Hotel Hilton Piura - GCM - 01

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 71

Produced on 2/10/2019 with Xpress Selection V8.6.5 - database DIL 13.8.

Project name HOTEL HILTON PIURA


Project address Peru
Reference PIURA
Client name JGJ
Revision GCM_01

Selection parameters of the indoor units can be found under the chapter Indoor unit details
Selection parameters of the outdoor units can be found under the chapter Outdoor unit details
Only the data published in the data book are correct. This program uses close approximations of these data.

1. Material List
Model Qty Description
RHXYQ12AYL 3 Heat pump VRV IV 380V(YL)
RHXYQ16AYL 1 Heat pump VRV IV 380V(YL)
RHXYQ18AYL 5 Heat pump VRV IV 380V(YL)
RHXYQ22AYL 3 Heat pump VRV IV 380V(YL)
RMXYQ3AVL 1 Heat pump VRV IV S 60HZ
RMXYQ6AVL 2 Heat pump VRV IV S 60HZ
EKEXV400 3 EKEXV
FXAQ20PVE 2 VRV AP - De Pared (Panel Plano)
FXDQ25PDVE 65 VRV D(PDVE) - Unidad delgada de conducto montada en techo
FXDQ32PDVE 30 VRV D(PDVE) - Unidad delgada de conducto montada en techo
FXDQ50NDVE 5 VRV D(PDVE) - Unidad delgada de conducto montada en techo
FXMQ100PAVE 4 VRV M-PA - Unidad de conducto montada en el techo
FXMQ140PAVE 7 VRV M-PA - Unidad de conducto montada en el techo
FXMQ200MAVE 3 VRV M-A - Unidad de conducto montada en el techo
FXMQ25PAVE 1 VRV M-PA - Unidad de conducto montada en el techo
FXMQ80PAVE 2 VRV M-PA - Unidad de conducto montada en el techo
FXZQ20MVE 15 VRV Z - Unidad de casete montada en el techo(Multiflujo Compacto)
KHRP26A22T 64 Refnet branch piping kit
KHRP26A33T 24 Refnet branch piping kit
KHRP26A72T 31 Refnet branch piping kit
KHRP26A73T + KHRP26M73TP 7 Refnet branch piping kit
BRC1E63 134 Wired Remote Controller (Navigation Remote Controller)
BYFQ60B3W1 15 Decoration panel
BHFP22P100 2 Outdoor unit multi connection piping kit
BHFP22P151 1 Outdoor unit multi connection piping kit
EKEQFCBA 3 VRV AHU Control box kit
R410A 124.3kg Extra refrigerant charge
Piping ¼" 367.3m
Piping ⅜" 377.2m
Piping ½" 435.0m
Piping ⅝" 365.1m
Piping ¾" 138.1m
Piping ⅞" 54.3m
Piping 1⅛" 210.6m
Piping 1¼" 6.4m
Piping 1½" 31.0m

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 1
2. Indoor Unit Details
2.1. Table of Abbreviations
Name Logical name of the device
FCU Device model name
Tmp C Indoor conditions in cooling (dry bulb temp. / wet bulb temp.)
Rq TC Required total cooling capacity
Max TC Available total cooling capacity
Rq SC Required sensible cooling capacity
Max SC Available sensible cooling capacity
Tevap Evaporating temperature of indoor unit coil
Tdis C Indoor unit discharge air temperature in cooling
Tmp H Indoor temperature in heating
Rq HC Required heating capacity
Max HC Available heating capacity
Tdis H Indoor unit discharge air temperature in heating
Airflow Supplied airflow
Sound Sound pressure low and high
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
WxHxD WidthxHeightxDepth
Wght Weight of the device

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 2
2.2. VRV - sotano - RMXYQ6AVL
Capacity data at conditions and connection ratio (129%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tdis C Tmp H Rq HC Max HC Tdis H Airflow
°C BTU/h BTU/h BTU/h BTU/h °C °C °C BTU/h BTU/h °C cfm
ATI-02 FXZQ20MVE 24.0 / 17.0 n/a 6653 n/a 5268 6.0 15.6 20.0 n/a 8530 33.6 318
ATI-02 FXZQ20MVE 24.0 / 17.0 n/a 6653 n/a 5268 6.0 15.6 20.0 n/a 8530 33.6 318
ATI-01 FXZQ20MVE 24.0 / 17.0 n/a 6653 n/a 5268 6.0 15.6 20.0 n/a 8530 33.6 318
ATI-01 FXZQ20MVE 24.0 / 17.0 n/a 6653 n/a 5268 6.0 15.6 20.0 n/a 8530 33.6 318
ATI-01 FXZQ20MVE 24.0 / 17.0 n/a 6653 n/a 5268 6.0 15.6 20.0 n/a 8530 33.6 318
ATI-01 FXZQ20MVE 24.0 / 17.0 n/a 6653 n/a 5268 6.0 15.6 20.0 n/a 8530 33.6 318
ATI-01 FXZQ20MVE 24.0 / 17.0 n/a 6653 n/a 5268 6.0 15.6 20.0 n/a 8530 33.6 318
ATI-02 FXZQ20MVE 24.0 / 17.0 n/a 6653 n/a 5268 6.0 15.6 20.0 n/a 8530 33.6 318
ATI-02 FXZQ20MVE 24.0 / 17.0 n/a 6653 n/a 5268 6.0 15.6 20.0 n/a 8530 33.6 318

Required cooling capacity towards the outdoor unit: 59880BTU/h.


Required heating capacity towards the outdoor unit: 76773BTU/h.
The sum of the required indoor unit capacities is 59880BTU/h for cooling and 76773BTU/h for heating.
However, the outdoor unit selection uses reduced load values for cooling of 53892BTU/h (= -10%) and for heating
of 69096BTU/h (= -10%).
Be aware that unrealistic reductions may lead to reduced comfort levels, different noise levels or increased wear
and tear.

The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest
temperature in case of heating mode), assuming the indoor unit is running at full load at the given indoor
temperature design conditions. In practice the discharge temperature will modulate based on actual capacity
requirements and during defrost mode (heating mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a
thermal comfort level.
The discharge temperature is lower than 35.0°C. Reducing the connection ratio may compensate this and may
raise the discharge temperature improving the thermal comfort level.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
ATI-02 25-30 220V 1ph 0.8 575×286×575 18
ATI-02 25-30 220V 1ph 0.8 575×286×575 18
ATI-01 25-30 220V 1ph 0.8 575×286×575 18
ATI-01 25-30 220V 1ph 0.8 575×286×575 18
ATI-01 25-30 220V 1ph 0.8 575×286×575 18
ATI-01 25-30 220V 1ph 0.8 575×286×575 18
ATI-01 25-30 220V 1ph 0.8 575×286×575 18
ATI-02 25-30 220V 1ph 0.8 575×286×575 18
ATI-02 25-30 220V 1ph 0.8 575×286×575 18

Outdoor unit placed 24.0m above the indoor units.


The minimum connection ratio for this height difference is 50%.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 3
2.3. VRV - piso 1 - RHXYQ24AYL
Capacity data at conditions and connection ratio (123%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tdis C Tmp H Rq HC Max HC Tdis H Airflow
°C BTU/h BTU/h BTU/h BTU/h °C °C °C BTU/h BTU/h °C cfm
ATI-10 FXMQ140PAVE 24.0 / 17.0 n/a 47597 n/a 36455 6.0 12.7 20.0 n/a 61419 39.1 1624
ATI-10 FXMQ140PAVE 24.0 / 17.0 n/a 47597 n/a 36455 6.0 12.7 20.0 n/a 61419 39.1 1624
ATI-10 FXMQ140PAVE 24.0 / 17.0 n/a 47597 n/a 36455 6.0 12.7 20.0 n/a 61419 39.1 1624
ATI-10 FXMQ140PAVE 24.0 / 17.0 n/a 47597 n/a 36455 6.0 12.7 20.0 n/a 61419 39.1 1624
ATI-08 FXMQ100PAVE 24.0 / 17.0 n/a 33267 n/a 25714 6.0 12.5 20.0 n/a 42652 39.1 1130
ATI-01 FXZQ20MVE 24.0 / 17.0 n/a 6653 n/a 5268 6.0 15.6 20.0 n/a 8530 33.6 318
ATI-01 FXZQ20MVE 24.0 / 17.0 n/a 6653 n/a 5268 6.0 15.6 20.0 n/a 8530 33.6 318
ATI-01 FXZQ20MVE 24.0 / 17.0 n/a 6653 n/a 5268 6.0 15.6 20.0 n/a 8530 33.6 318
ATI-01 FXZQ20MVE 24.0 / 17.0 n/a 6653 n/a 5268 6.0 15.6 20.0 n/a 8530 33.6 318

Required cooling capacity towards the outdoor unit: 250270BTU/h.


Required heating capacity towards the outdoor unit: 322447BTU/h.
The sum of the required indoor unit capacities is 250270BTU/h for cooling and 322447BTU/h for heating.
However, the outdoor unit selection uses reduced load values for cooling of 225243BTU/h (= -10%) and for heating
of 290203BTU/h (= -10%).
Be aware that unrealistic reductions may lead to reduced comfort levels, different noise levels or increased wear
and tear.

The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest
temperature in case of heating mode), assuming the indoor unit is running at full load at the given indoor
temperature design conditions. In practice the discharge temperature will modulate based on actual capacity
requirements and during defrost mode (heating mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a
thermal comfort level.
The discharge temperature is lower than 35.0°C. Reducing the connection ratio may compensate this and may
raise the discharge temperature improving the thermal comfort level.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
ATI-10 43-46 220V 1ph 3.4 1400×300×700 46
ATI-10 43-46 220V 1ph 3.4 1400×300×700 46
ATI-10 43-46 220V 1ph 3.4 1400×300×700 46
ATI-10 43-46 220V 1ph 3.4 1400×300×700 46
ATI-08 39-43 220V 1ph 2.9 1400×300×700 45
ATI-01 25-30 220V 1ph 0.8 575×286×575 18
ATI-01 25-30 220V 1ph 0.8 575×286×575 18
ATI-01 25-30 220V 1ph 0.8 575×286×575 18
ATI-01 25-30 220V 1ph 0.8 575×286×575 18

Outdoor unit placed at the same level as the indoor units.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 4
2.4. VRV - piso 1 extra - RMXYQ3AVL
Capacity data at conditions and connection ratio (83%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tdis C Tmp H Rq HC Max HC Tdis H Airflow
°C BTU/h BTU/h BTU/h BTU/h °C °C °C BTU/h BTU/h °C cfm
UI-01 FXAQ20PVE 24.0 / 17.0 n/a 6653 n/a 5903 6.0 12.7 20.0 n/a 8530 36.3 265
UI-01 FXAQ20PVE 24.0 / 17.0 n/a 6653 n/a 5903 6.0 12.7 20.0 n/a 8530 36.3 265
UE - 76 FXZQ20MVE 24.0 / 17.0 n/a 6653 n/a 5268 6.0 15.6 20.0 n/a 8530 33.6 318

Required cooling capacity towards the outdoor unit: 19960BTU/h.


Required heating capacity towards the outdoor unit: 25591BTU/h.

The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest
temperature in case of heating mode), assuming the indoor unit is running at full load at the given indoor
temperature design conditions. In practice the discharge temperature will modulate based on actual capacity
requirements and during defrost mode (heating mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a
thermal comfort level.
The discharge temperature is lower than 35.0°C. Reducing the connection ratio may compensate this and may
raise the discharge temperature improving the thermal comfort level.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
UI-01 31-35 220V 1ph 0.3 795×290×238 11
UI-01 31-35 220V 1ph 0.3 795×290×238 11
UE - 76 25-30 220V 1ph 0.8 575×286×575 18

Outdoor unit placed at the same level as the indoor units.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 5
2.5. VRV - piso 2 - RHXYQ44AYL
Capacity data at conditions and connection ratio (126%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tdis C Tmp H Rq HC Max HC Tdis H Airflow
°C BTU/h BTU/h BTU/h BTU/h °C °C °C BTU/h BTU/h °C cfm
ATI-11 FXMQ200MAVE 24.0 / 17.0 n/a 66534 n/a 51486 6.0 11.3 20.0 n/a 85304 41.0 2048
ATI-11 FXMQ200MAVE 24.0 / 17.0 n/a 66534 n/a 51486 6.0 11.3 20.0 n/a 85304 41.0 2048
ATI-11 FXMQ200MAVE 24.0 / 17.0 n/a 66534 n/a 51486 6.0 11.3 20.0 n/a 85304 41.0 2048
ATI-10 FXMQ140PAVE 24.0 / 17.0 n/a 47597 n/a 36455 6.0 12.7 20.0 n/a 61419 39.1 1624
ATI-10 FXMQ140PAVE 24.0 / 17.0 n/a 47597 n/a 36455 6.0 12.7 20.0 n/a 61419 39.1 1624
ATI-08 FXMQ100PAVE 24.0 / 17.0 n/a 33267 n/a 25714 6.0 12.5 20.0 n/a 42652 39.1 1130
ATI-08 FXMQ100PAVE 24.0 / 17.0 n/a 33267 n/a 25714 6.0 12.5 20.0 n/a 42652 39.1 1130
ATI-08 FXMQ100PAVE 24.0 / 17.0 n/a 33267 n/a 25714 6.0 12.5 20.0 n/a 42652 39.1 1130
ATI-07 FXMQ80PAVE 24.0 / 17.0 n/a 26614 n/a 21401 6.0 11.8 20.0 n/a 34121 39.5 883
ATI-07 FXMQ80PAVE 24.0 / 17.0 n/a 26614 n/a 21401 6.0 11.8 20.0 n/a 34121 39.5 883
ATI-06 FXMQ25PAVE 24.0 / 17.0 n/a 8359 n/a 7056 6.0 12.8 20.0 n/a 10919 37.3 318
ATI-01 FXZQ20MVE 24.0 / 17.0 n/a 6653 n/a 5268 6.0 15.6 20.0 n/a 8530 33.6 318

Required cooling capacity towards the outdoor unit: 462837BTU/h.


Required heating capacity towards the outdoor unit: 594395BTU/h.
The sum of the required indoor unit capacities is 462837BTU/h for cooling and 594395BTU/h for heating.
However, the outdoor unit selection uses reduced load values for cooling of 416553BTU/h (= -10%) and for heating
of 534956BTU/h (= -10%).
Be aware that unrealistic reductions may lead to reduced comfort levels, different noise levels or increased wear
and tear.

The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest
temperature in case of heating mode), assuming the indoor unit is running at full load at the given indoor
temperature design conditions. In practice the discharge temperature will modulate based on actual capacity
requirements and during defrost mode (heating mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a
thermal comfort level.
The discharge temperature is lower than 35.0°C. Reducing the connection ratio may compensate this and may
raise the discharge temperature improving the thermal comfort level.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
ATI-11 45.5-48.5 220V 1ph 9 1380×470×1100 137
ATI-11 45.5-48.5 220V 1ph 9 1380×470×1100 137
ATI-11 45.5-48.5 220V 1ph 9 1380×470×1100 137
ATI-10 43-46 220V 1ph 3.4 1400×300×700 46
ATI-10 43-46 220V 1ph 3.4 1400×300×700 46
ATI-08 39-43 220V 1ph 2.9 1400×300×700 45
ATI-08 39-43 220V 1ph 2.9 1400×300×700 45
ATI-08 39-43 220V 1ph 2.9 1400×300×700 45
ATI-07 39-43 220V 1ph 2.3 1000×300×700 35
ATI-07 39-43 220V 1ph 2.3 1000×300×700 35
ATI-06 28-33 220V 1ph 0.6 550×300×700 25
ATI-01 25-30 220V 1ph 0.8 575×286×575 18

Outdoor unit placed 21.0m above the indoor units.


The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 6
The minimum connection ratio for this height difference is 50%.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 7
2.6. VRV - piso 3 - RHXYQ18AYL
Capacity data at conditions and connection ratio (125%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tdis C Tmp H Rq HC Max HC Tdis H Airflow
°C BTU/h BTU/h BTU/h BTU/h °C °C °C BTU/h BTU/h °C cfm
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-04 FXDQ32PDVE 24.0 / 17.0 n/a 10748 n/a 7626 6.0 10.4 20.0 n/a 13649 44.4 283
ATI-04 FXDQ32PDVE 24.0 / 17.0 n/a 10748 n/a 7626 6.0 10.4 20.0 n/a 13649 44.4 283
ATI-04 FXDQ32PDVE 24.0 / 17.0 n/a 10748 n/a 7626 6.0 10.4 20.0 n/a 13649 44.4 283
ATI-04 FXDQ32PDVE 24.0 / 17.0 n/a 10748 n/a 7626 6.0 10.4 20.0 n/a 13649 44.4 283
ATI-04 FXDQ32PDVE 24.0 / 17.0 n/a 10748 n/a 7626 6.0 10.4 20.0 n/a 13649 44.4 283
ATI-04 FXDQ32PDVE 24.0 / 17.0 n/a 10748 n/a 7626 6.0 10.4 20.0 n/a 13649 44.4 283
ATI-05 FXDQ50NDVE 24.0 / 17.0 n/a 16548 n/a 12233 6.0 10.0 20.0 n/a 21496 44.6 441

Required cooling capacity towards the outdoor unit: 189708BTU/h.


Required heating capacity towards the outdoor unit: 245333BTU/h.
The sum of the required indoor unit capacities is 189708BTU/h for cooling and 245333BTU/h for heating.
However, the outdoor unit selection uses reduced load values for cooling of 170737BTU/h (= -10%) and for heating
of 220800BTU/h (= -10%).
Be aware that unrealistic reductions may lead to reduced comfort levels, different noise levels or increased wear
and tear.

The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest
temperature in case of heating mode), assuming the indoor unit is running at full load at the given indoor
temperature design conditions. In practice the discharge temperature will modulate based on actual capacity
requirements and during defrost mode (heating mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a
thermal comfort level.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 8
Name Sound PS MCA WxHxD Wght
dBA A mm kg
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-04 24-28 220V 1ph 0.9 700×200×620 23
ATI-04 24-28 220V 1ph 0.9 700×200×620 23
ATI-04 24-28 220V 1ph 0.9 700×200×620 23
ATI-04 24-28 220V 1ph 0.9 700×200×620 23
ATI-04 24-28 220V 1ph 0.9 700×200×620 23
ATI-04 24-28 220V 1ph 0.9 700×200×620 23
ATI-05 27-33 220V 1ph 1.3 900×200×620 28

Outdoor unit placed 15.0m above the indoor units.


The minimum connection ratio for this height difference is 50%.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 9
2.7. VRV - piso 4 - RHXYQ18AYL
Capacity data at conditions and connection ratio (125%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tdis C Tmp H Rq HC Max HC Tdis H Airflow
°C BTU/h BTU/h BTU/h BTU/h °C °C °C BTU/h BTU/h °C cfm
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-04 FXDQ32PDVE 24.0 / 17.0 n/a 10748 n/a 7626 6.0 10.4 20.0 n/a 13649 44.4 283
ATI-04 FXDQ32PDVE 24.0 / 17.0 n/a 10748 n/a 7626 6.0 10.4 20.0 n/a 13649 44.4 283
ATI-04 FXDQ32PDVE 24.0 / 17.0 n/a 10748 n/a 7626 6.0 10.4 20.0 n/a 13649 44.4 283
ATI-04 FXDQ32PDVE 24.0 / 17.0 n/a 10748 n/a 7626 6.0 10.4 20.0 n/a 13649 44.4 283
ATI-04 FXDQ32PDVE 24.0 / 17.0 n/a 10748 n/a 7626 6.0 10.4 20.0 n/a 13649 44.4 283
ATI-04 FXDQ32PDVE 24.0 / 17.0 n/a 10748 n/a 7626 6.0 10.4 20.0 n/a 13649 44.4 283
ATI-05 FXDQ50NDVE 24.0 / 17.0 n/a 16548 n/a 12233 6.0 10.0 20.0 n/a 21496 44.6 441

Required cooling capacity towards the outdoor unit: 189708BTU/h.


Required heating capacity towards the outdoor unit: 245333BTU/h.
The sum of the required indoor unit capacities is 189708BTU/h for cooling and 245333BTU/h for heating.
However, the outdoor unit selection uses reduced load values for cooling of 170737BTU/h (= -10%) and for heating
of 220800BTU/h (= -10%).
Be aware that unrealistic reductions may lead to reduced comfort levels, different noise levels or increased wear
and tear.

The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest
temperature in case of heating mode), assuming the indoor unit is running at full load at the given indoor
temperature design conditions. In practice the discharge temperature will modulate based on actual capacity
requirements and during defrost mode (heating mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a
thermal comfort level.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 10
Name Sound PS MCA WxHxD Wght
dBA A mm kg
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-04 24-28 220V 1ph 0.9 700×200×620 23
ATI-04 24-28 220V 1ph 0.9 700×200×620 23
ATI-04 24-28 220V 1ph 0.9 700×200×620 23
ATI-04 24-28 220V 1ph 0.9 700×200×620 23
ATI-04 24-28 220V 1ph 0.9 700×200×620 23
ATI-04 24-28 220V 1ph 0.9 700×200×620 23
ATI-05 27-33 220V 1ph 1.3 900×200×620 28

Outdoor unit placed 12.0m above the indoor units.


The minimum connection ratio for this height difference is 50%.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 11
2.8. VRV - piso 5 - RHXYQ18AYL
Capacity data at conditions and connection ratio (125%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tdis C Tmp H Rq HC Max HC Tdis H Airflow
°C BTU/h BTU/h BTU/h BTU/h °C °C °C BTU/h BTU/h °C cfm
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-04 FXDQ32PDVE 24.0 / 17.0 n/a 10748 n/a 7626 6.0 10.4 20.0 n/a 13649 44.4 283
ATI-04 FXDQ32PDVE 24.0 / 17.0 n/a 10748 n/a 7626 6.0 10.4 20.0 n/a 13649 44.4 283
ATI-04 FXDQ32PDVE 24.0 / 17.0 n/a 10748 n/a 7626 6.0 10.4 20.0 n/a 13649 44.4 283
ATI-04 FXDQ32PDVE 24.0 / 17.0 n/a 10748 n/a 7626 6.0 10.4 20.0 n/a 13649 44.4 283
ATI-04 FXDQ32PDVE 24.0 / 17.0 n/a 10748 n/a 7626 6.0 10.4 20.0 n/a 13649 44.4 283
ATI-04 FXDQ32PDVE 24.0 / 17.0 n/a 10748 n/a 7626 6.0 10.4 20.0 n/a 13649 44.4 283
ATI-05 FXDQ50NDVE 24.0 / 17.0 n/a 16548 n/a 12233 6.0 10.0 20.0 n/a 21496 44.6 441

Required cooling capacity towards the outdoor unit: 189708BTU/h.


Required heating capacity towards the outdoor unit: 245333BTU/h.
The sum of the required indoor unit capacities is 189708BTU/h for cooling and 245333BTU/h for heating.
However, the outdoor unit selection uses reduced load values for cooling of 170737BTU/h (= -10%) and for heating
of 220800BTU/h (= -10%).
Be aware that unrealistic reductions may lead to reduced comfort levels, different noise levels or increased wear
and tear.

The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest
temperature in case of heating mode), assuming the indoor unit is running at full load at the given indoor
temperature design conditions. In practice the discharge temperature will modulate based on actual capacity
requirements and during defrost mode (heating mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a
thermal comfort level.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 12
Name Sound PS MCA WxHxD Wght
dBA A mm kg
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-04 24-28 220V 1ph 0.9 700×200×620 23
ATI-04 24-28 220V 1ph 0.9 700×200×620 23
ATI-04 24-28 220V 1ph 0.9 700×200×620 23
ATI-04 24-28 220V 1ph 0.9 700×200×620 23
ATI-04 24-28 220V 1ph 0.9 700×200×620 23
ATI-04 24-28 220V 1ph 0.9 700×200×620 23
ATI-05 27-33 220V 1ph 1.3 900×200×620 28

Outdoor unit placed 9.0m above the indoor units.


The minimum connection ratio for this height difference is 50%.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 13
2.9. VRV - piso 6 - RHXYQ18AYL
Capacity data at conditions and connection ratio (125%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tdis C Tmp H Rq HC Max HC Tdis H Airflow
°C BTU/h BTU/h BTU/h BTU/h °C °C °C BTU/h BTU/h °C cfm
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-04 FXDQ32PDVE 24.0 / 17.0 n/a 10748 n/a 7626 6.0 10.4 20.0 n/a 13649 44.4 283
ATI-04 FXDQ32PDVE 24.0 / 17.0 n/a 10748 n/a 7626 6.0 10.4 20.0 n/a 13649 44.4 283
ATI-04 FXDQ32PDVE 24.0 / 17.0 n/a 10748 n/a 7626 6.0 10.4 20.0 n/a 13649 44.4 283
ATI-04 FXDQ32PDVE 24.0 / 17.0 n/a 10748 n/a 7626 6.0 10.4 20.0 n/a 13649 44.4 283
ATI-04 FXDQ32PDVE 24.0 / 17.0 n/a 10748 n/a 7626 6.0 10.4 20.0 n/a 13649 44.4 283
ATI-04 FXDQ32PDVE 24.0 / 17.0 n/a 10748 n/a 7626 6.0 10.4 20.0 n/a 13649 44.4 283
ATI-05 FXDQ50NDVE 24.0 / 17.0 n/a 16548 n/a 12233 6.0 10.0 20.0 n/a 21496 44.6 441

Required cooling capacity towards the outdoor unit: 189708BTU/h.


Required heating capacity towards the outdoor unit: 245333BTU/h.
The sum of the required indoor unit capacities is 189708BTU/h for cooling and 245333BTU/h for heating.
However, the outdoor unit selection uses reduced load values for cooling of 170737BTU/h (= -10%) and for heating
of 220800BTU/h (= -10%).
Be aware that unrealistic reductions may lead to reduced comfort levels, different noise levels or increased wear
and tear.

The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest
temperature in case of heating mode), assuming the indoor unit is running at full load at the given indoor
temperature design conditions. In practice the discharge temperature will modulate based on actual capacity
requirements and during defrost mode (heating mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a
thermal comfort level.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 14
Name Sound PS MCA WxHxD Wght
dBA A mm kg
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-04 24-28 220V 1ph 0.9 700×200×620 23
ATI-04 24-28 220V 1ph 0.9 700×200×620 23
ATI-04 24-28 220V 1ph 0.9 700×200×620 23
ATI-04 24-28 220V 1ph 0.9 700×200×620 23
ATI-04 24-28 220V 1ph 0.9 700×200×620 23
ATI-04 24-28 220V 1ph 0.9 700×200×620 23
ATI-05 27-33 220V 1ph 1.3 900×200×620 28

Outdoor unit placed 6.0m above the indoor units.


The minimum connection ratio for this height difference is 50%.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 15
2.10. VRV - piso 7 - RHXYQ18AYL
Capacity data at conditions and connection ratio (125%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tdis C Tmp H Rq HC Max HC Tdis H Airflow
°C BTU/h BTU/h BTU/h BTU/h °C °C °C BTU/h BTU/h °C cfm
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-03 FXDQ25PDVE 24.0 / 17.0 n/a 8359 n/a 6589 6.0 12.2 20.0 n/a 10919 39.5 283
ATI-04 FXDQ32PDVE 24.0 / 17.0 n/a 10748 n/a 7626 6.0 10.4 20.0 n/a 13649 44.4 283
ATI-04 FXDQ32PDVE 24.0 / 17.0 n/a 10748 n/a 7626 6.0 10.4 20.0 n/a 13649 44.4 283
ATI-04 FXDQ32PDVE 24.0 / 17.0 n/a 10748 n/a 7626 6.0 10.4 20.0 n/a 13649 44.4 283
ATI-04 FXDQ32PDVE 24.0 / 17.0 n/a 10748 n/a 7626 6.0 10.4 20.0 n/a 13649 44.4 283
ATI-04 FXDQ32PDVE 24.0 / 17.0 n/a 10748 n/a 7626 6.0 10.4 20.0 n/a 13649 44.4 283
ATI-04 FXDQ32PDVE 24.0 / 17.0 n/a 10748 n/a 7626 6.0 10.4 20.0 n/a 13649 44.4 283
ATI-05 FXDQ50NDVE 24.0 / 17.0 n/a 16548 n/a 12233 6.0 10.0 20.0 n/a 21496 44.6 441

Required cooling capacity towards the outdoor unit: 189708BTU/h.


Required heating capacity towards the outdoor unit: 245333BTU/h.
The sum of the required indoor unit capacities is 189708BTU/h for cooling and 245333BTU/h for heating.
However, the outdoor unit selection uses reduced load values for cooling of 170737BTU/h (= -10%) and for heating
of 220800BTU/h (= -10%).
Be aware that unrealistic reductions may lead to reduced comfort levels, different noise levels or increased wear
and tear.

The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest
temperature in case of heating mode), assuming the indoor unit is running at full load at the given indoor
temperature design conditions. In practice the discharge temperature will modulate based on actual capacity
requirements and during defrost mode (heating mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a
thermal comfort level.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 16
Name Sound PS MCA WxHxD Wght
dBA A mm kg
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-03 23-28 220V 1ph 0.9 700×200×620 23
ATI-04 24-28 220V 1ph 0.9 700×200×620 23
ATI-04 24-28 220V 1ph 0.9 700×200×620 23
ATI-04 24-28 220V 1ph 0.9 700×200×620 23
ATI-04 24-28 220V 1ph 0.9 700×200×620 23
ATI-04 24-28 220V 1ph 0.9 700×200×620 23
ATI-04 24-28 220V 1ph 0.9 700×200×620 23
ATI-05 27-33 220V 1ph 1.3 900×200×620 28

Outdoor unit placed 3.0m above the indoor units.


The minimum connection ratio for this height difference is 50%.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 17
2.11. VRV - azotea - RMXYQ6AVL
Capacity data at conditions and connection ratio (100%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tdis C Tmp H Rq HC Max HC Tdis H Airflow
°C BTU/h BTU/h BTU/h BTU/h °C °C °C BTU/h BTU/h °C cfm
UE - 73 FXMQ140PAVE 24.0 / 17.0 n/a 47597 n/a 36455 6.0 12.7 20.0 n/a 61419 39.1 1624

Required cooling capacity towards the outdoor unit: 47597BTU/h.


Required heating capacity towards the outdoor unit: 61419BTU/h.

The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest
temperature in case of heating mode), assuming the indoor unit is running at full load at the given indoor
temperature design conditions. In practice the discharge temperature will modulate based on actual capacity
requirements and during defrost mode (heating mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a
thermal comfort level.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
UE - 73 43-46 220V 1ph 3.4 1400×300×700 46

Outdoor unit placed at the same level as the indoor units.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 18
2.12. VRV - UMA - RHXYQ50AYL
Capacity data at conditions and connection ratio (96%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tdis C Tmp H Rq HC Max HC Tdis H Airflow
°C BTU/h BTU/h BTU/h BTU/h °C °C °C BTU/h BTU/h °C cfm
UMA - 01 (circuit 1) EKEXV400 32.0 / 24.0 n/a 168901 n/a 113966 6.0 n/a 20.0 n/a 165148 n/a n
UMA - 01 (circuit 2) EKEXV400 32.0 / 24.0 n/a 168901 n/a 113966 6.0 n/a 20.0 n/a 165148 n/a n
UMA - 01 (circuit 3) EKEXV400 32.0 / 24.0 n/a 168901 n/a 113966 6.0 n/a 20.0 n/a 165148 n/a n

Required cooling capacity towards the outdoor unit: 506703BTU/h.

The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest
temperature in case of heating mode), assuming the indoor unit is running at full load at the given indoor
temperature design conditions. In practice the discharge temperature will modulate based on actual capacity
requirements and during defrost mode (heating mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a
thermal comfort level.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
UMA - 01 (circuit 1) 380V 3ph 215×401×78 3 n/a n/a
UMA - 01 (circuit 2) 380V 3ph 215×401×78 3 n/a n/a
UMA - 01 (circuit 3) 380V 3ph 215×401×78 3 n/a n/a

Outdoor unit placed at the same level as the indoor units.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 19
3. Outdoor Unit Details
3.1. Table of Abbreviations
Name Logical name of the device
Model Device model name
▼ Optimized selection: Smaller outdoor model selected than standard proposed model
Tmp C Outdoor temperature in cooling
CC Available cooling capacity
Rq CC Required cooling capacity
Tmp H Outdoor conditions in heating (dry bulb temp. / wet bulb temp.)
HC Available heating capacity (integrated heating capacity)
Rq HC Required heating capacity
Piping Largest distance from indoor unit to outdoor unit
Bse Refr Standard factory refrigerant charge (5m actual piping length)
excluding extra refrigerant charge
For calculation of extra refrigerant charge refer to the databook
Ex Refr Extra refrigerant charge
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
WxHxD WidthxHeightxDepth
Wght Weight of the device

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 20
3.2. Outdoor Details
Name Model Comb Tmp C CC Rq CC Tmp H HC Rq HC
% °C BTU/h BTU/h °C BTU/h BTU/h
VRV - sotano RMXYQ6AVL ▼ 129 29.4 48251 (-10.5%) 53892 17.0 / 11.0 65124 (-5.7%) 69096
VRV - piso 1 RHXYQ24AYL ▼ 123 29.4 213811 (-5.1%) 225243 17.0 / 11.0 294917 290203
VRV - piso 1 extra RMXYQ3AVL 83 29.4 22979 19960 17.0 / 11.0 30549 25591
VRV - piso 2 RHXYQ44AYL ▼ 126 29.4 385277 (-7.5%) 416553 17.0 / 11.0 546276 534956
VRV - piso 3 RHXYQ18AYL ▼ 125 29.4 155091 (-9.2%) 170737 17.0 / 11.0 222413 220800
VRV - piso 4 RHXYQ18AYL ▼ 125 29.4 155167 (-9.1%) 170737 17.0 / 11.0 222413 220800
VRV - piso 5 RHXYQ18AYL ▼ 125 29.4 155242 (-9.1%) 170737 17.0 / 11.0 222413 220800
VRV - piso 6 RHXYQ18AYL ▼ 125 29.4 155318 (-9%) 170737 17.0 / 11.0 222413 220800
VRV - piso 7 RHXYQ18AYL ▼ 125 29.4 155393 (-9%) 170737 17.0 / 11.0 222413 220800
VRV - azotea RMXYQ6AVL ▼ 100 29.4 43973 (-7.6%) 47597 17.0 / 11.0 60840 (-0.9%) 61419
VRV - UMA RHXYQ50AYL 96 34.0 514699 506703 17.0 / 11.0 539119

Name Model Piping Refrigerant


m Type Bse Refr Ex Refr
kg kg
VRV - sotano RMXYQ6AVL 66.3 R410A 3.6 3.9
VRV - piso 1 RHXYQ24AYL 63.0 R410A 13.8 15.6
VRV - piso 1 extra RMXYQ3AVL 17.7 R410A 2.7 0.6
VRV - piso 2 RHXYQ44AYL 58.9 R410A 17.2 24.3
VRV - piso 3 RHXYQ18AYL 62.1 R410A 8.6 13.1
VRV - piso 4 RHXYQ18AYL 62.1 R410A 8.6 13.1
VRV - piso 5 RHXYQ18AYL 62.1 R410A 8.6 13.1
VRV - piso 6 RHXYQ18AYL 62.1 R410A 8.6 13.1
VRV - piso 7 RHXYQ18AYL 62.1 R410A 8.6 13.1
VRV - azotea RMXYQ6AVL 25.0 R410A 3.6 1.4
VRV - UMA RHXYQ50AYL 8.0 R410A 22.4 13.0

Name Model PS MCA WxHxD Wght


A mm kg
VRV - sotano RMXYQ6AVL 220V 1ph 27 900×1345×320 108
VRV - piso 1 RHXYQ24AYL 380V 3ph
× RHXYQ12AYL 24 930×1657×765 213
× RHXYQ12AYL 24 930×1657×765 213
VRV - piso 1 extra RMXYQ3AVL 220V 1ph 16.5 940×990×320 78
VRV - piso 2 RHXYQ44AYL 380V 3ph
× RHXYQ22AYL 46 1240×1657×765 317
× RHXYQ22AYL 46 1240×1657×765 317
VRV - piso 3 RHXYQ18AYL 380V 3ph 34.8 1240×1657×765 317
VRV - piso 4 RHXYQ18AYL 380V 3ph 34.8 1240×1657×765 317
VRV - piso 5 RHXYQ18AYL 380V 3ph 34.8 1240×1657×765 317
VRV - piso 6 RHXYQ18AYL 380V 3ph 34.8 1240×1657×765 317
VRV - piso 7 RHXYQ18AYL 380V 3ph 34.8 1240×1657×765 317
VRV - azotea RMXYQ6AVL 220V 1ph 27 900×1345×320 108
VRV - UMA RHXYQ50AYL 380V 3ph
× RHXYQ22AYL 46 1240×1657×765 317
× RHXYQ16AYL 31 1240×1657×765 285
× RHXYQ12AYL 24 930×1657×765 213

Sufficient distance should be respected between the modules according to the service & operation space rules as
mentioned in the databook.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 21
4. Piping Diagrams
Pipes marked with * in the diagrams must be connected to the device with a reducing joint.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 22
4.1. Piping VRV - sotano

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 23
VRV - sotano
RMXYQ6AVL

35.0m 4.0m
⅜"×¾" * ¼"×½"
KHRP26A22T

ATI-02
FXZQ20MVE
3.2m 4.3m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-02
FXZQ20MVE
3.5m 4.0m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-01
FXZQ20MVE
2.8m 4.3m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-01
FXZQ20MVE
2.7m 4.3m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-01
FXZQ20MVE
2.8m 3.5m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-01
FXZQ20MVE
6.1m 4.0m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-01
FXZQ20MVE
2.3m 1.0m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-02
FXZQ20MVE
3.9m
¼"×½"

ATI-02
FXZQ20MVE

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 24
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 25
4.2. Piping VRV - piso 1

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 26
VRV - piso 1
RHXYQ24AYL
RHXYQ12AYL RHXYQ12AYL

½"×1" ½"×1"

BHFP22P100

32.0m 8.3m 4.2m


⅝"×1⅛" ⅜"×⅞" ⅜"×⅝"
KHRP26A73T + KHRP26A33T
KHRP26M73TP
ATI-10
FXMQ140PAVE
3.5m
⅜"×⅝"

ATI-10
FXMQ140PAVE
3.8m 3.4m 3.8m
⅝"×1⅛" ⅜"×⅝" ¼"×½"
KHRP26A72T KHRP26A22T

ATI-01
FXZQ20MVE
1.8m 2.2m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-01
FXZQ20MVE
5.8m
⅜"×⅝"

ATI-08
FXMQ100PAVE
11.1m 4.2m 1.8m
½"×1⅛" ⅜"×⅝" ¼"×½"
KHRP26A72T KHRP26A22T

ATI-01
FXZQ20MVE
4.5m
¼"×½"

ATI-01
FXZQ20MVE
3.5m 1.3m
⅜"×⅞" ⅜"×⅝"
KHRP26A33T

ATI-10
FXMQ140PAVE
10.6m
⅜"×⅝"

ATI-10
FXMQ140PAVE

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 27
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 28
4.3. Piping VRV - piso 1 extra
VRV - piso 1 extra
RMXYQ3AVL

2.0m 2.5m 0.5m


⅜"×⅝" ⅜"×⅝" ¼"×½"
KHRP26A22T KHRP26A22T

UI-01
FXAQ20PVE
1.0m
¼"×½"

UI-01
FXAQ20PVE
15.2m
¼"×½"

UE - 76
FXZQ20MVE

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 29
4.4. Piping VRV - piso 2

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 30
VRV - piso 2
RHXYQ44AYL
RHXYQ22AYL RHXYQ22AYL

⅝"×1⅛" ⅝"×1⅛"

BHFP22P100

25.0m 3.0m 9.0m


¾"×1½" ¾"×1¼" ⅜"×⅝"
KHRP26A73T + KHRP26A73T +
KHRP26M73TP KHRP26M73TP
ATI-07
FXMQ80PAVE
1.6m 2.2m
⅝"×1⅛" ⅜"×¾"
KHRP26A72T

ATI-11
FXMQ200MAVE
1.3m 6.0m
½"×1⅛" ⅜"×⅝"
KHRP26A72T

ATI-10
FXMQ140PAVE
1.0m 2.7m
⅜"×⅞" ⅜"×⅝"
KHRP26A33T

ATI-07
FXMQ80PAVE
7.4m
⅜"×⅝"

ATI-10
FXMQ140PAVE
1.3m 3.5m
¾"×1¼" ¼"×½"
KHRP26A73T +
KHRP26M73TP
ATI-06
FXMQ25PAVE
1.6m 1.7m
¾"×1¼" ⅜"×¾"
KHRP26A73T +
KHRP26M73TP
ATI-11
FXMQ200MAVE
5.5m 3.8m
⅝"×1⅛" ⅜"×¾"
KHRP26A72T

ATI-11
FXMQ200MAVE
6.3m 8.2m
½"×1⅛" ⅜"×⅝"
KHRP26A72T

ATI-08
FXMQ100PAVE
1.5m 3.8m 1.5m
⅜"×⅞" ⅜"×⅝" ¼"×½"
KHRP26A33T KHRP26A22T

ATI-01
FXZQ20MVE
5.2m
⅜"×⅝"

ATI-08
FXMQ100PAVE
14.7m
⅜"×⅝"

ATI-08
FXMQ100PAVE

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 31
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 32
4.5. Piping VRV - piso 3

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 33
VRV - piso 3
RHXYQ18AYL

20.0m 1.2m 2.5m


⅝"×1⅛" ⅜"×¾" ¼"×½"
KHRP26A72T KHRP26A22T

ATI-03
FXDQ25PDVE
5.5m 2.6m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-04
FXDQ32PDVE
1.6m 3.1m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-03
FXDQ25PDVE
1.0m 2.7m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-03
FXDQ25PDVE
4.4m 2.9m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-03
FXDQ25PDVE
4.3m
¼"×½"

ATI-04
FXDQ32PDVE
1.3m 2.6m
½"×1⅛" ¼"×½"
KHRP26A72T

ATI-04
FXDQ32PDVE
5.5m 2.8m
½"×1⅛" ¼"×½"
KHRP26A72T

ATI-03
FXDQ25PDVE
1.0m 3.2m
½"×1⅛" ¼"×½"
KHRP26A72T

ATI-03
FXDQ25PDVE
1.6m 2.7m
½"×1⅛" ¼"×½"
KHRP26A72T

ATI-04
FXDQ32PDVE
1.1m 3.0m
⅜"×⅞" ¼"×½"
KHRP26A33T

ATI-03
FXDQ25PDVE
4.3m 2.9m
⅜"×⅞" ¼"×½"
KHRP26A33T

ATI-03
FXDQ25PDVE
1.0m 3.0m
⅜"×⅞" ¼"×½"
KHRP26A33T

ATI-03
FXDQ25PDVE
1.6m 2.9m
⅜"×⅞" ¼"×½"
KHRP26A33T

ATI-04
FXDQ32PDVE
1.0m 3.0m
⅜"×¾" ¼"×½"
KHRP26A22T

ATI-03
FXDQ25PDVE
4.4m 2.8m
⅜"×¾" ¼"×½"
KHRP26A22T

ATI-03
FXDQ25PDVE
2.4m 3.0m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-04
FXDQ32PDVE
1.0m 2.7m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-05
FXDQ50NDVE
4.6m 3.0m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-03
FXDQ25PDVE
4.3m
¼"×½"

ATI-03
FXDQ25PDVE

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 34
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 35
4.6. Piping VRV - piso 4

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 36
VRV - piso 4
RHXYQ18AYL

20.0m 1.2m 2.5m


⅝"×1⅛" ⅜"×¾" ¼"×½"
KHRP26A72T KHRP26A22T

ATI-03
FXDQ25PDVE
5.5m 2.6m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-04
FXDQ32PDVE
1.6m 3.1m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-03
FXDQ25PDVE
1.0m 2.7m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-03
FXDQ25PDVE
4.4m 2.9m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-03
FXDQ25PDVE
4.3m
¼"×½"

ATI-04
FXDQ32PDVE
1.3m 2.6m
½"×1⅛" ¼"×½"
KHRP26A72T

ATI-04
FXDQ32PDVE
5.5m 2.8m
½"×1⅛" ¼"×½"
KHRP26A72T

ATI-03
FXDQ25PDVE
1.0m 3.2m
½"×1⅛" ¼"×½"
KHRP26A72T

ATI-03
FXDQ25PDVE
1.6m 2.7m
½"×1⅛" ¼"×½"
KHRP26A72T

ATI-04
FXDQ32PDVE
1.1m 3.0m
⅜"×⅞" ¼"×½"
KHRP26A33T

ATI-03
FXDQ25PDVE
4.3m 2.9m
⅜"×⅞" ¼"×½"
KHRP26A33T

ATI-03
FXDQ25PDVE
1.0m 3.0m
⅜"×⅞" ¼"×½"
KHRP26A33T

ATI-03
FXDQ25PDVE
1.6m 2.9m
⅜"×⅞" ¼"×½"
KHRP26A33T

ATI-04
FXDQ32PDVE
1.0m 3.0m
⅜"×¾" ¼"×½"
KHRP26A22T

ATI-03
FXDQ25PDVE
4.4m 2.8m
⅜"×¾" ¼"×½"
KHRP26A22T

ATI-03
FXDQ25PDVE
2.4m 3.0m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-04
FXDQ32PDVE
1.0m 2.7m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-05
FXDQ50NDVE
4.6m 3.0m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-03
FXDQ25PDVE
4.3m
¼"×½"

ATI-03
FXDQ25PDVE

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 37
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 38
4.7. Piping VRV - piso 5

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 39
VRV - piso 5
RHXYQ18AYL

20.0m 1.2m 2.5m


⅝"×1⅛" ⅜"×¾" ¼"×½"
KHRP26A72T KHRP26A22T

ATI-03
FXDQ25PDVE
5.5m 2.6m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-04
FXDQ32PDVE
1.6m 3.1m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-03
FXDQ25PDVE
1.0m 2.7m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-03
FXDQ25PDVE
4.4m 2.9m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-03
FXDQ25PDVE
4.3m
¼"×½"

ATI-04
FXDQ32PDVE
1.3m 2.6m
½"×1⅛" ¼"×½"
KHRP26A72T

ATI-04
FXDQ32PDVE
5.5m 2.8m
½"×1⅛" ¼"×½"
KHRP26A72T

ATI-03
FXDQ25PDVE
1.0m 3.2m
½"×1⅛" ¼"×½"
KHRP26A72T

ATI-03
FXDQ25PDVE
1.6m 2.7m
½"×1⅛" ¼"×½"
KHRP26A72T

ATI-04
FXDQ32PDVE
1.1m 3.0m
⅜"×⅞" ¼"×½"
KHRP26A33T

ATI-03
FXDQ25PDVE
4.3m 2.9m
⅜"×⅞" ¼"×½"
KHRP26A33T

ATI-03
FXDQ25PDVE
1.0m 3.0m
⅜"×⅞" ¼"×½"
KHRP26A33T

ATI-03
FXDQ25PDVE
1.6m 2.9m
⅜"×⅞" ¼"×½"
KHRP26A33T

ATI-04
FXDQ32PDVE
1.0m 3.0m
⅜"×¾" ¼"×½"
KHRP26A22T

ATI-03
FXDQ25PDVE
4.4m 2.8m
⅜"×¾" ¼"×½"
KHRP26A22T

ATI-03
FXDQ25PDVE
2.4m 3.0m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-04
FXDQ32PDVE
1.0m 2.7m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-05
FXDQ50NDVE
4.6m 3.0m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-03
FXDQ25PDVE
4.3m
¼"×½"

ATI-03
FXDQ25PDVE

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 40
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 41
4.8. Piping VRV - piso 6

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 42
VRV - piso 6
RHXYQ18AYL

20.0m 1.2m 2.5m


⅝"×1⅛" ⅜"×¾" ¼"×½"
KHRP26A72T KHRP26A22T

ATI-03
FXDQ25PDVE
5.5m 2.6m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-04
FXDQ32PDVE
1.6m 3.1m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-03
FXDQ25PDVE
1.0m 2.7m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-03
FXDQ25PDVE
4.4m 2.9m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-03
FXDQ25PDVE
4.3m
¼"×½"

ATI-04
FXDQ32PDVE
1.3m 2.6m
½"×1⅛" ¼"×½"
KHRP26A72T

ATI-04
FXDQ32PDVE
5.5m 2.8m
½"×1⅛" ¼"×½"
KHRP26A72T

ATI-03
FXDQ25PDVE
1.0m 3.2m
½"×1⅛" ¼"×½"
KHRP26A72T

ATI-03
FXDQ25PDVE
1.6m 2.7m
½"×1⅛" ¼"×½"
KHRP26A72T

ATI-04
FXDQ32PDVE
1.1m 3.0m
⅜"×⅞" ¼"×½"
KHRP26A33T

ATI-03
FXDQ25PDVE
4.3m 2.9m
⅜"×⅞" ¼"×½"
KHRP26A33T

ATI-03
FXDQ25PDVE
1.0m 3.0m
⅜"×⅞" ¼"×½"
KHRP26A33T

ATI-03
FXDQ25PDVE
1.6m 2.9m
⅜"×⅞" ¼"×½"
KHRP26A33T

ATI-04
FXDQ32PDVE
1.0m 3.0m
⅜"×¾" ¼"×½"
KHRP26A22T

ATI-03
FXDQ25PDVE
4.4m 2.8m
⅜"×¾" ¼"×½"
KHRP26A22T

ATI-03
FXDQ25PDVE
2.4m 3.0m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-04
FXDQ32PDVE
1.0m 2.7m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-05
FXDQ50NDVE
4.6m 3.0m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-03
FXDQ25PDVE
4.3m
¼"×½"

ATI-03
FXDQ25PDVE

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 43
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 44
4.9. Piping VRV - piso 7

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 45
VRV - piso 7
RHXYQ18AYL

20.0m 1.2m 2.5m


⅝"×1⅛" ⅜"×¾" ¼"×½"
KHRP26A72T KHRP26A22T

ATI-03
FXDQ25PDVE
5.5m 2.6m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-04
FXDQ32PDVE
1.6m 3.1m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-03
FXDQ25PDVE
1.0m 2.7m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-03
FXDQ25PDVE
4.4m 2.9m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-03
FXDQ25PDVE
4.3m
¼"×½"

ATI-04
FXDQ32PDVE
1.3m 2.6m
½"×1⅛" ¼"×½"
KHRP26A72T

ATI-04
FXDQ32PDVE
5.5m 2.8m
½"×1⅛" ¼"×½"
KHRP26A72T

ATI-03
FXDQ25PDVE
1.0m 3.2m
½"×1⅛" ¼"×½"
KHRP26A72T

ATI-03
FXDQ25PDVE
1.6m 2.7m
½"×1⅛" ¼"×½"
KHRP26A72T

ATI-04
FXDQ32PDVE
1.1m 3.0m
⅜"×⅞" ¼"×½"
KHRP26A33T

ATI-03
FXDQ25PDVE
4.3m 2.9m
⅜"×⅞" ¼"×½"
KHRP26A33T

ATI-03
FXDQ25PDVE
1.0m 3.0m
⅜"×⅞" ¼"×½"
KHRP26A33T

ATI-03
FXDQ25PDVE
1.6m 2.9m
⅜"×⅞" ¼"×½"
KHRP26A33T

ATI-04
FXDQ32PDVE
1.0m 3.0m
⅜"×¾" ¼"×½"
KHRP26A22T

ATI-03
FXDQ25PDVE
4.4m 2.8m
⅜"×¾" ¼"×½"
KHRP26A22T

ATI-03
FXDQ25PDVE
2.4m 3.0m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-04
FXDQ32PDVE
1.0m 2.7m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-05
FXDQ50NDVE
4.6m 3.0m
⅜"×⅝" ¼"×½"
KHRP26A22T

ATI-03
FXDQ25PDVE
4.3m
¼"×½"

ATI-03
FXDQ25PDVE

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 46
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 47
4.10. Piping VRV - azotea
VRV - azotea
RMXYQ6AVL

25.0m
⅜"×¾"

UE - 73
FXMQ140PAVE

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 48
4.11. Piping VRV - UMA
VRV - UMA
RHXYQ50AYL
RHXYQ22AYL RHXYQ16AYL RHXYQ12AYL

⅝"×1⅛" ½"×1⅛" ½"×1"


¾"×1¼"
BHFP22P151

6.0m 1.0m
¾"×1½" ½"×1⅛"
KHRP26A73T +
KHRP26M73TP
UMA - 01 (circuit 1)
EKEXV400
0.5m 0.5m
¾"×1¼" ½"×1⅛"
KHRP26A73T +
KHRP26M73TP
UMA - 01 (circuit 2)
EKEXV400
0.5m
½"×1⅛"

UMA - 01 (circuit 3)
EKEXV400

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 49
5. Wiring Diagrams
P1P2 = Please select the cable type and size in accordance with the databook.
F1F2 = Please select the cable type and size in accordance with the databook.

5.1. Wiring VRV - sotano


P1,P2
VRV - sotano ATI-02 BRC1E63
RMXYQ6AVL FXZQ20MVE
IN F1,F2 F1,F2 L, N 0.8A 1ph

L,N 27A 1ph


P1,P2
ATI-02 BRC1E63
FXZQ20MVE
F1,F2 L, N 0.8A 1ph

P1,P2
ATI-01 BRC1E63
FXZQ20MVE
F1,F2 L, N 0.8A 1ph

P1,P2
ATI-01 BRC1E63
FXZQ20MVE
F1,F2 L, N 0.8A 1ph

P1,P2
ATI-01 BRC1E63
FXZQ20MVE
F1,F2 L, N 0.8A 1ph

P1,P2
ATI-01 BRC1E63
FXZQ20MVE
F1,F2 L, N 0.8A 1ph

P1,P2
ATI-01 BRC1E63
FXZQ20MVE
F1,F2 L, N 0.8A 1ph

P1,P2
ATI-02 BRC1E63
FXZQ20MVE
F1,F2 L, N 0.8A 1ph

P1,P2
ATI-02 BRC1E63
FXZQ20MVE
F1,F2 L, N 0.8A 1ph

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 50
5.2. Wiring VRV - piso 1
P1,P2
VRV - piso 1 ATI-10 BRC1E63
RHXYQ24AYL FXMQ140PAVE
IN F1,F2 F1,F2 L, N 3.4A 1ph
RHXYQ12AYL
Q1,Q2 L1,L2,L3,N P1,P2
ATI-10 BRC1E63
24A 3ph
FXMQ140PAVE
RHXYQ12AYL F1,F2 L, N 3.4A 1ph
Q1,Q2 L1,L2,L3,N
24A 3ph P1,P2
ATI-01 BRC1E63
FXZQ20MVE
F1,F2 L, N 0.8A 1ph

P1,P2
ATI-01 BRC1E63
FXZQ20MVE
F1,F2 L, N 0.8A 1ph

P1,P2
ATI-08 BRC1E63
FXMQ100PAVE
F1,F2 L, N 2.9A 1ph

P1,P2
ATI-01 BRC1E63
FXZQ20MVE
F1,F2 L, N 0.8A 1ph

P1,P2
ATI-01 BRC1E63
FXZQ20MVE
F1,F2 L, N 0.8A 1ph

P1,P2
ATI-10 BRC1E63
FXMQ140PAVE
F1,F2 L, N 3.4A 1ph

P1,P2
ATI-10 BRC1E63
FXMQ140PAVE
F1,F2 L, N 3.4A 1ph

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 51
5.3. Wiring VRV - piso 1 extra
P1,P2
VRV - piso 1 extra UI-01 BRC1E63
RMXYQ3AVL FXAQ20PVE
IN F1,F2 F1,F2 L, N 0.3A 1ph

L,N 16.5A 1ph


P1,P2
UI-01 BRC1E63
FXAQ20PVE
F1,F2 L, N 0.3A 1ph

P1,P2
UE - 76 BRC1E63
FXZQ20MVE
F1,F2 L, N 0.8A 1ph

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 52
5.4. Wiring VRV - piso 2
P1,P2
VRV - piso 2 ATI-07 BRC1E63
RHXYQ44AYL FXMQ80PAVE
IN F1,F2 F1,F2 L, N 2.3A 1ph
RHXYQ22AYL
Q1,Q2 L1,L2,L3,N P1,P2
ATI-11 BRC1E63
46A 3ph
FXMQ200MAVE
RHXYQ22AYL F1,F2 L, N 9A 1ph
Q1,Q2 L1,L2,L3,N
46A 3ph P1,P2
ATI-10 BRC1E63
FXMQ140PAVE
F1,F2 L, N 3.4A 1ph

P1,P2
ATI-07 BRC1E63
FXMQ80PAVE
F1,F2 L, N 2.3A 1ph

P1,P2
ATI-10 BRC1E63
FXMQ140PAVE
F1,F2 L, N 3.4A 1ph

P1,P2
ATI-06 BRC1E63
FXMQ25PAVE
F1,F2 L, N 0.6A 1ph

P1,P2
ATI-11 BRC1E63
FXMQ200MAVE
F1,F2 L, N 9A 1ph

P1,P2
ATI-11 BRC1E63
FXMQ200MAVE
F1,F2 L, N 9A 1ph

P1,P2
ATI-08 BRC1E63
FXMQ100PAVE
F1,F2 L, N 2.9A 1ph

P1,P2
ATI-01 BRC1E63
FXZQ20MVE
F1,F2 L, N 0.8A 1ph

P1,P2
ATI-08 BRC1E63
FXMQ100PAVE
F1,F2 L, N 2.9A 1ph

P1,P2
ATI-08 BRC1E63
FXMQ100PAVE
F1,F2 L, N 2.9A 1ph

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 53
5.5. Wiring VRV - piso 3

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 54
P1,P2
VRV - piso 3 ATI-03 BRC1E63
RHXYQ18AYL FXDQ25PDVE
IN F1,F2 F1,F2 L, N 0.9A 1ph

L1,L2,L3,N 34.8A 3ph


P1,P2
ATI-04 BRC1E63
FXDQ32PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-04 BRC1E63
FXDQ32PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-04 BRC1E63
FXDQ32PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-04 BRC1E63
FXDQ32PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-04 BRC1E63
FXDQ32PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-04 BRC1E63
FXDQ32PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-05 BRC1E63
FXDQ50NDVE
F1,F2 L, N 1.3A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 55
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 56
5.6. Wiring VRV - piso 4

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 57
P1,P2
VRV - piso 4 ATI-03 BRC1E63
RHXYQ18AYL FXDQ25PDVE
IN F1,F2 F1,F2 L, N 0.9A 1ph

L1,L2,L3,N 34.8A 3ph


P1,P2
ATI-04 BRC1E63
FXDQ32PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-04 BRC1E63
FXDQ32PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-04 BRC1E63
FXDQ32PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-04 BRC1E63
FXDQ32PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-04 BRC1E63
FXDQ32PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-04 BRC1E63
FXDQ32PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-05 BRC1E63
FXDQ50NDVE
F1,F2 L, N 1.3A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 58
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 59
5.7. Wiring VRV - piso 5

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 60
P1,P2
VRV - piso 5 ATI-03 BRC1E63
RHXYQ18AYL FXDQ25PDVE
IN F1,F2 F1,F2 L, N 0.9A 1ph

L1,L2,L3,N 34.8A 3ph


P1,P2
ATI-04 BRC1E63
FXDQ32PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-04 BRC1E63
FXDQ32PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-04 BRC1E63
FXDQ32PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-04 BRC1E63
FXDQ32PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-04 BRC1E63
FXDQ32PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-04 BRC1E63
FXDQ32PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-05 BRC1E63
FXDQ50NDVE
F1,F2 L, N 1.3A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 61
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 62
5.8. Wiring VRV - piso 6

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 63
P1,P2
VRV - piso 6 ATI-03 BRC1E63
RHXYQ18AYL FXDQ25PDVE
IN F1,F2 F1,F2 L, N 0.9A 1ph

L1,L2,L3,N 34.8A 3ph


P1,P2
ATI-04 BRC1E63
FXDQ32PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-04 BRC1E63
FXDQ32PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-04 BRC1E63
FXDQ32PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-04 BRC1E63
FXDQ32PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-04 BRC1E63
FXDQ32PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-04 BRC1E63
FXDQ32PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-05 BRC1E63
FXDQ50NDVE
F1,F2 L, N 1.3A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 64
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 65
5.9. Wiring VRV - piso 7

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 66
P1,P2
VRV - piso 7 ATI-03 BRC1E63
RHXYQ18AYL FXDQ25PDVE
IN F1,F2 F1,F2 L, N 0.9A 1ph

L1,L2,L3,N 34.8A 3ph


P1,P2
ATI-04 BRC1E63
FXDQ32PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-04 BRC1E63
FXDQ32PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-04 BRC1E63
FXDQ32PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-04 BRC1E63
FXDQ32PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-04 BRC1E63
FXDQ32PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-04 BRC1E63
FXDQ32PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-05 BRC1E63
FXDQ50NDVE
F1,F2 L, N 1.3A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph

P1,P2
ATI-03 BRC1E63
FXDQ25PDVE
F1,F2 L, N 0.9A 1ph
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 67
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 68
5.10. Wiring VRV - azotea
P1,P2
VRV - azotea UE - 73 BRC1E63
RMXYQ6AVL FXMQ140PAVE
IN F1,F2 F1,F2 L, N 3.4A 1ph

L,N 27A 1ph

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 69
5.11. Wiring VRV - UMA
VRV - UMA UMA - 01
RHXYQ50AYL EKEQFCBA
IN F1,F2 F1,F2 (circuit 1)
6×0.75
RHXYQ22AYL EKEXV400
Q1,Q2 L1,L2,L3,N
UMA - 01
46A 3ph
EKEQFCBA
RHXYQ16AYL F1,F2 (circuit 2)
6×0.75
Q1,Q2 L1,L2,L3,N EKEXV400
31A 3ph
UMA - 01
RHXYQ12AYL EKEQFCBA
Q1,Q2 L1,L2,L3,N F1,F2 (circuit 3)
24A 3ph 6×0.75
EKEXV400

For more details about the wiring towards the AHU, please refer to the installation manual.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 70
6. Device Options
6.1. Outdoor Unit Options
Model Description Used by
BHFP22P151 Outdoor unit multi connection piping kit VRV - UMA [RHXYQ50AYL]
BHFP22P100 Outdoor unit multi connection piping kit VRV - piso 2 [RHXYQ44AYL] VRV - piso 1 [RHXYQ24AYL]

6.2. Indoor Unit Options


Model Description Used by
BYFQ60B3W1 Decoration panel ATI-02 [FXZQ20MVE] ATI-02 [FXZQ20MVE] ATI-01 [FXZQ20MVE]
ATI-01 [FXZQ20MVE] ATI-01 [FXZQ20MVE] ATI-01 [FXZQ20MVE]
ATI-01 [FXZQ20MVE] ATI-02 [FXZQ20MVE] ATI-02 [FXZQ20MVE]
ATI-01 [FXZQ20MVE] ATI-01 [FXZQ20MVE] ATI-01 [FXZQ20MVE]
ATI-01 [FXZQ20MVE] ATI-01 [FXZQ20MVE] UE - 76 [FXZQ20MVE]

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 71