ENS-EL-SCH - 0002 Cable Schedule 000
ENS-EL-SCH - 0002 Cable Schedule 000
SANITARY SEWER
SYSTEM TREATMENT
UNIT
Cable Schedule
STP-001
ORIGINATOR
ENS-EL-SCH-0002 000
CABLE SCHEDULE
Description
( Destination from the
N Size Manufacturer Type Tag Name L
equipment to control
Panel )
1 POWER CABLE
Lifting Pump 1.5 HP DOL CU/XLPE/SWA 0.6KV/1KV-
1.2 4X4MM2 2M KABLO 6M
(P1A) 1119 Watt /PVC STP-001-02
Lifting Pump 1.5 HP DOL CU/XLPE/SWA 0.6KV/1KV-
1.3 4X4MM2 2M KABLO 6M
(P1B) 1119 Watt /PVC STP-001-03
Buffer Tank Pump 1.5 HP CU/XLPE/SWA 0.6KV/1KV-
1.4 4X4MM2 2M KABLO 5M
DOL 1119 Watt (P2A) /PVC STP-001-04
Buffer Tank Pump 1.5 HP CU/XLPE/SWA 0.6KV/1KV-
1.5 4X4MM2 2M KABLO 5M
DOL 1119 Watt (P2B) /PVC STP-001-05
Out Flow Of RBC Pump
CU/XLPE/SWA 0.6KV/1KV-
1.6 746 Watt 4X4MM2 2M KABLO 15M
/PVC STP-001-06
1 HP DOL (P3)
Outflow of screen Filter
CU/XLPE/SWA 0.6KV/1KV-
1.7 Pump 746 Watt 4X4MM2 2M KABLO 3M
/PVC STP-001-07
1 HP DOL (P4)
SAND Filter Backwash
CU/XLPE/SWA 0.6KV/1KV-
1.8 746 Watt 4X4MM2 2M KABLO 4M
/PVC STP-001-08
Pump 1 HP DOL (P5)
Treated Pump 2HP DOL CU/XLPE/SWA 0.6KV/1KV-
1.9 4X4MM2 2M KABLO 12M
1492 Watt (P6A) /PVC STP-001-09
Treated Pump 2HP DOL CU/XLPE/SWA 0.6KV/1KV-
1.10 4X4MM2 2M KABLO 12M
1492 Watt (P6B) /PVC STP-001-10
RBC Unit (biological CU/XLPE/SWA 0.6KV/1KV-
1.11 4X4MM2 2M KABLO 15M
treatment unit) 75 Watt /PVC STP-001-11
DELTA
For lighting for Filters 2PX0.75 CU/XLPE/SWA 0.3KV/0.5KV-
1.12 CROMPTON 4M
Room MM2 /PVC STP-001-12
CABLES
2 CONTROL CABLE
DELTA
Lifting Tank (Low-Hi-Hi Hi 5PX0.75 CU/XLPE/SWA CON-STP001-
2.1 CROMPTON 6M
(LS1-LS2-LS3) MM2 /PVC 01
CABLES
DELTA
2PX0.75 CU/XLPE/SWA CON-STP001-
2.2 Buffer Tank HI LEVEL (LS4) CROMPTON 5M
MM2 /PVC 02
CABLES
DELTA
Treated Tank (Low-Hi-Hi 5PX0.75 CU/XLPE/SWA CON-STP001-
2.3 CROMPTON 12M
Hi (LS1-LS2-LS3) MM2 /PVC 03
CABLES
DELTA
2PX0.75 CU/XLPE/SWA CON-STP001-
2.4 Pressure Switch CROMPTON 5M
MM2 /PVC 04
CABLES
DELTA
2PX0.75 CU/XLPE/SWA CON-STP001-
2.5 Sand filter CROMPTON 5M
MM2 /PVC 05
CABLES
BASIN 3 LIQUID BULK TERMINAL,Sokhna Port, Egypt
Contract No. PD-0113.018-2
Pump - Outflow of
P3 1 STP-001-P-003 Ebara JESXM 5
RBC unit
Pump -Outflow of
P4 1 STP-001-P-004 Ebara JESXM 5
Screens filter
pumps - Treated
P6A –P6B 2 STP-001-P-006A/B IMPO SK404
effluent water
Control WS1
Sand filter 1 STP-001-S-002
head: Clack
Dossi-3
Appendix A
DATA SHEET
FireKab 2M400
Construction
Plain annealed stranded copper wires (IEC/EN 228, HD 383, BS 6360, VDE0295
Conductor
Class 2)
Flame Barrier Mica tape
Insulation XLPE
Core Identification 4 Cores: Red – Black – Yellow - Blue
Lay-up Cores stranded together
Bedding LSOH, Black (RAL 9005)
Armour Single layer of round galvanized steel wire
Halogen free flame retardant compound (HFFR/LSZH/LSOH/FRNC) (EN 50290-2,
Sheath
VDE 0207 HM2, BS 7655 LTS1/LTS3), Red
Reference Standard BS 7846
Page 1 / 2
DATA SHEET
Cores / Size Contuctor Insulation Cable
(Cu) Thickness Diameter
(mm²) (stranded) (nom.mm) (mm)(±10%)
4x2.5 7x0,66 mm 0,7 16,2
4x4 7x0,83 mm 0,7 17,4
4x6 7x1,02 mm 0,7 119,7
4x10 7x1,37 mm 0,7 21,5
4x16 7x1,80 mm 0,7 23,9
4x25 7x2,19 mm 0,9 29,3
4x35 7x2,55 mm 0,9 31,9
4x50 7x3.0 mm 1 36
Cable Marking:
Fire Resistant Cable 2MKABLO LOT NO-01 - P/N :3P22B375001-06A FireKab 2M400 4x2.5 mm² 0.6/1 kV LSOH EC60331 BS 6387 CWZ
CE RoHS Month/Year meter mark
Fire Resistant Cable 2MKABLO LOT NO-01 - P/N :3P22B375002-06A FireKab 2M400 4x4 mm² 0.6/1 kV LSOH IEC60331 BS 6387 CWZ CE
RoHS Month/Year meter mark
Fire Resistant Cable 2MKABLO LOT NO-01 - P/N :3P22B375003-06A FireKab 2M400 4x6 mm² 0.6/1 kV LSOH IEC60331 BS 6387 CWZ CE
RoHS Month/Year meter mark
Fire Resistant Cable 2MKABLO LOT NO-01 - P/N :3P22B375004-06A FireKab 2M400 4x10 mm² 0.6/1 kV LSOH IEC60331 BS 6387 CWZ CE
RoHS Month/Year meter mark
Fire Resistant Cable 2MKABLO LOT NO-01 - P/N :3P22B375005-06A FireKab 2M400 4x16 mm² 0.6/1 kV LSOH IEC60331 BS 6387 CWZ CE
RoHS Month/Year meter mark
Fire Resistant Cable 2MKABLO LOT NO-01 - P/N :3P22B375006-06A FireKab 2M400 4x25 mm² 0.6/1 kV LSOH IEC60331 BS 6387 CWZ CE
RoHS Month/Year meter mark
Fire Resistant Cable 2MKABLO LOT NO-01 - P/N :3P22B375007-06A FireKab 2M400 4x35 mm² 0.6/1 kV LSOH IEC60331 BS 6387 CWZ CE
RoHS Month/Year meter mark
Fire Resistant Cable 2MKABLO LOT NO-01 - P/N :3P22B375008-06A FireKab 2M400 4x50 mm² 0.6/1 kV LSOH IEC60331 BS 6387 CWZ CE
RoHS Month/Year meter mark
Product Number :
Page 2 / 2
1
Control and Instrumentation Cables
2 Multipair PVC Insulated Instrumentation Cable DELTA CROMPTON CABLES
BS5308 Part 2 Type 2
3 Collective Screen, Armoured 300/500V
Application
7
These cables are designed to connect electrical instrument circuits and provide communication services in and around process
plants (e.g. petrochemical industry etc). Suitable for direct buried applications.
8
9 Specifications
• In accordance with BS 5308 Part 2. • Mild galvanised steel wires to BS EN10257-1.
10 • Conductors: Stranded (Class 2) or flexible (Class 5) • Outer Sheath: PVC outer sheath Type TM.1 to
copper conductors to BS EN 60228. BS EN 50363-4-1.
• Insulation: PVC insulation Type TI.1 to BS EN 50363-3. In addition, outer sheath displays following
11 characteristics:
• Pair Identification: See colour code chart 2 page 4:32.
Minimum oxygen index: 30%.
• 100mm maximum pair lay length (minimum 10 twists Maximum HCL Emission @ 800°C: 15%.
12 per metre).
• Flame retardant to BS EN 60332-3-24 & IEC60332-3-24
• Binder Tape: p.e.t.p. tape 50% overlap. Category C (NMV1.5).
13 • Collective Screen: tinned copper drain wire(s) under • Voltage Rating: 300/500V.
and in contact with aluminium/p.e.t.p. laminated tape
• Temperature Rating: 65°C maximum conductor
14 applied metallic side down.
operating temperature.
• PVC bedding Type TM.1 to BS EN 50363-4-1.
15
16
17
18
19
Anixter Number Number Nominal Nominal Insulation Nominal Armour Wire Nominal Approx Min Bending
of Cond Cond Thickness Diameter Diameter O/D Cable Radius 4
Pairs/ Area Stranding Under Weight (fixed bend)
Triple Armour
(Q) = Quad 16
N.B. The above part numbers apply to cables with blue outer sheaths. For black outer add -02, for green outer add -04.
15, 30 and 50 pair cables of the above type are also covered in BS5308 Part 2 and details are available upon request.
For further technical information refer to page 4:32. 17
18
19
17
18
19
ELECTRICAL CHARACTERISTICS 3
Maximum Mutual Capacitance Values:
Maximum mutual capacitance of the pairs or adjacent cores - 250pF/m
Maximum capacitance between any core and screen - 450pF/m
4
MAXIMUM D.C. CONDUCTOR RESISTANCE @ 20°C
5
Conductor Size Conductor Stranding Resistance @ 20ºC Maximum
mm2 #/mm Ω/km
6
Multi-Core Multipair
0.5 16/0.2 39.0 39.7
7
0.75 24/0.2 26.0 26.5
1.5 7/0.53 12.1 12.3
8
9
MAXIMUM L/R RATIO
Conductor Size Conductor L/R Ratio (for adjacent cores)
10
mm 2
pF/m = pico Farads per metre
0.5 25µH/Ω Ω/km = ohms per km
µH/Ω = micro Henrys per ohm 11
0.75 25µH/Ω
1.5 40µH/Ω
12
INFORMATION ON HANDLING AND USAGE AT LOW TEMPERATURES
Attention is drawn to the fact that as the temperature decreases PVC compounds become increasingly stiff and brittle, with the 13
result that if the cable is bent quickly into a small radius, or is struck sharply at temperatures in the region of 0°C or lower,
there is a risk of shattering the PVC components. To avoid the risk of damage during handling, therefore, it is desirable that the
cables specified in this standard should be installed only when both the cable and the ambient temperatures are above 0°C 14
and have been so for the previous 24 hrs, or where special precautions have been taken to maintain the cable above this
temperature. However, after installation, they will operate satisfactorily at temperatures between -40°C and +65°C providing 15
that at temperatures below 0°C they are not subject to movement or impact. The manufacturer should be consulted for precise
instructions if the cable is to be stored and/or used outside these temperature limits.