Load Calculation
Load Calculation
Load Calculation
CHAP CHAP
TABLE REFERENCE TABLE REFERENCES
REF REF
AREA OR SUNGAIN OR LOCAL TIME LOCAL TIME
ITEM FACTOR ESTIMATE FOR 15.00 PM PEAK LOAD 12.00 AM
QUANTITY TEMP. DIFF SUN TIME SUN TIME
SOLAR GAIN-GLASS (Btu/hr) 25,436 HOUR OF OPERATION 16
GLASS 50 SQ FT X 108.24 X 0.94 CONDITIONS DB WB % RH DP GR/LB
3&4
2
GLASS 50 SQ FT X 108.24 X 0.94 ROOM (RM) 76 50 0 0 0
GLASS 50 SQ FT X 108.24 X 0.94 DIFFERENCE 19 XXX XXX XXX 0
SKYLIGHT 50 SQ FT X 108.24 X 0.94 OUTDOOR AIR
SOLAR & TRANS. GAIN-WALLS & ROOF (Btu/hr) 9,956 VENTI- 40 PEOPLE X 50 CFM/PERSON = 2000
WALL 200 SQ FT X 19 X 0.32 LATION 1000 SQ FT X 5 CFM/SQ FT = 5000
WALL 200 SQ FT X 19 X 0.32 CFM VENTILATION = 5000
WALL 200 SQ FT X 19 X 0.32 SWINGING
WALL 200 SQ FT X 19 X 0.32 REVOLVING DOORS 50 PEOPLE X 12 CFM/PERSON = 600
6
ROOF-SUN 200 SQ FT X 19 X 0.67 INFIL- OPEN DOORS 3 DOORS X 100 CFM/DOOR = 300
5
HEAT
INTERNAL HEAT (Btu/hr) 4,050 ADP INDICATED ADP 53 F , SELECTED ADP 53 F
PEOPLE 25 PEOPLE X 63 DEHUMIDFIED AIR QUANTITY
TEMP.
3&7
STORAGE 25 SQ FT X 2 X 0.4
SUPPLY AIR QUANTITY
8
SUB TOTAL 2 (Btu/hr) 50,560 SUPPLY ROOM SENS. HEAT = 6,058 CFMSA
SAFETY FACTOR 10 % CFM 1.08 X 8.50 FDESIRE DIFF
ROOM SENSIBLE HEAT (Btu/hr) 55,616
7
SUPPLY DUCT + SUPPLY DUCT + FAN BYPASS 6058 CFM SA - 6,058 CFMDA = - CFMBA
HEAT GAIN % 15 LEAK LOSS % 10 H.P. 10 % CFM
OUTDOOR AIR 15 CFM X 19 F X 0.5 BF X 1.08 RESULTING ENT & LVG CONDITIONS AT APPARATUS
8
EFFECTIVE ROOM SENSIBLE HEAT(Btu/hr) 75,236 EDB TRM 76 F+ 0.83 CFMOA X (T 95 F -T 76 F) = TEDB 92 F
OA RM
LATENT HEAT (Btu/hr) 7,560 CFM+
6
INFILTRATION 300 CFM X 15 GR/LB X 0.68 LDB TADP 53 F+ 0.5 BF X (TEDB 92 F -T 53 F) = TLDB 72 F
ADP
PEOPLE 30 PEOPLE X 0
8 0
3&7
SUPPLY AIR DUCT LEAK LOSS 10 % 3. NORMALLY. USE "CFM VENTILATION" FOR "CFM OUTDOOR AIR" HOWEVER
OUTDOOR AIR 0 CFM X 0 GR/LbX 0.5 BF X 0.68 WHEN INFILTRATION IS TO BE OFFSET, REFER TO PAGE 92 TO DETERMINE
EFFECTIVE ROOM LATENT HEAT (Btu/hr) 8,316 "CFM OUTDOOR AIR."
EFFECTIVE ROOM TOTAL HEAT (Btu/hr) 83,552 4. WHEN INFILTRATION IS NOT TO BE OFFSET, AND "CFM VENTILATION IS LESS THAN
8
OUTDOOR AIR HEAT 1,635 "CFM INFILTRATION," THEN THE EXCESS INFILTRAITON IS ACCOUNTED FORHERE.
SENSIBLE : 450 CFM X 5 FX (1 - 0.5 BF)X1.08
LATENT : 510 CFM X 2 GR/Lb X (1 - 0.5 BF)X0.68
RETURN DUCT RETURN DUCTBX(1-
10 10
HEAT GAIN % + LEAK GAIN %
HP DEHUM. &
7
5 5
PUMP % + PIPE LOSS % * IF THIS DIFF TEMP IS TOO HIGH, DETERMINE SUPPLY CFM FOR DESIRED DIFFERENCE BY SUPPLY
SUB TOTAL 4 (Btu/hr) 2,126 AIR QUANTITY FORMLA.
#
WHEN BYPASSING MIXTURE OF OUTDOOR AND RETURN AIR, USE SUPPLY CFM WHEN BYPASSING
GRAND TOTAL HEAT (Btu/hr) 85,677
RETURN AIR ONLY, USE DEHUMIFIED CFM.
Windows area , sq ft
C12: Area of glassed structure that solar haet gain get thru at varies exposure. ( N,E,S,W,NE,SE
,SW,NW) , Chapter 3
Wall area , sq ft
C20: Area of wall or roof that conducted heat gain get thru at each exposure. ( ,E,S,W,NE,
SE,SW,NW)
C32: Power, kw
Grossory of power of operating motor in the A/C area. It can generate heat to be the cooling load.
C33: Power, kw
Grossory of power of lighting in the A/C area. It can generate heat to be the cooling load.
Outdoor air,CFM
C44: Quantity of outdoor air make up to the A/C system. See note 3 on the bottom of this calculation sheet (Table45,Page97 and Table 43, Page92)
Steam , Lb/Hr
C49: Amount of steam escape to conditioned space
People, Person
K16: Amount of people in the A/C area.
L21: Door,
The numbe of open door of the A/C area.