Lux Table - Illumination Level
Lux Table - Illumination Level
Lux Table - Illumination Level
CIRCULATION AREA
CORRIDORS, PASSAGEAWAY 100 100 1.2m above Intermediate Scallar illuminance to be less
floor than 1/8 horizontal planar
illuminance in adjacent area and
not less than 120 if there is no
daylight
Enquiry desk 500 300 desk intermediate Limit illuminance to assist view
or warm out at night
OUTDOOR
Controlled entrance or exit gates 50 50 working intermediate Working plane varies according
plane or warm to requirement
Entrances and exit car parks, 30 30 ground intermediate
or warm
Stores, stockyards 30 30 working intermediate Consider obstructions vertical
plane or warm surfaces often more important
Consulting rooms, treatment 500 400 desk or bed intermediate Examination lighting should be
area or warm provided
Rest rooms 150 150 table height warm Change in chanter from general
lighting desirable
STORE AND STOCK ROOMS 150 150 vertical intermediate
plane or warm
Telecommunication board 500 horizontal intermediate Avoid specular reflections on
switchboard rooms keyboard or warm boards
Aircraft engine testing 750 600 engines intermediate Portable luminaries relative
or warm
Inspection and repairs 500 500 aircraft intermediate Proof luminaries maybe required
(hangers) horizontal
and vertical
GARAGES
GAS WORK: Proof luminance maybe required and local lighting on instrumentation
and control possible low maintenance factors
Medium work e.g ‘go’ and ‘no 500 400 working Intermediate or
go’ gauge, sub-assemblies plane warm
Fine work e.g radio and 1000 600 working cool intermediate
telecommunication equipment, plane or warm
calibrated scales, precision
Very fine work e.g gauging 1500 750 working cool intermediate Local fighting and optical
and inspection of small plane or warm aids maybe used. Building
intricate parts illuminance not less than
750 lux
Minute work e.g very small 3000 1000 working cool intermediate Special lighting and
instruments plane or warm optical aids should be
used. Building
illuminance not less than
1000 lux
LABORATORIES
(GENERAL)
Receiving sorting, washing, 300 200 working intermediate or Proof luminaries maybe
drying, ironing (clending) plane warm required
dispatch, dry cleaning, bulk
machine work
Hand ironing, pressing, 300 working cool intermediate Proof luminaries maybe
inspection, mending, spotting plane or warm required
Fine bench and machine work 1000 500 working plane intermediate
fine automatic machine, or warm
medium grinding, fine buffing
and polishing
Grinding, granulating mixing 500 300 working plane intermediate Proof luminaries maybe
and drying, tableting, or warm required in all areas
sterilizing and washing,
preparation of solutions and
filling, labeling capping,
cartooning, warping
COMPOSING PRESS
RUBBER PROCESSING
FACTORIES
SLAUGHTER HOUSES
Gas and arc welding, rough 300 200 working plane intermediate
spot welding plane
Very fine soldering, spot 1500 750 working plane intermediate Optical aids maybe used
welding e.g radio valves building luminaries not
less then 750 lux
WOODWORKING SHOP
Rough sawing, bench work 300 200 bench plane intermediate Unguarded rotating
plane machinery maybe in used!
Local tungsten lighting or
other measure to avoid
stroboscopic effects
Sizing, planning, rough 500 300 working plane intermediate Lighting on vertical plane
sanding medium and bench plane important at bench
working glueing cooperage
Fine bench and machine work 750 400 working plane intermediate
fine sanding, finishing plane
OFFICE
General office with mainly 500 500 desk intermediate Minimize veiling
clerical tasks and typing office or warm reflections by suitable
luminaries locatiom
Deep plan general offices 750 300 desk intermediate
or warm
Business machine and typing 750 300 copy intermediate
or warm
Filling room 300 300 file labels intermediate File labels maybe vertical
or warm at floor level
Computer rooms 500 500 working plane intermediate Avoid specular reflections
or warm in concoles. Limit
illuminance where
internally lit signals are
used
Drawing offices, drawing 750 600 board cool Boards maybe vertical or
board intermediate incline
or warm
Reference table and general 500 300 table cool
intermediate
or warm
SHOP
Conventional with counters 500 500 counters cool Type of merchandise will
horizontal intermediate dictate required colour
or warm rendering. Localized
lighting needed to be
emphasized particular
spacing displays
Conventional with wall 500 500 display cool
displays vertical intermediate “
or warm
Theatre and concert halls 100 100 horizontal intermediate Dimming facilities
or required
warm
Multi purpose 500 300 seat level intermediate Dimming facilities usually
or warm required
FURTHER EDUCATION
ESTABLISHMENT
Lecture theatres general 500 300 Desk intermediate Provision for dimming
or maybe required. Provide
warm suitable lighting on
lectures face and notes.
Low noise level required
LIBRARIES
Light sensitive exhibits 150 150 display cool intermediate Illuminance are maxima
or warm
SCHOOL
Assembly hall general 300 200 working plane intermediate Provision for dimming
or warm should be included for
stage and film use
Teaching spaces general 300 200 working plane intermediate or Illuminance maybe
warm reduced to 150 lux in
space lit by tungster lamps
e.g nursery
Teaching spaces general 300 200 working plane intermediate or Illuminance maybe
warm reduced to 150 lux in
space lit by tungster lamps
e.g nursery and infant
school. Where the main
view is across the space
e.g to the chalkboard, the
LGI should be 16
TRANSPORT
TERMINAL BUILDING
HOSPITAL
Dimming required
X-ray department radio, 500 500 couch intermediate or
diagnostic and room warm
fluores copy
HOSPITAL
Decoration required
Radio therapy rooms 300 300 intermediate or
warm
Special lighting
Dental surgeries 300 300
HOMES
In all home areas,
Living rooms general 50 50 working plane intermediate or attention should be given
warm to lighting of room
surface. Luminance
should be selected and
positioned to give
occupants a compromise
between attractive sparkle
Casual reading 150 150 working plane intermediate or and unwanted glare.
warm Dimming is useful for
changing atmosphere.
Sewing and 300 300 working plane intermediate or Additional mirror lighting
darningsrudies warm required in bedrooms.
Desk and protuged Additional mirror lighting
required. Enclosed
Bedrooms general 50 50 floor intermediate or luminaries should be used
warm
HOMES
Illuminance must be
Garages 50 50 floor intermediate increased 50-100% above
recommendation for
homes. Particular
(HOME OLD PEOPLES) attentions must be paid to
avoid glare and to reveal
steps and obstruction.
Two ways switches
should be installed for
through stairs etc.
MULTIPURPOSE
SPORTS ALL
For some sports side
Athletics, basketball, 300 200 instrument of lighting or localized
bowls, judo, gymnastic, warm lighting (e.g at the net in
hockey ball 700 500 floor badminton) is preferred.
Arrange switching to give
illuminance appropriate to
activity
BILLIARD ROOMS
GENERAL