Functional description
If the winding temperature nears the response temperature of the PTC
thermistors, the increased sensor resistance is perceived by the
INT369 R. If the tripping value is exceeded the output relay drops out
immediately and locks out.
Reset is achieved by interrupting the supply voltage for at least 5 sec,
provided that the fault condition has been corrected. Sensor and mains
INT369 R
circuit are galvanically insulated.
The unit must be connected by trained electrical personnel. The
unit must be connected by trained electrical personnel. All valid
european and national standards for connecting electrical equip-
ment must be observed.
INT369 R
Technical specifications
Supply AC 50/60Hz 120/240V
L1 L2 X C S1 S2 S3 M1 M2 -15...+10% 3VA
Permitted ambient temperature -40...+70°C
Temperature sensor PTC
120/240V
50/60Hz
Number of sensors 3
Rtrip 13kΩ ±3kΩ
Rreset 3,25kΩ ±0.5kΩ
M Relay AC 240V, 2.5A, C300
Mechanical service life Approx. 1 Mio. switching cycles
Housing material PA66/PA6, glass-fibre-reinforced
Wiring diagram Protection class acc. to EN 60529 IP00
Product group A
Approval UL File No. E75899
Connection type 6.3mm flat connection
15.9 64.8 5.85 Mounting Screw-mounted
4.7
M1 M2 L1 L2
Order data
Dual voltage 22 A 276 S24
72.1
81.5
Edition: 710.00306.0
X C S1 S2 S3
∅4.6
34.5 76.5
Dimensions in mm