does not hamper the
normal operation of FIRSTVISION.
In order to use site plans created with previous versions of FIRSTVISION, you must upgrade them to
be compatible with FIRSTVISION version 2.0 using the IncidentMonitor Upgrade Wizard. For more
information, please refer to Section 2.2, “Upgrading an Old FIRSTVISION Building Site to
FIRSTVISION version 2.0,” in the ONYX® FirstVision Configuration Tool Programming Manual,
PN 53035.
Primary Power Source Requirements for the FIRSTVISION primary power source are
contingent on the discretion of the local Authority Having Jurisdiction (AHJ). If the AHJ
determines that FIRSTVISION is not a required component of the fire system, battery backup is
optional. The primary power source can be any UL 1481 listed power supply meeting the
requirements shown in Table 2.1, “Power Supply Required Ranges”. However, if the AHJ
determines that FIRSTVISION is a required component of the fire system, then the primary power
source must be a +24 VDC, UL 1481 listed, power limited, battery backed, regulated power supply.
TYPICAL
NOTE: It is advisable to power the FIRSTVISION from its own dedicated 24V 3A UL-listed non-
resettable power supply.
NOTE: You can use this information to install the FIRSTVISION enclosure and to make power
supply connections to the enclosure’s control board or you can refer to the ONYX®FIRSTVISION™
Enclosure Installation Instructions (P/N 53105).
14.88
19” LCD
23.06 VIEWING
11.92
26.70
Use the following information as a guideline to accomplish the installation of the FIRSTVISION
enclosure and prepare the power supply components/connections for the FIRSTVISION LCD.
Perform all installations in accordance with building construction, local code requirements, and/or
as described in the manufacturer’s documentation.
Step 1. Mount the FIRSTVISION enclosure on an inside wall of the building.
NOTE: The dimensions shown in Figure 2.2, “Mounting Holes and Enclosure Dimensions
(inches)” on page 25 are the exact measurements of the enclosure. Make the enclosure hole
slightly larger (approximately 1/8”) than the enclosure for an easier fit.
a. Prepare a rough opening in the wall at the location FIRSTVISION will be mounted
according to the enclosure’s dimensions shown below.
.32 .32
.55
24.63
10.45
22.03
10.45
DIAGONAL DIMENSION
32.645 IN (829.185mm)
b. Remove the enclosure’s knockout(s) that will be used to route your LAN cable and
power supply’s cable through.
c. Place the enclosure inside of the rough opening (with the LCD hinges on the left).
d. Attach the enclosure to the wall at the six locations provided using field supplied
fasteners.
NOTE: Make sure the enclosure is level before fastening it to the wall.
Mounting Hole
(6 places)
Step 2. Mount the external power supply according to the manufacturer’s instructions.
Step 3. Route the external power supply wiring into the enclosure through one of the available
knockouts, and then connect it to the control board as shown in Figure 2.4 on page 26.
Step 4. Route the LAN cable into the enclosure through one of the available knockouts.
Knockouts
.41
3.47
1.60 1.10
1.28 1.75
24.53
backboack of L
f LCDCD Power Cable
display
from LCD
J1
The FIRSTVISION
enclosure is factory
assembled and wired to
install/connect the LCD.
P1
Common GND
Enclosure’s
Control Board
Step 4. Swing the LCD closed and fasten it closed by using the 2 factory supplied black pan head
machined screws.
Step 5. Close the LCD’s glass paneled door.
Step 6. Use the factory supplied door key to lock the closed door.
Step 7. Verify the door locks and unlocks with each turn of the key.
Step 8. You are now ready to perform “Enabling FIRSTVISION to Monitor A Campus” on page 29.
NOTE: You must unlock the front door of FIRSTVISION to gain access to the USB ports.
NOTE: To gain access to the PS/2 connectors, you must remove the screws holding the LCD
closed and then you must swing the LCD out.
USB
VIDEO OUT
KBD
POWER
COM 1 MOUSE
LAN LAN
Step 2. If not already connected; connect FIRSTVISION to your IP Network by attaching customer
supplied CAT-5 ethernet cable to the LAN (Local Area Network) port.
USB
VIDEO OUT
KBD
POWER
COM 1 MOUSE
LAN LAN
Active/Enabled
USB
VIDEO OUT
KBD
POWER
COM 1 MOUSE
LAN LAN
Three options:
* Direct connection using a cross over
Ethernet cable
* Connection using 2 standard CAT-5
Ethernet cables and a UL-listed hub
* Connection to the customer supplied
Optional Rapid Eye™ Digital Video Ethernet (TCP/IP) Network.
Network*
Ethernet (TCP/IP)
Network
NFN Network
(v5.0 or later)
USB
VIDEO OUT
KBD
POWER
COM 1 MOUSE
LAN LAN
Three options:
* Direct connection using a cross over
Ethernet cable
* Connection using 2 standard CAT-5
Ethernet cables and a UL-listed hub
* Connection to the customer supplied
Optional Rapid Eye™ Digital Video Ethernet (TCP/IP) Network.
Network*
Ethernet (TCP/IP)
Network
NFN Network
(v5.0 or later)
3. After the progress bar disappears; the software application will automatically start because a
shortcut to the application has been placed in the product’s Startup folder.
The gateway that FIRSTVISION monitors (setup with Add Gateway Connection) has a factory
setting of 192.168.1.2.
• If it is necessary to change this factory setting; refer to “Establish Gateway Communication”
on page 39 for information.
• If it is necessary to change a gateway’s IP address, refer to the gateway’s respective
installation manual.
• If you are using a Rapid Eye™ DVR and configuring cameras to stream live video in the
FIRSTVISION system, contact the IT personnel of the site for proper Network Settings
(Default Gateway, IP Address, Subnet Mask etc.) of the FIRSTVISION machine.
NOTE: Do NOT change the factory boot setup for FIRSTVISION’s host computer (that is,
administrator is automatically logged in at startup), or add any user accounts.
It is essential that the FIRSTVISION host computer remain configured to automatically log in the
administrator account at startup, without asking for a password.
Automatic Updates
NOTE: Automatic Updates must be turned OFF for FIRSTVISION to function correctly. Do NOT
change this factory setting.
To verify automatic updates are turned off, from the Windows taskbar click Start Control Panel
Security Center Automatic Updates.
NOTE: If the FIRSTVISION application is running, you must end the application by pressing the
Esc key before you can access the Windows taskbar.
You may still update your Windows operating system manually. To manually update Windows,
open a web browser and go to http://www.update.microsoft.com/microsoftupdate/v6/default.aspx?.
Windows Firewall
NOTE: Contact IT personnel of the site to get the proper network and firewall settings to connect
the FIRSTVISION machine to internet.
Since the Windows firewall is turned on by default, Windows may display a security alert the first
time FIRSTVISION or CCTV Gateway tries to connect to the network.
If this happens, click Unblock to allow the program to function as intended. You should only need
to do this once for each program (FIRSTVISION and CCTV Gateway).
Screen Saver
FIRSTVISION supports Windows Screen Saver settings that extend the display’s life and prevent
screen image burn in. Only Windows screen saver application is supported, do NOT use a third-
party screen saver application.
NOTE: A Screen Saver selection has been made at the factory. Those factory settings use a
predetermined screen saver image and "Wait" setting of 10 minutes.
FIRSTVISION’s screen saver is displayed when its Wait setting is reached only if:
• There are no events that FIRSTVISION processes are being reported to FIRSTVISION.
• All the gateways configured in the FIRSTVISION are connected.
If events that FIRSTVISION processes are being reported to FIRSTVISION or the gateway connection
is lost; FIRSTVISION’s screen saver will disable and the software application will display. The
screen saver will remain disabled as long as there is an event that FIRSTVISION processes being
reported. After all the events that FIRSTVISION processes have been remedied (cleared/restored);
the screen saver will be automatically enabled after its Wait setting is reached.
NOTE: The screen saver is also automatically disabled if DVR(s) and cameras are configured in
the system or if FIRSTVISION loses its connection to the DVR. The camera device icons are
marked with red “X”s in these instances.
NOTE: If FIRSTVISION goes into screen saver, an open video window closes and the display,
when it is next shown, shows the Campus View.
Windows Screen Saver and Wait settings are made on the Display Properties window (i.e. Screen
Saver tab). The Screen saver field options are "None" and "My Picture Slideshow". You can load
and use your own screen saver images but they can NOT be of the 3D type.
Consult Windows information for details about making Display Properties settings.
NOTE: Correct time and date settings ensure times shown on FIRSTVISION display and in event
logs are accurate—crucial information for responding Firefighters.
Step 1. Double click the digital clock on the right side of the Windows taskbar.
Step 2. Verify the time and date are shown correctly in the dialogue that appears, and then click
the Time Zone tab.
Step 3. Check the box next to “Automatically adjust clock for daylight saving changes.”
Step 4. Select your local time zone from the drop menu.
Step 4. Right click on Local Area Connections 2 in the Network Connections window and select
Properties from the list of choices. The Local Area Connection Properties window
displays.
Step 5. On the General tab click on "Internet Protocol (TCP/IP)", then click on the Properties
button. The Internet Protocol (TCP/IP) Properties window displays.
Step 8. Confirm that is 255.255.255.0 in the Subnet Mask field to choose the internal network (the
address is dependent on your network).
Step 9. Complete your entry by clicking on OK.
Step 10. Restart Windows. FIRSTVISION will automatically start. Communication between
FIRSTVISION and your LAN should be established.
Step 11. Verify the connection by doing either of the following:
• Check the Gateway icon in the upper left corner of the display (no X over icon means
connected).
• Ping the gateway:
• Shut down FIRSTVISION.
• Select Start Command Prompt to display a command prompt window.
• Type in "Ping <Gateway IP Address>". If the response to the Ping is returned from
the Gateway, then the connection is established.
NOTE: If you will be connecting to a Rapid Eye™ DVR for video feed, you can also ping the
DVR to ensure Ethernet connectivity between FIRSTVISION and the DVR.
It is anticipated that the factory settings for a gateway may probably work for your application and
it is recommended you use them, if possible, instead of setting up new settings. If you want to
change the factory settings use the following information
NOTE: Your LAN connection must be established before you add a gateway.
NOTE: In order to setup a network (gateway), you must re-export your campus design to XML.
See “How to Export Your Campus Design for Copying to FIRSTVISION” in ONYX®FIRSTVISION™
Configuration Tool Manual - 53035.
NOTE: You must reboot the FIRSTVISION machine any time you update Site.xml, in order for the
FIRSTVISION application to use the updated site information.
NOTE: The factory default Gateway IP address setting is: 192.168.1.2. If you need to change
this setting, then use the following information.
Gateway IP address
Redundant Gateway IP
address
NOTE: You must reboot the FIRSTVISION machine any time you update Site.xml, in order for the
FIRSTVISION application to use the updated site information.
NOTE: Each FIRSTVISION machine functions as a time server. If you have an embedded
gateway serving a FIRSTVISION client, then you can configure the gateway to synchronize its time
with the FIRSTVISION machine.
NOTE: You must reboot the FIRSTVISION machine any time you update Site.xml, in order for the
FIRSTVISION application to use the updated site information.
Step 1. Establish a physical connection between your PC or storage device (i.e. where your
campus design Site.xml file and related folders are stored) and FIRSTVISION.
Step 2. Use Window Explorer on FIRSTVISION to find, select, and copy the file Site.xml file and
the folders Data, Datasheets, Floorplans, and Resources to the following folder on
FIRSTVISION: C:/Facilities Monitoring/FIT.
NOTE: The Resources folder will be present only if you have created custom icons for your
campus.
NOTE: The Datasheets folder will be present only if you have attached a Material Safety Data
Sheet in .pdf format to a hazardous material with the Chemical Editor, and placed a HAZMAT
Area icon for that material on your campus. For more information, please refer to the section,
“Describe Hazardous Materials with the Chemical Editor” in the Configuration Tool Programming
Manual.
NOTE: Overwrite the folder and files, do NOT delete the existing Site.xml and Floorplans folder.
prior to this step.
Step 3. You should now perform “Choose Which Building(s) To Monitor Using Profile Selector”
on page 42.
Step 2. Check the boxes beside only the buildings you want FIRSTVISION to monitor.
Step 3. You can also check the tree heading, “Buildings,” to have FIRSTVISION monitor all
buildings on the campus.
NOTE: All buildings configured in the campus are listed in the Profile Selector. If an expected
building is missing from this list, run the Configuration Tool to investigate the campus design.
Step 4. You should now restart FIRSTVISION and wait until Windows is displayed.
NOTE: An application is loading message will display. It may take some time to load the file
depending upon the components of the campus (number of icons and building floors). If the
message is displayed; do NOT attempt to double click the icon again.
4.1 Printing
Many FIRSTVISION screens can be printed by touching the print icon. This feature makes the
information portable. It can be especially helpful for listed information, such as contact information
and information from the event list.
Touching the print icon prints the information on the current FIRSTVISION screen to the Windows®
default network printer.
NOTE: The print icon functions only once a default printer has been configured through the
Windows® operating system on the FIRSTVISION device.
If there are no off-normal events when FIRSTVISION first launches, the campus view is shown.
Campus view shows an overview of the entire site FIRSTVISION is monitoring. Campus view
provides this information:
• The campus name appears as a title.
• The Gateway Connection Icon in the upper left corner of the user interface indicates whether
FIRSTVISION is connected to your gateway (a red X displayed inside the icon means that
FIRSTVISION has lost connection to at least one NFN or CCTV gateway).
NOTE: If the CCTV Gateway loses its connection to a configured DVR, camera icons
configured for that DVR are marked with a red X.
• Each building being monitored is shown in its relative location, represented by an interactive
icon. A building icon is green when the building has no alarms. If a building is reporting any
alarms, its icon flashes red. A flashing green icon indicates a building from which FIRSTVISION
has just begun receiving events—a building icon flashing green will soon begin flashing red.
Touching a building icon displays the building view.
• In the upper right portion of the display are three buttons which control the zoom level of the
campus view. There are six zoom level settings. As you navigate among floors, FIRSTVISION
remembers your zoom level setting for each floor. Specifically, these buttons:
– —Increase zoom level
– —Revert to original center and zoom level
– —Decrease zoom level
NOTE: Device icons that use device IDs are displayed on FIRSTVISION only when they report an
event type that FIRSTVISION processes.
• A miniature map of the current floor plan appears below the time display. When the zoom level
limits the portion of the floor plan you can see, a red outline on this map shows you the area
you are viewing in relation to the rest of the floor plan.
• A row of larger buttons, Information, Campus View and Event List, appears across the top of
the display. The Campus View button restores the campus view. Details about the Information
and Event List buttons are provided later in this section.
Floor Number Buttons
With the front door open; touching a floor number button displays the corresponding floor in the
building layout.
NOTE: For buildings with more than 11 floors, the floor navigation system works differently. See
“Floor Range Buttons” on page 50.
Information Buttons
Touching the Information button opens the information window. Toggle the information window to
display either building information, or building personnel contact information, by pressing the
appropriate tab.
NOTE: Refer to the section Shutoff Icons in 53035 FIRSTVISION Configuration Tool Programming
Manual for descriptions of shutoff devices, primary building shutoff designation, and the custom
device label information that can be set up to appear on this screen.
With the front door open; touching an icon displays information about the image.
Message Description
Message Description
Lost Signal... Re-acquiring live… After displaying a, "No signal" message, FIRSTVISION
checks to see whether the camera’s DVR is still
communicating on the network. If so, FIRSTVISION
displays this reacquiring message while it attempts
to acquire live video feed.
NOTE: When FIRSTVISION is monitoring a campus which is reporting events at a very fast rate,
live video may appear sluggish. This is because FIRSTVISION gives events priority over live video.
Note these considerations when operating FIRSTVISION with a video feed window open. When a
video feed window is open:
• Newly registered events appear.
• The icon representing the first device in alarm does not animate.
• Devices registering alarms no longer flash in sequence to indicate the order in which events
were received.
• The video feed window remains open even if you toggle the view between floors or between
building and campus views.
• The Information window and Event List may be opened.
• You can use the zoom level setting buttons to zoom in or out.
• You cannot drag a point on the floor or campus map to pan the screen.
• An open video window cannot be repositioned on the screen.
• If the DVR serving a camera is disconnected, touching the camera icon opens a window with
information about the disconnected DVR.
• After ten minutes, when there are no off-normal events and all configured gateways are
communicating properly, FIRSTVISION launches its screen saver to preserve the touch screen.
An open video feed window is automatically closed when the screen saver launches.
• Normal operation resumes once all video feed windows are closed.
Both of these behaviors must be configured when the campus is designed using the FIRSTVISION
Configuration Tool. For more information, refer to the Section “Configure Sound and Door
Unlocking Options” in ONYX®FIRSTVISION™ Configuration Tool Manual, PN 53035.
Touching the Gateway Connection Icon reveals more information, including the Gateway Type of
the disconnected gateway.
When an NFN gateway is disconnected, FIRSTVISION will not receive events from that gateway. It
is absolutely necessary to restore connectivity to the gateway to ensure the most accurate and up to
date information is being displayed. In order to investigate connectivity issues, you need to operate
FIRSTVISION like a personal computer. To do this:
Step 1. Follow the steps in “Make Connections to FIRSTVISION” on page 29 to attach a keyboard
and mouse to FIRSTVISION.
Step 2. Shut down the FIRSTVISION software application by pressing the Esc key.
See “Establish Communication Between Your LAN and FIRSTVISION” on page 37 and “Establish
Gateway Communication” on page 39 for information about gateway connectivity.
When a connection to a DVR through the CCTV Gateway is lost, FIRSTVISION cannot display
video feed from any camera connected to that DVR. In order to investigate connectivity issues, you
need to operate FIRSTVISION like a personal computer. To do this:
Step 1. Follow the steps in “Make Connections to FIRSTVISION” on page 29 to attach a keyboard
and mouse to FIRSTVISION.
Step 2. Shut down the FIRSTVISION software application by pressing the Esc key.
Check to make sure the CCTV Gateway is running. When the CCTV Gateway is running, an icon
is displayed in the notification area of the Windows taskbar. Moving the mouse pointer over the
icon displays information about the gateway connection and connected DVRs.
See Appendix A, “Troubleshooting with The Rapid EyeTM CCTV Gateway Configuration Tool”.
Also, refer to Honeywell System Administrator’s Guide: Using Admin and View software to
configure Multi-Media units and manage the accounts of Operators—Rapid Eye™ Multi-Media,
Rapid Eye™ Multi-Media DSP, Rapid Eye™ Multi-Media LT - K5403V11 for information about
Digital Video Network connectivity.
NOTE: If the CCTV Gateway loses its connection to a configured DVR, camera icons
configured for that DVR are marked with a red X.
When a monitored campus first reports a fire alarm, the FIRSTVISION front door unlocks and the
view changes to indicate which floor and building the fire alarm is on. A red field surrounding the
Campus View button shows how many buildings have devices reporting alarms. A special icon
animation indicates the first device in each building to report an alarm. If multiple fire alarms are
reported on a single floor, the device icons on that floor blink in a sequence that indicates the order
in which they registered events.
Event List
With the front door open; touching the Event List button displays a listing of the current alarms.
NOTE: Remember to go to FIRSTVISION after a fire alarm has been cleared from the monitored
network because FIRSTVISION’s door will need to be latched closed.
FIRSTVISION automatically detects the USB drive, and asks if you want to download the log file
onto it. Touch Yes to download the log file onto the USB flash memory drive.
0 seconds 1. The enclosure unlocks and the touch screen displays the floor on which the alarm
activated.
0 seconds 2. The Incident Commander enters the building at the main entrance, goes to FIRSTVISION
and opens the enclosure to view the screen.
10 4. After verifying the building and seeing fire location, the Commander radios firefighting
seconds team. As he calls, he continues observation:
– Checks layouts of other floors and the roof (as shown in the example in Figure 5.2) to
be sure the fire is contained on only those levels.
– Checks which detector(s) is activated. If multiple detectors are activated he can
determine the progression of the fire by interpreting the blinking sequence of the
detectors and base his assessment of the situation on that displayed information.
– Checks for presence of hazardous materials near the fire on its respective floor. (as
shown in the example in Figure 5.3)
– Reads material safety data PDFs describing hazardous materials (as shown in the
example in Figure 5.4)
– Checks for the location of elevators, stairways, water supplies, and entry and exit
routes.
Note: Notice the Caution on this background about the tensioned concrete roof. It was added
as an Annotation to this floor plan using the Configuration Tool.
20 5. The Commander begins directing the team how to attack the fire: where to enter the
seconds building, how to approach the fire area, where to get water, how to vent the fire.
6. By viewing live video feed, the Commander is able to confirm that no windows have
blown out. Since the room with the fire is directly under the roof, it seems best to vent the
smoke through the roof. He touches the Information button, and then touches the
Building Information tab to be sure there are no structural details that could cause
problems. (as shown in the example in Figure 5.5) Here, he sees that the roof is
tensioned concrete and tells the team that they will have to knock out a window from the
outside of the building for venting.
30-60 7. The Incident Commander has gathered the data required to plan the attack and relayed
seconds the information to the team. Within two minutes of arrival, the team is containing and
putting out the fire.
Fire Scene 2
In this scenario, the fire is near the front of the building and the main entrance drive, so trucks can
be positioned easily. If the fire occurred in a back corner or the far side of the building, the Incident
Commander would use the Campus View to see safe routes for driving the trucks closer to the fire
(as shown in the example in Figure 5.6).
If hazardous materials were stored near the fire, the Commander would touch the Hazard icon to
see what the materials were and how to handle fire in the area (as shown in the example in
Figure 5.7).
If the materials were unfamiliar, the Commander could touch the Information button, and then
touch the Contact Information tab to see the on call number for the State Hazardous Material expert
(as shown in the example in Figure 5.8). That expert would advise the team of dangers, or come
personally to the scene.
If a Material Safety Data Sheet (MSDS) were provided for the hazardous materials in question, the
Commander could also touch Data Sheet to view the MSDS PDF.
OR
• Double-click the CCTV Gateway Configuration Tool icon on the Windows Desktop, OR
• Right click the CCTV Gateway icon in the notification area of the Windows taskbar, and then
click Debugging Tool in the menu that appears.
NOTE: The dropdown address menu shows only the IP addresses of the currently running
CCTV Gateways "as seen" in the network.
Figure A.2 Rapid EyeTM CCTV Gateway Configuration Tool Address Bar
Figure A.3 Rapid EyeTM CCTV Gateway Configuration Tool Node Panel
Click a CCTV Gateway listed in the Node Panel to see a list of DVRs connected to the CCTV
Gateway. The IP address of each DVR is shown.
Click the “+” beside a DVR IP address to expand a list of all cameras connected to that DVR.
Figure A.4 Rapid EyeTM CCTV Gateway Configuration Tool: DVRs on Gateway
Click the name of a camera connected to a DVR to display information about that camera in the
Property/Value Panel.
Figure A.5 Rapid EyeTM CCTV Gateway Configuration Tool: Cameras on DVR
NOTE: If a video is being viewed by any FIRSTVISION unit on the same IP network as the
computer running the CCTV Gateway Configuration Tool, the device status appears as,
“Streaming,” with a green label.
A.4.2 View
All these choices display read only information windows, no editing can be done on the
information displayed from these windows.
• Refresh Gateway List - Used to generate a new list of CCTV Gateways that will be available
from the CCTV Gateway Configuration Tool’s Address menu. For more information, refer to
“Address Menu” on page 76.
• Refresh Nodes List - Used to ping the nodes connected to the current CCTV Gateway and
display their information.
• Clients - Used to display a window which lists all the clients that are connected to all the
CCTV Gateways running on the same subnet as the computer running the CCTV Gateway
Configuration Tool.
A.4.3 Configure
• Diagnostic Mode- Toggles Diagnostic Mode on and off. When CCTV Gateway Configuration
Tool runs in Diagnostic Mode, additional information is displayed in the scrolling pane at the
bottom of the CCTV Gateway Configuration Tool window.
Debug DVR mode can be used to log in independently to a DVR without the help of a CCTV
Gateway. This is can be useful to debug a connection to a DVR if a CCTV Gateway cannot connect
to a particular DVR.
NOTE: If you are logging into a DVR using this option and you are watching a live video in the
FIRSTVISION unit, you might lose video signal for a brief period of time.
A.4.5 Help
• About - Display version information.
G
Gateway Config Tool
layout 75
H
Help menu
descriptions 78
I
Installation
Environmental Conditions 19
L
LAN 30
M
manual conventions 19
manuals
related 21
Monitor Power 35
N
Node Compatibility 13
R
Refresh Gateway List 77
Refresh Nodes List 77
S
Specifications 9
Touchscreen, PC 9, 10
Warn-HL-08-2009.fm
www.notifier.com